Experiment Three Phase transformers -...

13
OBJECTIVE: When you have completed this Experiment, you should be able to: Describe a three-phase transformer . Being familiar with operating characteristics of three phase transformers. Being able connect transformer windings in Y and ∆ configurations, and verify that windings are connected with the proper phase relationships. Voltage and current measurements will be used to study transformer operation and working characteristics. Overview: Three-phase double-wound transformers are mainly used in power transmission and are usually of the core type. They basically consist of three pairs of single-phase windings mounted on one core, as shown in Figure 6.1, The primary and secondary windings in Figure 6.1 are wound on top of each other in the form of concentric cylinders, The windings may be with the primary delta-connected and the secondary star-connected, or star-delta, star-star or delta-delta, depending on its use. Figure 6.1: Three-phase transformer A delta connection is shown in Figure 6.2 (a) and a star connection in Figure 6.2(b). Islamic University of Gaza Faculty of Engineering Electrical Engineering department Electric Machines Lab Eng. Mohammed S. Jouda Eng. Omar A. Qarmout Eng. Amani S. Abu Reyala Experiment 6 Three Phase transformers

Transcript of Experiment Three Phase transformers -...

Page 1: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

OBJECTIVE:

When you have completed this Experiment, you should be able to: Describe a three-phase transformer . Being familiar with operating characteristics of three phase transformers. Being able connect transformer windings in Y and ∆ configurations, and

verify that windings are connected with the proper phase relationships. Voltage and current measurements will be used to study transformer operation

and working characteristics.

Overview:

Three-phase double-wound transformers are mainly used in power transmission and are usually of the core type. They basically consist of three pairs of single-phase windings mounted on one core, as shown in Figure 6.1, The primary and secondary windings in Figure 6.1 are wound on top of each other in the form of concentric cylinders, The windings may be with the primary delta-connected and the secondary star-connected, or star-delta, star-star or delta-delta, depending on its use.

Figure 6.1: Three-phase transformer

A delta connection is shown in Figure 6.2 (a) and a star connection in Figure 6.2(b).

Islamic University of Gaza Faculty of Engineering Electrical Engineering department

Electric Machines Lab Eng. Mohammed S. Jouda Eng. Omar A. Qarmout Eng. Amani S. Abu Reyala

Experiment

6

Three Phase transformers

Page 2: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

Figure 6.1: Delta and Star connection

The main features of three-phase circuits that are important to recall are that there are two types of connections, Y and ∆. Furthermore, in Y-connected three phase circuits, the line voltages are greater than the phase voltages by the factor √3 and the line and phase currents are equal. On the other hand, in ∆-connected three-phase circuits, the line currents are greater than the phase currents by the factor √3 and the line and phase voltages are equal. A three-phase transformer can be a single unit or three single-phase units, and the primary and secondary windings can be connected in either Y or ∆ to give four types of connections, ∆-∆, Y-Y, ∆-Y, and Y-∆. Usually, three-phase power systems has a line voltage of 208 V (380 V or 415 V in some countries), and standard 120-V voltage (220 V or 240 V in some countries) can be obtained between a line wire and the neutral wire as shown in Figure 6.3. The Y connected secondary provides three-phase 120/208-V power using 4 wires as shown, and the primary side of the transformer may be connected in ∆ like in the figure, or in Y. One big advantage of using a ∆ configuration for the primary is that only three wires are needed to distribute the three phases.

Figure 6.3: Commercial Three-Phase 120/208-V Power System

An advantage of a ∆-∆ connection is that two single-phase transformers (instead of three) can be operated in what is known as the open-∆ or "V" configuration if one of the three transformers becomes damaged or is removed from service. The open-∆ transformer bank still delivers phase voltages and currents in the correct relationship, but the capacity of the bank is reduced to 57.7% (1/√3) of the total nominal capacity available with three transformers in service.

