FAC2611-0U Advanced Application Field Equipment Controller ...

25
FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions MS-FAC2611-0U Part No. 24-10143-01620, Rev. Software Release 8.1 Issued March 2018 Application The FAC2611 Advanced Application Field Equipment Controller (FAC) is part of the Metasys® system Field Equipment Controller family. The FAC26 Series controllers run pre-engineered and user-programmed applications and provide the inputs and outputs required to monitor and control a wide variety of HVAC equipment. FAC26 field controllers operate on an RS-485 BACnet® MS/TP Bus as BACnet Advanced Application Controllers (B-AACs) and integrate into Johnson Controls® and third-party BACnet systems. FAC26 controllers include an integral real-time clock, which enables the controllers to monitor and control schedules, calendars, and trends; and operate for extended periods of time as stand-alone controllers when offline from the system network. Important: The MS-FAC2611-0U model is used in Metasys Release 8.1 smoke control applications and is UL 864 UUKL/UUKLC 10th Edition Smoke Control Listed. You must refer to the Metasys® System UL 864 10th Edition UUKL/ORD-C100-13 UUKLC Smoke Control System Technical Bulletin (LIT-12012487) for detailed requirements and procedures for installing, commissioning, and operating UL 864 UUKL/UUKLC Listed Metasys system devices. The UL 864 UUKL/UUKLC listing for Smoke Control Equipment is voided if (1) you do not use the required software tools at the required versions; or (2) you do not meet the requirements or do not follow the procedures as documented in the Metasys® System UL 864 10th Edition UUKL/ORD-C100-13 UUKLC Smoke Control System Technical Bulletin (LIT-12012487). Switchable Communications Protocols The Family Controllers and network sensors communicate using the standard BACnet protocol, based on the ANSI/ASHRAE 135-2004. The BACnet protocol is a standard for ANSI, ASHRAE, and the International Standards Organization (ISO) for building controls. Most FEC, VMA16, VMA18,IOM field controllers are BTL-listed as BACnet Application Specific Controllers (B-ASCs). FAC field controllers and the VMA1930 Field Controller are BTL-listed as BACnet Advanced Application Controllers (B-AACs). You can use Release 10.3 and Release Module (RM) 10.2 of the Controller Configuration Tool (CCT) to switch the Field Bus communications protocol in supported FEC, FAC and VMA controllers to be either the standard BACnet MSTP or the N2 protocol. All new controllers use BACnet MSTP as the default communications protocol. Switchable communications protocols in the MSTP models provide a cost-effective upgrade and modernization path for customers with existing N2 controllers. The N2-capable FEC Family Controllers can be used as functional replacements for legacy N2 controllers. The N2-capable FEC Family Controllers: have the input and output (I/O) quantities and characteristics of the FEC Family Controllers must be programmed with CCT, which has similar, but not identical programming capabilities as HVACPro, GX9100, GPL, and other legacy tools support SA Bus devices are available in Buy American versions (most models) are listed for UL864 UUKL/UUKLC (some models). N2 is supported as part of the Metasys® 10th Edition listing for Smoke Control System Equipment. 1 FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Transcript of FAC2611-0U Advanced Application Field Equipment Controller ...

Page 1: FAC2611-0U Advanced Application Field Equipment Controller ...

FAC2611-0U Advanced Application Field EquipmentController Installation InstructionsMS-FAC2611-0U

Part No. 24-10143-01620, Rev. —Software Release 8.1Issued March 2018

ApplicationThe FAC2611 Advanced Application Field EquipmentController (FAC) is part of the Metasys® system FieldEquipment Controller family. The FAC26 Seriescontrollers run pre-engineered and user-programmedapplications and provide the inputs and outputs requiredto monitor and control a wide variety of HVAC equipment.

FAC26 field controllers operate on an RS-485 BACnet®MS/TP Bus as BACnet Advanced Application Controllers(B-AACs) and integrate into Johnson Controls® andthird-party BACnet systems.

FAC26 controllers include an integral real-time clock,which enables the controllers to monitor and controlschedules, calendars, and trends; and operate forextended periods of time as stand-alone controllers whenoffline from the system network.

Important: The MS-FAC2611-0U model is used inMetasys Release 8.1 smoke controlapplications and is UL 864 UUKL/UUKLC10th Edition Smoke Control Listed. Youmust refer to theMetasys® System UL 86410th Edition UUKL/ORD-C100-13 UUKLCSmoke Control System Technical Bulletin(LIT-12012487) for detailed requirementsand procedures for installing,commissioning, and operating UL 864UUKL/UUKLC Listed Metasys systemdevices. The UL 864 UUKL/UUKLC listingfor Smoke Control Equipment is voided if(1) you do not use the required softwaretools at the required versions; or (2) you donot meet the requirements or do not followthe procedures as documented in theMetasys® System UL 864 10th EditionUUKL/ORD-C100-13 UUKLC SmokeControl System Technical Bulletin(LIT-12012487).

Switchable CommunicationsProtocolsThe Family Controllers and network sensors communicateusing the standard BACnet protocol, based on theANSI/ASHRAE 135-2004. The BACnet protocol is astandard for ANSI, ASHRAE, and the InternationalStandards Organization (ISO) for building controls.

Most FEC, VMA16, VMA18,IOM field controllers areBTL-listed as BACnet Application Specific Controllers(B-ASCs). FAC field controllers and the VMA1930 FieldController are BTL-listed as BACnet Advanced ApplicationControllers (B-AACs).

You can use Release 10.3 and Release Module (RM)10.2 of the Controller Configuration Tool (CCT) to switchthe Field Bus communications protocol in supported FEC,FAC and VMA controllers to be either the standardBACnet MSTP or the N2 protocol. All new controllers useBACnet MSTP as the default communications protocol.Switchable communications protocols in the MSTPmodels provide a cost-effective upgrade andmodernization path for customers with existing N2controllers.

