FC360 Panel Configurator FC360 Desktop Editor Operation...

34
FC360 Panel Configurator FC360 Desktop Editor Operation Manual A6V10450595_en--_a Building Technologies 2016-07-22 Control Products and Systems

Transcript of FC360 Panel Configurator FC360 Desktop Editor Operation...

Page 1: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

FC360 Panel Configurator

FC360 Desktop Editor

Operation Manual

A6V10450595_en--_a Building Technologies 2016-07-22 Control Products and Systems

Page 2: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Legal notice

Legal notice Technical specifications and availability subject to change without notice. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724-2424 www.siemens.com/buildingtechnologies Edition: 2016-07-22 Document ID: A6V10450595_en--_a © Siemens Switzerland Ltd, 2016

2 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 3: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Table of Contents

1 About this document ............................................................................. 5 1.1 Applicable documents ................................................................................. 6 1.2 Abbreviations .............................................................................................. 7 1.3 Download center ......................................................................................... 7 1.4 History of changes ...................................................................................... 8 1.5 Cyber security disclaimer ............................................................................ 8

2 Introduction .......................................................................................... 9

3 Installation ......................................................................................... 10 3.1 Connect PC to panel ..................................................................................10 3.2 Start software ............................................................................................10

3.2.1 ‘FC360 Panel Configurator’ .........................................................10 3.2.2 'FC360 Desktop Editor' ...............................................................11

3.3 Exit software ..............................................................................................11

4 GUI ................................................................................................... 12 4.1 Overview of program window .....................................................................12 4.2 Task card ..................................................................................................13 4.3 Toolbar ......................................................................................................14

4.3.1 'FC360 Panel Configurator' .........................................................14 4.3.2 'FC360 Desktop Editor' ...............................................................14

5 Program operation .............................................................................. 15 5.1 'Site' task card ...........................................................................................15 5.2 'Detection & Control' task card ...................................................................18

5.2.1 Configure loop / stub ...................................................................19 5.2.2 Configure Onboard IO .................................................................24 5.2.3 Configure output card (4M) .........................................................25 5.2.4 Configure communication interface .............................................26

5.3 'Cause & Effect' task card ..........................................................................27 5.4 'Administration' task card ...........................................................................28 5.5 'Other Settings' task card ...........................................................................30

6 Troubleshooting ................................................................................. 33 6.1 PC disconnect from panel ..........................................................................33

3 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 4: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

4 | 34

Page 5: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

About this document Applicable documents 1

1 About this document Goal and purpose This document describes the configuration of FC360 fire detection system by using ‘FC360 Panel Configurator’ and 'FC360 Desktop Editor'.

Scope The information in documents A6V10421795 is prerequisite for configuration of the fire detection system with ‘FC360 Panel Configurator’ and 'FC360 Desktop Editor'.

Target groups The information in this document is intended for the following target groups:

Target group Activity Qualification

Commissioning personnel ● Configure the product at the place of installation according to customer-specific requirements.

● Check the product operability and release the product for use by the operator.

● Searches for and corrects malfunctions.

● Has obtained suitable specialist training for the function and for the products.

● Has attended the training courses for commissioning personnel.

Maintenance personnel ● Carries out all maintenance work. ● Checks that the products are in

perfect working order. ● Searches for and corrects

malfunctions.

● Has obtained suitable specialist training for the function and for the products.

Document identification The document ID is structured as follows: A6Vxxxxxxxx_aaAA_vv A6Vxxxxxxxx_--AA_vv A6Vxxxxxxxx_aa--_vv A6Vxxxxxxxx_----_vv

ID coding1 Description

A6Vxxxxxxxx

STEP-ID generated by the STEP system

_ Separator

aa Language abbreviation in accordance with ISO 639-1

AA Country abbreviation in accordance with ISO-3166-1

-- Multilingual or international

vv Document version, single or double digit: a, b, …z; aa, ab, …az; ba, bb, …bz; etc.

1 Some documents have different ID that are generated by an earlier system. There are also documents with up-to date ID codes along with additional features in the designation.

5 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 6: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

About this document Applicable documents 1

ID code Examples

ID_languageCOUNTRY_version -- = multilingual or international

A6V10215123_deDE_a A6V10215123_en--_a A6V10315123_----_a

Date format The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD).

