Facilities Access Service
Product Technical Specification RELEASE 3.0
This document forms part of NBN Co’s Wholesale Broadband Agreement which is a Standard Form of Access Agreement for the purposes of Part XIC of the Competition and Consumer Act 2010.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 2
NBN Co Limited
Facilities Access Service Product Technical Specification
21/12/2012 Release: 3.0
Copyright
This document is subject to copyright and must not be used except as permitted below or under the Copyright Act 1968 (Cth). You must not reproduce or publish this document in whole or in part for commercial gain without the prior written consent of NBN Co. You may reproduce and publish this document in whole or in part for educational or non-commercial purposes as approved by NBN Co in writing.
Copyright © 2012 NBN Co Limited. All rights reserved. Not for general distribution.
Environment
NBN Co asks that you consider the environment before printing this document.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 3
Contents
1 Scope and purpose ..................................................................................................... 4
1.1 Purpose................................................................................................................................ 4
1.2 Scope ................................................................................................................................... 4
1.3 Definitions ............................................................................................................................ 4
2 Introduction ................................................................................................................. 5
3 Product Description .................................................................................................... 6
3.1 Cross Connect ..................................................................................................................... 6
3.2 NBN Co Co-location ............................................................................................................ 6
3.3 NBN Co ODF Termination Point .......................................................................................... 6
3.4 Building Entry Service .......................................................................................................... 6
3.5 Relationship between different types of the Facilities Access Service ................................ 7
3.6 Examples of types of interconnection that can be achieved ............................................... 8
3.6.1 Cross Connects .................................................................................................... 8
3.6.2 Interconnection ..................................................................................................... 9
4 Technical Specifications ............................................................................................. 10
4.1 Cross Connects ................................................................................................................... 10
4.1.1 Point of carriage service handover between NBN Co Network and Customer Network 11
4.2 NBN Co Co-location ............................................................................................................ 12
4.2.1 Equipment rack specifications .............................................................................. 12
4.2.2 Cabling ................................................................................................................. 15
4.2.3 Power ................................................................................................................... 17
4.2.4 Earthing ................................................................................................................ 19
4.2.5 Electromagnetic interference................................................................................ 19
4.2.6 Test switched sockets .......................................................................................... 19
4.2.7 Allowed Equipment for NBN Co Co-location ........................................................ 20
4.2.8 Environmental ...................................................................................................... 21
4.2.9 Facilities................................................................................................................ 22
4.3 NBN Co ODF Termination Point .......................................................................................... 23
4.3.1 Building Entry Rights ............................................................................................ 23
4.3.2 Cabling ................................................................................................................. 23
4.3.3 Fibre Termination Trays ....................................................................................... 23
4.4 Building Entry Service .......................................................................................................... 25
4.4.1 Usage Scenarios .................................................................................................. 25
4.4.2 Technical Specifications ....................................................................................... 27
5 Glossary ....................................................................................................................... 30
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 4
1 Scope and purpose
1.1 Purpose
The purpose of this document is to set out the technical specifications for NBN Co’s Facilities Access Service.
1.2 Scope
This document relates to the Facilities Access Service only and may be varied by NBN Co from time to time in accordance with the Wholesale Broadband Agreement.
This document does not apply to NBN Co’s interim facilities access solution for Temporary POIs. Nor does it contain information regarding access to the buildings in which POI Sites or Aggregation Node Sites are located. For information regarding access to the buildings in which POI Sites or Aggregation Node Sites are located, please refer to section 3 of the Product Description for the Facilities Access Service.
This document forms part of the Wholesale Broadband Agreement. It should be read in conjunction with:
the Product Description for the Facilities Access Service;
the Service Levels Schedule which forms part of the WBA Product Catalogue;
the Price List that forms part of the WBA Product Catalogue;
the modules of the Wholesale Broadband Agreement; and
the NBN Co Operations Manual.
1.3 Definitions
A capitalised term used in this document has the meaning given to that term in the Glossary for this document.
If a capitalised term is not defined in the Glossary for this document, it has the meaning given to that term in the Dictionary for the Wholesale Broadband Agreement or the WBA Product Catalogue.
In this document, a reference to a “POI” is to be read and interpreted as a reference to a “POI (other than a Temporary POI)”, unless indicated otherwise.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 5
2 Introduction
The Facilities Access Service supports interconnection between the Customer Network and the NBN Co Network at each of the 121 Points of Interconnection. Each of the 121 Points of Interconnection are located within a POI Site.
The Facilities Access Service comprises one or more of the following:
Cross Connect; and
NBN Co Co-location; and
NBN Co ODF Termination Point; and
Building Entry Service
Each POI Site or Aggregation Node Site is located within a building or buildings that are classified as either a Type 1 Facility or a Type 2 Facility.
Please refer to the Product Description for the Facilities Access Service for more information describing the Facilities Access Service.
The Facilities Access Service is agnostic of end user access technology (fibre, wireless or satellite).
In accordance with the terms of the Wholesale Broadband Agreement, Customer may acquire the type (or types) of the Facilities Access Service which suits Customer’s interconnection requirements in respect of each POI.
Details about Building Entry Rights are also set out in the Product Description for the Facilities Access Service.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 6
3 Product Description
3.1 Cross Connect
Please refer to section 2.1 of the Product Description for the Facilities Access Service for a description of Cross Connects.
3.2 NBN Co Co-location
Please refer to section 2.2 of the Product Description for the Facilities Access Service for a description of NBN Co Co-location.
3.3 NBN Co ODF Termination Point
Please refer to section 2.3 of the Product Description for the Facilities Access Service for a description of NBN Co ODF Termination Point.