The N2-capable FEC Family Controllers can be used asfunctional replacements for legacy N2 controllers. TheN2-capable FEC Family Controllers:• have the input and output (I/O) quantities and

characteristics of the FEC Family Controllers• must be programmed with CCT, which has similar,

but not identical programming capabilities asHVACPro, GX9100, GPL, and other legacy tools

• support SA Bus devices• are available in Buy American versions (most models)• are listed for UL864 UUKL/UUKLC (some models).

N2 is supported as part of theMetasys® 10th Editionlisting for Smoke Control System Equipment.

1FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 2: FAC2611-0U Advanced Application Field Equipment Controller ...

The N2-capable FEC family controllers:• do not support Zone Bus (for example, TMZ sensors

and M100 actuators) or XT-Bus (System 91) devices(for example, XT, XTM, and XP modules)

• do not support a wireless connection to the N2 bus• do not support NxE passthrough

North American EmissionsCompliance

CanadaThis Class (A) digital apparatus meets all therequirements of the Canadian Interference-CausingEquipment Regulations.

Cet appareil numérique de la Classe (A) respecte toutesles exigences du Règlement sur le matériel brouilleurdu Canada.

United StatesThis equipment has been tested and found to complywith the limits for a Class A digital device pursuant toPart 15 of the FCC Rules. These limits are designed toprovide reasonable protection against harmfulinterference when this equipment is operated in acommercial environment. This equipment generates,uses, and can radiate radio frequency energy and, if notinstalled and used in accordance with the instructionmanual, may cause harmful interference to radiocommunications. Operation of this equipment in aresidential areamay cause harmful interference, in whichcase the users will be required to correct the interferenceat their own expense.

InstallationObserve these guidelines when installing a field controller:

• Transport the controller in the original container tominimize vibration and shock damage.

• Verify that all parts shipped with the controller.• Do not drop the controller or subject it to physical

shock.

Parts Included• one field controller with removable terminal blocks

(Power, SA, and FC bus are removable)• one installation instructions sheet

Materials and Special Tools Needed• three fasteners appropriate for the mounting surface

(M4 screws or #8 screws)• one 20 cm (8 in.) or longer piece of 35 mm DIN rail

and appropriate hardware for DIN rail mount (only)• small straight-blade screwdriver for securing wires in

the terminal blocks

MountingObserve these guidelines when mounting a fieldcontroller:

• Ensure the mounting surface can support thecontroller, DIN rail, and any user-supplied enclosure.

• Mount the controller horizontally on 35 mm DIN railwhenever possible.

• Mount the controller in the proper mounting position(Figure 1).

• Mount the controller on a hard, even surfacewhenever possible in wall-mount applications.

• Use shims or washers to mount the controller securelyand evenly on the mounting surface.

• Mount the controller in an area free of corrosivevapors and observe the Ambient Conditionsrequirements in Table 10.

• Provide for sufficient space around the controller forcable and wire connections for easy cover removaland good ventilation through the controller (50 mm[2 in.] minimum on the top, bottom, and front of thecontroller).

• Do not mount the controller on surfaces prone tovibration, such as duct work.

• Do not mount the controller in areas whereelectromagnetic emissions from other devices orwiring can interfere with controller communication.

Observe these additional guidelines when mounting afield controller in a panel or enclosure:

• Mount the controller so that the enclosure walls donot obstruct cover removal or ventilation through thecontroller.

• Mount the controller so that the power transformerand other devices do not radiate excessive heat tothe controller.

• Do not install the controller in an airtight enclosure.

2FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 3: FAC2611-0U Advanced Application Field Equipment Controller ...

Figure 1: Field Controller Mounting Positions

DIN Rail Mount ApplicationsMounting the field controller horizontal on 35 mmDIN railis the preferred mounting method.

To mount a field controller on 35 mm DIN rail:

1. Securely mount a 20 cm (8 in.) or longer section of35 mmDIN rail horizontal and centered in the desiredspace so that the controller mounts in the horizontalposition shown in Figure 1.

2. Pull the two bottom mounting clips outward from thecontroller to the extended position (Figure 2).

3. Hang the controller on the DIN rail by the hooks atthe top of the (DIN rail) channel on the back of thecontroller (Figure 2), and position the controller snuglyagainst the DIN rail.

4. Push the bottommounting clips inward (up) to securethe controller on the DIN rail.

To remove the controller from the DIN rail, pull thebottom mounting clips out to the extended positionand carefully lift the controller off the DIN rail.

Wall Mount ApplicationsTo mount a field controller directly on a wall or other flatvertical surface:

1. Pull the two bottom mounting clips outward andensure they are locked in the extended position asshown in Figure 2.

2. Mark the mounting hole locations on the wall usingthe dimensions in Figure 2 and one of the mountpositions shown in Figure 1. Or hold the controller upto the wall or surface in a proper mount position andmark the hole locations through the mounting clips.

3. Drill holes in the wall or surface at the markedlocations, and insert appropriate wall anchors in theholes (if necessary).

4. Hold the controller in place, and insert the screwsthrough the mounting clips and into the holes (oranchors). Carefully tighten all of the screws.

Important: Do not overtighten themounting screws.Overtightening the screwsmay damagethe mounting clips.

Figure 2: Back of Controller Showing ExtendedMounting Clips, DIN Rail Channel, and Mounting

Dimensions, mm (in.)

3FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 4: FAC2611-0U Advanced Application Field Equipment Controller ...