Page 3: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

In the ∆-∆ and Y-Y configurations, the line voltage at the secondary is equal to the line voltage at the primary times the inverse of the turns ratio. In the ∆-Y configuration, the line voltage at the secondary is equal to the line voltage at the primary times the inverse of the turn ratio times √3. In the Y-∆ configuration, the line voltage at the secondary is equal to the line voltage at the primary times the inverse of the turn ratio times 1/√3. Regardless of how the windings in a three-phase transformer are connected, precautions must be taken to ensure that the secondaries are connected with the proper phase relationships. For a Y configuration, this means that the voltage measured across any two secondary windings (line voltage) must be √3 times greater than the voltage across either winding (phase voltage). If not, the connections must be reversed before continuing. With a ∆ configuration, the voltage measured between the ends of two series connected secondary windings must equal the voltage across either winding. If not, the connections must be reversed. When one end of the third winding is connected, the voltage measured across all three series-connected windings must equal zero before connecting them together to close the ∆. It is extremely important to verify that the voltage within the ∆ equals zero before the ∆ is closed. If not, the resulting current will be very high and damage the windings.

Three-Phase Transformer Connections: Objectives:

When you have completed this exercise, you will be able to connect three-phase transformers in ∆-∆ and Y-Y configurations. You will measure winding voltages to verify that the secondary windings are connected with the proper phase relationships, and you will verify that the voltage within a ∆ equals zero before the ∆ is closed.

Discussion:

As mentioned earlier, four common ways of connecting transformer windings to form a three-phase transformer are: ∆-∆, Y-Y, ∆-Y, and Y-∆, as shown in Figures 6.4 and 6.5. In order to set up a Y connection, first connect the three components (windings) together at a common point for interconnection with the neutral wire, and then connect the other end of each component in turn to the three line wires. To set up a ∆ connection, connect the first component in series with the second, the second in series with the third, and the third in series with the first to close the ∆ loop. The three line wires are then separately connected to each of the junction nodes in the ∆ loop.

Figure 6.4: ∆-∆ and Y-Y Connections

Page 4: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

Figure 6.5: ∆-Y and Y-∆ Connections

Before a three-phase transformer is put into service, the phase relationships must be verified. For a Y configuration, the line voltages at the secondary windings must all be √3 times greater than the corresponding phase voltages. If not, winding connections must be reversed. To verify that phase relationships are correct for a Y configuration, the voltage between two windings (EAB) is measured as shown in Figure 6.6 (a) to confirm that it is √3 times greater than the line-to-neutral voltage across either winding (for example EAN). The voltages between the third winding and the others (EBC and ECA) are then measured to confirm that they are also √3 times greater than the phase voltage (EAN), as shown in Figure 6.6 (b).

Figure 6.6: Confirming Phase Relationships in a Y-Connected Secondary

For a ∆ configuration, the line voltages at the secondary windings must all be equal. If not, winding connections must be reversed. To verify that phase relationships are correct for a ∆ configuration, the voltage across two series connected windings (ECA) is measured as shown in Figure 6.7 (a) to confirm that it equals the voltage across either winding (EAB and EBC). The third winding is then connected in series, and the voltage across the series combination of the three windings is measured to confirm that it is zero before the ∆ is closed, as shown in Figure 6.7 (b). This is extremely important for a ∆ configuration; because a very high short circuit current will flow if the voltage within the ∆ is not equal to zero when it is closed.

Page 5: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

Figure 6.7: Confirming that the ∆ Voltage Equals Zero

Procedure

1. Connect the Three-Phase Transformer module in the ∆-∆ configuration shown in Figure 6.8.

Figure 6.8: Three-Phase Transformer Connected in ∆-∆

2. Turn on the power and adjust the voltage control to obtain the line-to-line voltage ES equals 200V. Use E1 to measure the winding voltages and record the results.