3.4 Building Entry Service
Please refer to section 2.4 of the Product Description for the Facilities Access Service for a description of Building Entry Service.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 7
3.5 Relationship between different types of the Facilities Access Service
By way of example only, Figures 2 and 3 below illustrate the relationship between the different types of the Facilities Access Service applicable, depending on whether the POI is established in: (1) a “POI Site with an Incorporated Aggregation Node Site” (as that term is defined in the Product Description for the Facilities Access Service) – see Figure 2; or (2) a “POI Site with an Annexed Aggregation Node Site” (as that term is defined in the Product Description for the Facilities Access Service”) – see Figure 3.
NBN Co
ODF
NBN Co
Equipment
Equipment
rack
Customer
Active
Equipment
Street
Pits & Duct
NBN Co
Co-location
POI Site with Incorporated Aggregation Node Site
Point of Interconnect
Physical
Access
NBN Co
Network
Cross Connects
ODF
Termination
Point
Building Entry
Service
(Customer to
acquire directly
from NBN Co
(Type 1) or
Underlying Facility
Provider (Type 2)
NNI
(Not provided as
part of Facilities
Access Service)
Figure 2: Relationship between different types of the Facilities Access Service at a POI Site with Incorporated Aggregation Node Site
NBN Co
ODF
NBN Co
Equipment
Equipment
rack
Customer
Active
Equipment
Street
Pits & Duct
NBN Co
Co-location
POI Site
Point of Interconnect
Physical
Access
NBN Co
Network
Building Entry
Service
(Customer to
acquire directly
from NBN Co
(Type 1) or
Underlying Facility
Provider (Type 2)
Cross
Connects
NBN Co
ODF
Annexed Aggregation Node Site
NNI
(Not provided as part of
Facilities Access Service)
ODF
Termination
Point
Inter Site
Links
Physical
Access
Figure 3: Relationship between different types of the Facilities Access Service at a POI Site with Annexed Aggregation Node Site
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 8
3.6 Examples of types of interconnection that can be achieved
This section sets out a number of examples of the types of cross connections and types of interconnection that can be achieved using various combinations of the types of the Facilities Access Service. These examples are however not exhaustive.
3.6.1 Cross Connects
Table 1 sets out the types of connections that can be achieved between different points on an NBN Co ODF using Cross Connects.
To/From
(Points of appearance on an NBN Co ODF)
Customer’s lead-in or backhaul transmission
cable NNI
Equipment rack made available to Customer as
part of NBN Co Co-location
Customer’s lead-in or backhaul transmission
cable Y Y Y
NNI Y N* Y
Equipment rack made available to Customer as
part of NBN Co Co-location Y Y Y
Table 1: Matrix of permissible connections that can be achieved using Cross Connects
*Direct NNI to NNI connection is not possible because traffic egressing the NNI at the POI is required to traverse an IP device prior to being injected back into the NBN Co Network. For more information, please refer to the NBN Co Ethernet Bitstream Access Service – Product Technical Specification.
In respect of the Facilities Access Service, a Customer’s lead-in or backhaul transmission cable is defined as either:
a transmission cable brought in from the street into the POI Site and delivered to an NBN Co ODF; or
a transmission cable brought in from elsewhere within the building or buildings in which the POI Site
is located and delivered to an NBN Co ODF.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 9
3.6.2 Interconnection
Figure 4 below illustrates a type of interconnection that can be achieved using a combination of NBN Co ODF Termination Point, Cross Connects and NBN Co Co-location in respect of the same POI.
ODF
A
ODF
BRack Rack
NBN Co ODFsRed lines denote Customer’s lead-in or backhaul transmission cables (either from the street or from elsewhere within the building in which the POI is located (e.g. TEBA) connected to an NBN Co ODF by NBN Co as part of “NBN Co ODF Termination Point”
Blue lines denote the 24 core pre-cabled and pre-terminated single mode fibre tie cables provided by NBN Co as part of “NBN Co Co-location”
Customer
Active
Equip.
Patch
Panel
Customer
Active
Equip.
Patch
Panel
Customer
Active
Equip.
Patch
Panel
Customer
Active
Equip.
Patch
Panel
Red lines denote Customer patch cables(not provided as part of the Facilities Access Service)
Dotted black lines denote the connections provided by NBN Co as part of “Cross Connects”
Patch Panel Patch PanelPatch Panel
NBN
Active
Equipment
(e.g. NNI)
NBN
Active
Equipment
(e.g. NNI)
TrayTray
Patch Panel
Figure 4: Type of interconnection that can be achieved using a combination of NBN Co ODF Termination Point, Cross Connects and NBN Co Co-location.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 10
4 Technical Specifications
4.1 Cross Connects
Figure 5 below illustrates the permissible connections that can be established in respect of a POI by Customer acquiring Cross Connects.
NBN Co Point of Interconnect
NBN Co Internal Infrastructure
Customer E
Co-location Rack
Customer B
(Backhaul Provider)Co-location Rack
Customer A
Co-location Rack
NBN Co NNI – Customer A
Customer A – Street Fibre
Customer B – Fibre from TEBA or elsewhere in facility
Customer C – Street Fibre
Termination Point
A
A
E
E
B
D
NBN Co
ODF
C
NBN Co
ODF
NBN Co NNI – Customer E
NBN Co NNI – Customer D
NBN Co NNI - Customer C
EAS/EFS
etc.
Permanent infrastructure provided by NBN Co
Provided by Customer
Patching performed by NBN Co
Figure 5: Logical connectivity diagram of permissible Cross Connects
Subject to the terms of the Product Description for the Facilities Access Service, NBN Co shall be responsible for the following in respect of Cross Connects supplied by NBN Co to Customer:
installing all Cross Connects within an NBN Co ODF;
providing the materials used to install all Cross Connects within an NBN Co ODF; and
ongoing maintenance of all Cross Connects.
