Feasibility Studies for Small Scale Hydropower Additions-17

download Feasibility Studies for Small Scale Hydropower Additions-17

of 54

Transcript of Feasibility Studies for Small Scale Hydropower Additions-17

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    1/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    April 2015

    Contents

    Metal-Enclosed Drawout SwitchgearLow Voltage20

    Sheet 20001

    Metal-Enc

    losedDrawo

    ut

    Switchgear

    Low

    Voltage Metal-Enclosed Drawout Switchgear

    Low Voltage

    Magnum DS(For detailed information on MagnumDS breakers, refer to Tab 26.)

    General Description

    Structure . . . . . . . . . . . . . . . 20.1-1

    Bus. . . . . . . . . . . . . . . . . . . . 20.1-2

    Wiring . . . . . . . . . . . . . . . . . 20.1-3

    Instrumentation/Metering . . 20.1-4

    Accessories/Options. . . . . . 20.1-4

    Magnum DS FrontAccessible Switchgear. . . 20.1-5

    Magnum DS Arc-Resistant Switchgear . . . . 20.1-6

    Magnum DS PowerCircuit Breakers . . . . . . . . 20.1-7

    Magnum DS SwitchgearTrip Units . . . . . . . . . . . . . 20.1-9

    Arcflash ReductionMaintenance System. . . . 20.1-10

    Series NRX . . . . . . . . . . . . . 20.1-13

    Metering andMonitoring Devices . . . . . 20.1-16

    Technical Data

    Voltage and Bus Ratings . . 20.1-18

    Heat Loss. . . . . . . . . . . . . . . 20.1-18

    Standards . . . . . . . . . . . . . . 20.1-18

    Breaker Ratings . . . . . . . . . 20.1-20

    Breaker Control Voltages. . . 20.1-21

    CT Metering Accuracies. . . 20.1-23

    Voltage Transformers. . . . . 20.1-23

    Control Power Transformers 20.1-23

    Layout Dimensions

    Breaker Arrangements . . . . 20.1-27

    Floor Plan/Conduit Area. . . . 20.1-36

    Switchgear Section View . . . 20.1-38Outdoor Enclosure . . . . . . . 20.1-41

    Arc-ResistantLayout Restrictions . . . . . 20.1-43

    Center of Gravity/Weights . 20.1-48

    Specifications

    See Eatons Product SpecificationGuide,available on CD or on the Web.

    CSI Format:

    1995 2010

    Section 16426A Section 26 23 00.11

    Metal-Enclosed Drawout SwitchgearLow Voltage and DSLII

    For DS/DSIIor DSL/DSLIISwitchgear,please consult factory at 1-800-257-3278.

    Specifications

    See Eatons Product SpecificationGuide, available on CD or on the Web.

    CSI Format:

    1995 2010

    Section 16426B Section 26 23 00.13

    Magnum DS Switchgear

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    2/54

    0.0-2

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    002

    This page intentionally left blank.

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    3/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    General Description003

    Magnum DS SwitchgearStandard Construction

    Eatons Magnum DSpower circuitbreaker switchgear is backed by40 years of power circuit breaker and

    switchgear development that haveset the industry standards for quality,reliability, maintainability andextended operating life, when itcomes to protecting and monitoringlow voltage electrical distributionsystems. Magnum DS switchgear isdesigned to meet the changing needsof our customers by providing:

    Lower installation andmaintenance costs

    Higher interrupting ratings and with-stand ratings

    Better coordination capability

    Increased tripping sensitivity

    Enhanced safety measures

    Higher quality, reliability andmaintainability

    Communications and powerquality monitoring andmeasuring capabilities

    Flexible layouts that maximizeuse of capital by minimizingequipment footprint

    Magnum DS switchgear can meet theneeds of general applications, serviceentrances, harsh environments, multi-ple source transfers, special groundingsystems and many others.

    With a modern design, Magnum DSmetal-enclosed low voltage switchgearand power circuit breakers provide:

    100% rated, fully selectiveprotection

    Integral microprocessor-basedbreaker tripping systems

    Two-step stored-energy breakerclosing

    Standard 100 kA short-circuitbus bracing

    Optional 150 and 200 kAshort-circuit bus bracing

    Optional metal barriers to isolate the

    cable compartment from thebus compartment

    Both indoor and outdoor aisle andaisleless enclosures

    Full range of safety solutionsdealing with arc flash hazardand operator error

    Many other features for coordinated,safe, convenient, trouble-free, andeconomical control and protection oflow voltage distribution systems arealso provided.

    Magnum DS Switchgear

    Magnum DS breakers are designed to:

    ANSI Standards C37.13, C37.16,C37.17, C37.50

    UL 1066

    Magnum DS switchgear conforms tothe following standards:

    CSAC22.2, No. 31-M89

    ANSI C37.20.1

    ANSI C37.51

    ULStandard 1558 and ULStandard 891

    American Bureau of Shipping (ABS)

    Built in an ISOcertified facility

    Maximum ratings for Magnum DSswitchgear are 600 Vac, 10,000Acontinuous cross bus and 200,000Ashort-circuit capacity.

    Seismic Qualification

    Refer to Tab 1for information onseismic qualification for this andother Eaton products.

    Structure FeaturesStandard finish: Gray paint finish(ANSI 61) using a modern, completelyautomated and continuously moni-tored electrostatic powder coating.This continually monitored systemincludes spray de-grease and clean,spray rinse, iron phosphate spraycoating spray rinse, non-chemical seal,oven drying, electrostatic powderspray paint coating and oven curing.

    Integral base: The ruggedly formedbase greatly increases the rigidity ofthe structure, reduces the possibility ofdamage during the installation of theequipment, and is suitable for rolling,jacking and handling. A lifting angleis permanently welded into the buscompartment structure for increasedstrength. The bottom frame structuremembers are indented to allow theinsertion of a pry bar.

    Heavy-duty door hinges: Eachbreaker door is mounted with hingepins. Removal of the door is easilyaccomplished by just lifting the hinge

    pin. This allows easy access to thebreaker internal compartment forinspection and maintenance.

    Rear cover/doors: In Magnum DSswitchgear, standard rear boltedcovers are provided. They are splitinto two sections to facilitate handlingduring removal and installation.Optional rear doors are also available.

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    4/54

    0.1-2

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    General Description004

    Through-the-door design: Thefollowing functions may be performedwithout the need to open the circuitbreaker doorlever the breakerbetween positions, operate manualcharging system and view the spring

    charge status flag, close and openbreaker, view and adjust trip unit andread the breaker rating nameplate.

    Through-the-Door Design

    Cassette design: The breaker cassettesupports the breaker in the cell, as wellas on the movable extension railswhen the breaker is placed into orremoved from the cell. The extensionrails allow the breaker to be drawnout without having to de-energize theentire switchgear lineup.

    Accessibility: When the door is open orremoved, each breaker compartmentprovides front access to isolated,vertical wireways, primary discon-nects, cell current transformers andother breaker compartment accessoriesfor ease of field wiring and trouble-shooting field connections.

    Breaker Cell

    Four-position drawout: Breakers canbe in connected, test, disconnected orremoved position. The breaker can bemoved between the connected, testand disconnected positions while thecompartment door is closed.

    Closing spring automatic discharge:Mechanical interlocking automaticallydischarges the closing springs whenthe breaker is removed from itscompartment.

    Optional safety shutters: Positive

    acting safety shutters that isolate thebreaker connections to the main buswhen the breaker is withdrawn fromthe cell is an option offered for addi-tional safety beyond our standarddesign. They reduce the potentialof accidental contact with live bus.Insulating covers (boots) arefurnished on live main stationarydisconnecting contacts in compart-ments equipped for future breakers.

    Breaker inspection: When withdrawnon the rails, breaker is completelyaccessible for visual inspection; tilting isnot necessary. The rails are permanent

    parts of every breaker compartment.Interference interlocks: Supplied onbreakers and in compartments wherethe compartments are of the samephysical size. Interference interlocksensure an incorrect breaker cannotbe inserted.

    Optional key interlock (switchgearmounted): This mechanism holds thebreaker cell mechanically trip-free toprevent electrical or manual closing.Breaker can be stored in compartment,and completely removed for mainte-nance or for use as a spare withoutdisturbing the interlock. Modification

    of the breaker is not required. Anadditional single cylinder breakermounted key interlock is availableas an option.

    Optional mechanical interlock:Available between adjacent breakersto ensure the proper sequence ofoperation between two circuit breakersor a circuit breaker and a fuse truck.

    Bus Features

    Buses and connections: Verticaland cross bus ratings in Magnum DSswitchgear are based on a UL andANSI standard temperature rise of

    65 C above a maximum ambient airtemperature of 40 C. As an option,55C temp rise over a maximumambient air temp of 40 C is available.

    Bus ampacities: Vertical and cross busratings in Magnum DS are 2000, 3200,4000 and 5000 A. In addition, a 6000,8000 and 10,000 A cross bus rating isavailable. Vertical section bus is sizedper main cross bus maximum ratingor by ANSI C37.20.1 Section 7.4.1.3.Table 11 to a maximum of 5000 A.

    Bus bracing: Unique vertical busconfiguration provides an optionalindustry-leading short-circuit with-stand rating of 200,000 A. Standardbracing is 100,000 A. The U shaped

    bar is the heart of the Magnum DS

    vertical bus. This configurationprovides a much higher mechanicalstrength. To further demonstratethe strength and rigidity of this bussystem, it has been verified throughtesting to withstand 85,000 A short-circuit for a full 60 cycles.

    Silver plating: Bolted, silver-platedcopper main buses are standard. Theplating is over the entire length of thebar, not just at the joints. Optionaltin-plated copper buses are available.

    Bus joints: All joints are bolted andsecured with Belleville-type springwashers for maximum joint integrity.These washers reduce the potential ofjoint hardware loosening during thechange of joint temperature associatedwith variations of the loads. Optionalmaintenance-free hardware is alsoavailable.