Reference document and source language ● The source language of this document is English (en). ● The reference version of this document is the international version in English.

The international version is not localized. The reference document has the following designation: ID_en--_x x = version, en = English, -- = international

Conventions for text marking Markups Special markups are shown in this document as follows:

⊳ Requirement for a behavior instruction

1. 2.

Behavior instruction with at least two operation sequences

– Version, option, or detailed information for a behavior instruction

⇨ Intermediate result of a behavior instruction

⇨ End result of a behavior instruction

● Numbered lists and behavior instructions with an operation sequence

[➙ X] Reference to a page number

'Text' Quotation, reproduced identically

<Key> Identification of keys

> In addition to mathematical operator, for identification between steps in a sequence, e.g., 'Menu bar' > 'Help' > 'Help topics'

Supplementary information and tips

The 'i' symbol identifies supplementary information and tips for an easier way of working.

1.1 Applicable documents

Number Name

A6V10421795 Technical manual of FC361-xx

6 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 7: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

About this document Abbreviations 1

1.2 Abbreviations

Abbreviations Explication

AVC Alarm Verification Concept

EOL End of Line

MCP Manual Call Point

PSU Power Supply Unit

PMI Person Machine Interface

EVAC Evacuation

GUI Graphical User Interface

EMC Electro Magnetic Compatibility

1.3 Download center You can download various types of documents, such as data sheets, installation instructions, and license texts via the following Internet address: http://siemens.com/bt/download Enter the document ID in the 'Find by keyword' input box.

You will also find information about search variants and links to mobile applications (apps) for various systems on the home page.

7 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 8: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

About this document History of changes 1

1.4 History of changes The reference document's version applies to all languages into which the reference document is translated.

The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version.

The table below shows this document’s history of changes:

Version Edition date Brief description

a 2016-07-22 First version

The language versions and country variants produced by a local company have the same modification index as the corresponding reference document. They are not however included in the table below.

The table below shows the published language versions and country variants with the corresponding modification index:

Modification index en_-- de_-- fr_-- it_-- es_--

a X - - X -

X = published

- = no publication with this modification index

1.5 Cyber security disclaimer Products, solutions and services from Siemens include security functions to ensure the secure operation of building automation and control, fire safety, security management, and physical security systems. The security functions on these products, solutions and services are important components of a comprehensive security concept. Drafting, implementing and managing a comprehensive and up-to-date security concept, customized to individual needs, is nevertheless necessary, and may result in additional plant- or site-specific preventive measures to ensure secure operation of your site regarding building automation and control, fire safety, security management, and physical security. These measures may include, for example, separating networks, physically protecting system components, user training, multi-level defensive measures, etc. For additional information on security as part of building technology and our product, solution and service offerings, please contact your Siemens sales representative or project department. We strongly recommend to always comply with our security advisories on the latest security threats, patches and other related measures. http://www.siemens.com/cert/en/cert-security-advisories.htm

8 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 9: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Introduction 2

2 Introduction Two tools are used to configure FC360 system easily and conveniently: ● FC360 Panel Configurator ● FC360 Desktop Editor The below table describes the functions of the tools:

Tools Functions

FC360 Panel Configurator

● Online configuration ● Apply configuration ● Backup configuration ● Restore configuration ● Reset alarm counter ● Synchronize system time

FC360 Desktop Editor

● Update firmware ● Modify configuration file

‘FC360 Desktop Editor' is available at www.siemens.com/buildingtechnologies/Cerberus-fit. ‘FC360 Panel Configurator' is integrated in the panel.

9 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 10: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Installation Connect PC to panel 3

3 Installation

3.1 Connect PC to panel A PC is required for most commissioning, maintenance and repair work. The figure below shows the connection between PC and panel.

X26 Terminal of PC connection 1 Cable, type CAT 5 or CAT 7, crossover, max. 100 m

WARNING

Risk to system integrity through unauthorized access Malfunction and not ready for alarm activation ● Access to the station only with direct PC connection according to document

A6V10421795 and A6V10450595. ● Connection to networks is expressly prohibited.

Adobe Flash Player is required on PC.