Note that:
the hardware and cabling between the equipment rack in which Customer Active Equipment is
installed (as part of NBN Co Co-location) and an NBN Co ODF; and
the pre-cabled and pre-terminated single mode optic fibres within the equipment rack in which
Customer Active Equipment is installed (as part of NBN Co Co-location) and an NBN Co ODF,
are provided by NBN Co as part of NBN Co Co-location (and not as part of Cross Connects) as described in section 4.2.2.1 of this document.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 11
4.1.1 Point of carriage service handover between NBN Co Network and Customer Network
The point of carriage service handover between the NBN Co Network and the Customer Network is dependent on the type of the Facilities Access Service acquired by Customer in respect of the relevant POI.
4.1.1.1 NBN Co ODF Termination Point and Cross Connects
Where Customer acquires NBN Co ODF Termination Point and an associated Cross Connect (but not NBN Co Co-location), the point of carriage service handover will be the optical port interface on the fibre termination tray within an NBN Co ODF on which Customer’s lead-in or backhaul fibre transmission cable is terminated.
4.1.1.2 NBN Co Co-location
Where Customer acquires NBN Co Co-location and an associated NBN Co ODF Termination Point and/or Cross Connect, the point of carriage service handover will be the optical interface on the fibre patch panel for that equipment rack as illustrated in Figure 6 below.
The NNI, as described in the Product Descriptions for the NFAS, the Product Description for the NWAS and NBN Co Ethernet Bitstream Service – Product Technical Specification, supplied by NBN Co under the Wholesale Broadband Agreement, is unaffected by the description of the point of carriage service handover between the NBN Co Network and the Customer Network as described in this section.
Figure 6: Point of carriage service handover between the NBN Co Network and the Customer Network (depending on the type of Facilities Access Service acquired by Customer in respect of the relevant POI).
ODF
TPRack
NBN Co ODFsRed line denotes Customer’s lead-in or backhaul transmission cable
NBN
Active
Equipment
(e.g. NNI)
Patch Panel
Tray
Customer
Active
Equip.
Patch
Panel
Equipment rack
Point of carriage service handover between the NBN Co Network and the Customer Network (depending on form of Facilities Access Service acquired by Customer in respect of the relevant POI)
Patch Panel
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 12
4.2 NBN Co Co-location
This section applies to the NBN Co Co-location type of the Facilities Access Service only.
4.2.1 Equipment rack specifications
4.2.1.1 Size and dimensions
As specified in the Product Description for the Facilities Access Service, equipment racks can be ordered by Customer as either ‘lockable full height equipment racks’ or ‘lockable half height equipment racks’.
4.2.1.1.1 ‘Lockable full height equipment rack’ specifications
NBN Co will ensure that all ‘lockable full height equipment racks’ that are supplied by NBN Co to Customer will have the following specifications:
External rack dimensions of 2195mm high and 1000mm depth including door handles as per ANSI/EIA
RS-310C
Minimum internal depth clearance between the front and rear door frames of 900mm
40 usable rack units (ANSI)
19 inch ANSI rail spacing (a 21 inch ETSI retrofit kit can be ordered at any time)
Four equipment mounting rails (the rear two rails can be reconfigured for varying depths)
Use of the four equipment rails can sustain up to 600 kilograms of static weight per rack
Rack units shall be individually numbered
A fixed cable tray mounted vertically inside the rack, with a minimum width of 150mm
Rack space will be accessible by Customer from the front and rear of the racks, but not from the sides
of the racks
Side panels and power distribution units will be fitted to all racks
4.2.1.1.2 ‘Lockable half height equipment rack’ specifications
NBN Co will ensure that all ‘lockable half height equipment racks’ subdivisions that are supplied by NBN Co to Customer as part of NBN Co Co-location will have the following specifications:
External rack dimensions of 2195mm high and 1000mm depth including door handles as per ANSI/EIA
RS-310C (Two Rack subdivisions)
Minimum internal depth clearance between the front and rear door frames of 900mm
A fixed, vented dividing shelf shall provide segregation between top and bottom rack divisions
Cabling to the bottom subdivision is protected from top subdivision
16 usable rack units (ANSI)
19 inch ANSI rail spacing (a 21 inch ETSI retrofit kit can be ordered at any time)
Four equipment mounting rails (the rear two rails can be reconfigured for varying depths)
Use of the four equipment rails can sustain up to 300 kilograms of static weight per rack
Rack units shall be individually numbered
A fixed cable tray mounted vertically inside the rack, with a minimum width of 150mm
Rack space will be accessible by Customer from the front and rear of the racks, but not from the sides
of the racks
Side panels and power distribution units will be fitted to all racks
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 13
4.2.1.2 Equipment rack configuration
In respect of lockable full and lockable half height equipment racks, the default rack configurations are illustrated in Figure 7.
Default dimensions are as follows (+/- 15mm):
Clearance between front and rear equipment rails of 715mm for full height racks
Clearance between front and rear equipment rails of 708mm for half height racks
Clearance between door frames of 910mm for full height and half height racks
Clearance between front and rear door mesh of 955mm for full height and half height racks
Clearance between front equipment rails and front door frame of 155mm for full height and half
height racks
Clearance between rear equipment rails and rear door frame of 40mm for full height racks
Clearance between rear equipment rails and rear door frame of 47mm for half height racks
Figure 7: Plan view perspective of the default rack configurations with dimensions and clearances shown.
4.2.1.3 Doors
NBN Co will ensure that front and rear lockable doors are provided in respect of each equipment rack.
NBN Co will ensure that these doors are ventilated by mesh and provide an equivalent open area of at least 63%.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 14
4.2.1.4 Panels
NBN Co will ensure that side and top panels are provided in respect of each equipment rack and are configured such that they cannot be removed (in the normal course of usage) whilst front and rear doors of the equipment rack are locked.