    Full neutral: For four-wire applications,the neutral bus is rated 100% of mainbus rating as standard. Neutral ratingsup to a maximum of 10,000 A areavailable as an option. Additionally,four-pole breakers can be used inconjunction with four-wire systems.

    Ground: A ground bus is furnished

    the full length of the switchgearassembly and is fitted with terminalsfor purchasers connections.

    Glass reinforced polyester andUltramidstandoff insulation system:Glass reinforced polyester has beenused on both low and medium voltageswitchgear for decades. By combiningthis industry proven material withUltramid insulation, a total systemproviding exceptional mechanical anddielectric withstand strength, as wellas high resistance to heat, flame andmoisture, is produced. Substantialtesting to demonstrate acceleratedeffects of heating and cooling on the

    mechanical and dielectric propertiesof this system prove it to providesuperior performance for decadesof trouble-free operation.

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    5/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    General Description005

    Optional conductor insulationcovering: For applications requiringadditional bus protection in harshenvironments, Magnum DS switchgearis designed for the addition of optionalconductor insulation covering, in

    addition to providing full UL airclearance without insulation. Thismaterial is applied during the assemblyof the bus, and covers all vertical andhorizontal phase bus bars. Removableboots provide access to section-to-section bus joints for inspection andmaintenance purposes. This insulationis not available for vertical sections con-taining Series NRX breakers.

    Optional Insulated Bus

    Barriers: Optional grounded metalbarriers isolate the main bus andconnections from the cable compart-

    ment providing added safety to theworkers while reducing the potentialof objects falling into the bus compart-ment. In addition, vertical barriersbetween cable sections can be addedto reduce potential hazards. Barriersare removable to give access to thebus compartment for inspection andmaintenance. Barriers can be eithersolid metal or vented for ease ofinfrared scanning.

    Optional Bus Compartment andVertical Section Barriers

    Wiring FeaturesCable compartment: The cablecompartment gives ample roomfor terminating the power cables.Removable top roof sheets allowfor easy conduit hub installation.

    The floor of the cable compartmentis open to allow cable entry fromunderground duct banks. Optionalfloor plates are available.

    In addition to cable, Pow-R-Waybus-way and nonsegregated bus duct canbe terminated in the compartment.

    Lug pad: The lugs are located on thebreaker run-backs to accommodate lugorientations at a 45 angle to reducethe bending radius of the cable neededfor making the connections, thusreducing installation and maintenancetime. Mechanical setscrew type lugsare standard. Optional NEMA

    two-hole compression lugs are avail-able as an option.

    Control wireway: An isolatedvertical wireway is provided forrouting of factory and field wiringin each switchgear section. Breakersecondary terminal blocks aremounted as standard above eachcircuit breaker. The terminal blocks arerated 30 A, and will accept bare wire,ring or spade terminals for wire sizeranges of #22#10. Extruded loops arepunched in side sheets of the verticalwireway to allow securing of customercontrol wiring without the use of

    adhesive wire anchors.

    Control circuits may be wired in allcells without removing the circuitbreaker. In addition, power circuitsmay be connected in the rear of theswitchgear at the same time controlcircuits are being wired in the frontof the switchgear.

    For applications involving excessivewiring, or nonstandard terminal blocks,terminal blocks are mounted on therear frame with the power cableswhere they are readily accessible forcustomers connections and inspection.

    Control wire: Standard wire is TypeSIS insulated stranded copper, extraflexible No. 14 AWG minimum.

    Control wire marking:Each wireis imprinted with ink cured under ultra-violet light for durability and for easyidentification by the user. The enhancedsolvent resistance and durability of theaerospace grade UV cure ink has been

    tested for severe environments. Theimprinting is made every 3.00 inches(76.2 mm) along the length of the wireto make field troubleshooting easier.The point of origin, wire designationand point of destination are imprintedin the following format: . Eachdevice has a uniquely designated zone. indicatesthe direction of the wire destination.As an option, wire marking can bemade using sleeve type or heatshrink sleeve type.

    Control Wire Marking

    Secondary terminal compartment:There are 72 finger-safe secondaryconnections for a standard frameMagnum breaker, 60 for a narrowframe Magnum breaker and 54 for

    a Series NRX breaker. The customerssecondary terminal connections arelocated at the front of the structurebehind a separate door providingaccess to these connections withoutthe need to open the breakercompartment door.

    Short-circuiting terminal blocks:One provided for each set ofinstrumentation or relayingapplication current transformers.

    Shipping split connection: At eachshipping split, the control connectionsare made with plug-in terminal blocksrated 600 V, 40 A. The terminal blocksmechanically interlock without remov-ing the line or load connections. Thismethod of making the shipping splitcontrol connections increases thespeed of installation and reduces thepotential of incorrect connections.

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    6/54

    0.1-4

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    General Description006

    Instrumentation/Metering FeaturesFlexibility: Magnum DS switchgearallows for a variety of metering options:

    Analog switchboard type meterssuch as ammeters, voltmeters,

    watthour, power factor and so on Electronic power metering such as

    the Power Xpert, PX 2000, IQ 250/260 and IQ Analyzer

    Instrument door-mounted meters.For feeder circuit instrumentation,2% accuracy ammeters andammeter switches can be mountedon the secondary contact compart-ment door between the breakercompartment doors. The ammetersand switches are immediatelyassociated with definite breakercircuits. Other devices, such ascontrol pushbuttons, breaker controlswitches, indicating lights and test

    switches can be mounted on thesepanels, within space limitations

    See Tabs 2, 3 and4for Metering andPower Management products.

    Voltage transformers: Voltagetransformers are rated 10 kV BIL,and are protected by both primaryand secondary fuses. The primaryfuses are of the current limiting type.

    Current transformers: Currenttransformers for metering and instru-mentation are mounted in the breakercompartments and are front accessi-ble. Secondary wiring between the

    current transformer and the standardshorting terminal block is color-codedfor ease of identification.

    Control power transformers:Control transformers are providedwhen required for AC control of circuitbreakers, space heaters and/or trans-former fans. Like voltage transformers,they are protected by current limitingprimary fuses. Non-current limitingfuses are used on the secondary sideto protect branch circuits.

    Instrumentationdoor-mountedsecondary terminal compartmentdoor: Devices, such as control push-buttons, indicating lights, switches andanalog meters can be mountedon these panels, within space limita-

    tions. The ammeters and switches areimmediately associated with definitebreaker circuits.

    Devices Mounted on SecondaryTerminal Compartment Door

    Instrument compartment door:Devices, such as electronic powermetering and analog switchboard typemeters that do not fit on the secondaryterminal compartment door, aremounted on the instrument compart-ment door or on a panel of a blank cell.

    Power Xpert Meter Display

    Accessories and Options Features

    Switchgear accessories: Standardaccessories furnished with eachMagnum DS switchgear assemblyinclude:

    One breaker levering crank

    Insulating covers or bootsfurnished on live main stationarydisconnecting contacts in compart-ments equipped for future breakers

    Removable cover to block openingin the door when the breaker istemporarily removed from itscompartment

    Optional Accessories

    Traveling type circuit breaker lifter,rail-mounted on top of switchgear

    Floor-running portable circuitbreaker lifter and transfer truckwith manual lifting mechanism. This

    requires approximately 84.00 inches(2133.6 mm) deep front aisle space

    Test cabinet for electrically operatedbreakers, with pushbuttons, controlcable and receptacle, for separatemounting. Optional space heatersto be placed in the bottom of thebreaker, cable and bus compart-ments. Space heaters are providedas standard in outdoor gear toreduce condensation

    Portable test kit (MTK2000) forsecondary injection testing andverification of trip units. Usesstandard 120 V, 15 A, single-phase,60 Hz supply, available fromany outlet. Allows for testingof both Magnum DS andSeries NRX breakers

    Remote racking device (MRR1000)for both breaker racking andoperation (open/close) from a safedistance. Mounts to any existingMagnum DS breaker. Uses standard120 V, 15 A, single-phase, 60 Hzsupply, available from any outlet

    Optional Switchgear Mounted Lifter

    MRR1000

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    7/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    General Description007

    Enhanced Switchgear Options

    Infrared scanning windows for busthermal scans

    White interior panels for easeof visibility in instrumentcompartments

    Maintenance-free (Torque-&-Forget)bus hardware

    Lug booting that provides additionalprotection against accidentalcontact to live parts in the cablecompartment

    Grounding balls and covers forprotecting maintenance personneldownstream of switchgear feederbreakers

    Electronic remote control devicethat allows for breaker to openand close away from the frontof the switchgear

    Grounding Balls and Covers

    Remote Control Device

    MTK2000 Trip Unit Test Kit

    Magnum DS Front-Accessible Switchgear

    Magnum DS Front-Accessible Switchgear42.00-Inch (1066.8 mm) Deep Enclosure

    When floor space is limited, or roomconstraints dictate that equipmentbe mounted against a wall, whycompromise on switchgear design?

    Eatons Magnum DS front-accessibleswitchgear combines the robustness ofUL1558 low voltage switchgear withthe flexibility of UL 891 switchboarddesign. The front-accessible switch-gear offering allows mounting against a

    wall, or in other tight locations, wherea standard rear-accessible switchgearlineup would not normally fit. The threedivisions of rear-accessible switchgearare redistributed into two verticalsections, with the breaker and the busin one half and cable and bus in theother half on the right-hand side. Bothsections can be easily accessed byoperators and maintenance personnelfrom the front of the switchgear.