Figure 3: FAC2611 Physical Features

Table 1: FAC2611 Physical FeaturesPhysical Feature: Description and ReferencesCalloutBinary Output (BO) Source Power Selection Jumpers: Position jumpers to select internal or external 24 VACsupply power for Binary Outputs. (see Binary Output (BO) Source Power Selection Jumpers)

1

Device Address DIP Switch Block (see Setting the Device Addresses)2

Mounting Clips (see Mounting)3

Configurable Outputs (CO) Terminal Block: Can be defined as Voltage Analog Output (0-10 VDC) or Binary Output(24 VAC Triac). (see Table 3)

4

Analog Output (AO) Terminal Block: Can be defined as Voltage Analog Output (0-10 VDC) Current Analog Output(4-20 mA). (see Table 3)

5

24 VAC, Class 2 Supply Power Terminal Block (see Supply Power Terminal Block)6

Cover Lift Tab (see Removing the Controller Cover )7

Field Controller (FC) Bus Terminal Block (see FC Bus Terminal Block)8

Sensor Actuator (SA) Bus Terminal Block (see SA Bus Terminal Block)9

Sensor Port: (SA Bus) RJ-12 6-Pin Modular Jack (see Sensor Port)10

Binary Input (BI) Terminal Block: Dry Contact Maintained or Pulse Counter/Accumulator Mode (see Table 3)11

Universal Inputs (UI) Terminal Block: Can be defined as Voltage Analog Input (0-10 VDC), Current Analog Input(4-20 mA), Resistive Analog Inputs (0-600k ohm), or Dry Contact Binary Input. (see Table 3)

12

End-of-Line (EOL) Switch, located under the cover. (see Setting the End-of-Line (EOL) Switch)13

LED Status Indicators (see Table 8)14

FC Bus Port (RJ-12 6-pin Modular Jack) (see FC Bus Port)15

Binary Outputs (BO) Terminal Block: 24 VAC Triac (see Table 3)16

4FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 5: FAC2611-0U Advanced Application Field Equipment Controller ...

WiringObserve the following guidelines when wiring a controller:

Risk of Electric Shock: Disconnect the power supplybefore making electrical connections to avoid electricshock.

Mise En Garde: Risque de décharge électrique:Débrancher l'alimentation avant de réaliser toutraccordement électrique afin d'éviter tout risque dedécharge électrique.

Risk of Property Damage: Do not apply power to thesystem before checking all wiring connections. Shortcircuited or improperly connected wires may result inpermanent damage to the equipment.

Mise En Garde: Risque de dégâts matériels: Ne pasmettre le système sous tension avant d'avoir vérifié tousles raccords de câblage. Des fils formant un court-circuitou connectés de façon incorrecte risquentd'endommager irrémédiablement l'équipement.

Important: Do not exceed the controller electricalratings. Exceeding controller electricalratings can result in permanent damage tothe controller and void any warranty.

Important: Use copper conductors only. Make all wiringin accordance with local, national, andregional regulations.

Important: Electrostatic discharge can damagecontroller components. Use properelectrostatic discharge precautions duringinstallation, setup, and servicing to avoiddamaging the controller.

For detailed information on configuring and wiring anMS/TP Bus, FC bus, and SA bus, refer to the MS/TPCommunications Bus Technical Bulletin (LIT-12011034).For detailed information on wiring an N2 network, referto the N2 Communications Bus Technical Bulletin(LIT-636018).

FAC Terminal Blocks and Bus PortsSee Figure 3 for terminal block and bus port locations onthe FAC2611 controller. Observe the following guidelineswhen wiring a controller.

Input and Output Terminal BlocksOn most field controller models, all of the fixed inputterminal blocks are mounted on the bottom of thecontroller, and the output terminal blocks are mountedon the top of the controller. See Table 3 for moreinformation about I/O terminal functions, requirements,and ratings.

FC Bus Terminal BlockThe FC Bus terminal block is a blue, removable,4-terminal plug that fits into a board-mounted jack.

Wire the removable FC bus terminal block plugs on thecontroller, and other controllers in a daisy-chainconfiguration using 3-wire twisted, shielded cable asshown in Figure 4. See Comm Bus and Power SupplyTerminal Block Rating and Requirements Table for moreinformation.

Figure 4: FC Bus Terminal Block Wiring

Note: The FC bus Shield (SHLD) terminal is isolatedand can be used to connect (daisy chain) theshields for FC bus wiring.

SA Bus Terminal BlockThe SA Bus terminal block is a brown, removable,4-terminal plug that fits into a board-mounted jack.

Wire the removable SA Bus terminal block plugs on thecontroller, and other SA bus devices in a daisy-chainconfiguration using 4-wire twisted, shielded cable asshown in Figure 5. See Comm Bus and Power SupplyTerminal Block Rating and Requirements Table for moreinformation.

5FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 6: FAC2611-0U Advanced Application Field Equipment Controller ...

Figure 5: SA Bus Terminal Block Wiring

Note: The SA PWR terminal supplies 15 VDC. The SAPWR terminal can be used to connect (daisychain) the 15 VDC power leads on the SA bus.

FC Bus PortThe FC bus port on the front of the controller is an RJ-12,6-position modular jack that provides a connection forthe Bluetooth® Commissioning Converter, or ZFR/ZFRPro Wireless Field Bus Router.

The FC bus port is connected internally to the FC busterminal block. See Comm Bus and Power SupplyTerminal Block Rating and Requirements Table for moreinformation. The FC bus port pin assignment is shown inFigure 6.

Note: When the FAC is configured for N2 networkcommunication, the FC bus port is not used.

Figure 6: Pin Number Assignments for Sensor, SABus, and FC Bus Ports on Field Controllers

Sensor PortThe Sensor (SA Bus) port on the bottom of the controlleris an RJ-12, 6-position modular jack that provides aconnection for the VAV Balancing Tool, specified networksensors, or other SA Bus devices with RJ-12 plugs.

The Sensor port is connected internally to the SA busterminal block. See Comm Bus and Power SupplyTerminal Block Rating and Requirements Table for moreinformation. The Sensor Port pin assignment is shownin Figure 6.

Supply Power Terminal BlockThe 24 VAC supply power terminal block is a gray,removable, 3-terminal plug that fits into a board-mountedjack on the top right of the controller.

Wire the 24 VAC supply power wires from the transformerto the HOT and COM terminals on the terminal plug asshown in Figure 7. The middle terminal on the supplypower terminal block is not used. See Comm Bus andPower Supply Terminal Block Rating and RequirementsTable for more information about the Supply TerminalBlock.

Figure 7: 24 VACSupply Power Terminal BlockWiring

Important: Connect 24 VAC supply power to the fieldcontroller and all other network devices sothat transformer phasing is uniform acrossthe network devices. Powering networkdevices with uniform 24 VAC supply powerphasing reduces noise, interference, andground loop problems. The field controllerdoes not require an earth groundconnection.

6FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 7: FAC2611-0U Advanced Application Field Equipment Controller ...

Wireless Network Applications Important: Wireless operation is not approved forsmoke control applications. Refer to theMetasys® System UL 864 10th EditionUUKL/ORD-C100-13 UUKLC SmokeControl System Technical Bulletin(LIT-12012487) for detailed requirementsand procedures for installing,commissioning, and operating UL 864UUKL/UUKLC Listed Metasys systemdevices.

Termination DetailsA set of Johnson Controls® termination diagrams provides details for wiring inputs and outputs to the controllers.See the figures in this section for the applicable termination diagrams.

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of FieldDevice

UITemperatureSensor

UIVoltage Input -External Source

UIVoltage Input -Internal Source

7FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 8: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of FieldDevice

UIVoltage Input(Self-Powered)

UICurrent Input -External Source(Isolated)

UICurrent Input -Internal Source(2-wire)

UICurrent Input -Internal Source(3 wire)

UICurrent Input -External Source(in Loop)

8FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 9: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of FieldDevice

UIFeedback fromEPP-1000

UI or BIDry Contact(Binary Input)

AO0–10 VDCOutputto Actuator(External Source)

AO0–10 VDCOutputto Actuator(Internal Source)

AOCurrent Output

9FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 10: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of FieldDevice

AO24 VAC TriacOutput (SwitchLow, ExternalSource)

AOAnalog Output(Current)

AO4–20 mA Outputto Actuator

AO4–20 mA Outputto Actuator

10FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 11: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of FieldDevice

BOIncrementalControl toActuator (SwitchLow, ExternallySourced)(Triac JumpersWhereApplicable)

BO24 VAC BinaryOutput (SwitchLow, ExternallySourced)(Triac JumpersWhereApplicable)

BO24 VAC BinaryOutput (SwitchHigh, ExternallySourced)(Triac JumpersWhereApplicable)

BOIncrementalControl toActuator (SwitchHigh, ExternallySourced)(Triac JumpersWhereApplicable)

11FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 12: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of FieldDevice

Note: The bottom jack (J2) on the TE-700 and TE-6x00 Series Sensors is not usable as azone bus or an SAB connection.

SA BusNetwork Stat withPhone Jack(Fixed Address =199)

SA BusNetwork Stat withTerminalsAddressable

SA BusNetwork Stat withTerminals (FixedAddress = 199)

12FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 13: FAC2611-0U Advanced Application Field Equipment Controller ...

Terminal Wiring Guidelines,Functions, Ratings, andRequirements

Input and Output Wiring GuidelinesTable 3 provides information and guidelines about thefunctions, ratings, and requirements for the controllerinput and output terminals; and references guidelines fordetermining proper wire sizes and cable lengths.

In addition to the wiring guidelines in Table 3, observethese guidelines when wiring controller inputs andoutputs:

• Run all low-voltage wiring and cables separate fromhigh-voltage wiring.

• All input and output cables, regardless of wire size ornumber of wires, should consist of stranded, insulated,and twisted copper wires.

• Shielded cable is not required for input or outputcables.

• Shielded cable is recommended for input and outputcables that are exposed to high electromagnetic orradio frequency noise.

• Inputs/outputs with cables less than 30 m (100 ft)typically do not require an offset in the software setup.Cable runs over 30 m (100 ft) may require an offsetin the input/output software setup.

Table 3: FAC2611 Terminal Blocks, Functions, Ratings, Requirements, and CablesDetermine Wire Size andMaximum Cable Length

Function, Ratings, RequirementsTerminalLabel

Terminal BlockLabel

Same as (Universal) INn

Note: Use 3-wire cable fordevices that sourcepower from the +15Vterminal.

15 VDC Power Source for active (3-wire) input devicesconnected to the Universal INn terminals.

Provides 100 mA total current

+15 VUNIVERSAL

(Inputs)

See Guideline A in Table 4.Analog Input - Voltage Mode (0–10 VDC)

10 VDC maximum input voltage

Internal 75k ohm Pull-down

INn

See Guideline B in Table 4.Analog Input - Current Mode (4–20 mA)

Internal 100 ohm load impedance

Note: Current loop jumpers are fail-safe to maintain aclosed 4 to 20 mA current loop, even when thepower to the controller is interrupted or off. See UICurrent Loop Jumpers.

See Guideline A in Table 4.Analog Input - Resistive Mode (0–600k ohm)

Internal 12 V. 15k ohm pull up

Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel[Johnson Controls® sensor], 1k Platinum, and A99B SiliconTemperature Sensor) Negative Temperature Coefficient(NTC) Sensor

See Guideline A in Table 4.Binary Input - Dry Contact Maintained Mode

1 second minimum pulse width

Internal 12 V. 15k ohm pull up

Same as (Universal) INnUniversal Input Common for all Universal Input terminals

Note: All Universal ICOMn terminals share a common,which is isolated from all other commons.

ICOMn

13FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 14: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 3: FAC2611 Terminal Blocks, Functions, Ratings, Requirements, and CablesDetermine Wire Size andMaximum Cable Length

Function, Ratings, RequirementsTerminalLabel

Terminal BlockLabel

See Guideline A in Table 4.Binary Input - Dry Contact Maintained Mode

0.01 second minimum pulse width

Internal 18 V. 3k ohm pull up

INnBINARY

(Inputs)

Binary Input - Pulse Counter/Accumulator Mode

0.01 second minimum pulse width

(50 Hz at 50% duty cycle)

Internal 18 V. 3k ohm pull up

Binary Input Common for all Binary Input (IN) terminals

Note: All Binary ICOMn terminals share a common, whichis isolated from all other commons, except theConfigurableOutput (CO) common (OCOMn) whenthe CO is defined as an Analog Output.

ICOMn

See Guideline C in Table 4.Analog Output - Voltage Mode (0–10 VDC)

10 VDC maximum output voltage

10 mA maximum output current

Required an external load of 1,000 ohm or more.