3.2 Start software

3.2.1 ‘FC360 Panel Configurator’ 'FC360 Panel Configurator' can be started as follows:

1. Open a web browser.

2. Enter web address with: http://fc360.siemens.com or http://192.168.251.100

3. Enter password (9999).

4. Click 'Engineering tool'. The tool is open.

X2611

10 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 11: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Installation Exit software 3

3.2.2 'FC360 Desktop Editor' 'FC360 Desktop Editor' can be started as follows:

1. Double click the software shortcut icon on the desktop or

– In the taskbar, click 'Start' > 'Programs' > 'Siemens' > 'FC360' > 'FC360 Desktop Editor'.

2. Select 'Language:'.

3. Click 'Enter'.

4. Select 'Create a new configuration' for self training purposes or 'Open an existing configuration' for real modification:

– If the 'Create a new configuration' is selected, select 'Country settings:' and then detector line topology. Click 'OK' to finish.

– If the 'Open an existing configuration' is selected, a dialog window is open. Select a desired file and click 'Open'.

'FC360 Desktop Editor' is open and ready for modification.

3.3 Exit software Exit the tools as follows: ● In the menu bar, click 'File' > 'Exit'. ● Click the 'X' button in the title bar. The software reminds you to save the changes before exiting.

11 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 12: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

GUI Overview of program window 4

4 GUI

4.1 Overview of program window

1 Title 2 Task cards 3 Information on the selected task card 4 Toolbar 5 Quick guide 6 Information on country and access level 1

1 Applies to 'FC360 Panel Configurator' only.

12 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 13: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

GUI Task card 4

4.2 Task card

Task Function

Site Configures site information.

Detection & Control Modifies device property and configures site specific setup (i.e. zone and section assignment).

Cause & Effect Configures logic controls.

Administration 1 ● Changes password of access levels 2 / 3 / 3.1. ● Uploads event memory from panel to PC. ● Uploads test report from panel to PC. ● Uploads / downloads user manuals, engineering

manuals and site document. Other settings Configures special settings.

1 Applies to 'FC360 Panel Configurator' only.

13 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 14: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

GUI Toolbar 4

4.3 Toolbar

4.3.1 'FC360 Panel Configurator'

Tool Function Apply Downloads the current configuration to the panel (takes effect

immediately). Backup There are two options:

● Backup current panel’s configuration to PC ● Backup all changes in current browser to PC

Restore Restores / downloads an existing configuration from PC to panel.

About Shows 'FC360 Panel Configurator' version, Panel software version, Output card (4M) version and P2 UART version.

Logout Logs out of 'FC360 Panel Configurator'.

The panel restarts automatically if you apply configuration or restore an existing configuration to panel.

4.3.2 'FC360 Desktop Editor'

Tool Function

New Creates a new configuration (for self training purpose).

Open Opens an existing configuration.

Save as Saves an existing configuration.

Update Firmware Updates panel firmware.

About Shows ‘FC360 Desktop Editor’ version, Panel software version, Output card (4M) version, P2 UART version.

The panel restarts after firmware is updated and must be at access level 3.

14 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 15: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Site' task card 5

5 Program operation This chapter describes how to configure the FC360 fire alarm system.

5.1 'Site' task card

Command Functionality

Reset alarm counter 1 Sets alarm count to 0.

1 Applies to 'FC360 Panel Configurator' only.

Field Functionality

Name Inputs site name.

Installer name 1 Inputs installer name.

Contact tel. 1 Inputs contact telephone (only number 0…9 possible).

Service reminder enable ● Checkbox activated: 'Service Date' field is indicated, input valid date, due date of next service, 'Service needed' message is displayed on panel.

● Checkbox deactivated (default): No service reminder.

15 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 16: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Site' task card 5

Field Functionality

Timed channel active The output is activated at the set time if the logic control between 'Timed Channel' (Cause) and outputs (Effect) in the 'Cause & Effect' task card is configured.

Timed channel inactive The output is deactivated at the set time if the logic control between 'Timed Channel' (Cause) and outputs (Effect) in the 'Cause & Effect' task card is configured.

Addressable sounders tone 1

Selects tone type: ● Continuous tone (default for tone 1) ● 1s intermittent (default for tone 2) ● Sweep down ● Slow whoop 0.5s pause ● 500Hz pulsing ● 500Hz intermittent ● 500Hz continuous ● 560Hz alternating ● 420Hz intermittent ● Slow whoop 025s pause ● 970Hz 1s pause The selected tone type is selectable in the 'Cause & Effect' task card.

Addressable sounders tone 2

See above.