    Product Offering

    UL 1558

    20008000 A bus

    8006000 A breakers 100, 150 and 200 kA bus designs

    600 Vac class

    NEMA 1 indoor (corner sectionavailable for layout flexibility)

    NEMA 3R outdoor, both aisle andaisleless enclosures

    Application Description CommercialOffice buildings, high

    rise and convention centers

    IndustrialAutomotive, petro-chemical, pharmaceutical, pulpand paper, utility and data centers

    InstitutionalUniversitiesand hospitals

    GovernmentWater treatment,federal buildings and municipalities

    Critical Power OEMsGeneratorand UPS manufacturers

    Features

    Standard 42.00-inch (1066.8 mm)switchgear depth

    Up to 4-high breaker arrangement

    Breaker sections are 18.00, 22.00,24.00 or 44.00 inches (457.2, 558.8,609.6 or 1117.6 mm) wide depending

    on breaker type and frame sizes Cable compartments are 18.00, 22.00,

    24.00, 30.00 or 44.00 inches (457.2,558.8, 609.6, 762.0 or 1117.6 mm) widedepending on cable orconduit sizes

    Substation arrangement, with closecoupling to dry-type or liquid-filledtransformers, where required

    Benefits Improved uptimeHighest

    withstand ratings in the industryallow for levels of selectivecoordination never seen before

    Improved maintainabilityDedicated secondary terminalswith separate access door andfront accessible control wireway

    Increased reliabilityModulardesign allows for reduced partsfor both structures and breakers

    Increased safetyEnhancedperformance suite of options

    Reduced installation costsFirstUL 1558 switchgear designed to beplaced against a wall, allowing forreduced floor plan requirementswithout sacrificing design

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    8/54

    0.1-6

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    General Description008

    Magnum DS Arc-Resistant Switchgear

    ArcGard Magnum DS Switchgear

    Arc-resistant low voltage switchgearis a new development in the MagnumDS line that protects operating andmaintenance personnel from danger-ous arcing faults by channeling the arcenergy out the top of the switchgear.Arc faults, caused by human erroror insulation failure, can generatethermal energy as high as 35,000 Fand a blast equivalent to 20.7 lbs ofTNT. While arc-resistant gear does notprevent these arcs from occurring, itdoes safely redirect and contain thesearcs that do occur, regardless of theoriginating location of the arc. ArcGardMagnum DS switchgear has been

    tested in all three compartments for afull 0.5 seconds, passing ANSI Type 2and Type 2B standards at 100 kA at508 V and 85 kA at 635 V.

    Arc-Resistant SwitchgearAccessibility Types

    Arc-resistant switchgear performanceis defined by its accessibility type inaccordance with IEEE test guideC37.20.7 as follows:

    Type 1: Switchgear with arc-resistantdesigns or features at the freelyaccessible front of the equipment only.

    Type 2: Switchgear with arc-resistantdesigns or features at the freelyaccessible exterior (front, backand sides) of the equipment only.(Type 2 incorporates Type 1.)

    Type 2B: Switchgear with Type 2accessibility plus arc-resistant infront of the instrument/controlcompartment with the instrument/control compartment door opened.(Type 2B incorporates Type 2.)

    Normal Operating ConditionsArc-resistant features are intendedto provide an additional degree ofprotection to the personnel performingnormal operating duties in close prox-imity to the equipment while

    the equipment is operating undernormal conditions.

    The normal operating conditions forproper application of arc-resistantswitchgear designs are as follows:

    All doors and covers are properlyclosed and latched

    Pressure relief devices are free tooperate

    The fault energy available to theequipment does not exceed therating of the equipment (short-circuit current and duration)

    There are no obstructions around

    the equipment that could direct thearc fault products into an areaintended to be protected

    The equipment is properlygrounded

    The user should also refer todocuments such as NFPA 70E, forsafety training and safe work practicesand methods of evaluating safe workdistances from energized equipmentbased on the potential flash hazard,and use proper PPE when workingon or near energized equipmentwith the door/cover opened or notproperly secured.

    Arc-Resistant SwitchgearProduct OfferingArc-resistant switchgear comesstandard with:

    Up to 100 kA short circuit at 508 Vacmaximum and 85 kA short circuit at635 Vac maximum

    Up to 10 kA horizontal main buscontinuous current

    Up to 5 kA vertical buscontinuous current

    Magnum DS power circuitbreaker frame ratings between

    800 A and 6000 A Up to four high breaker configura-

    tion with no additional layoutrestrictions (requires 10-footfloor to ceiling clearance)

    Additional safety withoutincreasing the footprint ofregular Magnum DS switchgear

    Standard Features ANSI Type 2 arc-resistance: Type 2

    arc-resistant switchgear regardlessof whether the arc originates thebreaker, bus or cable compartment

    Stronger door and latch:The robustdoors are made of heavy 12 gaugemetal and secured with two-pointlatches

    Bellows and Two-Point Door Latch

    Breaker bellows:Bellows surroundthe breaker door, preventing arcgasses from escaping around thenose of the breaker while ensuringeasy racking of the breaker into thedisconnected position

    Rear dynamic flap system:Theventilation openings in the breakermust be open during operation toallow proper equipment ventilation,but sealed off during an arc event.The rear dynamic flap system usesgravity to keep the flaps open

    during normal operating conditionsand the arc pressure wave to closethe flaps during an arcing event. Itis a passively designed system sothere are no electrical or automatedparts that could break or fail

    Rear Dynamic Flap System

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    9/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    General Description009

    Ventilation system:Each breakercompartment is vented to allowionized gas to flow into the bus com-partment from any locationin the switchgear and out thetop of the switchgear through

    the hinged flaps Bottom or top cable or bus

    duct entry

    Cable compartment floor plates

    Optional Features

    ANSI Type 2B arc-resistance

    Plenum: The plenum is mountedon top of arc-resistant gear to directdangerous arc gasses as they leavethe switchgear. The exit path caneither be a side or rear exit, witha 4-foot blast zone around the exit

    Zone selective interlockingprotection: Zone selective interlock-

    ing capability is also available inarc-resistant gear, allowing thebreaker closest to the fault to tripwithout any preset time delay whilethe remainder of the distributionsystem remains online

    Arcflash Reduction MaintenanceSystem

    Safety shutters

    One piece hinged and boltedrear panel

    Insulated bus

    Vented bus/cable compartmentbarriers:Bus/cable compartmentbarriers are only available vented to

    allow flow of arc gasses in the caseof an arc event

    Cable compartmentsegregation barrier

    Standards and Certifications

    UL 1558/UL 1066

    ANSI C37.20.1, C37.13, C37.51

    ANSI C37.20.7

    CSA C22.2 No 31-04

    Third-party UL witnessedand certified

    NFPA 70E

    Magnum DS PowerCircuit Breakers

    Eatons Type MDS power circuitbreakers constitute a complete,modern and rugged line of low voltage

    power circuit breakers using EatonsDE-IONprinciple of arc extinction.The breaker family is distinguishedby its similarity of appearanceand operation frame to frame. Allframe sizes are either manually orelectrically operated. Refer to Tab 26for detailed information on MagnumDS low voltage power circuit breakers.

    Breaker Features

    Four Physical Frame Sizes

    Narrow, standard, double narrow anddouble to promote breaker applicationin compact modular enclosures and to

    improve enclosure density.

    Contacts

    Magnum DS has silver tungstenmoving contacts and silver graphitestationary contacts. The contactsprovide a long-wearing, low-resistancejoint. The contacts are protected fromarcing damage even after repeatedinterruptions by the heel-toe action,which causes the integral arcingcontacts to mate before the maincontacts part. The arcing contactsthen part last, striking the arc awayfrom the main contacts.

    The main contacts are of the butt typeand are composed of multiple fingersto give many points of contact withoutalignment being critical.

    Magnum DS Breaker Contacts(Arc Chutes Removed)

    Stored-Energy Mechanism

    A cam-type closing mechanismcloses the breaker. It receives itsenergy from a spring that can becharged by a manual handle on thefront of the breaker or by a universalelectric motor.

    Release of the stored energyis accomplished by manuallydepressing a button on the frontof the breaker or electrically energizinga releasing solenoid.

    Magnum DS Low Voltage Power CircuitBreakers have high withstand ratingsfrom 42 to100 kA to provide for maximumsystem coordination and selectivity.

    Magnum MDSL Current Limiting PowerCircuit Breakers have integral currentlimiters to provide interrupting ratingsof 200 kA at 600 Vac.

    Magnum MDSX Current Limiting PowerCircuit Breakers have fast openingcontacts to provide interrupting ratingsup to 200 kA at 480 Vac without fuses.

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    10/54

    0.1-8

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    General Description010

    Arc Chute

    There are three basic means ofextinguishing an arc: lengtheningthe arc path; cooling by gas blast orcontraction; deionizing or physicallyremoving the conduction particles

    from the arc path.The DE-ION principle is incorporatedin all Magnum DS circuit breakers.This makes possible faster arcextinction for a given contact travel,ensures positive interruption andminimum contact burning.

    Levering Mechanism

    The worm gear levering mechanismis self-contained on the breakerdrawout element and engagesslots in the breaker compartment.A standard 3/8-inch (10 mm) driveset is used to lever the breakerbetween the connected, test and

    disconnected positions.

    Mechanical interlocking is arrangedso that levering cannot be accom-plished unless the breaker is in theopened position.

    Protection During Levering Operation

    When levering the breaker betweenthe connected, test and disconnectedpositions, the operator is protectedfrom contact with live parts by thebreaker door.

    True two-step stored energy closing:Refers to the sequence required tocharge and close the breaker.

    1. The breaker closing springs arecharged either through themanual-charging handle or bythe optional charging motor.The breaker is mechanically inter-locked to prevent closing of thebreaker until the closing springsare fully charged.

    2. With the closing springs fullycharged, the breaker can thenbe closed by pressing the manualclose pushbutton on the breaker,or by the optional spring releasecoil through a remote electricalsignal.

    This means that the energy requiredto open the breaker is always restoredfollowing a closing operation.

    Stored energy is energy held inwaiting, ready to open or close thebreaker within five cycles or less.The unique cam and spring designprovides necessary energy for a singleclose-open sequence as well as the

    energy for multiple charge-closeoperations such as this possiblesequence: charge-close-recharge-open-close-open.