E1-2 = ----- V, E1-7= ----- V, E1-12 = ----- V E3-5 = ----- V, E3-10 = ----- V, E3-15 = ---- V

3. Do the measurements confirm that the secondary windings are connected with the

proper phase relationships? ----- Yes ----- No

4. Are the voltages within the secondary ∆ equal to zero, thus confirming that it is safe

to close the ∆? ----- Yes ----- No

Note: The value of E3-15 will not be exactly zero volts because of small imbalances in the three-phase line voltages. If it is more than 5 V, the winding connections have to be checked carefully.

Page 6: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

5. When the winding connections are confirmed to be correct, close the ∆ on the secondary side of the transformer. Connect E1, E2, and E3 to measure the line voltages at the secondary. Turn on the power and adjust the voltage control to obtain ES equals 200V. Note that the transformer is connected using the 1:1 ratio, so the primary and secondary voltages should be equal.

6. Observe the voltage phasors on the Phasor Analyzer. 7. Turn off the power. Connect E2 to measure line voltage E1-2 on the primary side.

Turn on the power and adjust the voltage control voltage to obtain ES equals 200V. Compare the voltage phasor of E1-2 on the primary side with that of E3-5 on the secondary side. Does the Phasor Analyzer display show that the voltages are equal and in phase, except for possibly a small difference due to transformer reactance?

----- Yes ----- No

8. Turn off the power and connect the Three-Phase Transformer module in the Y-Y configuration shown in Figure 6.9

Figure 6.9: Three-Phase Transformer Connected in Y-Y

9. Turn on the power and adjust the voltage control to obtain ES equals 200V. Use E1 to measure the winding voltages and record the results.

E1-6 = ----- V, E1-11 = ----- V, E6-11 = ----- V E1-2 = ----- V, E6-7 = ----- V, E11-12 = ----- V E3-8 = ----- V, E3-13 = ----- V, E8-13 = -----V E3-5 = -----V, E8-10 = ----- V, E13-15 = -----V

10. Do the measurements confirm that the secondary windings are connected with the proper phase relationships?

----- Yes ----- No

11. Are the line-to-line voltages on the primary and secondary sides of the transformer √3 times greater than the line-to-neutral values?

----- Yes ----- No

Page 7: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

12. Connect E1, E2, and E3 to measure phase voltages E3-5, E8-10, and E13-15 at the secondary. Turn on the power and adjust ES at about the same value as used previously.

13. Observe the voltage phasors on the Phasor Analyzer. Does the display confirm they are equal with a 120o phase shift between each of them?

----- Yes ----- No

14. Turn off the power without modifying the setting of the voltage control. 15. Connect E2 to measure phase voltage E1-2 on the primary side. Turn on the power

and compare the voltage phasor of E1-2 on the primary side with that of E3-5 on the secondary side. Does the Phasor Analyzer display show that the voltages are equal and in phase, except for possibly a small difference due to transformer reactance?

----- Yes ----- No

By using the virtual instrumentation ( LVVL Program ): Repeat all above procedure by using LVVL Program and Switch on the power supply unit and adjust the voltage control to obtain the line-to-line voltage 100 V, Measure and record all above.

Conclusion

You connected transformer windings in three-phase ∆-∆ and Y-Y configurations, and measured winding voltages to ensure that secondary windings were connected with the proper phase relationships. You confirmed that the voltage within a ∆ was zero before closing the ∆, and that the ∆-∆ and Y-Y configurations produced no phase shift between the incoming primary voltages and the outgoing secondary voltages.

Voltage and Current Relationships:

Objectives

When you have completed this exercise, you will be familiar with the voltage and current ratios of three-phase transformers connected in ∆-Y and Y-∆ configurations. Measurements of primary and secondary voltages will demonstrate that these configurations create a phase shift between the incoming and outgoing voltages.