Note: The Analog Output (AO) operates in the VoltageMode when connected to devices with impedancesgreater than 1,000 ohm. Devices that drop below1,000 ohmmay not operate as intended for VoltageMode applications.

OUTnANALOG

(Outputs)

Analog Output - Current Mode (4–20 mA)

Requires and external load between 0 and 300 ohm.

Note: The Analog Output (AO) operates in the CurrentMode when connected to devices with impedancesless than 300 ohm. Devices with impedancesgreater than 300 may not operate as intended forCurrent Mode applications.

Analog Output Signal Common for all Analog OUTterminals.

Note: All Analog Output Common terminals (OCOMn)share a common, which is isolated from all othercommons.

OCOMn

14FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 15: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 3: FAC2611 Terminal Blocks, Functions, Ratings, Requirements, and CablesDetermine Wire Size andMaximum Cable Length

Function, Ratings, RequirementsTerminalLabel

Terminal BlockLabel

See Guideline C in Table 4.Binary Output - 24 VAC Triac (External Power Source)

Connects OUTn to OCOMn when activated.

External Power Source Requirements:

30 VAC maximum output voltage

0.5 A maximum output current

1.3 A at 25% duty cycle

Maximum 6 cycles/hour with M9220BGx-3

40 mA minimum load current

OUTnBINARY

(Output)

Power SelectionJumper positioned toExternal (EXT) power.

Binary Output Common (for OUTn terminal)

Note: Each Binary Output Common terminal (OCOMn)is isolated from all other commons, including otherBinary Output Common terminals.

OCOMn

See Guideline C in Table 4.Binary Output - 24 VAC Triac (Internal Power Source)

Sources internal 24VAC power (24~ HOT).

OUTnBINARY

(Output)

Power SelectionJumper positioned toInternal (INT) power.

Binary Output - 24 VAC Triac (Internal Power Source)

Connects OCOMn to 24~ when activated.

Internal Power Source:

30 VAC maximum output voltage

0.5 A maximum output current

1.3 A at 25% duty cycle

Maximum 6 cycles/hour with M9220BGx-3

40 mA minimum load current

OCOMn

15FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 16: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 3: FAC2611 Terminal Blocks, Functions, Ratings, Requirements, and CablesDetermine Wire Size andMaximum Cable Length

Function, Ratings, RequirementsTerminalLabel

Terminal BlockLabel

See Guideline A in Table 4.Analog Output - Voltage Mode (0–10 VDC)

10 VDC maximum output voltage

10 mA maximum output current

Required an external load of 1,000 ohm or more.

OUTnCONFIGURABLE

(Outputs)

See Guideline C in Table 4.Binary Output - 24 VAC Triac (External Power Sourceonly)

Connects OUTn to OCOMn when activated.

External Power Source Requirements:

30 VAC maximum output voltage

0.5 A maximum output current

1.3 A at 25% duty cycle

Maximum 6 cycles/hour with M9220BGx-3

40 mA minimum load current

Same as (Configurable)OUTn.AnalogOutput Signal CommonAll Configurable Outputs(COs) defined as Analog Outputs (AOs) share a common,which is isolated from all other commons except the BinaryInput common.

Binary Output Signal Common All Configurable Outputs(COs) defined as Binary Outputs are isolated from all othercommons, including other CO commons.

OCOMn

16FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 17: FAC2611-0U Advanced Application Field Equipment Controller ...

Cable and Wire Length GuidelinesTable 4 defines cable length guidelines for the various wire sizes that may be used for wiring low-voltage (<30 V)input and outputs.Table 4: Cable Length Guidelines for Recommended Wire Sizes for Low-Voltage (<30 V) Inputs and Outputs

AssumptionsMaximum CableLength and Type

Wire Size/Gauge and TypeGuideline1

100 mV maximum voltage drop

Depending on cable and the connected inputor output device, you may have to define anoffset in the setup software for the input oroutput point.

457 m (1,500 ft) twistedwire

1.0 mm (18 AWG) stranded copperA

297 m (975 ft) twisted wire0.8 mm (20 AWG) stranded copper

183 m (600 ft) twisted wire0.6 mm (22 AWG) stranded copper

107 m (350 ft) twisted wire0.5 mm (24 AWG) stranded copper

100 mV maximum voltage drop

Depending on cable and the connected inputor output device, you may have to define anoffset in the setup software for the input oroutput point.

229 m (750 ft) twisted wire1.0 mm (18 AWG) stranded copperB

137 m (450 ft) twisted wire0.8 mm (20 AWG) stranded copper

91 m (300 ft) twisted wire0.6 mm (22 AWG) stranded copper

61 m (200 ft) twisted wire0.5 mm (24 AWG) stranded copper

N/ASee Figure 8 to determinecable length. Use twistedwire cable.

See Figure 8 to select wire size/gauge.Use stranded copper wire

C

1 The required wire sizes and lengths for high-voltage (>30 V) Relay Outputs are determined by the load connected to therelay, and local, national, or regional electrical codes.

Maximum Cable Length versus Load CurrentUse Figure 8 to estimate the maximum cable length relative to the wire size and the load current (in mA) when wiringinputs and outputs.

Note: Figure 8 applies to low-voltage (<30 V) inputs and outputs only.

Figure 8: Maximum Wire Length for Low-Voltage (<30 V) Inputs and Outputs by Current and Wire Size

17FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 18: FAC2611-0U Advanced Application Field Equipment Controller ...

SA/FC Bus and Supply PowerWiring GuidelinesCommBus and Power Supply Terminal Block Rating andRequirements Table provides information about thefunctions, ratings, and requirements for thecommunication bus and supply power terminals; andguidelines for wire sizes, cable types, and cable lengthswhen wiring the controller's communication buses andsupply power.

Important: Refer to the N2 Modernization Guide forLegacy N2 Controllers (LIT-12012005) forguidelines when using this device on an N2bus.

In addition to the guidelines in Comm Bus and PowerSupply Terminal Block Rating and Requirements Table,observe these guidelines when wiring an SA or FC busand the 24 VAC supply power:

• Run all low-voltage wiring and cables separate fromhigh-voltage wiring.