    The closing springs are interlockedwith the breaker racking mechanismto ensure the closing springs aredischarged before the breaker canbe removed from the compartment.

    Provisions for padlocking: All breakersinclude provision for padlocking opento prevent electrical or manual closing.This padlocking can secure the breakerin the connected, test or disconnectedposition by preventing levering of the

    breaker.Ease of inspection and maintenance:Magnum DS breakers are designed formaximum accessibility and the utmostease of inspection and maintenance.

    Manually operated breakers:Manually operated breakers areequipped with a manual charginghandle to charge the closing springs.Manual closing and tripping pushbut-tons are used to operate the breaker.Remote closing and tripping can beaccomplished by installing optionalelectric spring release and shunt tripcoils (see Tables 20.1-10and 20.1-11for

    available control voltages, currentsand motor-operated spring chargingtimes). The breaker closing springsmust be charged manually, thenremote closing and tripping signalscan be sent to the breaker.

    Electrically operated breakers:Electrically operated breakers areequipped with a spring charging motorand electrically operatedspring release and shunt trip coils(see Tables 20.1-10and 20.1-11foravailable control voltages, currentsand motor-operated spring chargingtimes). The breaker manual charginghandle can be used to charge theclosing springs when power is notavailable to the charging motor.

    Optional Breaker Attachmentsand Accessories

    Shunt trip device (ST): Providesfor remote electrically controlledbreaker opening when energizedby a rated voltage input

    Spring charge motor (MOT):Charges the breaker closing springsautomatically, facilitating remote orlocal closing. The motor assemblyincludes its own cut-off switch thatchanges state at the end of thecharging cycle. This contact can bewired out for external indication

    Spring release device (SR):Providesfor remote electrically controlledbreaker closing when its coils areenergized by a rated voltage input

    Undervoltage release (UVR):Trips the breaker when an existingvoltage signal is lost or falls below

    an established threshold Auxiliary switch: Up to 6a/6b

    auxiliary individual dedicatedcontacts are available for customeruse to indicate if the breaker is inthe OPEN or CLOSE position

    Mechanical trip indicator flag:The red trip indicator flag pops outto provide local visual indicationwhen the Digitrip RMS trip unitacts to trip the breaker on an over-current condition. Available in twooptions: an interlocked version thatmechanically locks out the breakeruntil the indicator is manually resetand a non-interlocked version forindication only

    Bell alarm/overcurrent trip switch(OTS): Provides two Form C contactsthat change state when the DigitripRMS trip unit acts to trip the breaker.The contacts are available forexternal indication or customeruse and are manually reset by themechanical trip indicator

    Padlockable pushbutton cover:Permits padlocking hinged coverplates to block access to the PUSHON and PUSH OFF buttons on thebreaker faceplate

    Mechanical operations counter:

    Records mechanical operations ofthe breaker over its installed life

    Key off lock provisions: Enablesmounting of a single cylinder Kirk,Castell or Ronis Key Lock to lock thebreaker in the OPEN position

    Latch check switch: Provides oneForm C contact that changes statewhen the breaker is ready toclose. Can be wired to the springrelease device for fast transferapplications or wired for externalready-to-close indication

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    11/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    General DescriptionElectronic Trip Units011

    Magnum DS SwitchgearTrip Units

    Digitrip RMS trip unit. EatonsDigitrip RMS trip units feature adependent curve that is depicted in

    the nameplate by a blue shaded areaof the trip curve. The dependent curveaffords better protection flexibility.Additionally, all of the trip units have,as standard, thermal memory, 50/60 Hzoperation and thermal self-protectionat 90 C.

    Digitrip RMS integral microprocessor-based breaker overcurrent tripsystems: Provide maximum reliabilitywith true rms sensing as standard,gives excellent repeatability andrequires minimum maintenance.No external control source isrequired for its protective functions.

    Digitrip 1150+

    Trip functions: Magnum DS trip unitsprovide the maximum in flexibility andare available in the following configu-rations: LSI, LSIG, LSIA (ground faultalarm only). In each case, either theshort delay or instantaneous (not both)

    functions may be defeated. Thisreduces the need for spare breakerinventories and provides maximumusage of interchangeable breakers.

    Digitrip RMS 520: Enables the useras many as nine phase and groundcurrent protection settings for maxi-mum flexibility in trip-curve shapingand multi-unit coordination, and addszone selective interlocking.

    Digitrip RMS 520M: Adds phase,neutral and ground current meteringwith a four-character LCD displaywindow with 2% current meteringaccuracy and type LSIA alarm when

    ground fault settings are exceeded.Digitrip RMS 520MC: Adds communi-cation of trip values and breaker status(open, close and tripped). AddsArcflash Reduction MaintenanceSystem (ARMS).

    Digitrip RMS 1150+: Providesprogrammability for more sophisti-cated distribution systems. AddsArcflash Reduction MaintenanceSystem (ARMS).

    Increased protection and

    coordination capabilities Systems monitoring information

    including power factor, voltagecurrent, harmonic distortionvalues, and waveform capturewith a three-line, (eight charactersper line) LED display

    Two programmable contacts forcustomer use

    Time stamping of trip events forimproved troubleshooting anddiagnostics

    Accuracy of 1% on metered valuesand 2% on energy and power

    Systems diagnostic information

    Web enabled or PowerNetcommunications

    Breaker health menu

    Additional protection functions:

    Undervoltage/overvoltage

    Underfrequency/overfrequency

    Voltage unbalance

    Reverse power

    Zone selective interlocking: TheDigitrip RMS zone selective interlocking(ZSI) capability provides positivesystem coordination without timedelays. ZSI allows the breaker closestto the fault to trip without any preset

    time delay. The breaker closest to thefault trips first, while the remainderof the distribution system remainsonline, thus avoiding unnecessaryand costly downtime.

    The use of ZSI in Spot NetworkSystems is not recommended byEaton. See the discussion in section 18for the technical reasons why Eatondoes not recommend ZSI in SpotNetwork Systems.

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    12/54

    0.1-10

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    General DescriptionElectronic Trip Units012

    Arcflash ReductionMaintenance System

    The Arcflash Reduction MaintenanceSystem Maintenance Mode functionof the Digitrip 520MC and 1150+ can

    reduce arc flash incident energy that isgenerated on a fault condition. EatonsArcflash Reduction MaintenanceSystem employs a separate, dedicatedanalog trip circuit that eliminatesmicroprocessor latencies, resultingin clearing times that are faster thanstandard instantaneous tripping. Thisprovides superior arc flash reductionto competing systems that simplylower the standard instantaneouspickup set point.

    There are three ways to arm theMaintenance Mode Arc FlashReduction setting. One method is

    locally at the trip unit front panel. Forthe 520MC, the 2-position switch in theMaintenance Mode section of the tripunit is used. Turning the switch to theON position will arm the setting. Forthe 1150+, the local front keypad isused to enable the Maintenance Modesetting. The setting is located in theSYSTEM submenu of programmablesettings (PGM SET).

    For the second method of arming theMaintenance Mode function, a remoteswitch wired through the breakersecondary contacts can remotelyarm the Maintenance Mode setting. Ahigh-quality gold-plated or palladium

    contact is required in this application.A third method to arm the mainte-nance setting is via a communicationdevice. This can be accomplishedthrough a Power XpertGateway.A BIM (Breaker Interface Module),Power Xpert software or PowerNetsystem is another communicationmethod to arm the setting.

    For Magnum DS breakers, the ArcflashReduction Maintenance System settinghas five unique settings (2.5, 4.0, 6.0, 8.0,10.0 x In). To adjust this setting, a rotaryswitch on the trip unit face is providedfor the 520MC while the 1150+ trip unit

    uses its local keypad. For the SeriesNRX breakers, the Arcflash ReductionMaintenance System setting has aconstant setting of 5000 A.

    For all three arming methods, the520MC provides a blue LED to confirmthe Maintenance Mode function is on.In addition, there is also a normallyopen breaker contact that allows theuser to wire in an external stacklight orannunciator for remote indication. Forthe 1150+, the message MaintenanceMode Enabled will be shown on itsLED display. The 1150+ also has analarm relay that can be programmedto track the Maintenance Mode state.

    The Maintenance Mode function willprovide fast tripping even when theregular Instantaneous is set to OFF.The Instantaneous LED position isalso used to indicate a trip initiatedby the Maintenance Mode setting.

    The 520MC LCD display, if powered,will indicate with four dashes whilethe 1150+ will display the messageMaintenance Mode Trip.

    Arcflash Reduction Maintenance System

    The Arcflash Reduction MaintenanceSystem can be wired out to a separatelockable switch/light combinationmounted on the switchgear for easeof operation. Additionally, the switchcan be wired out to a remote stationfor operation outside the arc flashboundary of the switchgear, and thealarm can be wired to an optionalbeacon or audible device.

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    13/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20.1April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    Low Voltage Trip UnitSelection Data013

    Table 20.1-1. Digitrip Trip Units for Magnum DS and SB ANSI/UL Rated Power Circuit Breakers

    1 Over and undervoltage alarm or trip, overand underfrequency alarm or trip, voltageunbalance alarm or trip, reverse power tripand phase rotation alarm are included.

    2 1200 A maximum ground fault setting perUL/NEC.

    3 Test set for secondary injection.

    Legend: In = Rating Plug and Sensor Rating.Ir = Long Delay Pickup setting.

