example of thesis format

download example of thesis format

of 44

Transcript of example of thesis format

  • 8/7/2019 example of thesis format

    1/44

    REDUCING HARMONIC VOLTAGE AT INDUSTRIAL AREADISTRIBUTION NETWORK USING NETWORK CONFIGURATION

    MANAGEMENT

    by

    MOHD SHAHED BIN LATIF

    Thesis submitted in fulfillment of the requirementsfor the degree of

    BEng. (Electrical & Electronic Engineering)

    March 2008

    ii

  • 8/7/2019 example of thesis format

    2/44

    ACKNOWLEDGEMENTS

    This research could not been completed and this thesis cannot be written

    without the scholarship and resources provided by Tenaga Nasional Berhad.

    Thanks to my supervisor, Dr. Ir. Syafruddin Masri, for the guidance and

    encouragement during my study process. Also thanks to my colleagues at

    Gelugor Power Station, Penang who always support and encourage me and,

    the staff at Regional Control Centre, Bayan Lepas who provided me all the

    information required for my research. And finally, thanks to my family, especially

    my departed wife who offered moral support and endured this long process with

    me.

    iii

  • 8/7/2019 example of thesis format

    3/44

    TABLE OF CONTENTS

    PAGE

    ACKNOWLEDGEMENTS iiTABLE OF CONTENTS iiiLIST OF TABLES viLIST OF FIGURES viiiLIST OF ABBREVIATION xABSTRAK xiABSTRACT xii

    CHAPTER ONE : INTRODUCTION

    1.1 Overview on Harmonic 11.2 Standards on Harmonic 31.3 Harmonic Mitigation 41.4 Time-Varying Harmonic 51.5 Industrial Area 61.6 Factors Contributing to Harmonic Fluctuation 71.7 Evaluating Harmonic Characteristic 81.8 Objective and Scope of Research 81.9 Methodology 91.10 Contribution of This Study 101.11 Overview of Thesis 11

    CHAPTER TWO : LITERATURE SURVEY

    2.1 Background 12

    2.2 Basic on Harmonics 12

    2.3 Harmonic Characteristic of Industrial Area 16

    2.4 Harmonic Standards 192.5 Time Varying Harmonic 22

    2.6 Harmonic Mitigation and Economic Consideration 242.7 Identifying Harmonic Source 26

    CHAPTER THREE : SIMULATION AND ANALYSIS

    3.1 Effect of Consumer Load Fluctuation Size 303.2 Effect of Consumer Location 313.3 Effect of Different Network Configuration 333.4 Effect of Network Total Load 333.5 Voltage Total Harmonic Distortion Calculation 343.6 Baseline for Comparison 36

    3.7 Evaluating Probabilistic Aspect of Harmonic Voltage 383.8 Simulation on Effect of Consumer Load Fluctuation Size 40

    iv

  • 8/7/2019 example of thesis format

    4/44

    3.9 Simulation on Effect of Consumer Location in NetworkBranch

    41

    3.10 Simulation on Effect of Different Network Configuration 423.11 Simulation on Effect of Adding New Load 42

    CHAPTER FOUR : TEST NETWORK, MODELING AND

    PARAMETERS4.1 Industrial Area Distribution Network 434.2 Component Rated Values and Impedance Modeling 45

    4.2.1 Transmission System 454.2.2 Transformer 474.2.3 Cables 48

    4.2.4 Consumer Loads 504.2.5 Harmonic Source 51

    4.3 Probability of Network Loading 524.4 Simulation Software 53

    CHAPTER FIVE : SIMULATION RESULTS AND DISCUSSION

    5.1 Rated Voltage Total Harmonic Distortion 585.2 Simulation I Results And Analysis 595.3 Simulation II Results And Analysis 625.4 Analysis of Distance of Disturbance on THDv Variation 635.5 Results and Analysis for Configuration B and C 65

    5.6 Analysis for Different Branch Loading 695.7 Result of Adding New Linear Load 705.8 Discussions 71

    CHAPTER SIX : CONCLUSIONS AND RECOMMENDATION

    6.1 Conclusions 756.2 Recommendation for Future Study 77

    REFERENCES 78

    APPENDICESAppendix A - Table of Random Load LevelAppendix B - Results for Effect of Load Variability in Configuration AAppendix C - Results for Effect of Load Variability in Configuration A

    at 2/3 Current Harmonic

    Appendix D - Results for Effect of Load Variability in Configuration Aat 1/3 Current Harmonic