4.2.1.5 Equipment rack security
4.2.1.5.1 Locks
NBN Co shall:
fit locks to the front and rear of the equipment rack doors;
ensure each equipment rack door has a three point locking system;
manage keys and access authorisation in respect of equipment racks;
manage the issuance and revocation of keys and access authorisation in respect of equipment racks;
and
provide a method by which locks fitted by NBN Co can be rekeyed or reconfigured on request.
Please refer to the Product Description for the Facilities Access Service for further terms that apply in relation to the locks, keys and access cards.
4.2.1.5.2 Cameras
Please refer to the Product Description for the Facilities Access Service for terms that apply in relation to the use of cameras within NBN Co Co-location space.
4.2.1.5.3 Door alarms
NBN Co will ensure that equipment racks supplied as part of NBN Co Co-location are fitted with pre-cabled door switches on the front and rear doors that are designed to enable Customer to monitor door state (i.e. open/closed). The door switches are pre-cabled with 1.5 metre length, 0.5mm diameter solid conductor cable. If Customer wishes to monitor door state, Customer must provide its own monitoring equipment and connect the provided door switch cabling in accordance with NBN Co’s instructions (set out below and otherwise as notified by NBN Co to Customer from time to time). NBN Co is not responsible for monitoring any door switches, door alarms or door states (i.e. open/closed) in relation to equipment racks supplied as part of NBN Co Co-location, or installing, operating or maintaining any such monitoring equipment and monitoring cabling within those equipment racks.
If Customer wishes to connect its own monitoring equipment to the provided door switch cabling, Customer can use the door switch Normally Open (NO) or Normally Closed (NC) and common outputs.
The maximum voltage and current that can be switched or interrupted by the door switch is 63V and 0.5A.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 15
4.2.2 Cabling
4.2.2.1 Cable specifications
NBN Co will procure, install and maintain 24 core, pre-cabled and pre-terminated single mode fibre tie cables in respect of each ‘lockable full height equipment rack’ and each ‘lockable half height equipment rack’ subdivision. These tie cables form part of fixed infrastructure and will be connected to (and run between) an NBN Co ODF Termination Point and the fibre patch panel within each equipment rack supplied as part of NBN Co Co-location.
In respect of each ‘lockable full height equipment rack’ and each ‘lockable half height equipment rack’ subdivision, the pre-cabled and pre-terminated single mode fibre tie cables will present the 24 terminated fibres on a 1 RU patch panel with SC/APC connectors.
If Customer requires augmentation to the pre-cabled and pre-terminated single mode fibre tie cables beyond the original 24 fibres, Customer may request a quote directly from NBN Co. If NBN Co is able and elects to do so, it will provide such augmentation on the terms of a quote agreed between NBN Co and Customer.
Where Customer agrees to the quote provided by NBN Co, NBN Co will:
provide up to an additional 24 terminated fibres and fibre termination tray where Customer has
started using the pre-cabled and pre-terminated single mode fibre tie cables and cannot disrupt the
services running over these cables; or
replace the initial 24 port fibre patch panel with a 72 fibre tray and tie cables where Customer has not
yet started using the pre-cabled and pre-terminated single mode fibre tie cables.
Customer is responsible for procuring, installing and maintaining its own single mode patch leads between the fibre patch panel within the relevant equipment rack and the Customer Active Equipment installed within that relevant equipment rack.
4.2.2.2 Cabling restrictions
Customer and its Personnel are permitted to perform cabling within equipment racks that have been made available as part of NBN Co Co-location, on the terms set out in the Product Description.
Customer and its Personnel must not perform any cabling works externally to equipment racks that have been made available as part of NBN Co Co-location.
If Customer requires “Rack to Rack” connectivity, Customer must only utilise the core, pre-cabled and pre-terminated fibre tie cables provided by NBN Co and which traverses the NBN Co ODFs.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 16
4.2.2.2.1 Fibre strand attributes
The fibre strand attributes set out below only relate to fibre provided by NBN Co to Customer under the Facilities Access Service. The tables below exclude splice losses.
Individual strands:
All strands shall be single mode optical fibre.
All fibre strand attributes shall meet or exceed the recommendations as set out in ITU-T G.652
Standard, Characteristics of a Single Mode Optical Fibre and Cable, Table 4 G.652-G.652D attributes,
Telcordia GR-20-CORE, IEC 60793, and IEC 60794.
Point discontinuities shall have an optical loss no greater than 0.10dB.
NBN Co specific optical insertion losses are listed in Table 2.
NBN Co specific Dispersion values are listed in Table 3.
Wavelength (nm) Mean Insertion Loss
(dB/km)
Standard Deviation
(dB/km)
Maximum Insertion
Loss (dB/km)
1310 0.31 0.0133 0.35
1383 0.31 0.0133 0.35
1490 0.22 0.0066 0.24
1550 0.20 0.0033 0.21
1625 0.22 0.0033 0.23
Table 2: Maximum Optical Values
Wavelength (nm) Dispersion Value [ps/(nm.km)]
1550 ≤ 18.0
1625 ≤ 22.0
Table 3: Maximum Dispersion Values
Patch leads provided by NBN Co shall meet or exceed the recommendations as set out in ITU-T G.657.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 17
4.2.3 Power
4.2.3.1 Amount
Please refer to the Product Description for the Facilities Access Service for terms that apply in relation to power supply to equipment racks.
NBN Co will supply a feed of up to a maximum of 3kW at each ‘lockable full height equipment rack’ and a feed of up to a maximum of 1.5kW at each ‘lockable half height equipment rack’ subdivision. These are the standard power limitations.