    Trip Unit Type Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+1

    Ampere RangeInterrupting rating at 480 Vrms sensing

    200600 0A42200 kAYes

    2006000 A42200 kAYes

    2006000 A42200 kAYes

    2006000A42200 kAYes

    Protection and Coordination

    Protection Ordering optionsfixed rating plug (In)overtemperature trip

    LI, LSI, LSIGYesYes

    LSI, LSIG, LSIAYesYes

    LSI, LSIG, LSIAYesYes

    LSI, LSIG, LSIAYesYes

    Longdelayprotection(L)

    Long delay pickupLong delay time I2t at 6 x IrLong delay time I4tIEEE curves

    0.41.0 x (In)224 secondsNoNo

    0.41.0 x (In)224 secondsNoNo

    0.41.0 x (In)224 secondsNoNo

    0.41.0 x (In)224 seconds15 secondsYes

    Long Delay Thermal MemoryHigh Load Alarm

    YesNo

    YesNo

    YesNo

    Yes0.51.0 x (Ir)

    Shortdelayprotection(S)

    Short delay pickupShort delay time I2t at 8 x IrShort delay time flatShort delay time ZSI

    2001000% x (Ir) & M1100500 ms100500 msYes

    2001000% x (Ir) & M1100500 ms100500 msYes

    2001000% x (Ir) & M1100500 ms100500 msYes

    2001000% x (Ir) & M1100500 ms100500 msYes

    Instanta-neousprotection(I)

    Instantaneous pickupmaking current releaseoff position

    2001000% x (In) & M1YesLSI & LSIG

    2001000% x (In) & M1YesYes

    2001000% x (In) & M1YesYes

    2001000% x (In) & M1YesYes

    Groundfaultprotection(G) 2

    Ground fault alarmGround fault pickupGround fault delay I2t at 0.625 x In

    No25100% x (In)100500 ms

    Yes25100% x (In)100500 ms

    Yes25100% x (In)100500 ms

    Yes24100% x (In)100500 ms

    Ground fault delay flatGround fault ZSIGround fault thermal memory

    100500 msYesYes

    100500 msYesYes

    100500 msYesYes

    100500 msYesYes

    Disable ground fault protection No No No No

    Neutral protection (N) Model LSI Model LSI Model LSI Model LSI

    System Diagnostics

    Cause of trip LEDsMagnitude of trip information

    YesNo

    YesYes

    Yes

    YesYes

    Yes

    Remote signal contactsProgrammable contacts

    NoNo

    YesNo

    YesNo

    YesYes

    System Monitoring

    Digital displayCurrent (% ) full scale sensor

    NoNo

    4-character LCDYes +/2%

    4-character LCDYes +/2%

    24-character LEDYes +/1%

    Voltage (%) L to LPower and energy (%)Apparent power kVA and demand

    NoNoNo

    NoNoNo

    NoNoNo

    Yes +/1%Yes +/2%Yes

    Reactive power kvarPower factorCrest factor

    NoNoNo

    NoNoNo

    NoNoNo

    YesYesYes

    Power qualityharmonics% THD, waveform capture

    NoNo

    NoNo

    NoNo

    YesYes

    System Communications

    TypePower supply in breaker

    NoN/A

    NoOptional

    INCOM/PowerNetStandard

    INCOM/PowerNet/TripLinkStandard

    Additional Features

    Trip log (three events)Electronic operations counter

    NoNo

    NoNo

    NoNo

    YesYes

    Testing method 3

    Waveform captureTest setNo

    Test setNo

    Test setNo

    Integral and test setYes

    Arcflash Reduction Maintenance SystemBreaker health monitorProgrammable relay functions

    NoNoNo

    NoNoNo

    YesNoNo

    YesYesYes 1

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    14/54

    0.1-12

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    Low Voltage Trip UnitSelection Data014

    Table 20.1-2. Magnum DS Breakers Digitrip Adjustable Trip Settings

    1 In= Rating plug valueIr= Long delay pickup setting x In

    2 I2t response

    Time/CurrentCharacteristic

    PickupSetting

    PickupPoint 1

    Time Bands,Seconds

    Long delay 0.4, 0.5, 0.6, 0.7,0.8, 0.9, 0.95, 1.0

    Intimes longdelay setting

    2, 4, 7, 10, 12,15, 20, 24

    Instantaneous Off, 2, 3, 4, 6, 8,

    10, M1

    Intimes

    instantaneoussetting

    Short delay 2, 2.5, 3, 4, 6, 8,10, M1

    Irtimes shortdelay setting

    0.1, 0.2, 0.3, 0.4, 0.5flat response0.1, 0.03, 0.05 2

    Ground fault 0.25, 0.3, 0.35, 0.4,0.5, 0.6, 0.75, 1.0

    Intimes groundfault setting

    0.1, 0.2, 0.3, 0.4, 0.5(flat response)0.1, 0.3, 0.5 2

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    15/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20.1April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    Series NRXGeneral Description015

    Series NRX

    Series NRX Breakers Have a CompactBut Powerful Size to Provide InterruptingRatings up to 65 kA at 480 Vac

    General Description

    The Series NRX provides the perfor-mance of a power circuit breaker65 kA interrupting at 480 Vacin thecompact size of a molded case breaker.It offers the protection and features ofa power circuit breaker, along withincreased flexibility at a portion ofthe size.

    All frame sizes are either electricallyor mechanically operated. The SeriesNRX is tested to 20,000 mechanicaloperations and 10,000 electricaloperationssignificantly higher thanindustry standards, such as UL andIEC, require or the capabilities of

    equivalent products on the market.Thus, your maintenance personnelcan do what needs to be done, insteadof spending valuable time inspectingand maintaining the breakers inthe system.

    In switchgear, its important that thebreaker be easily accessible duringscheduled equipment maintenance.The design of the breaker and cassetteenables full use of the breaker handleand cassette rails with a gloved hand,

    allowing electricians to remain in theappropriate PPE protective gear.

    The breakers ergonomic design alsomaximizes functionality. IndividualSeries NRX breaker door will open ina saloon or barn type of arrange-ment so that personnel can access oneof the side-by-side breakers withouthaving to interact with the other. Thebreakers handle allows the operatorto easily apply leverage across sevencomplete strokes (with an averageof only 21 lbs of force) chargingthe breaker quickly and easily, andmaking it easier to cycle when neededduring commissioning or scheduled

    maintenance. Series NRX breakers usea true two-step stored energy mecha-nism similar to Magnum DS breakers.

    The reduced weight of the Series NRXmakes it easier to handle during start-up and scheduled inspection. A three-pole, fully populated drawout breakerweighs only 54 lbs/24 kg.

    The Series NRX enables twice as manyfeeder breakers in a standard structurefor a reduction in overall assembly sizeof up to 50%.

    The small size, 10.00 inches (254.0 mm)wide by 10.70 inches (271.8 mm) deep

    by 14.20 inches (360.7 mm) high, ofthe Series NRX allows for much higherdensities of power circuit breakersin a structureup to eight breakersin a 24.00-inch (609.6 mm) widestructureand a 2.50-inch (63.5 mm)customer wireway. This means that twoSeries NRX breakers can be mountedside-by-side in the same space typicallyused for one Magnum DS breaker.

    The Series NRX breakers can also bemixed and matched with Magnum DSbreakers, increasing layout flexibilityand providing the ability to stackfeeder breakers around larger mainand tie breakers. See layout guide formore details.

    All optional Magnum DS breakerattachments and accessories are alsoavailable for the Series NRX breakers.Series NRX accessories can be quicklyinstalled at the job site, without anyspecial tools. Each breaker comes

    standard with an accessory tray; theneeded accessories simply plug andlock into the tray.

    The Series NRX uses one CT for thebreaker frame. This eliminates theneed to match CTs and rating plugs tochange the continuous current ratingof the breaker. For example, changingfrom 1200 to 800 A on previous breakerdesigns required changing CT from1200 to 800 A and changing the ratingplug from 1200 to 800 A. The SeriesNRX breaker simplifies this processby only requiring changing the 1200 Arating plug to 800 A. This is accom-plished through the Series NRXs

    Rogowski air core CT. The Rogowskicoil does not saturate like a traditionalferrous core CT, allowing the CT to beused across a broad current rangewith greater accuracy. One sensoraccommodates 2001200 A range.

    A full range of trip units, ranging frombasic protection (LSI or LSIG) to meter-ing, system diagnostics, protectiverelay functions and communications,complement the breaker offering.Two of the trip unit models, theDigitrip 520M and 1150, include(optional) Eatons Arcflash ReductionMaintenance System, built to reduce

    arc flash energy on a downstreamunit during system maintenance. Zoneselective interlocking is also available.

    When communication capabilityis required, the Series NRX breakerhas cassette-mounted modules,eliminating the need for readdressingreplacement breakers. These DIN railmounted modules save space andtime during installation and areavailable for field mounting capability.Modules for Modus and EatonsINCOM system are available withfuture releases for PROFIBUS andEthernet compatible with EatonsPower Xpert Architecture protocols.

    Refer to Tab 26for more detailedinformation on Series NRX breakers.

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    16/54

    0.1-14

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    Low Voltage Trip UnitSelection Data016

    Table 20.1-3. Digitrip Trip Units for Series NRX ANSI/UL Rated Circuit Breakers

    1 1200 A maximum ground fault setting per UL/NECT.2 Optional communications modules available: Ethernet (Web-browsing,

    Modbus TCP/IP and SNMP), Modbus RTU, INCOM, PROFIBUS DP.3 Test set for secondary injection.

    Legend: In = Rating Plug and Sensor Rating.Ir = Long Delay Pickup setting.