Discussion

As seen in the previous exercise, primary and secondary voltages in ∆-∆ and Y-Y connections are in phase and the voltage at the secondary is equal to the voltage at the primary times the inverse of the turns ratio. In ∆-Y and Y-∆ connections however, there will be a 30o phase difference between the primary and secondary voltages. Also, in the ∆-Y configuration, the line voltage at the secondary is equal to the line voltage at the primary times the inverse of the turn ratio times √3. On the other hand, in the Y-∆ configuration, the line voltage at the secondary is equal to the line voltage at the primary times the inverse of the turn ratio times 1/√3. The 30o phase shift between the primary and secondary does not create any problems for isolated groups of loads connected to the outgoing lines from the secondary. However, if the outgoing lines from the secondary of a three-phase transformer have to be connected in parallel with another source, the phase shift might make such a parallel connection impossible, even if the line voltages are the same. Recall that in order for three-phase circuits and sources to be connected in parallel, line voltages must be equal, have the same phase sequence, and be in phase when the parallel connection is made.

Page 8: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

Figure 6.10 shows a three-phase transformer, with a turns-ratio equal to 1:1, connected in the ∆-Y configuration and feeding a three-phase load. The voltage across each primary winding EPRI equals the incoming line voltage, but the outgoing line voltage ESEC is √3 times that voltage because the voltage across any two secondary windings is √3 times greater than the voltage across a single secondary winding. Note that if the three-phase transformer had a turns ratio of 1:10, the line voltage at the secondary would be 10 x √3 times greater the line voltage at the primary, because the inverse of the turns ratio is multiplied by the √3 factor. The line current in the secondary is the same as the phase current, but the line current in the primary is √3 times greater than the corresponding phase current.

Figure 6.10: Three-Phase ∆-Y Configuration

Procedure:

1. Connect the Three-Phase Transformer module in the Y-∆ configuration shown in Figure 6.11. Make sure that the voltage within the ∆ is zero before closing the ∆.

Figure 6.11: Three-Phase Transformer Connected in Y-∆

2. Turn on the power and adjust the voltage control to obtain the line-to-line voltage ES equals 200V. Connect E1, E2, and E3 to measure the line voltages at the primary and record the results. Find also the average value of the line voltage given.

E1-6 = ----- V, E11-1 = ----- V, E6-11 = ----- V

AVG (E1, E2, E3) = ----- V

Page 9: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

3. Observe the voltage phasors on the Phasor Analyzer. Are they approximately equal with a 120o phase shift between each of them?

----- Yes ----- No

4. Turn off the power without modifying the setting of the voltage control. Connect E1, E2, and E3 to now measure the line voltages at the secondary. Turn on the power and record the line voltages as well as the average value of the line voltages.

E3-5 = ----- V, E8-10 = ----- V, E13-15 = ----- V

AVG (E1, E2, E3) = ----- V

5. Observe the voltage phasors on the Phasor Analyzer. Does the display confirm they are equal with a 120o phase shift between each of them?

----- Yes ----- No

6. Turn off the power without modifying the setting of the voltage control. Connect E2 to measure line voltage E1-6 on the primary side. Turn on the power and compare the voltage phasor of E1-6 on the primary side with that of E3-5 on the secondary side. Does the Phasor Analyzer display confirm a phase shift of around 30o between the two?

----- Yes ----- No

7. Calculate the ratio AVG ESEC / AVG EPRI using the values recorded in steps 6 and 9. Is it approximately equal to 1/√3?

----- Yes ----- No

8. Turn off the power and connect the Three-Phase Transformer module in the ∆-Y configuration shown in Figure 6.12. Set the Resistive Load module thus R equals 1100Ω, and connect I1, I2, and I3 to measure the three line currents to the load.

9. Connect E1, E2, and E3 to measure the line voltages at the primary, turn on the power, and adjust the voltage control to obtain the line-to-line voltage of ES equals 200V. Record the value of the line voltages, as well as the average value.

E1-2 = ----- V, E6-7 = ----- V, E11-12 = ----- V AVG (E1, E2, E3) = ----- V

Figure 6.12: Three-Phase Transformer Connected in ∆-Y

Page 10: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

10. Observe the voltage and current phasors on the Phasor Analyzer. Does the display confirm that the voltage and current phasors are in phase?