AVC T1 time Selects reaction time T1 from the following: ● 0.5min ● 1min ● 1.5mins ● 2mins ● 2.5mins ● 3mins (default) ● 3.5mins ● 4mins

16 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 17: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Site' task card 5

Field Functionality

AVC T2 time Selects investigation time T2 from the following: ● 2mins ● 2.5mins ● 3mins ● 3.5mins ● 4mins ● 4.5mins ● 5mins (default) ● 5.5mins ● 6mins ● 6.5mins ● 7mins ● 7.5mins ● 8mins ● 8.5mins ● 9mins ● 9.5mins ● 10mins Allowed time under EN 54-2 is T1+T2 ≤10 min.

Timed switching to unmanned

● Checkbox activated: Automatically switches from 'Manned' to 'Unmanned'. You can set switching time to 'Unmanned'.

● Checkbox deactivated (default): Does not automatically switch from 'Manned' to 'Unmanned'.

1 The information is displayed on the panel.

17 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 18: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Detection & Control' task card 5

5.2 'Detection & Control' task card

1 Toolbar 2 Information view on the selected task card 3 Devices icons 1 4 'Device Properties' view 5 Task cards

Command Functionality

Edit device 1 Checked: devices icons and 'Add sounder base' & 'Delete device' commands are displayed. You can drag the icons to the information view if you want to add a new device. Unchecked: devices icons and 'Add sounder base' & 'Delete device' commands are not displayed. You cannot add / delete new device.

Add sounder base 1 Add sounder base to a detector.

Delete device 1 Delete a device.

Link to cause & effect Links to corresponding logic control for the selected device or zone.

Clear highlight Clears all the highlighted lines. Search device Inputs device ID to search device.

1 Applies to 'FC360 Desktop Editor' for self training purpose only.

You MUST NOT add / remove devices in an existing configuration!

18 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 19: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Detection & Control' task card 5

Task Functionality

Loop Configures devices on the loop.

Stub 1 Configures devices on the stub1.

Stub 2 Configures devices on the stub2.

Onboard IO Configures sounder lines, programmable IO, relays on mainboard.

Output card 4M Configures outputs on output card (4M).

Com. interface Configures RS232 module.

The loop view and stub1 / stub2 view cannot be configured simultaneously. It depends on the C-NET topology.

5.2.1 Configure loop / stub

The 'Loop' task card or 'Stub 1' / 'Stub 2' task card configure all connected field devices on C-NET. After the panel executes 'Auto-configure', the zones and sections are created automatically and all connected devices are assigned to corresponding zones and sections with the default settings. After successfully logging in to 'FC360 Panel Configurator', you can modify the zone number, zone type, zone text, section number and section text. Some specified parameters for a device can be modified in 'Device Properties' view.

Detector parameter set

Devices Parameters Functionality OP720 Sensitivity Selects sensitivity from the following:

● 01: Standard (Default) ● Sensitive

HI720 Detection method Selects detection method from the following: ● A2S ● A2R (Default)

HI722 Detection method Selects detection method from the following: ● A2S (Default) ● A2R

19 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 20: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Detection & Control' task card 5

Devices Parameters Functionality

OH720 Sensitivity Selects sensitivity from the following: ● Robust (Default) ● Sensitive

OOH740 Parameter set Selects parameter set from the following: ● (OOT): Balanced (Default) ● (OOT): Harsh ● (OOT): Sensitive

OOHC740 Parameter set Selects parameter set from the following: ● (OOT): Sensitive ● Balanced (Default) ● Harsh

FDF241-9 Sensitivity Selects parameter set from the following: ● Robust (Default) ● 02: Universal ● Universal Fast ● Sensitive ● Sensitive Fast ● Rapid ● Motor Test Rig

FDL241-9 Sensitivity Selects parameter set from the following: ● 01: Standard (Default) ● 03: Sensitive ● 05:Very sensitive

Detailed information on 'AVC Function' and 'Type A Function' setting is available in document A6V10421795. See chapter 'Applicable documents [➙ 6]'.

Detailed description of the parameter sets is available in the documentation of the corresponding detector.

Sounder base

Device Parameter Functionality

DBS720 Volume Specifies sound level in the activated status. Selects volume from the following: ● High ● Medium

20 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 21: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Detection & Control' task card 5

Alarm sounder and interbase

Device Parameter Functionality

FDS221 FDS229 DBS721 DBS728 DBS729

Location Inputs location text.