    Trip Unit Type Digitrip 520 Digitrip 520M Digitrip 1150

    Ampere rangeInterrupting rating at 480 Vrms sensing

    2001600A42 kAYes

    2001600 A42 kAYes

    2001600A42 kAYes

    Protection and Coordination

    Protection StylesFixed rating plug (In)Overtemperature trip

    LI, LSI, LSIGYesYes

    LSI, LSIG, LSIA, RLSI, RLSIG, RLSIAYesYes

    LSI, LSIG, LSIA, RLSI, RLSIG, RLSIAYesYes

    Long delayprotection (L)

    Long delay pickupLong delay time I2t at 6 x IrLong delay time I4tIEEE curves

    0.51.0 x (In)224 secondsNoNo

    0.51.0 x (In)224 secondsNoNo

    0.51.0 x (In)224 seconds15 secondsYes

    Long delay thermal memoryHigh load alarm

    YesNo

    YesYes (LSI only)

    Yes0.51.0 x (Ir)

    Short delayprotection (S)

    Short delay pickupShort delay time I2t at 8 x IrShort delay time flatShort delay time ZSI

    2001000% x (Ir)100500 ms100500 msYes (optional)

    2001000% x (Ir)100500 ms100500 msYes (optional)

    2001000% x (Ir)100500 ms100500 msYes (optional)

    Instantaneousprotection (I)

    Instantaneous pickupMaking current releaseOff position

    2001200% x (In)YesLSI and LSIG

    2001200% x (In)YesYes

    2001200% x (In) and M1YesYes

    Ground faultprotection (G) 1

    Ground fault alarmGround fault pickupGround fault delay I2t at .625 x In

    No25100% x (In)100500 ms

    Yes25100% x (In)100500 ms

    Yes24100% x (In)100500 ms

    Ground fault delay flatGround fault ZSIGround fault thermal memory

    100500 msYes (optional)Yes

    100500 msYes (optional)Yes

    100500 msYes (optional)Yes

    Disable ground fault protection No No No

    Neutral protection (N) Yes Yes Yes

    System Diagnostics

    Cause-of-trip LEDsMagnitude of trip information

    YesNo

    YesYes

    YesYes

    Remote signal contactsProgrammable contacts

    NoNo

    YesNo

    YesYes

    System Monitoring

    Digital displayCurrent (%)

    NoNo

    4-character LCDYes 2% full scale

    Color graphic LCDYes 1% of reading

    Voltage (%) L to LPower and energy (%)Apparent power kVA and demand

    NoNoNo

    NoNoNo

    Yes 1% of readingYes 2% of readingYes

    Reactive power kVARPower factorCrest factor

    NoNoNo

    NoNoNo

    YesYesYes

    Power qualityharmonics% THD, waveform capture

    NoNo

    NoNo

    YesYes

    System Communications

    Type

    Power supply

    No

    N/A

    Yes 2

    +24 Vdc

    Yes 2

    +24 VdcAdditional Features

    Trip logElectronic operations counter

    NoNo

    NoNo

    YesYes

    Testing method 3

    Waveform captureTest setNo

    Test setNo

    Integral and test setYes (current and voltage)

    Arcflash Reduction Maintenance SystemBreaker health monitorProgrammable relay functions

    NoNoNo

    Yes (RLSI, RLSIG, RLSIA)NoNo

    Yes (RLSI, RLSIG, RLSIA)YesYes

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    17/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20.1April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    Low Voltage Trip UnitSelection Data017

    Table 20.1-4. Digitrip Adjustable Trip Settings for Series NRX Breakers

    1 In= Rating plug valueIr= Long delay pickup setting x In

    2 I2t response.

    Time/CurrentCharacteristic

    PickupSetting

    PickupPoint 1

    Time Band,Seconds

    Long delay 0.5, 0.6, 0.7, 0.75,0.8, 0.9, 0.95, 1.0

    Intimeslong delay setting

    2, 4, 7, 10, 12, 15, 20, 24(at 6 times pickup value)

    Instantaneous 2, 3, 4, 6, 8, 10, 12 Intimes

    instantaneous setting

    Short delay 2, 2.5, 3, 4, 5, 6, 8, 10 Irtimesshort delay setting

    0.1, 0.2, 0.3, 0.4, 0.05(flat response)0.1, 0.3, 0.5 2

    Ground fault 0.25, 0.3, 0.35, 0.4,0.5, 0.6, 0.75, 1.0(1200 A maximum)

    Intimesground fault setting

    0.1, 0.2, 0.3, 0.4, 0.05(flat response)0.1, 0.3, 0.5 2

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    18/54

    0.1-16

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    General DescriptionMetering and Monitoring Devices018

    Power Xpert

    Incoming Line Power Meter

    See Tab 3.

    Power Xpert

    General Description

    The Power Xpert Meter 4000/6000/8000 Series monitors the criticalaspects of an electrical distributionsystem. This premier power qualitymetering instrument is simple to use,

    and is powerful, scalable and highlyflexible. The Power Xpert Meter4000/6000/8000 offers a new levelof intuitive user interface design,presenting critical electricaldistribution system informationin simple-to-navigate and easy-to-understand information architecture.

    The Power Xpert Meter 4000/6000/8000 graphic display visualizes theinformation from up to16 metermodules. The embedded Web serverdisplays complex power quality datausing standard Internet browsers andallows for device configuration fromthe browser.

    Both the local graphic display and theembedded Web server present realtime, historical and event informationin a browser-style graphical formatto help the user interpret key circuitinformation, such as:

    Current loading

    Voltage and power levels

    Power factor

    Energy usage

    I/O status

    Power quality measurements

    Harmonic plots

    Disturbance and transientwaveforms

    ITIC disturbance summary screen

    The Power Xpert Meter 4000/6000/8000 graphic display uses a simpletwist and click navigation controldial to easily navigate the menus andto drill down into increasing levelsof important detail. A back keyenhances the browser-like navigationof the graphic display.

    The Web server provides the energyand demand readings required to helpmanage the cost of energy. It alsoprovides critical information regard-ing power quality, such as harmonicdistortion, flicker, crest factor, K-Factor

    and more. For detailed information,refer to Tab 3.

    Power Xpert Meter 2000

    Power Xpert Meter 2000

    General Description

    The Power Xpert 2000 Series Meterpower quality instrument monitors themost critical aspects of an electricaldistribution system. This premierpower quality metering instrumentuses the latest in advanced technologyto make it simple to use, and ispowerful, scalable and highly flexible.The Power Xpert 2000 offers the samelevel of intuitive user interface designas the Power Xpert 4000/6000/8000Meter, presenting critical electricaldistribution system information ina simple-to-navigate and easy-to-understand information architecture.

    The embedded Web server displays

    comprehensive power quality datausing standard Internet browsers andallows for device configuration fromthe browser. The embedded Webserver presents real-time, historicaland event information in a browser-style graphical format to help the userinterpret information such as currentloading, voltage and power levels,power factor, energy usage, I/O statusand power quality measurements, aswell as harmonic plots. The embeddedWeb server also offers a waveformview to visualize steady-stateharmonic content, which is criticalfor power quality analysis.

    The Web server provides the energyand demand readings required to helpmanage the cost of energy.

    Applications

    Identify Power Quality Problems to Help:

    Protect motors from damage

    Preserve the integrity of processesand batches

    Prevent blown capacitor bank fuses Protect transformers and

    conductors from overheating

    Monitor Circuit Loading to Help:

    Avoid overloads and nuisanceoverload trips

    Maximize equipment use

    Manage emergency overloads

    Manage Energy Use to Help:

    Reduce peak demand charges andpower factor penalties

    Identify excessive energyconsumption

    For more details, see Tab 3.

    IQ 250/260

    Incoming Line Metering

    See Tab 3.

    IQ 250/260

    This microprocessor device providesmetering that meets ANSI C12.20revenue metering accuracy, and hascapabilities such as fast sampling rateand accurate metering for a full rangeof power attributes. In addition, theIQ 250 and IQ 260 Meters are preparedfor the future. Built-in slots allow forupgrades to capabilities yet to bedeveloped.

    Comprehensive metering

    High-end accuracy

    Self-test capability to validateaccuracy

    Large, easy-to-read display Local or remote configuration

    Industry-standard communicationprotocols

    Mix-and-match input/output options

    Integration with EatonsPower Xpert Architecture

    Field-upgradeable

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    19/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20.1April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    General DescriptionMetering and Monitoring Devices019

    IQ 130/140/150

    General Description

    The IQ 100 meter family providescapabilities you would not normallyexpect in affordable, compact meters,

    such as fast sampling rate andaccurate metering for a full rangeof power attributes. Providing thefirst line of defense against costlypower problems, Eatons IQ 100 serieselectronic power meters can performthe work of an entire wall of legacymetering equipment using todaystechnology.

    When space is at a premium, yetyou need ANSI C12.20 accuracy, theIQ 100 series fits the bill. These metersare ideal for electrical equipmentassemblies, machine control panels,such as panelboard and switchboardmains and feeders, low voltage metal-enclosed switchgear feeders andmotor control centers. Requiring farless space than other meters withsimilar functionality, IQ 100 seriesmeters fit into a standard ANSI orIEC cutout on a panelboard or otherelectrical equipment, and thereforefit easily into retrofit applications.

    Typical Applications

    Utility and commercial metering

    Substations, industrial facilities,power generation sites andcampuses

    Submetering

    Load studies and voltage recording Analog meter replacement

    Features and Benefits

    Measure and display real-timeinformation about critical powerparameters with a sampling rateof 400 samples per cycle

    Monitor power use and quality withANSI C12.20 accuracy (0.5%)

    Verify meter accuracy with KYZ testpulse self-certification capabilities

    Optional Modbus RTUcommunications

    Available as transducer only or

    with display Designed to accommodate

    upgrades

    Integrate into Eatons Power XpertArchitecture for a holistic systemlevel view

    For more information, refer to Tab 3.

    Breaker Interface Module II(BIMII)

    Local Subnetwork Display

    See Tab 4.

    Breaker Interface Module II (BIMII)

    The breaker interface module is apanel-mounted device that performsthe following functions:

    Monitors and displays parametersfrom Digitrip 1150+ circuit breakertrip unit. Supports as many as 50of these devices up to 10,000 ft

    (3048 m) away Communicates the information from

    these protective and energy moni-toring devices over a PowerNetnetwork to a computer or PLC

    CommunicationsFor remote power monitoring andsoftware, see PowerNet Tab 2.

    Low Voltage HighResistance GroundingSee Tab 36for more details.

    C-HRG Wall-Mounted Unit(Separately Mounted Resistors Not Shown)

    Where continuity of service is a highpriority, high-resistance grounding canadd the safety of a grounded systemwhile minimizing the risk of serviceinterruptions due to grounds. Theconcept is a simple one: provide a pathfor ground current via a resistance thatlimits the current magnitude, andmonitor to determine when anabnormal condition exists.