If Customer requires more than 3kW and up to a maximum of 6kW of power in respect of a particular ‘lockable full height equipment rack’, Customer must acquire NBN Co Co-location (if available) in respect of a directly adjacent ‘lockable full height equipment rack’. If Customer acquires NBN Co Co-location in respect of a directly adjacent ‘lockable full height equipment rack’ for this purpose, then Customer may install its Customer Active Equipment such that the full 6kW is consumed in the footprint of one of the two ‘lockable full height equipment racks’ and 0kW is consumed in the adjacent ‘lockable full height equipment rack’. If a directly adjacent ‘lockable full height equipment rack’ is not available, then the standard power limitations will apply.
With respect to Customer Active Equipment, the ratio of inrush current to maximum continuous input current shall not exceed the limits specified in clause 4.7.1 of ETSI ETS 300 132-2 when measured with test circuit in accordance with clause 4.7.2 of ETSI ETS 300 132-2. The maximum instantaneous value of inrush current for an equipment interface shall not exceed 500A.
Power utilisation may be monitored by NBN Co.
4.2.3.2 Specification
NBN Co will supply -48V DC telecommunications power. The operating voltage range shall be in the range of -40.5V DC to -60V DC.
4.2.3.3 Presentation
NBN Co will provide a single DC power distribution unit (DCD) in respect of each ‘lockable full height equipment rack’ or ‘lockable half height equipment rack’ subdivision to enable Customer Active Equipment to be powered.
Ten circuit breaker positions are available on the DCD – five positions for each power feed (A + B). Customer is responsible for providing its own NBN Co approved pluggable circuit breakers.
NBN Co-approved pluggable circuit breakers are:
Eltek 165A Circuit breaker – Part Number C401203
Eltek 100A Circuit Breaker – Part Number 289595
Eltek 80A Circuit breaker – Part Number C401261
Eltek 50A Circuit breaker – Part Number 288474
Eltek 40A Circuit Breaker – Part Number C401260
Eltek 30A Circuit Breaker – Part Number C401259
Eltek 25A Circuit Breaker – Part Number C401296
Eltek 20A Circuit Breaker – Part Number C401295
Eltek 16A Circuit Breaker – Part Number C401294
Eltek 5A Circuit Breaker – Part Number 289155
Eltek 2A Circuit Breaker – Part Number C401258
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 18
4.2.3.4 DC Distribution unit
Customer is responsible for providing its own DC cabling between the DCD and Customer Active Equipment.
DC and earthing cabling provided by Customer must comply with AS/NZS 3015:2004 and as such, the cable sheath colours must be provided as follows:
Positive (Also called 0V, return or Positive earth) is red in colour
Negative (Also called -48V or active) is blue in colour
Earth is green/yellow in colour
Customer side DC cabling must be of a dimension, at, or between 2.5mm and 25mm cross sectional area and may be terminated to each individual circuit breaker output lug. Customer must ensure that the circuit breaker output terminal cable lug nuts are not exposed to torque exceeding 4.5 Newton metres.
When populated with approved circuit breakers, the DCD provides for circuit breaker trip alarm output via a voltage free relay. Customer may connect to the relay base for the purpose of monitoring circuit breaker trip alarms. Upon circuit breaker trip, all relay contacts transition simultaneously. Figure 8 below shows the mapping of the contact outputs on the relay base.
Figure 8: Relay base output.
The voltage free dry contact relay is rated to 60V, 0.5A.
The DCD provides LED indicators on the front panel. The green LED represents that DC power is present and there are no circuit breakers in a tripped state. The red LED represents that DC power is active, but a circuit breaker has tripped and is in the OFF position.
Other than for the purposes of connecting Customer side DC cabling and alarm output cabling, Customer must not tamper with, modify, move or remove the DCD, DCD power supply feed cabling, or power monitoring system.
4.2.3.5 Diverse feeds / redundancy
Where available, NBN Co will provide two -48 V DC feeds (A and B) to each equipment rack.
Where available, NBN Co will provide the A and B feeds within a single DCD allowing up to five breakers on each feed. In certain circumstances, the A and B feeds may be fed from a single source.
4.2.3.6 AC in equipment racks
NBN Co is not responsible for providing an AC power supply in respect of equipment racks.
Customer must not generate or attempt to generate an AC power supply within equipment racks.
8NO 7NO 6NO 5NO
4NC 3NC 2NC 1NC
- +
12COM 11COM 10COM 9COM
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 19
4.2.4 Earthing
NBN Co will ensure that equipment racks shall be:
earthed in accordance with AS/NZS 3015:2004 “ELVDC Power Supplies for Telecommunications” as
updated from time to time;
wired and configured for 3-wire earthing practices in respect of NBN Co Co-location space located
within Type 1 Facilities and 2-wire earthing in respect of NBN Co Co-location space located within
Type 2 Facilities; and
configured with two earth connection points – one at the top and one at the base of the equipment
rack.
Customer must not tamper with or remove rack earthing.
4.2.5 Electromagnetic interference
Equipment installed by or on behalf of Customer within equipment racks must not radiate or conduct electromagnetic interference in excess of the limits defined in the following standards:
EN55024 (Class A) – Immunity
CISPR22 (Class A or Class B depending upon the environment) – Emissions
EN61000-3 – Electromagnetic compatibility
AS/NZS 60950.1:2010 (SELV) - Safety
4.2.6 Test switched sockets
Where available, NBN Co will make available to Customer 230V 10A switched sockets (which meet AS 60038:2000) in pendant form hanging in the aisle from the ceiling or mounted to the bottom of the superstructure or in equipment rack aisles at periodic intervals. Subject to prior arrangements with NBN Co, the test switched sockets may only be used by Customer for incidental and temporary power connection only, such as to power a laptop or test equipment. NBN Co may, without notice, disconnect any connections made to the switched sockets.