• All SA and FC bus cables, regardless of wire size,should be twisted, insulated, stranded copper wire.

• Shielded cable is strongly recommended for all SAand FC bus cables.

• Refer to the MS/TP Communications Bus TechnicalBulletin (LIT-12011034) for detailed informationregarding wire size and cable length requirements forSA and FC buses.

Table 5: Communications Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, andCables

Recommended Cable TypeFunction, Electrical Ratings/RequirementsTerminalLabels

TerminalBlock/PortLabel

0.6 mm (22 AWG) stranded, 3-wiretwisted, shielded cablerecommended

FC Bus Communications+

-FC BUS1

Signal Reference (Common) for Bus communicationsCOM

Isolated terminal (optional shield drain connection )SHLD

Bluetooth Commissioning Converterretractable cable or 24 AWG 3-pairCAT 3 Cable <30.5 m (100 ft)

RJ-12 6-Position Modular Connector provides:

FC Bus Communications

FC Bus Signal Reference and 15 VDC Common

15 VDC, 180 mA, Power for Bluetooth CommissioningConverter or ZFR or ZFR Pro Wireless Router

FC BusFC BUS1

(Port)

0.6 mm (22 AWG) stranded, 4-wire(2 twisted-pairs), shielded cablerecommended.

Note: The + and - wire are onetwisted pair, and the COMand SA PWR are thesecond twisted pair ofwires.

SA Bus Communications+

-SA BUS1

SA Bus Signal Reference and 15 VDC CommonCOM

15 VDC Supply Power for Devices on the SA Bus

(Maximum total current draw for bA Bus is 240 mA.)

SA PWR

24 AWG 3-pair CAT3 cable <30.5m (100 ft)

RJ-12 6-Position Modular Connector provides:

SA Bus Communications

SA Bus Signal Reference and 15 VDC Common

15 VDC Power for devices on the SA bus and BluetoothCommissioning Converter

SensorSensor1

18FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 19: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 5: Communications Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, andCables

Recommended Cable TypeFunction, Electrical Ratings/RequirementsTerminalLabels

TerminalBlock/PortLabel

0.8 mm to 1.0 mm

(18 AWG) 2-wire

24 VAC Power Supply - Hot

Supplies 20–30 VAC (Nominal 24 VAC)

HOT24~

24 VAC Power Supply Common (Isolated from all otherCommon terminals on controller)

14 VA

COM

1 The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38.4k baud. For moreinformation, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).

Setup and Adjustments

Setting the Device AddressesMetasys® field controllers are master devices on MS/TP(SA or FC) buses. Before operating field controllers ona bus, you must set a valid and unique device addressfor each controller on the bus. You set a field controller'sdevice address by setting the positions of the switcheson the DIP switch block at the top of the controller (Figure3). Device addresses 4 through 127 are the validaddresses for these controllers.

The DIP switch block has eight switches numbered 128,64, 32, 16, 8, 4, 2, and 1 (Figure 9). Switches 64 through1 are device address switches. Switch 128 is a modeswitch that enables a controller to operate on a ZFR/ZFRPro Series Wireless Field Bus. Set switch 128 to Off forall hard-wired SA and FC bus applications.

Figure 9: Device Address DIP Switch Block Set toAddress 21

Note: Metasys® field controllers ship with switch 128ON and the remaining address switches offrendering the controllers wired slave devices,which do not operate on MS/TP buses, but do notinterfere with bus operation. Set a valid andunique device address on the controller beforeapplying power to the controller on the bus.

To set the device addresses on Metasys® fieldcontrollers:

1. Set all of the switches on the address DIP switchblock (128 through 1) to Off.

2. Set one or more of the seven address switches (64though 1) to ON, so that the sum of the switchnumbers set to ON equals the intended deviceaddress. See Table 6 for valid device addresses.

Set the highest number switch that is less than orequal to the intended device address to ON. Thencontinue setting lower numbered switches until thetotal equals the intended address. For example, if theintended device address is 21, set switch 16 to ONfirst, then set switch 4 ON, followed by switch 1(16+4+1= 21). See Figure 9.

3. Set switch 128 to OFF for all hard-wired SA and FCbus applications.

Note: Do not connect a controller with switch 128set to ON to an active (hard-wired) SA or FCbus. When a controller with switch 128 set toON and a device address from 4 to 127 isconnected to a wired field bus, the entire fieldbus is rendered inoperable until the controlleris disconnected or switch 128 is set to Off.

4. Set a unique and sequential device address for eachof the controllers connected on the SA or FC busstarting with device address 4.

To ensure the best bus performance, set sequentialdevice addresses with no gaps in the device addressrange (4, 5, 6, 7, 8, 9, and so on). The controllers donot need to be physically connected on the bus intheir numerical device address order.

5. Write each controller's device address on the whitelabel below the DIP switch block on the controller'scover.

Table 6 describes the FC bus and SA bus devicesaddresses for Johnson Controls® MS/TPcommunications bus applications.

19FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 20: FAC2611-0U Advanced Application Field Equipment Controller ...

Refer to the MS/TP Communications Bus TechnicalBulletin (LIT-12011034) for more information oncontroller device addresses and how to set them onMS/TP buses.

Table 6: SA/FC Bus Device Address DescriptionsUse on DescriptionDevice

AddressReserved for FC Bus Supervisory Controller(not for use on controllers).

0

(Switch128 Off)

Reserved for peripheral devices (not for useon controllers).

1 to 3

(Switch128 Off)

Used for MS/TP master devices (controllers)that are hardwired to an SA bus or FC bus.

4 to 127

(Switch128 Off)

Setting the N2 Controller Address tobe Greater than 127N2-configured controllers support the full range ofpossible N2 device addresses provided by the N2 protocolstandard (1-255). However, these controllers requirespecial configuration for addresses above 127.

Use the following instructions for controllers greater than127.Note: Before you perform this procedure, make sure

that your controller has been converted fromBACnet to N2 protocol first.

Note: This special configuration is required becausecontroller addresses above 127 were originallyintended for use with the Wireless Field Bussystem.