    This provides for maximum continuityof service, because no tripping occursfor the resistance limited ground fault.

    HRG can be installed as stand-aloneequipment (as shown in photo) or canbe integrated into Magnum DS lowvoltage switchgear; however, the useof HRG is restricted to systems thatdo not have single-phase or phase toneutral loads.

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    20/54

    0.1-18

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    Technical Data020

    Ratings

    Table 20.1-5. Voltage Ratings (AC)

    Table 20.1-6. Available Bus Ratings

    Table 20.1-7. Heat Loss Data 1

    Estimated Heat Loss Per Breaker (Watts)

    1 For lower than maximum load currents, wattloss may be estimated by reducing the fullload loss by the following:

    WL = (IL/IFL)2WFL

    Where:WL = Load WattsWFL = Full Load WattsIL = Actual Load CurrentIFL = Full Load Current

    2 Contact Eaton.

    Vertical section bus is sized permain cross bus maximum rating orby ANSI C37.20.1 Section 7.4.13 Table11 to a maximum of 5000 A. (4000 A in18.00-inch [457.2 mm] structure.)

    Note: In addition to the available bus

    bracings shown in Table 20.1-6,the bus has been tested for short-circuit values of 85,000 A for a full60 cycles.

    Closing Times of Magnum DSand Series NRX Breakers

    5 cycles or less

    SystemVoltage

    MaximumVoltage

    208/240

    480600

    254

    508635

    Cross BusAmpacity

    Bus BracingkA

    200032004000

    100, 150, 200

    500060008000

    10,000

    100, 150, 200

    BreakerFrame

    DrawoutMountingOnly

    800

    16002000

    150

    329374

    3200400050006000

    719749

    10002

    Estimated Heat Loss Per Structure (Watts) 1

    Loss is based on fully loaded vertical andcross bus rating in a structure as given below.

    Rating VerticalBus

    CrossBus

    200032004000

    41016231097

    28811631169

    50006000

    800010,000

    14102

    88612652

    2

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    21/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20.1April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    Technical Data021

    Table 20.1-8. Indoor 2000 A LVA Loss Analysis R2

    Notes: Full Load of Section or Breaker comes from the frame or bus ratings of the product.Actual Amperes is a loading profile over all the devices for the operating scenario of interest.Rating Factor is a value that appropriately weights the nominal losses at full load to the actual losses for the actual loading value.The formula is Rating Factor = (Actual Loading/Full Load Rating) x (Actual Loading/Full Load Rating).The Rating Factor is applied (multiplied) by the Full Load Loss Watts to get Net Watts for each item.See Table 20.1-7for Nominal heat loss data for devices and sections.

    Case 1 Double-Ended Losses Each Main Load of 50%

    Item No. Quantity Tie Open Load = 1806 AmperesDescription

    IFL Full LoadRating

    WFL WattsFull Load Loss

    IL Actual LoadingAmperes

    RatingFactor

    WL WattsItem Loss

    1 1 2000 A 480 Main Bus 2000 700 903 0.204 142.70

    2 1 2000 A Main M1 Breaker 2000 775 903 0.204 157.99

    3 1 2000 A Distribution Section 2000 700 903 0.204 142.70

    4 1 800AF/500AT MDS Feeder CB 800 150 350 0.191 28.71

    5 1 800AF/400AT MDS Feeder CB 800 150 180 0.051 7.59

    6 1 800AF/300AT MDS Feeder CB 800 150 200 0.063 9.38

    7 1 800AF/200AT MDS Feeder CB 800 150 73 0.008 1.25

    8 1 2000 A Tie and Section Bus 2000 675 0 0.000 0.00

    9 1 2000 A 480 Volt Distribution Bus 2000 700 903 0.204 1 42.70

    10 1 800AF/600AT MDS Feeder CB 800 150 403 0.254 38.06

    11 1 800AF/300AT MDS Feeder CB 800 150 175 0.048 7.18

    12 1 800AF/250AT MDS Feeder CB 800 150 150 0.035 5.27

    13 1 800AF/150AT MDS Feeder CB 800 150 75 0.009 1.32

    14 1 2000 A Main M2 Breaker 2000 775 903 0.204 157.99

    15 1 2000 A 480 Bus Main Bus 2000 700 903 0.204 142.70

    Total with Each Main at 50% Load 985.52

    Case 2 Single Ended Losses One Main Load of 100%

    Item No. Quantity Tie Closed Load = 1806 AmperesDescription

    IFL Full LoadRating

    WFL WattsFull Load Loss

    IL Actual LoadingAmperes

    RatingFactor

    WL Watts NetItem Loss

    1 1 2000 A 480 Main Bus 2000 700 1806 0.815 570.79

    2 1 2000 A Main M1 Breaker 2000 775 1801 0.811 628.45

    3 1 2000 A Distribution Section 2000 700 903 0.204 142.70

    4 1 800AF/500AT MDS Feeder CB 800 150 350 0.191 28.71

    5 1 800AF/400AT MDS Feeder CB 800 150 180 0.051 7.59

    6 1 800AF/300AT MDS Feeder CB 800 150 200 0.063 9.38

    7 1 800AF/200AT MDS Feeder CB 800 150 73 0.008 1.25

    8 1 2000 A Tie and Section Bus 2000 675 903 0.204 137.60

    9 1 2000 A 480 Volt Distribution Bus 2000 700 903 0.204 142.70

    10 1 800AF/600AT MDS Feeder CB 800 150 403 0.254 38.06

    11 1 800AF/300AT MDS Feeder CB 800 150 175 0.048 7.18

    12 1 800AF/250AT MDS Feeder CB 800 150 150 0.035 5.27

    13 1 800AF/150AT MDS Feeder CB 800 150 75 0.009 1.32

    14 1 2000 A Main M2 Breaker 2000 775 0 0.000 0.00

    15 1 2000 A 480 Bus Main Bus 2000 700 0 0.000 0.00

    Total with One Main at 100% Load 1720.99

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    22/54

    0.1-20

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    Technical Data022

    Magnum DS Switchgear Class UL 1066

    Magnum DS and Series NRX Low Voltage Power Circuit Breaker Family ANSI Rated for Switchgear Applications

    Table 20.1-9. Magnum DS Switchgear Class UL 1066 Low Voltage Power Circuit Breakers

    1 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS trip unit. Interruption ratings for non-automatic breakers are equalto the published short-time withstand rating. These interruption ratings are based on the standard duty cycle consisting of an open operation, a15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle forshort-time ratings consists of maintaining the rated current for two periods of 1/2 second each, with a 15-second interval of zero current betweenthe two periods.

    2 Magnum MDSL current limiting power circuit breaker with integral current limiters. Current limiter selected determines short-time and fixedinstantaneous trip rating. Maximum voltage rating is 600 Vac.

    3 Magnum MDSX current limiting power circuit breaker with fast opening contacts.4 Product to be tested. Contact Eaton for product rating.5 Series NRX uses the same sensors for all trip settings. No changes to sensors required.

    FrameAmperes

    BreakerType

    Frame Type rms Symmetrical Current Ratings kA50/60 Hz 1

    Short-TimeWithstandRating

    Fixed InternalInstantaneousTrip

    Available Current Sensorand Rating Plugs forDigitrip RMS Trip Unit(Establishes BreakerIn

    Rating)

    Interruptingat 254 Vac

    Interruptingat 508 Vac

    Interruptingat 635 Vac

    800 MDN-408MDN-508MDN-608MDN-C08

    NarrowNarrowNarrowNarrow

    425065

    100

    425065

    100

    42506565

    42506520

    18 x In

    200, 250, 300, 400, 600, 800

    MDS-408MDS-608MDS-808MDS-C08MDS-L08 2

    StandardStandardStandardStandardStandard

    426585

    100200

    426585

    100200

    426585

    100200

    42658585

    85

    NRX-408 5

    NRX-508 5

    NRX-608 5

    CompactCompactCompact

    858585

    425065

    353535

    42 kA at 254 Vac42 kA at 508 Vac35 kA at 635 Vac

    200, 250, 300, 400, 500, 600,800 5

    1600 MDN-416MDN-516MDN-616MDN-C16

    NarrowNarrowNarrowNarrow

    425065

    100

    425065

    100

    42506565

    42506530

    18 x In

    200, 250, 300, 400, 600, 800,1000, 1200, 1600

    MDS-616MDS-816MDS-C16MDS-L16 2

    MDS-X16 3

    StandardStandardStandardStandardStandard

    6585100200200

    6585100200200

    6585100200

    4

    658585

    30

    8530

    2000 MDN-620MDN-C20

    NarrowNarrow

    65100

    65100

    6565

    6535

    18 x In

    200, 250, 300, 400, 600, 800,1000, 1200, 1600, 2000

    MDS-620MDS-820MDS-C20MDS-L20 2

    MDS-X20 3

    StandardStandardStandardStandardStandard

    6585

    100200200

    6585

    100200200

    6585

    100200

    4

    658585

    30

    8530

    3200 MDS-632MDS-832MDS-C32

    StandardStandardStandard

    6585

    100

    6585

    100

    6585

    100

    658585

    85

    200, 250, 300, 400, 600, 800,1000, 1200, 1600, 2000,2500, 3000, 3200

    MDS-X32 3 Double 200 200 4 50 50

    4000 MDN-640MDN-840MDN-C40

    Double NarrowDouble NarrowDouble Narrow

    6585

    100

    6585

    100

    656565

    6585

    100

    2000, 2500, 3200, 4000

    MDS-840MDS-C40MDS-X40 3

    DoubleDoubleDouble

    85100200

    85100200

    85100

    4

    8510050

    50

    2000, 2500, 3200, 4000

    Standard Magnum DS

    Narrow Magnum DSDouble Magnum DSSeries NRX

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    23/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20.1April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    Technical Data023

    Table 20.1-9. Magnum DS Switchgear Class UL 1066 Low Voltage Power Circuit Breakers (Continued)

    1 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS trip unit. Interruption ratings for non-automatic breakers are equalto the published short-time withstand rating. These interruption ratings are based on the standard duty cycle consisting of an open operation, a15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle forshort-time ratings consists of maintaining the rated current for two periods of 1/2 second each, with a 15-second interval of zero current betweenthe two periods.