As these switched sockets may not be protected by safety switches or residual current devices, it is recommended that 230V AC connected equipment be protected by a portable Residual Current Device that meets AS/NZS 3760:2010 and is certified as being suitable for use connection to a Residual Current Device.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 20
4.2.7 Allowed Equipment for NBN Co Co-location
Without limiting anything in the Product Description for the Facilities Access Service, Customer may install and operate the following types of equipment in an equipment rack supplied by NBN Co as part of NBN Co Co-location:
Equipment use to support NBN related network access
Ethernet Switches
Transmission equipment
Routers (including BNG, B-RAS and general purpose routers)
Servers used to authenticate and configure NBN end users (including RADIUS, DHCP, AAA and ACS)
Voice equipment such as a Softswitch or Session Border Controller
Video conferencing controller
Bandwidth management devices
Management equipment (including terminal servers and alarm devices)
Test or monitoring equipment
Other types of equipment notified by NBN Co to Customer from time to time or otherwise approved
by NBN Co in writing
Without limiting anything in the Product Description for the Facilities Access Service, Customer must not install or operate any of the following types of equipment in an equipment rack supplied by NBN Co as part of NBN Co Co-location:
Equipment used to support non-NBN related network access
Content storage or content distribution network equipment
Servers used for hosting or cloud applications
Devices that are used to store, forward and route professional profile video and audio
Coding and Multiplexing equipment
Transmission devices for voice interconnect (including X.161)
DSLAM Equipment or associated splitters
Mobile Base Station equipment and other Wireless and RF Devices
DC to AC Inverters
Any AC powered equipment
Other types of equipment notified by NBN Co to Customer from time to time
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 21
4.2.8 Environmental
4.2.8.1 Climate control
As described in the Product Description for the Facilities Access Service, NBN Co will use reasonable endeavours to maintain the ambient temperature of the area in which NBN Co Co-location is made available by NBN Co to Customer. NBN Co will use reasonable endeavours to provide climate control up to a maximum ambient temperature of 45ºC with a maximum rate of change of temperature of 1.33ºC/minute.
4.2.8.2 Air handling
NBN Co will ensure that air handling is provided within the NBN Co Co-location space to facilitate hot aisle/cold aisle, with the cold aisle provided at the front of the equipment rack.
Customer must ensure that all Customer Active Equipment used or installed within the NBN Co Co-location space maintains front-to-back air handling.
4.2.8.3 Fire suppression
NBN Co will ensure that fire suppression is provided in accordance with the Building Code of Australia in respect of NBN Co Co-location space that is located within Type 1 Facilities.
4.2.8.4 Lighting
NBN Co will ensure that general lighting is supplied within the area in which NBN Co Co-location is made available and that such lighting meets AS/NZS 1680.1:2006, Interior and workplace lighting – General principles and recommendations.
4.2.8.5 Static suppression
NBN Co may, but is not obliged to provide, grounded antistatic flooring and static discharge points within NBN Co Co-location space.
4.2.8.6 Cardboard eradication
Customer must ensure that:
any equipment that is delivered on behalf of Customer to the building in which NBN Co Co-location
space is located is unpacked outside of the NBN Co Co-location space to prevent airborne
contaminants; and
all packaging and waste materials for equipment that is delivered on behalf of Customer to the
building in which NBN Co Co-location space is located is immediately removed and disposed of by
Customer Personnel.
4.2.8.7 Metalwork
Customer must not use or install any equipment within equipment racks or the NBN Co Co-location space that has a surface or plating finish which may produce conducting flakes or particles.
This includes hot dip galvanizing which may produce zinc whiskers or burrs.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 22
4.2.9 Facilities
4.2.9.1 Parking spaces
Where there are parking spaces available for NBN Co’s use at the building in which NBN Co Co-location space is located, Customer may access those parking spaces for maintenance and operational purposes, provided they are not already in use by NBN Co or Other NBN Co Customers, subject to reasonable conditions that may be notified by NBN Co to Customer from time to time.
On request by NBN Co, Customer must move any vehicle parked by or on behalf of Customer in a parking space that is available for NBN Co’s use at the building in which NBN Co Co-location space.
4.2.9.2 Loading dock
Where there is a loading dock available for NBN Co’s use at the building in which NBN Co Co-location space is located, Customer may access it for maintenance and operational purposes, provided it is not already in use by NBN Co or Other NBN Co Customers, subject to reasonable conditions that may be notified by NBN Co to Customer from time to time.
4.2.9.3 Lifts
Where goods lifts, cranes, mechanical lifting devices, slings and chains are present within the building in which NBN Co Co-location space is located, subject to Customer obtaining and maintaining the necessary accreditations, Customer may use those facilities with NBN Co’s consent, subject to reasonable conditions that may be notified by NBN Co to Customer from time to time.
If Customer wishes to use an uncertified mechanical lift device that is available at the building in which NBN Co Co-location space is located, Customer is responsible for organising and paying for the certification of that device prior to using that device.
Customer must not use, or permit or authorise the use of, any uncertified mechanical lift device that is available at the building in which NBN Co Co-location space is located.
4.2.9.4 Ladders
Customer may use approved non-conducting ladders within the NBN Co Co-location space. Customer must not use any non-approved or conducting ladders within the NBN Co Co-location space. Customer must ensure that all ladders used by Customer Personnel comply with the occupational health and safety requirements of the building in which NBN Co Co-location space is located and any other requirements provided by NBN Co to Customer from time to time.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 23
4.3 NBN Co ODF Termination Point
4.3.1 Building Entry Rights
Please refer to section 1.7 of the Product Description for the Facilities Access Service for a description of Building Entry Rights, an explanation of the relevance of Building Entry Rights and the terms that apply in respect of Building Entry Rights.