1. Disconnect the 24 VAC supply from the controller.2. Remove the FC Bus connector from the controller.3. Set the address switch set to the desired N2 address.4. Set the address switch segment labeled 128 to OFF.5. Reconnect the 24 VAC supply to the controller.6. Using an SA bus connection, download the firmware

and controller application file. The download processasks to confirm switching the communication protocolto N2.

7. Click OK.8. After the download is finished, disconnect the 24

VAC supply to the controller.9. Set the address switch segment labeled 128 to ON.

10. Reattach the FC Bus connector to the controller.11. Reconnect the 24 VAC supply to the controller.

Removing the Controller CoverImportant: Electrostatic discharge can damage

controller components. Use properelectrostatic discharge precautions duringinstallation, setup, and servicing to avoiddamaging the controller.

Important: Disconnect all power sources to thecontroller before removing cover andchanging the position of any jumper or theEOL switch on the controller. Failure todisconnect power before changing a jumperor EOL switch position can result in damageto the controller and void any warranties.

The controller cover is held in place by four plastic latchesthat extend from the base and snap into slots on theinside of the housing cover.

To remove the controller cover:

1. Place your fingertips under the two cover lift tabs onthe sides of the housing cover and gently pry the topof the cover away from the base to release the coverfrom the two upper latches.

2. Pivot the top of the cover further to release it from thelower two latches.

3. Replace the cover by placing it squarely over thebase, and then gently and evenly push the cover onto the latches until they snap into the latched position.

Figure 10: FAC26 with Cover Removed Showing EOLSwitch and Jumper Positions

20FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 21: FAC2611-0U Advanced Application Field Equipment Controller ...

Setting the End-of-Line (EOL) SwitchEach field controller has an EOL switch, which, when setto ON, sets the controller as a terminating device on thebus. See Figure 10 for the EOL switch location. Thedefault EOL switch position is Off.

Figure 11: End-of-Line Switch Positions

To set the EOL switch on a field controller:

1. Determine the physical location of the field controlleron the FC bus.

2. Determine if the controller must be set as aterminating device on the bus.

Note: Refer to the MS/TP Communications BusTechnical Bulletin (LIT-12011034) for detailedinformation regarding EOL termination rulesand EOL switch settings on FC buses.

3. If the controller is a terminating device on the FC bus,set the EOL switch to ON. If the controller is not aterminating device on the bus, set the EOL switch toOff.

When a controller is connected to power with its EOLswitch set to ON, the amber EOL LED on thecontroller cover is lit.

Setting the Input and OutputJumpers

Risk of Electric Shock: Disconnect supply power tothe field controller before attempting to adjust the BinaryOutput Source Power Selection Jumpers. Failure todisconnect the supply power may result in electric shock.

Mise En Garde: Risque de décharge électrique

Débrancher l'alimentation de l'controller avant toutréglage du Binary Output Source Power SelectionJumpers. Le non-respect de cette précaution risque deprovoquer une décharge électrique.

Binary Output (BO) Source PowerSelection Jumpers

Risk of Electric Shock: Disconnect supply power tothe field controller before attempting to adjust the BinaryOutput Source Power Selection Jumpers. Failure todisconnect the supply power may result in electric shock.

Mise En Garde: Risque de décharge électrique:Débrancher l'alimentation de l'controller avant toutréglage du Binary Output Source Power SelectionJumpers. Le non-respect de cette précaution risque deprovoquer une décharge électrique.

Important: Do not connect an external power sourceto a binary output (BO) when the BO powersource jumper is in the internal power (INT)position. Connecting external power to aBO that sources internal power can damagethe controller and void any warranties.

The BO source power selection jumpers determinewhether a BO provides internal power (sourced from thefield controller) to the output load (INT position) orrequires an external power source (EXT position) for theoutput load. Figure 12 shows an example of a controllerBOs and the associated power selection jumpers to theright of the BOs terminal block.

Figure 12: Example Binary Outputs and theAssociated Source Power Jumper Positions

21FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 22: FAC2611-0U Advanced Application Field Equipment Controller ...

UI Current Loop JumpersThe current loop fail-safe jumpers are on the circuit boardunder the controller cover near the UI terminals (Figure10). When a UI is defined (in the system software) as a4-20 mA Analog Input and the UI’s current loop jumperis in the Disabled (default) position (Figure 13), the 4-20mA current loop circuit opens whenever power to thecontroller is interrupted or off.

Figure 13: Current Loop Jumper Positions

Setting the current loop jumper to the Enabled position(Figure 13) connects an internal 100 ohm resistor acrossthe UI terminals, which maintains the 4-20 mA currentloop circuit even when power to the controller isinterrupted or off.

Important: Current Loop jumpers must be in theDisabled (default) position for all UIs thatare not set up to operate as 4-20 mA analoginputs.

Table 7 identifies the current loop switches associatedwith each UI on the FAC2611 controller.

Table 7: FAC2611 UI Inputs and Jumper LabelsSwitch Label on Current Loop DIPSwitch Block Board

Universal InputLabel

J20IN1

J21IN2

J22IN3

J23IN4

J24IN5

J25IN6

Commissioning Field ControllersYou commission BACnet® MS/TP field controllers withthe Controller Configuration Tool (CCT) software. Referto Controller Tool Help (LIT-12011147) for detailedinformation on commissioning field controllers.

22FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 23: FAC2611-0U Advanced Application Field Equipment Controller ...

Troubleshooting Field ControllersObserve the Status LEDs on the front of the field controller and see table below to troubleshoot the controller.

Table 8: Status LEDs and Descriptions of LED StatesDescription of LED StatesNormal LED

StateLED ColorLED Label

Off Steady = No Supply Power or the controller’s polyswitch/resettable fuseis open. Check Output wiring for short circuits and cycle power to controller.

On Steady = Power Connected

On SteadyGreenPOWER

Off Steady = No Faults

On Steady = Device Fault; no application loaded; Main Code downloadrequired, if controller is in Boot mode.