Volume Specifies sound level in the activated status. Selects volume from the following: ● High ● Medium ● Low

External alarm indicator

Device Parameter Functionality

FDCAI221 Location Inputs location text.

Input module

Device Parameter Functionality

FDCI221 FDCI222

Location Inputs location text.

Short circuit monitoring enabled

● Checkbox activated (Default): monitors the input line for short circuits.

● Checkbox deactivated: input is not monitored for short circuits.

Inversion Selects inversion mode from the following: ● Normal (Default) ● Inversion

Input/output module

Device Parameter Functionality

FDCIO221 FDCIO222 FDCIO224

Location Inputs location text.

Short circuit monitoring enabled

● Checkbox activated (Default): monitors the input line for short circuits.

● Checkbox deactivated: input is not monitored for short circuits.

Inversion Selects inversion mode from the following: ● Normal (Default) ● Inversion

Output mode The output remains the following status after activation: ● Inactive: Off / Active: On (Default) ● Inactive: Off/ Active: Single Pulse 1s ● Inactive: Off / Active: Single Pulse 5s ● Inactive: Off / Active: Single Pulse 20s ● Inactive: On / Active: Off

21 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 22: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Detection & Control' task card 5

Device Parameter Functionality

Fail safe Defines the position of the output in case of error: ● Freeze (Default) ● Open ● Close

Output style (only for FDCIO221)

Selects output style from the following: ● Monitored output (Default) ● Dry contact

Zone Module

Device Parameter Functionality

FDCI723

Location Inputs location text.

Response time setting Selects response time from the following: ● Alarm:0s/Malfunction:10s (Default) ● Alarm:15.5s/Malfunction:10.5s ● Alarm:16s/Malfunction:11s ● Alarm:17.5s/Malfunction:12.5s ● Alarm:20s/Malfunction:15s ● Alarm:25s/Malfunction:20s ● Alarm:35s/Malfunction:30s ● Alarm:60s/Malfunction:55s ● Alarm: 75s / Malfunction: 70s ● Alarm:105s/Malfunction:100s ● Alarm:135s/Malfunction:130s ● Alarm:165s/Malfunction:160s ● Alarm:195s/Malfunction:190s ● Alarm:225s/Malfunction:220s ● Alarm:255s/Malfunction:250s

Line type Selects from the following: ● Current limiting alarm load (conventional detector line) ● Voltage limiting alarm load (Default, collective detector

line) EOL type Selects inversion mode from the following:

● EOL22 ● 20V transzorb diobe (Default) ● Ex line EOL22

Floor repeater Display / Floor repeater terminal

Device Parameter Functionality

FT2010 FT2011

Location Inputs location text.

User PIN ● Inputs device configuration PIN.

1. List faults 1 ● Checkbox activated: faults can be displayed. ● Checkbox deactivated (Default): faults are not

displayed.

22 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 23: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Detection & Control' task card 5

Device Parameter Functionality

2. Not used 1 Not used.

3. List isolations 1 ● Checkbox activated: isolations can be displayed. ● Checkbox deactivated (Default): isolations are not

displayed.

4. List technical messages 1

● Checkbox activated: technical messages can be displayed.

● Checkbox deactivated (Default): technical are not displayed.

5. Activate/deactivate sounders 1

● Checkbox activated: function ‘Silence / Resound’ is available via the function key.

● Checkbox deactivated (Default): function ‘Silence / Resound’ is not available via the function key.

6. Isolate RT fire 1 ● Checkbox activated: function ‘disable / enable all RT fire outputs’ is available via the function key.

● Checkbox deactivated (Default): function ‘disable / enable all RT fire outputs’ is not available via the function key.

1 This function is only available for FT2010.

Line separator

Device Parameter Functionality

FDCL221 Location Inputs location text.

See also 'Other Settings' task card [➙ 30]

23 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 24: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Detection & Control' task card 5

5.2.2 Configure Onboard IO

The panel mainboard has two sounder lines, four programmable IOs and three relays. The customer specified text can be modified in the information view. Some specified properties can be modified in ‘Device Property’ view.

Sounder line Customer text can be modified and no other properties are available.