    Appendix E - Load Variability Results for Configurations A, B and C

    Appendix F - Difference in Network Branch Load and Difference InTHDv Between Configuration B and C

    v

  • 8/7/2019 example of thesis format

    5/44

    vi

  • 8/7/2019 example of thesis format

    6/44

    LIST OF TABLES

    PAGE

    2.1 Harmonic Phase Sequence 15

    2.2 Basis for harmonic current limits based on IEEE 519-1992

    20

    2.3 Current distortion limit for general distribution systems(120V through 69000V)

    20

    2.4 Voltage Distortion Limits 21

    3.1 Load Variability Level 39

    4.1 System Base Value 45

    4.2 Transmission System Parameter 46

    4.3 Cables Data 48

    4.4 Consumer Plant Rated Load and Power Factor 50

    4.5 Harmonic Current Spectrum 52

    4.6 Probability of Network Loading 53

    5.1 Configuration A Average THDv for Range of NetworkLoad Demand

    60

    5.2 Configuration A - Probability and Cumulative Probabilityof Ranged THDv

    60

    5.3 Variation of THDv Result for Total Tripping Of EachConsumer Load

    62

    5.4 THDv Variability Result for Total Tripping of Each

    Consumer Based on Consumer Distance to PCC

    64

    5.5 Configuration B - Average THDv for Range of NetworkLoad Demand

    66

    5.6 Configuration B - Probability and Cumulative Probabilityof Ranged THDv

    67

    5.7 Configuration C - Average THDv for Range of NetworkLoad Demand

    67

    vii

  • 8/7/2019 example of thesis format

    7/44

    5.8 Configuration C - Probability and Cumulative Probabilityof Ranged THDv

    67

    5.9 THDv at PCC as a Result of Adding New Load 70

    viii

  • 8/7/2019 example of thesis format

    8/44

    LIST OF FIGURES

    PAGE

    1.1Methodology flow chart

    10

    2.1 Harmonic Current and Voltage Distortion 13

    2.2 A 33KV Industrial Area Distribution Network 17

    2.3 Balanced harmonic characteristic at industrial areanetwork

    18

    2.4 Minimal levels of triplen and even current harmonic 18

    2.5 Typical distribution network of an industrial area 19

    2.6 Harmonic voltage fluctuation at an industrial areaincoming feeder

    22

    3.1 Factors affecting harmonic voltage fluctuation and factorswithin utilitys control

    29

    3.2 Effect of consumer distance from PCC 32

    3.3 Process flowcharts for calculating total harmonic voltage

    distortion (THDv) at PCC

    35

    3.4 A 33KV Test distribution network (Configuration A) 37

    3.5 Network Configuration B 37

    3.6 Network Configuration C 38

    4.1 A 33KV test distribution network 444.2 Equivalent pi-circuit model for cables 48

    4.3 Aggregate load model 51

    4.4 Sample of component model programming usingspreadsheet

    54

    5.1 Harmonic voltage at each harmonic order forconfiguration A

    58

    5.2 Harmonic voltage Distortion characteristic for networkconfiguration A at maximum current harmonic and varyingconsumer loads

    59

    ix

  • 8/7/2019 example of thesis format

    9/44

    5.3 Configuration A THDv pdf and cpf 61

    5.4 Scatter plot for different level of current harmonic 62

    5.5 Correlation between load fluctuation size and THDv

    variability

    63

    5.6 Correlation between consumer load distance to PCC andTHDv variability range at PCC due to total tripping of eachload

    64

    5.7 Harmonic voltage level at each harmonic for configurationB and C using the same random load level data,simulation and calculation