4.3.2 Cabling
Only NBN Co and its authorised contractors are permitted to introduce external cabling to NBN Co Equipment, including to an NBN Co ODF. Customer must not introduce or attempt to introduce any external cabling to NBN Co Equipment, including to an NBN Co ODF or to an equipment rack supplied by NBN Co as part of NBN Co Co-location.
Where Customer, after:
acquiring the Building Entry Service from NBN Co in relation to Type 1 Facilities; or
obtaining Building Entry Rights from the Underlying Facility Provider in relation to Type 2 Facilities,
has hauled their cable into the building in which the Aggregation Node Site is located and wishes to have their lead-in or backhaul transmission cable (whether it is from the street or elsewhere within the building) terminated at an NBN Co ODF, Customer must ensure that at least 15 metres of slack cable is left beside the NBN Co ODF nominated by NBN Co. Customer must ensure that the slack cable is coiled up neatly and safely beside that NBN Co ODF. The cable must also be clearly labelled with the Customer’s name and circuit details, using a durable and securely adhered label at the end of the cable length. The label should be printed using a size 18 font such as the example in Figure 9 below. Handwritten labels will not be accepted.
Figure 9: Example of a cable label.
Provided that Customer has complied with the above requirements, NBN Co will then prepare and terminate (fusion splice) the Customer’s lead-in or backhaul transmission cabling into a fibre termination tray within the NBN Co-nominated NBN Co ODF.
At the time of ordering NBN Co ODF Termination Point, Customer can specify which fibres of their lead-in or backhaul cable require splicing and whether transposition of fibres is required. If no transposition is specified, it will be assumed that the standard colour code applies as specified in AS/CA S008:2010, Table B7 (Optical Fibre Colour Code).
Subsequent to NBN Co terminating the Customer cable within the NBN Co-nominated NBN Co ODF, Customer may request inspection of the terminated cable. During this inspection, Customer may temporarily connect their test equipment and test the terminations.
4.3.3 Fibre Termination Trays
Customer may use up to two NBN Co-provided fibre termination trays for the purposes of terminating Customer’s lead-in or backhaul transmission cabling. At the time of ordering, Customer may choose fibre termination trays in either 24 or 72 fibre counts and in either loose tube or ribbon fibre type.
CUSTOMER NAME
CIRCUIT ABCD123456789
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 24
4.3.3.1 24 fibre termination tray
Where Customer orders a 24 fibre termination tray, NBN Co will provide a 1 RU fibre termination tray with 24 single mode pigtails, in standard colour coding, pre-terminated with SC/APC connectors, 24 pre-mounted SC/APC adaptors and 2 splice trays.
4.3.3.2 72 fibre termination tray
Where Customer orders a 72 fibre termination tray, NBN Co will provide a 2 RU fibre termination tray with 72 single mode pigtails, in standard colour coding, pre-terminated with SC/APC connectors, 72 pre-mounted SC/APC adaptors and 6 splice trays.
4.3.3.3 Port nomenclature
Where Customer orders NBN Co ODF Termination Point or Cross Connects for the purposes of connecting to the NBN Co NNI,
odd port numbers represent TX (light out) from NBN Co Equipment towards Customer’s equipment;
and
even port numbers represent RX (light in) towards NBN Co Equipment.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 25
4.4 Building Entry Service
The Building Entry Service operates in conjunction with other types of the Facilities Access Service, namely NBN Co ODF Termination Point and Cross Connects. Accordingly, in order for Customer to install and interconnect its lead-in or backhaul transmission cable to an NNI in respect of a POI in a Type 1 Facility, Customer needs to acquire the Building Entry Service, NBN Co ODF Termination Point and a Cross Connect, as illustrated in Figure 10 below.
Figure 10: Building Entry Service
Note that Customer’s lead-in or backhaul transmission cables entering an NBN Co Type 1 facility using the Building Entry Service must be presented by Customer at the NBN Co internal cable chamber. The hand-off point depicted in Figure 10 between the Building Entry Service and the NBN Co ODF Termination Point service indicates the point where Customer is responsible for presenting Customer’s lead-in or backhaul transmission cables as installed using the Building Entry Service, in a manner that can be further carried through to an NBN Co ODF by NBN Co, for the purposes of connection to the NBN Co ODF Termination Point.
Customer is responsible for ordering the NBN Co ODF Termination Point service as required, for the installation by NBN Co of Customer’s lead-in or backhaul transmission cables (introduced using the Building Entry Service) from the NBN Co internal cable chamber through to the NBN Co ODFs.
4.4.1 Usage Scenarios
After Customer’s lead-in or backhaul transmission cables are installed between the NBN Co internal cable chamber and the NBN Co ODF and connected by NBN Co to the NBN Co ODF (supplied by NBN Co as part of NBN Co ODF Termination Point), Customer’s lead-in or backhaul transmission cables can then be connected to other appearances on the NBN Co ODF, including the appearance of an NNI or NBN Co Co-location, by using Cross Connects supplied by NBN Co.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 26
The appearance of Customer’s lead-in or backhaul transmission cable on the NBN Co ODF (supplied by NBN Co as part of NBN Co ODF Termination Point) can then be connected to the NNI (utilising Cross Connects supplied by NBN Co), thereby allowing Customer to carry traffic to and from End Users (utilising CVCs, AVCs and UNIs supplied by NBN Co as part of NFAS or NWAS, as applicable).