Programmable IOs

Field Functionality

Programmable type Selects 'Programmable type' from the following: ● Digital Input (Default for input) ● Digital Output (Default for output)

Input usage Selects 'Input usage' from the following: ● class change (Default) ● Evacuation usage ● Reset command ● Access level 2 ● Disable RT Fire and RT Fault devices ● Activate manned ● Toggle between manned/ unmanned ● Initiate extra PSU fault ● Dailer (RT Fire Device) Fault ● Initiate fire brigade is called ● Acknowledge command

24 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 25: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Detection & Control' task card 5

Relays

Field Functionality

contact usage Selects 'contact usage' from the following: ● RT fire (Default for Relay 1) ● RT fault (Default for Relay 2) ● Fire control (Default for Relay 3)

5.2.3 Configure output card (4M)

The output card (4M) has four programmable outputs. The default setting for the outputs are: ● OUT1: RT fire ● OUT2: RT fault ● OUT3 / OUT4 : Sounder line The customer specified text can be modified in the information view. Two parameters can be configured in 'Device properties' view.

Field Functionality

Output usage Selects 'Output usage' from the following: ● Fire control ● RT fire ● RT fault ● Sounder line

Monitor creeping open / short

● Checkbox activated: additionally monitors creeping open/short of the output line

● Checkbox deactivated (default): creeping open/short of the output line is not monitored, but normal open/short is.

25 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 26: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Detection & Control' task card 5

5.2.4 Configure communication interface Communication interface configures the RS232 module connected to the event printer.

RS232 module

Text column is editable.

None of these parameters can be changed. Refer to these parameters to configure the external printer.

26 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 27: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Cause & Effect' task card 5

5.3 'Cause & Effect' task card

Logic controls are configured in the 'Cause & Effect' task card. After the panel executes 'Auto-configure' or you manually assign devices to corresponding zones, all possible causes are listed in the left column and all possible control outputs are listed on the top row. All possible controls between cause and effect are marked with circles or dropdown lists where the column and line intersect. The dropdown list configures all sounder lines or all EVAC zones. You can select 'Continuous' / 'Pulse' or 'Tone 1' / 'Tone 2’ from dropdown list. The priority for Tone 1 is higher than Tone 2 if Tone 1 and Tone 2 are activated simultaneously. The circle configures programmable IOs and relay outputs on the mainboard and outputs on the output card (4M) as well as all control zones. The grey circles indicate that it is not activated, while the green circles indicate it is activated. Click it to change the circle color to activate/deactivate the controls based on the layout plan with the adhesive labels.

Command Functionality

Clear all cause & effects Clears all controls set by user.

Clear highlight Clears all highlighted areas.

Max. 1000 logic controls can be configured.

27 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 28: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Administration' task card 5

5.4 'Administration' task card

This chapter is only available for 'FC360 Panel Configurator'.

Command Functionality

Synchronize system time with PC

Synchronizes panel time with PC time.

Restore factory setting Restores panel configuration to factory setting.

Save configuration summary

Exports the current configuration to a readable CSV file.

Change password of access level 2 / 3 / 3.1

Field Functionality

Old password Enters the old password.

New password Enters new password.

Confirm password Enters new password again.

Change Clicks to confirm.

28 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 29: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Administration' task card 5

System Info

Field Button Functionality

Event memory Upload to PC Uploads event memory to PC. The data is saved as a CSV file.

Test report Upload to PC Uploads test report to PC. The data is saved as a CSV file.

Quick guide

Field Button Functionality

User manuals Upload to PC Uploads user manuals to PC with ZIP file.

Download to panel (AL3) Downloads user manuals to panel with ZIP file. (Access level 3 password is required)

Eng. Manuals Upload to PC Uploads Eng. manuals to PC with ZIP file.

Download to panel (AL3) Downloads Eng. manuals to panel with ZIP file. (Access level 3 password is required)

Site documents Upload to PC Uploads site documents to PC with ZIP file.

Download to panel (AL3) Downloads site documents to panel with ZIP file. (Access level 3 password is required)

29 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 30: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Other settings' task card 5

5.5 'Other settings' task card

Field Functionality

MCP broken glass message 1 ● Checkbox activated: 'Glass Broken Device’ message will be displayed after detector line reset (ACK + Reset) when an MCP remains activated (i.e. glass not replaced).