----- Yes ----- No

11. Turn off the power without modifying the setting of the voltage control. Connect E1, E2,

and E3 to now measure the line voltages E3-8, E8-13, and E13-3 on the secondary side. Turn on the power. Does the Phasor Analyzer display show that the voltage phasors lead the current phasors by 30o?

----- Yes ----- No

Note: Since the currents in the secondary are in phase with the voltages in the primary, the Phasor Analyzer display is equivalent to observing all voltage phasors at the same time, except for the difference in scale between the parameters.

12. Return to the Metering application and record the measured values for the line voltages at the secondary, and also the average value.

E3-8 = ----- V, E8-13 = ----- V, E13-3 = -----V AVG (E1, E2, E3) = ----- V

13. Calculate the ratio AVG ESEC / AVG EPRI using the values recorded in steps 9 and 12. Is it approximately equal to √3?

----- Yes ----- No

14. Turn off the power and connect I1 and I2 to measure the line and phase currents on the primary side of the ∆-Y configuration by opening the circuit at points X and Y shown in Figure 5.10. Remember to reconnect the load resistors at the secondary when I1 and I2 are disconnected.

15. Turn on the power and calculate the ratio ILINE / IPHASE for the primary circuit using the measured currents. Is the ratio approximately equal to √3?

----- Yes ----- No 16. Is the line current on the primary side approximately equal to the line current on the

secondary side? ----- Yes ----- No

By using the virtual instrumentation ( LVVL Program ): Repeat all above procedure by using LVVL Program and Switch on the power supply unit and adjust the voltage control to obtain the line-to-line voltage 100 V, Measure and record all above. CONCLUSION

You connected a 1:1 three-phase transformer in Y-∆ and ∆-Y configurations, and saw that the line voltage between primary and secondary either increased or decreased by a √3 factor. You also confirmed that the outgoing line voltages at the secondary were shifted 30o with respect to the incoming line voltages at the primary.

Page 11: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

The Open-∆ Connection:

Objective

When you have completed this exercise, you will be able to connect two transformers in an open-∆ configuration to supply a balanced three-phase load. You will also be able to demonstrate that the maximum power in the open-∆ configuration is 57.7% (1/√3) the capacity of a normal ∆-∆ configuration. Discussion

The open-∆ connection allows three-phase balanced loads to be supplied using only two transformers. This configuration is useful if the amount of load power is not excessive, or when one of the three transformers must be taken out of service because of damage or some other reason. The most important thing to note is that the power capacity in the open-∆ configuration is 57.7% of the total capacity of the normal ∆-∆ configuration, or 86.6% of the capacity of the two remaining transformers. The reason for this is quite simple, and Figure 6.13 will be used to illustrate the explanation.

Figure 6.13: Open-∆ Configuration

In a standard ∆ configuration, the line current is √3 times greater than the current flowing in the phase winding. When one of the transformers is absent, full line current flows through the phase windings, since line and phase currents are the same in an open-∆ configuration. The large increase in current will cause the phase windings to overheat and will damage the transformer unless load power is reduced. The line current must therefore be reduced by √3, meaning that the power capacity in the open-∆ configuration is limited to 57.7% of the power capacity normal ∆-∆ configuration. The following example illustrates the calculation of maximum power. When three 50-kVA transformers are connected in ∆-∆ configuration, the total capacity of the bank is their sum, or 150. For two transformers in an open-∆ configuration, the capacity is 150 /3, or 86.6, which is the same as 86.6% of the total capacity of two transformers (0.866 x 100 ' 86.6). PROCEDURE

1. Connect the Three-Phase Transformer module in the ∆-∆ configuration shown in Figure 6.14. Close the ∆s at primary terminals 7, 11 (point X) and secondary terminals 10, 13 (point Y) last, and use separate wires for the connections. Connect E1 and I1 at the primary and E2, I2, and I3 at the secondary as shown. Make sure the current within the secondary ∆ equals zero before applying full power to the circuit.

