FacilityLong2C KEMA
-
Upload
tibin-joseph -
Category
Documents
-
view
221 -
download
0
Transcript of FacilityLong2C KEMA
-
7/29/2019 FacilityLong2C KEMA
1/2
Researchinfrastrusture(s):
KEMA KEMANederland
KEMAisanindependentcompanywithaninternational
reputationforhighleveltechnicalandbusinessconsultancy,
testing,inspections,certificationandresearchforbusinesses
intheenergyindustry,assistingover500clientsinmore
than70countries.KEMAhasestablishedofficesand
subsidiariesworldwideandemploysaround1,500fulltime
professionalsandleadingexpertsinmanyfacetsofthe
electricityindustry.With80yearsofexperience,KEMA
appliesglobalexperienceandregionalinsightinservingthe
completespectrumofparticipantsintheenergy
marketplaceandoffersafullrangeofservices.
InmanyEuropeancountries,ourexpertsconsultingteams
andresearchershavetakenaleadingroleinassisting
governments,agencies,utilitiesandcustomerswithitems
likerenewableenergy,energystorageandactualtopics
relatedtoCO2emissionandinnovativegridsolutions.KEMA
isoneoftheinitiatorsoftheEuropeanTechnologyPlatform
SmartGridsprogramme.
KEMAs
CEO
is
at
present
chaiman
ofthisplatform.KEMAhasbeenbuildingthePower
ElectronicLab(2008)andwilloperatethislabtogetherwith
ECN,UniversityofDelftandUniversityof
Eindhoven.
KEMAisinvolvedinnumerousrelevantEuropean(research)
projects.
WithintheDERRIprojectKEMAwillcontributeintestingof
largescaleRESinverters.KEMAwillprovideresearchaccess
tothealmostfinishedpublicprivatePowerElectronicsLab,
builtaroundauniquemediumvoltagebacktoback
converterthatcansimulateaprogrammablegridorload.
Web: www.kema.com
(NL)
PowerElectronicsLab (Arnhem)
ThePowerElectronicsLab(PEL)inArnhemtakesaunique
positionintheworldbecauseofthevoltageandpower
range.Firstofallitisessentialtounderstandthatthis
laboratoryisnotlikeanyofthealreadyexistingKEMA
laboratories,not
in
functionality,
purpose
nor
organisational
structure.Thelaboratoryisowned,andwillberun,bythe
independentfoundationcalledthe"stichtingEMVT
laboratorium".KEMAhas50%shareinthisfoundationand
thedutchgovernmenttheother50%.Theuseofthe
laboratoryfacilitieswillthereforealsoreflectthisratioand
beavailabletoKEMAfor50%ofthetimeatcommercial
ratesand50%ofthetimeforresearchactivities
coordinatedbyaDutchresearchinstituteonenergy,ECN,
togetherwith
the
technical
universities
in
Delft
and
Eindhoven.
Thelaboratoryinfrastructurehasbeendesignedtoenablea
varietyofelectricalcircuits,includingtheoptiontocirculate
powerwithinthelaboratorybyconnectingthevirtualgrid,
throughthedeviceundertest,backtothefeedinggrid.
Alternativelyalargediversityofpassiveloadsareavailablein
thelabandalreadysetuptobeeasilyconnectedtotestany
circuit.
Afullyequippedmeasuringsystemisprovidedinthesafety
ofthecommandroom.Moreover,thecommandroom
overlooksthelaboratoryflooronwhichthedeviceunder
testisclearlyvisible.Thelaboratoryisbuiltaroundafully
programmablepowerelectronicsconverterthatcaneither
createacustom
PQ
grid
or
represent
acustom
load.
The
specificationsofthiscentralpieceofequipmentare:
Threephase(plusneutralwire)powersystematlineline
voltagesupto3.3kV(3phasesindependentlycontrollable);
Bidirectionalpowerflowcapabilityof1MVA(four
quadrantoperation);
FundamentalpowerfrequencyadjustablefromDC 75Hz;
Overloadcapability1.25p.u.@10s,3p.u.@1s;
Harmonicvoltagedistortionupto2400Hz;
Dips,unbalance,voltageandfrequencyvariations,
interruptions.
Thelaboratoryisequippedwithflexibleresistive(0.5MW),
inductive(1MVAr)andcapacitive(1MVAr)loadsanda
connectionto
the
utility
grid
with
off
load
tap
changer
(400
V...4kV)toprovidemaximumflexibilityforR&Dandtesting.
Thegridhastwomainoperationmodes:
1)Firstisthebasicstaticoperationmodewithafixed
fundamentalfrequency,inwhichitispossibleto
superimposeawidevarietyofharmonicdistortionsontop
ofthebasefrequencytosimulateabadlypollutedgrid,ora
badlypollutedload(inreversepowerflowdirection).These
amplitudesofthefundamentalfrequency,aswellasthatof
theharmonicsvoltages,canbevariedonlineandareclosed
loopcontrolledtoalargeextent.
2)Secondly,thereisthedynamicmodeofoperation.Inthis
operationmodeallkindsofothergridphenomenacanbe
produced,e.g.voltageandfrequencyvariationswiththe
abilityto
include
voltage
dips,
phase
jumps
and
rapid
voltage
changes.
Theprogrammedgridwillalsobecapableofcopingwith
unbalancedloads/sourcesandstillprovidethecapabilityto
superimposeharmonicvoltagesandinstigatedynamic
networkphenomenaontoit.
Forthefutureitisenvisionedtocreateaconnectiontoa
RealTimeDigitalSimulator(RTDS)whichislocatedinDelft
UniversityofTechnologytofurtherfacilitateresearchonthe
interactionbetweenDERunitsandthepowersystem.
Web: www.kema.com