    2 Magnum MDSX current limiting power circuit breaker with fast opening contacts.3 Breaker applied in a tested fan-cooled enclosure.4 Product to be tested. Contact Eaton for product rating.

    Table 20.1-10. Magnum Breaker Control Device Application GuideVdc

    Table 20.1-11. Magnum Breaker Control Device Application GuideVac

    FrameAmperes

    BreakerType

    FrameType

    rms Symmetrical Current Ratings kA50/60 Hz 1

    Short-TimeWithstandRating

    Fixed InternalInstantaneousTrip

    Available Current Sensor & RatingPlugs for Digitrip RMS Trip Unit(Establishes Breaker InRating)Interrupting

    at 254 VacInterruptingat 508 Vac

    Interruptingat 635 Vac

    5000 MDS-850

    MDS-C50MDS-X50 23

    Double

    DoubleDouble

    85

    100200

    85

    100200

    85

    1004

    85

    10050

    50

    2500, 3200, 4000, 5000

    6000 MDS-C60 3 Double 100 100 100 100 3200, 4000, 5000, 6000

    Breaker Control DeviceNominal Voltage

    24 Vdc 32 Vdc 48 Vdc 125 Vdc 250 Vdc

    Shunt Trip (ST)

    Operational voltage rangePower consumption (inrush)Opening time

    Trip circuit 70110%(Required for 35 ms)Seconds

    1726 Vdc250 watts35 ms

    3453 Vdc250 watts35 ms

    77138 Vdc450 watts35 ms

    154275 Vdc450 watts35 ms

    Spring Release (SR)Operational voltage rangePower consumption (inrush)Closing time

    Close circuit 70110%(Required for 200 ms)Seconds

    1726 Vdc250 watts40 ms

    3453 Vdc250 watts40 ms

    77138 Vdc450 watts40 ms

    154275 Vdc450 watts40 ms

    Spring Charge Motor (MOT)Operational voltage rangeAmps (running)Amps (inrush)Power consumptionCharging time

    85110% voltageRunning % ofrunning seconds

    2026 Vdc12.0 A300%300 watts5 sec

    4153 Vdc5.0 A500%250 watts5 Sec

    94138 Vdc2.0 A600%250 watts5 Sec

    187275 Vdc1.0 A600%250 watts5 Sec

    Undervoltage Release (UVR)Operational voltage rangeDrop-out voltage rangePower consumption (inrush)Power consumption (continuous)

    Opening time

    85110% voltage3060% voltageRequired for 200 msRequired for 400 ms

    Seconds

    2026 Vdc714 Vdc250 watts18 watts

    70 ms

    2735 Vdc1019 Vdc275 watts15 watts

    70 ms

    4153 Vdc1429 Vdc275 watts18 watts

    70 ms

    94138 Vdc3375 Vdc450 watts10 watts

    70 ms

    187275 Vdc66150 Vdc450 watts10 watts

    70 msAuxiliary SwitchesMinimum loadContact rating

    Inductive load 0.5 A 0.5 A 0.5 A 0.25 A

    Breaker Control DeviceNominal Voltage

    120 Vac 240 Vac 415 Vac 480 Vac 600 Vac

    Shunt Trip (ST)Operational voltage rangePower consumption (inrush)Opening time

    Trip circuit 70110%(Required for 35 ms)Seconds

    77140 Vac450 VA35 ms

    146264 Vac450 VA35 ms

    Spring Release (SR)Operational voltage rangePower consumption (inrush)Closing time

    Close circuit 70110%(Required for 200 ms)Seconds

    77140 Vac450 VA40 ms

    146264 Vac450 VA40 ms

    Spring Charge Motor (MOT)Operational voltage rangeAmps (running)Amps (inrush)Power consumptionCharging time

    85110% voltageRunning % ofrunning seconds

    94140 Vac2.0 A600%250 VA5 Sec

    177264 Vac1.0 A600%250 VA5 Sec

    Undervoltage Release (UVR)Operational voltage rangeDrop-out voltage rangePower consumption (inrush)Power consumption (continuous)Opening time

    85110% voltage3060% voltageRequired for 200 msRequired for 400 msSeconds

    94140 Vac3376 Vac450 VA10 VA70 ms

    177264 Vac62144 Vac400 VA10 VA70 ms

    323457 Vac114249 Vac480 VA10 VA70 ms

    408528 Vac144288 Vac400 VA10 VA70 ms

    510660 Vac180360 Vac400 VA10 VA70 ms

    Auxiliary SwitchesMinimum loadContact rating

    Inductive load 10 A 10 A

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    24/54

    0.1-22

    For more information, visit: www.eaton.com/consultants CA08104001E

    April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    i

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    0

    1

    Magnum DS

    Technical Data024

    Table 20.1-12. Series NRX Breaker Control Device Application GuideVdc

    Table 20.1-13. Series NRX Breaker Control Device Application GuideVac

    Breaker Control DeviceNominal Voltage

    24 Vdc 32 Vdc 48 Vdc 125 Vdc 250 Vdc

    Shunt Trip (ST)Operational voltage rangePower consumption (inrush)

    Opening time

    Trip circuits 70110%(Required for 35 ms)

    Seconds

    1726 Vdc500 VA

    25 ms

    3453 Vdc530 VA

    25 ms

    77138 Vdc540 VA

    25 ms

    154275 Vdc515 VA

    25 msSpring Release (SR)Operational voltage rangePower consumption (inrush)Closing time

    Trip circuits 70110%(Required for 200 ms)Seconds

    1726 Vdc500 VA25 ms

    3453 Vdc530 VA25 ms

    77138 Vdc540 VA25 ms

    154275 Vdc515 VA25 ms

    Spring Release Motor (MOT)Operational voltage rangeAmperes (running)Amperes (inrush)Power consumptionCharging time

    Trip circuits 85110%Running % of runningSeconds

    2026 Vdc5 A500%150 VA3 seconds

    4153 Vdc3 A500%150 VA3 seconds

    94138 Vdc1 A500%150 VA3 seconds

    187275 Vdc1 A1000%280 VA4 seconds

    Undervoltage Release (UVR)Operational voltage rangeDrop-out voltage rangePower consumption (inrush)Power consumption (continuous)Opening time

    Trip circuits 85110%3560% voltageRequired for 200 msRequired for 400 msSeconds

    2026 Vdc814 Vdc500 VA5 VA50 ms

    2735 Vdc1119 Vdc620 VA5 VA50 ms

    4153 Vdc1729 Vdc850 VA5 VA50 ms

    94138 Vdc4494 Vdc890 VA5 VA50 ms

    187275 Vdc88132 Vdc910 VA5 VA50 ms

    Auxiliary Switches

    Minimum loadContact rating

    Inductive load 0.5 A 0.25 A

    Breaker Control DeviceNominal Voltage

    120 Vac 240 Vac 415 Vac 480 Vac 600 Vac

    Shunt Trip (ST)Operational voltage rangePower consumption (inrush)Opening time

    Trip circuits 70110%(Required for 35 ms)Seconds

    77140 Vac540 VA25 ms

    146264 Vac500 VA25 ms

    Spring Release (SR)Operational voltage rangePower consumption (inrush)Closing time

    Trip circuits 70110%(Required for 200 ms)Seconds

    77140 Vac540 VA25 ms

    146264 Vac500 VA25 ms

    Spring Release Motor (MOT)Operational voltage rangeAmperes (running)Amperes (inrush)Power consumptionCharging time

    Trip circuits 85110%Running % of runningSeconds

    94140 Vac2 A300%280 VA3 seconds

    177264 Vac1 A1000%280 VA4 seconds

    Undervoltage Release (UVR)Operational voltage rangeDrop-out voltage rangePower consumption (inrush)Power consumption (continuous)Opening time

    Trip circuits 85110%3560% voltageRequired for 200 msRequired for 400 msSeconds

    94138 Vac4494 Vac890 VA5 VA50 ms

    177264 Vac84125 Vac910 VA5 VA50 ms

    323457 Vac145228 Vac960 VA5 VA50 ms

    408528 Vac168288 Vac800 VA8 VA50 ms

    510660 Vac210360 Vac800 VA12 VA50 ms

    Auxiliary SwitchesMinimum loadContact rating

    Inductive load 10 A

  • 7/26/2019 Feasibility Studies for Small Scale Hydropower Additions-17

    25/54

    CA08104001E For more information, visit: www.eaton.com/consultants

    20.1April 2015

    Metal-Enclosed Drawout SwitchgearLow Voltage

    Sheet 20

    Magnum DS

    Technical Data025

    Ratings

    The narrow-band characteristic curveallows close coordination with DigitripRMS tripping devices. Repeatability iswithin 2%.

    The maximum breaker current ratingfor any breaker frame size is deter-mined by the rating of the sensor used.

    The breaker current rating for anyframe size can be changed by simplychanging the sensors and associatedrating plug, which are easily removedfrom the breaker drawout element.The wide range of long-delay pickupmakes one set of sensors more flexibleon a wider range of loads. The DigitripRMS itself need not be changed whenthe associated sensors and ratingplugs are changed.

    Eatons Digitrip RMS can be suppliedin various combinations of fourindependent, adjustable, overcurrentprotection functions:

    Long delay (L)

    Instantaneous (I)

    Short delay (S)

    Ground (G)

    Ground alarm only (A)

    Every Eaton Magnum DS trip unitcomes standard with LSI characteris-tics. Optional ground (G) or groundalarm (A) may also be provided.These trip units also provide theability to defeat instantaneous toprovide LS protection only. In addition,short delay protection may be set to