Blink - 2 Hz = Download or Startup in progress, not ready for normal operation

Rapid blink = SA Bus communications issue

Off SteadyRedFAULT

Blink - 2 Hz = Data Transmission (normal communication)

Off Steady = No Data Transmission (N/A - auto baud not supported)

On Steady = Communication lost, waiting to join communication ring

Blink - 2 HzGreenSA BUS

Blink - 2 Hz = Data Transmission (normal communication)

Off Steady = No Data Transmission (auto baud in progress)

On Steady = Communication lost, waiting to join communication ring

Blink - 2 HzGreenFC BUS

On Steady = EOL switch in ON position

Off Steady = EOL switch in Off position

Off (Except onterminatingdevices)

AmberEOL

Repair InformationThe MS-FAC2611-0U model is UL 864 10th EditionUUKL/ORD-C100-13 UUKLC listed for smoke control. Ifa field controller fails to operate within its specifications,contact the Johnson Controls Repair Center in Louisville,Kentucky, at 1-502-671-7312.

AccessoriesSee Table 9 for field controller accessories ordering information.Table 9: Accessories Ordering Information

DescriptionProduct Code NumberTransformer, 120/24 VAC, 96 VA, with circuit breaker and 120 VAC outlet, approved for SmokeControl

PAN-PWRSP-U

Technical SpecificationsTable 10: FAC2611-0U Field Application Controller

MS-FAC2611-0U Field Application Controller, UL/cUL 864 Listed for Smoke ControlProduct Code Numbers

24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supplyClass 2 (North America)

Supply Voltage

23FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 24: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 10: FAC2611-0U Field Application Controller14 VA maximum

Note: VA rating does not include any power supplied to the peripheral devicesconnected to Binary Outputs (BOs) or Configurable Outputs (COs), whichcan consume up to 12 VA for each BO or CO; for a possible totalconsumption of an additional 84 VA (maximum).

Power Consumption

Operating: 0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing

Storage: -40 to 80°C (-40 to 176°F); 5 to 95% RH noncondensing

Ambient Conditions

DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and128–255 are reserved and not valid controller addresses.)

Controller Addressing for BACnetMS/TP

DIP switch set; valid control device addresses 1-255Controller Addressing for N2

RS-485: selectable BACnet MS/TP or N2

3-wire FC Bus between the supervisory controller and field controllers

4-wire SA Bus between field controller, network sensors and other sensor/actuatordevices, includes a lead to source 15 VDC supply power (from field controller) tobus devices.

Communications Bus

H8SX/166xR Renesas® 32-bit microcontrollerProcessor

4 MB Flash Memory and 1 MB Random Access Memory (RAM)Memory

Super capacitor maintains power to the onboard real-time clock for a minimum of72 hours when supply power to the controller is disconnected.

Real-Time Clock Backup Power Supply

6 - Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0-600k ohm, or Binary DryContact

2 - Binary Inputs:Defined as Dry Contact Maintained or Pulse Counter/AccumulatorMode

3 - Binary Outputs: Defined as 24 VAC Triac (selectable internal or external sourcepower)

4 - Configurable Outputs: Defined as 0-10 VDC or 24 VAC Triac BO

2 - Analog Outputs: Defined as 0–10 VDC or 4–20 mA

Input and Output Capabilities

Input: 16-bit resolution

Output: 16-bit resolution, +/- 200 mV accuracy in 0-10 VDC applications

Analog Input/AnalogOutput Resolutionand Accuracy

Input/Output: Fixed Screw Terminal Blocks

SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable Screw TerminalBlocks

SA/FC Bus Port: RJ-12 6-Pin Modular Jacks

Terminations

Horizontal on single 35 mmDIN rail mount (preferred), or screwmount on flat surfacewith three integral mounting clips on controller

Mounting

Enclosurematerial: ABS and polycarbonate UL94 5VB; Self-extinguishing, PlenumRated

Housing

150 x 190 x 53 mm (5-7/8 x 7-1/2 x 2-1/8 in.) including terminals and mounting clipsNote: Mounting space requires an additional 50 mm (2 in.) space on top, bottom

and front face of controller for easy cover removal, ventilation and wireterminations.

Dimensions (Height x Width x Depth)

0.5 kg (1.1 lb)Weight

24FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Page 25: FAC2611-0U Advanced Application Field Equipment Controller ...

Table 10: FAC2611-0U Field Application ControllerUnited States: UL Listed, File E107041, CCN PAZX, UL 916, Energy ManagementEquipment; FCC Compliant to CFR47, Part 15, Subpart B, Class A

UL Listed, File S4977, UL 864 UUKL/UUKLC 10th Edition Listed, Smoke ControlUnits and Accessories for Fire Alarm Systems Equipment

Compliance

Canada: UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, SignalEquipment; Industry Canada Compliant, ICES-003

UL Listed, File S4977, UL 864 UUKL/ORD-C100-13 10th Edition Listed, SmokeControl Units and Accessories for Fire Alarm Systems

Europe: Johnson Controls declares that this product is in compliance with theessential requirements and other relevant provisions of the EMC Directive.

Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant

BACnet International: BACnet Testing Laboratories (BTL) Protocol Revision 7Listed BACnet Advanced Application Specific Controller (B-ASC)

The performance specifications are nominal and conform to acceptable industry standard. For application at conditionsbeyond these specifications, consult the local Johnson Controls® office. Johnson Controls shall not be liable fordamages resulting from misapplication or misuse of its products.

APAC Single Point of Contact:NA/SA Single Point of Contact:European Single Point of Contact:JOHNSON CONTROLS

C/OCONTROLSPRODUCTMANAGEMENT

NO. 22 BLOCK D NEW DISTRICT

WUXI JIANGSU PROVINCE 214142

CHINA

JOHNSON CONTROLS

507 E MICHIGAN ST

MILWAUKEE WI 53202

USA

JOHNSON CONTROLS

WESTENDHOF 3

45143 ESSEN

GERMANY

Building Technologies & Solutions507 E. Michigan Street, Milwaukee, WI 53202

Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.All other marks herein are the marks of their respective owners.© 2018 Johnson Controls

www.johnsoncontrols.comPublished in U.S.A.

25FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions