20
Failure Modes of Underground MV Cables: Failure Modes of Underground MV Cables: Electrical and Thermal Modelling P A Wallace M Alsharif DMH b D M Hepburn C Zhou COMSOL Conference Milan 2009 Presented at the COMSOL Conference 2009 Milan

Transcript of Failure Modes of Underground MV Cables:Failure Modes of Underground MV Cables ... · 2009. 12....

  • Failure Modes of Underground MV Cables:Failure Modes of Underground MV Cables:Electrical and Thermal Modelling

    P A WallaceM Alsharif

    D M H bD M HepburnC Zhou

    COMSOL Conference Milan 2009

    Presented at the COMSOL Conference 2009 Milan

  • What is This Nasty Looking Object?What is This Nasty Looking Object?

    COMSOL Conference Milan 2009

  • 3 Phase Paper Insulated Lead Covered (PILC) Cable3 Phase Paper Insulated Lead Covered (PILC) Cable

    COMSOL Conference Milan 2009

  • Medium Voltage Distribution NetworkMedium Voltage Distribution Network

    Between the HV transmission network.. ( long distance, 100s kV, frequently overhead)

    ..and the household electricity supply..(230 V, domestic)

    ..lies the MV distribution network.(moderate distances 10s kV frequently underground)(moderate distances,10s kV, frequently underground)

    COMSOL Conference Milan 2009

  • Inventory of MV cables by Year of InstallationInventory of MV cables by Year of Installation

    COMSOL Conference Milan 2009

    Supplied by ‘ a Utility Company’

  • A Legacy Infrastructure (in large Part..)A Legacy Infrastructure (in large Part..)

    A ‘utility company’ has 38000 km of MV cable within its area of operation.

    Much of the cable infrastructure is operating beyond its design life expectancyits design life expectancy.

    The current rate of replacement is 100 km/year The current rate of replacement is 100 km/year

    On-line condition monitoring sensors are being g ginstalled to detect Partial Discharge (PD) activity..

    ? ..but how to interprete the data?

    COMSOL Conference Milan 2009

  • Partial DischargePartial Discharge

    PD is a localized electricaldischarge that only partiallydischarge that only partiallybridges the insulation betweenconductors which may or maynot occur adjacent to anot occur adjacent to aconductor.

    COMSOL Conference Milan 2009

  • Partial Discharge Partial Discharge –– E Field in Discharging VoidE Field in Discharging Void

    fromBoggs, S. A. (1990) Partial Discharge - Part 111:Cavitv-Induced PD in Solid

    COMSOL Conference Milan 2009

    Dielectrics. IEEE Electrical Insulation Magazine, 1990-Vo1.6, No.6

  • Correlation between Cable Load and PD ActivityCorrelation between Cable Load and PD Activity

    From the same ‘Utility Company’

    COMSOL Conference Milan 2009

  • Two ModelsTwo Models

    A long time scale (hundreds of hours) thermal A long time scale (hundreds of hours) thermal model..

    ..will provide the background conditions for a..

    ..short time scale (20 ms!) electrostatic model.

    COMSOL Conference Milan 2009

  • Electrostatic ModelElectrostatic Model

    V V

    Vr

    E

    0

    Subject to BC

    Sheath : V = 0Conductors : V(t) = V0cos(wt + 2nπ/3) n = 0,1,2

    COMSOL Conference Milan 2009

  • Electric Field in PILC CableElectric Field in PILC Cable

    COMSOL Conference Milan 2009

  • Increased Field in Insulator VoidIncreased Field in Insulator Void

    COMSOL Conference Milan 2009

  • Tangential Component of Field within Insulation BeltTangential Component of Field within Insulation Belt

    COMSOL Conference Milan 2009

  • Thermal ModelThermal Model

    T ︶ onscontributi sheath and ︵conductor where

    sc

    p

    QQQ

    QTktTC

    c

    c ARIQ

    2

    2006:1-1-60287 IEC BS following s

    cs A

    QQ

    Subject to IC: T(t) = 288 KSubject to BC: Tboundary = 288K

    COMSOL Conference Milan 2009

    j boundary

  • Step Step ReponseReponse

    COMSOL Conference Milan 2009

  • Response to Real Load over One WeekResponse to Real Load over One Week

    Load Data from the usual ‘Utility Company’

    COMSOL Conference Milan 2009

    y p y

  • Temperature Distribution within CableTemperature Distribution within Cable

    COMSOL Conference Milan 2009

  • Comparisons requires with existing commercial Comparisons requires with existing commercial products, for example..products, for example..

    COMSOL Conference Milan 2009

  • Future WorkFuture Work

    Incorporate Thermo-Mechanical Effects into the plong term model.

    Run the short time scale model using thebackground conditions of temperature anddeformation established by the long term modeldeformation established by the long term model

    THANK YOUFOR YOUR ATTENTION

    COMSOL Conference Milan 2009