Page 12: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

Figure 6.14: Demonstrating an Open-∆ Configuration

2. Connect the Resistive Load module as shown and set R to 629Ω by placing all switches in the on position. Connect E3 in parallel with one of the resistor as shown in Figure 6.14. Turn on the power and adjust the voltage control to obtain the line-to-line voltage ES equals 200V. Record the line and phase (winding) values indicated by the meters as well as the apparent powers indicated by meters PQS1 and PQS2.

E1 = ----- V, E2 = ----- V, E3 = ----- V I1 = ----- A, I2 = ----- A, I3 = ----- A

S1 = ----- VA, S2 = ----- VA, S3 = ----- VA

3. Do the meters show that the primary and secondary line voltages are equal (E1, E2), and the current in the primary windings equals that flowing in the secondary windings (I1, I2)?

----- Yes ----- No

4. Is the line current to the load shown by I3 around √3 times greater than phase- current I2 in the secondary winding?

----- Yes ----- No

Note: Observe also that the load voltage shown by E3 is √3 times less than line voltage E2 at the secondary.

5. Carefully open the primary ∆ at point X by disconnecting the wire at primary terminal 11, and observe the change in line and phase currents. Exercise caution when you open the ∆ since high voltage is present on the wire.

6. 7. Do the phase currents at the primary and secondary (I1, I2) increase by a large amount, as

well as the values of S1 and S2? ----- Yes ----- No

8. Is the increase approximately equal to √3? ----- Yes ----- No

9. With the open-∆ configuration, does the phase current in the secondary now equal the line current to the load?

----- Yes ----- No

Page 13: Experiment Three Phase transformers - site.iugaza.edu.pssite.iugaza.edu.ps/mjouda/files/Exp-62.pdf · star-delta, star-star or delta-delta, ... in Y-connected three phase circuits,

10. Close the ∆ at point X, and open the secondary at point Y by disconnecting the wire at terminal 13. Once again exercise caution with the open connection. Do you observe the same results as in the previous steps?

----- Yes ----- No

11. Turn off the power without readjusting the voltage control. Remove the connecting wires completely between primary terminals 7, 11 and secondary terminals 10, 13.

12. Turn on the power. Since the load power requirement has not changed, are the currents in the primary and secondary windings still at the same high level?

----- Yes ----- No

13. By what amount should the load resistance be increased to lower the currents in the windings to the value measured in step 2? Note that increasing load resistance lowers the current flowing in the load, hence load power.

14. Adjust the value of the load resistors to obtain the same winding current as measured in step 2. What value do you obtain?

15. Record the apparent power indicated by meters PQS1 and PQS3. S1 = ----- VA, S3 = ----- VA

16. Is the value of apparent power S3 approximately 57.7% less than that measured in step 2,

thus confirming that load power must be reduced to avoid exceeding the current rating of the transformer windings?

----- Yes ----- No

17. Turn off the power without readjusting the voltage control and reconnect the ∆s at terminals 7, 11, and terminals 10, 13. Connect E1, E2, E3, I1, I2, and I3 to measure the line voltages and line currents at the secondary.

18. Turn on the power and then use the Phasor Analyzer to observe the voltage and current phasors. Once again, open the ∆s at the primary, and then the secondary in the same sequence as steps in 5- 9.

19. Does the Phasor Analyzer display confirm that there is no change in the three-phase load voltages and currents?

----- Yes ----- No

CONCLUSION

You set up a three-phase transformer in the open-∆ configuration and observed that it supplies a three-phase load with voltages and currents in the proper phase relationships. You also demonstrated that load power must be reduced by 57.7% (1/√3) to avoid exceeding the current rating of the phase windings

Exercise:

what's meaning of scott transformer ?