By way of example only, the following scenarios illustrate how the Building Entry Service can be used by Customer in conjunction with other types of the Facilities Access Service and other Products supplied by NBN Co under the WBA to supply services to End Users:
a. by acquiring a Cross Connect between the appearance of Customer’s lead-in or backhaul transmission
cable on the NBN Co ODF and the appearance of the NNI on the NBN Co ODF, Customer can supply
services to End Users utilising CVCs, AVCs and UNIs supplied by NBN Co as part of NFAS or NWAS, as
applicable:
Figure 11: Use of Building Entry Services for delivery of services to End Users
b. by acquiring a Cross Connect between the appearance of Customer’s lead-in or backhaul transmission
cable on an NBN Co ODF and the appearance of NBN Co Co-location on an NBN Co ODF, Customer can
establish a connection to Customer Active Equipment that is installed in equipment racks made
available by NBN Co as part of NBN Co Co-location.
Figure 12: Use of Building Entry Services for connecting to Customer Active Equipment installed in equipment racks made available as part of NBN Co Co-location
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 27
4.4.2 Technical Specifications
4.4.2.1 Points of Termination
The two end-points for the NBN Co Building Entry Service are:
the beginning of the relevant NBN Co starter duct at the Type 1 Facility; and
the NBN Co internal cable chamber within the Type 1 Facility.
Fibre cabling introduced to the NBN Co Cable Chamber will be identified by its specified labelling details (as further described in section 4.4.2.1.4).
4.4.2.1.1 External Pit Termination
Customer is responsible for commissioning and maintenance of the infrastructure beyond the beginning of the NBN Co starter duct at the Type 1 Facility, including the external pit beyond the NBN Co property boundary.
NBN Co has installed starter ducts between the NBN Co pit and the property boundary for interconnection to Customer or third party pits.
4.4.2.1.2 Cable Chamber Termination
Each Building Entry Service entitles the Customer to draw a single fibre cable from the beginning of the relevant NBN Co starter duct at the Type 1 Facility, through the designated ducting, and into the NBN Co internal cable chamber within the Type 1 Facility. This fibre cabling must be coiled and secured by Customer in a safe manner that can be further carried by NBN Co to either the NBN Co ODF (using NBN CO ODF Termination Point) .
The Building Entry Service currently does not accommodate the installation of patching/splicing facilities within the NBN Co internal cable chamber. Customer is required to perform all fibre patching/splicing outside of the NBN Co property boundary.
Where more than one fibre cable is required to satisfy multiple Customer scenarios as described in Section 4.4.1, Customer is required to separately purchase the Building Entry Service in respect of each such cable.
4.4.2.1.3 Fibre Presentation
Customer’s lead-in or backhaul transmission cables must be presented within the NBN Co internal cable chamber as a coil of 20 metres in length.
Customer must ensure that the slack cable is coiled up neatly and safely with labelling as per section 4.4.2.1.4.
4.4.2.1.4 Fibre Cable Labelling
Customer’s lead-in or backhaul transmission cables must be clearly labelled with the Customer’s name and circuit details, using a durable and securely adhered label at the end of the cable length. The label should be printed using a size 18 font such as the example in Figure 13. Handwritten labels will not be accepted.
Figure 13: Example of a cable label
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 28
4.4.2.1.5 Fibre Cable Sheathing
Customer is responsible for ensuring that Customer’s lead-in or backhaul transmission cables introduced into the NBN Co internal cable chamber (which will subsequently be introduced into the NBN Co ODF by NBN Co as part of NBN Co’s supply of NBN Co ODF Termination Point) is of a construction suitable for outside plant operation.
4.4.2.2 Conduit Characteristics
This section describes the technical characteristics of the conduit used to carry Customer’s lead-in or backhaul transmission cables from the external pit to the NBN Co internal cable chamber.
4.4.2.2.1 Physical Specifications
Upon acceptance of a Building Entry Service order, NBN Co will allocate to Customer a single conduit (conforming to the P100 specification as per Comms Alliance G645:2011, section 7.1), feeding from the nominated external pit, to the NBN Co internal cable chamber.
4.4.2.2.2 Establishing Connectivity between External Pit and NBN Co starter duct
Customers who wish to establish connectivity between either a new or an existing pit and an NBN Co starter duct, must contact NBN Co and arrange for the allocation and access to ducts before commencing construction.
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 29
4.4.2.2.3 Conduit Naming Convention
Ducts are identified within the NBN Co internal cable chamber using the naming convention illustrated in Figure 14 below.
Figure 14: Duct Naming Convention
4.4.2.2.4 Conduit Sealing
Customer is responsible for sealing of the allocated ducts before and after the installation of Customer’s lead-in or backhaul transmission cables.
4.4.2.3 Building Entry Diversity
Type 1 Facilities allow building entry diversity, as illustrated in Figure 15 below. Customer may construct a diverse entry architecture using multiple Building Entry Services in respect of the same Type 1 Facility, highlighting the requirement for diversity of services through the ordering process (i.e. detailed design).
Figure 15: NBN Co Building Entry Service Highlighting Diverse Fibre Entry
SFAA – WBA Product Catalogue – Facilities Access Service Product Technical Specification release 3.0 – 21 December 2012 30
5 Glossary
AAA Authentication, Authorisation, Accounting
AC Alternating Current
ACS Automatic Configuration Server
DC Direct Current
DCD DC Distribution Unit
DHCP Dynamic Host Configuration Protocol
EACS Electronic Access Card System
EAS Ethernet Aggregation Switch
EFS Ethernet Fanout Switch
mm Millimetres
nm Nanometres
NNI Network to Network Interface
ODF Optical Distribution Frame
ODF TP Optical Distribution Frame Termination Point
POI Point of Interconnect
P/N Part Number
RADIUS Remote Authentication Dial In User Service
RU Rack Unit
RX Receive
SC/APC Subscriber Connector Angled Polished Connector
TX Transmit