● Checkbox deactivated: a new alarm will be reported when the panel restarts the detector line and the MCP is still activated.

Sounder outputs activation via silence/resound button

● Checkbox activated: All sounders can be activated / deactivated by <Silence / Resound> button at any time.

● Checkbox deactivated: All sounders can be deactivated / activated by <Silence / Resound> button only after they are activated.

Resound sounders on new alarm

● Checkbox activated: All sounders resound with a new alarm. ● Checkbox deactivated: All sounders do not resound with a new alarm.

Lamp test activation possible at access level I

● Checkbox activated: The lamp test function is available at access levels 1, 2 and 3.

● Checkbox deactivated: The lamp test function is available at access levels 2 and 3.

Acknowledge used as silence ● Checkbox activated: <Acknowledge> button silence all sounders. ● Checkbox deactivated: <Acknowledge> button does not silence all

sounders.

30 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 31: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Other settings' task card 5

Field Functionality

Acknowledge availability at access level I

● Checkbox activated: The <Acknowledge> button is available at access levels 1, 2 and 3.

● Checkbox deactivated: The <Acknowledge> button is available at access levels 2 and 3.

Block ackn./reset if RT is active

● Checkbox activated: <Acknowledge> and <Reset> button on FT2010 and programmed input used as ‘Acknowledge’ and ‘Reset’ are blocked if ‘Fire brigade is called’ is activated.

RT Fire LED activated by ● 'RT fire': The 'RT fire' LED is on if the RT fire relay is activated. ● 'Fire brigade is called': The 'RT fire' LED is on if a 'Fire brigade is called'

event occurs (the digital input is activated by an external contact.).

Internal AI operation in idle mode

● 'Normal: Off': The internal AI is off if the C-NET device is in normal status. ● 'Normal: flashing': The internal AI is flashing if the C-NET device is in

normal status.

Main power fault delay function

● 'On': Mains power delay function is available. ● 'Off': Mains power delay function is unavailable.

Main power delay time When mains power delay function is available, the delay time can be selected from the following: ● 1 min ● 5 mins ● 10 mins ● 29 mins

Automatically adjust clock for daylight saving time

● Checkbox activated: Panel switches automatically between summer / winter time each year.

● Checkbox deactivated: Panel does not switch automatically between summer / winter time each year.

31 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 32: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Program operation 'Other settings' task card 5

Field Functionality

Enable DHCP server ● Checkbox activated: Panel distributes an IP address to PC. On PC side you can configure the network connection between PC and panel at the below window:

1. Obtain an IP address automatically (We recommend using the Windows

default setting) 2. Use the following IP address (not recommended)

– IP address: 192.168.251.xxx (xxx can be 1-254, 100 cannot be used) – Subnet mask: 255.255.255.0 (recommended) – Default gateway: 192.168.251.19 (recommended)

● Checkbox deactivated: Panel does not distribute an IP address to PC. On PC side, you must manually configure the network connection between PC and panel by selecting 'Use the following IP address'. See above.

Panel IP address: 192.168.251.100 (default, do not change)

Subnet mask 255.255.255.0 (default, do not change)

Default gateway 192.168.251.19 (default, do not change)

MCP cannot be disabled ● Checkbox activated: MCP cannot be disabled. ● Checkbox deactivated: MCP can be disabled.

1 The ‘Glass Broken Device’ message from an activated MCP disappears automatically 15 seconds after reset (i.e. replacement of glass).

The default value of each item is based on the country selection.

32 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 33: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Troubleshooting PC disconnect from panel 6

6 Troubleshooting

6.1 PC disconnect from panel The following information dialog is displayed if you are using 'FC360 Panel Configurator' and PC disconnects from the panel:

Action: 1. Check cable connection.

2. Click <OK>. 'FC360 Panel Configurator' restarts.

33 | 34 Building Technologies A6V10450595_en--_a

Fire Safety 2016-07-22

Page 34: FC360 Panel Configurator FC360 Desktop Editor Operation Manualdownload.solarelektro.nl/tps/branddetectie/siemens/cerberus Fit... · FC360 Panel Configurator FC360 Desktop Editor Operation

Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug +41 41-724 24 24 www.siemens.com/buildingtechnologies

© Siemens Switzerland Ltd, 2016 Technical specifications and availability subject to change without notice.

Document ID: A6V10450595_en--_a Edition: 2016-07-22