    65

    5.8 Scatter plot of THDv for the three different configuration at

    random load level

    66

    5.9 Configuration B THDv pdf and cpf 68

    5.10 Configuration C THDv pdf and cpf 68

    5.11 Correlation between difference in branches total load anddifference in configuration B and C THDv

    69

    x

  • 8/7/2019 example of thesis format

    10/44

    LIST OF ABBREVIATION

    ASD Adjustable speed drives

    BK Breaker

    Cpf Cumulative probability function

    CIGRE International Congress of Large Power Systems

    IEC International Electrotechnical Commission

    IEEE Institute of Electrical and Electronics Engineers

    IEEE PES IEEE Power Engineering Society

    ISC Short Circuit Current

    IL Load Current

    LPC Large Power Consumer

    MS Microsoft

    MVA Mega Volt Ampere

    NOP Normally open position

    Pdf Probability density function

    PCC Point of Common Coupling

    SCC Short Circuit Current

    SCR Short Circuit Ratio

    SHI Shunt Harmonic Impedance

    THD Total Harmonic Distortion

    THDv Voltage Total Harmonic Distortion

    xi

  • 8/7/2019 example of thesis format

    11/44

    MENGURANGKAN VOLTAN HARMONIK DI RANGKAIAN PEMBAHAGIANKAWASAN INDUSTRI MENGGUNAKAN PENGURUSAN KONFIGURASI

    RANGKAIAN

    ABSTRAK

    Syarikat pembekal elektrik diperlukan untuk mengekalkan tahap voltan

    harmonik di dalam sistem di bawah batas piawaian. Namun, voltan harmonik

    berubah mengikut masa dan disebabkan oleh naik turun tahap arus harmonik

    dan perubahan impedans rangkaian. Mengurangkan harmonik menggunakan

    kaedah sedia ada adalah mahal untuk pembekal tenaga dan memerlukan

    pertimbangan ekonomi. Pemerhatian dan analisa ke atas rangkaian

    pembahagian kawasan industri menunjukkan perubahan pada impedans

    rangkaian disebabkan oleh perubahan beban pelanggan dan perubahan

    konfigurasi rangkaian boleh menyebabkan perubahan ketara terhadap kadar

    voltan total harmonic distortion (THD) pada point of common coupling (PCC).

    Simulasi terhadap rangkaian pembahagian ujian, menganalisa faktor seperti

    saiz perubahan beban pelanggan dan lokasi beban sepanjang rangkaian, dapat

    mengurangkan perubahan maksima voltan THD sebanyak 21.7% dari satu

    pelanggan. Mengubah konfigurasi rangkaian dapat mengurangkan voltan THD

    sebanyak 10.6% sementara menambah 5MVA beban tambahan mengurangkan

    voltan THD sebanyak 3.5%. Jumlah pengurangan adalah bermakna

    memandangkan caranya yang mudah dengan kos yang minima menjadikannya

    sesuai untuk pembekal tenaga atau pelanggan gunakan sebagai cara

    tambahan menghalang voltan harmonik daripada melebihi had piawaian atau

    memperbaiki bentuk gelombang voltan.

    xii

  • 8/7/2019 example of thesis format

    12/44

    REDUCING HARMONIC VOLTAGE AT INDUSTRIAL AREA DISTRIBUTIONNETWORK USING NETWORK CONFIGURATION MANAGEMENT

    ABSTRACT

    Electric utility company is required to maintain harmonic voltage level in the

    system below the standards limit. However, harmonic voltage is time variant

    and is caused by fluctuation of current harmonic level and changes in network

    impedance. Mitigating harmonic using existing methods is costly for utility and

    requires economic consideration. Observation and analysis on an industrial

    area distribution network shows that network impedance fluctuation caused by

    consumer loads variability and changing network configuration can significantly

    change voltage total harmonic distortion (THD) level at point of common

    coupling (PCC). Simulation on a test distribution network, analyzing factors

    such as size of fluctuating consumer load and location of load along radial

    network, is able to reduce maximum voltage THD variability from a single load

    up to 21.7%. Changing network configuration can achieve voltage THD

    reduction up to 10.6% while adding 5MVA additional load into the network

    reduced voltage THD up to 3.5%. Amount of reduction is significant considering

    the methods simplicity and with minimum cost which makes it feasible for utility

    or consumer to use as an additional method to prevent harmonic voltage from

    exceeding the standards limit or to improve voltage waveform.

    xiii

  • 8/7/2019 example of thesis format

    13/44

    CHAPTER ONE

    INTRODUCTION

    Demand for quality power supply is becoming a major issue for

    consumer, especially large power consumer (LPC) such as industrial

    community. Electric utility company is expected to comply with power quality

    standards. One of power quality index is related to harmonic distortion. Unlike

    other power quality indexes such as transient, sag and swell which occur

    intermittently, harmonic distortion exist continuously in electrical network. This

    chapter describes issues regarding harmonic distortion at an industrial area

    distribution network from utilitys perspective.

    1.1Overview on Harmonic

    Harmonics in electrical power system is becoming a major concern for electric

    utility company and consumers. It is produced by power electronics and other

    equipments which are called non-linear loads. Examples of nonlinear loads are

    computers, fluorescent lamp and television in residential while variable speed

    drives, inverters and arc furnaces are mostly common in industrial areas.

    Increasing numbers of these loads in electrical system for the purpose of, such

    as improving energy efficiency, has caused an increase in harmonics pollution.

    These loads draw non-sinusoidal current from the system. The waveform is

    normally periodic according to supply frequency which is either 50Hz or 60Hz

    depending on the country.

    14

  • 8/7/2019 example of thesis format

    14/44

    Effect of high level of voltage or current harmonics can cause transformer

    heating, nuisance tripping of fuse, circuit breaker and protective devices, high

    current in neutral conductor and distorted voltage waveform. Capacitors are

    sensitive to harmonic voltage while transformers are sensitive to current

    harmonics. There are many researches which study the effect of harmonics

    which affects both utility and consumers. Greater concerns have been

    expressed by industries which have equipment or processes that are sensitive

    to distortion on the supply voltage which affect their plant operation and

    productivity.

    Resonance is another problem related to harmonics. It occurs when

    harmonic current produced by non-linear load interacts with system impedance

    to produce high harmonic voltage. Two types of resonance can occur in the

    system, either series resonance or parallel resonance, depending on the

    structure of the network. This problem is most common in industrial plant due to

    the interaction of series of power factor correction capacitors and transformers

    inductance.

    All triplen harmonics (odd multiples of three i.e. 3, 9, 15 ) is zero

    sequence and cannot flow in a balanced three-wire systems or loads.

    Therefore, the delta-wye-grounded transformer at the entrance of industrial

    plant can block the triplen harmonic from entering utility distribution system.

    However, triplen harmonic current flows in neutral conductor and are three

    times in magnitude.

    15

  • 8/7/2019 example of thesis format

    15/44

    1.2 Standards on Harmonic

    Institute of Electrical and Electronics Engineers (IEEE) has come out with

    standards and guidelines regarding harmonics. One of the standards, IEEE

    Standard 519-1992, provides comprehensive recommended guidelines on

    investigation, assessment and measurement of harmonics in power system.

    The standard includes steady state limits on current harmonic and harmonic

    voltages at all system voltage levels. The limit was set for a steady state

    operation and for worst case scenario.

    Another international standards and conformity assessment body,

    International Electrotechnical Commission (IEC), produced a standard, IEC

    61000-3-6, which also provides guidelines to address harmonics issue with sets

    of steady state limits. Both standards are in common where the limits were

    derived based on a basic principle of insuring voltage quality and shared

    responsibility between utility and customer (Halpin, 2005). Both lay the

    responsibility on consumer to limit the penetration of current harmonic into

    power system while utility company is responsible to limit harmonic voltage at

    point of common coupling (PCC). According to IEEE definition, point of common

    coupling is a point anywhere in the entire system where utility and consumer

    can have access for direct measurement and the indices is meaningful to both.

    Example of steady state harmonic voltage limit from IEEE Std. 519-1992

    at PCC for medium voltage level (< 69 kV) is 5% THD and 3% individual voltage

    distortion. In reality, harmonic is time-variant and it changes over time due to

    several factors. Both standards recognize this condition and allow the limits to

    16

  • 8/7/2019 example of thesis format

    16/44

    be exceeded for short duration. IEC has provided a set of time-varying limits

    based on percentile over a period of time i.e. 95th and 99th for very short time (3

    second) and short time (10 minute) aggregate measurements.

    1.3 Harmonic Mitigation

    Several methods of mitigating harmonics have been developed over the

    years. The most common method is using filter, either passive or active.

    Passive filter block certain harmonic bandwidth while active filter injects current

    into the system to cancel the current harmonic waveforms. Both methods have

    their advantages and disadvantages, for example, advantage of passive filter is

    easy to design and active filter can monitor many frequencies simultaneously

    while disadvantage of passive filter is bulky in size and active filter is costly

    (Izhar et. al., 2003). Harmonic filters are useful and practical to be implemented

    by consumer near the proximity of the non-linear load at the low voltage system.

    Another method which is normally used by consumers is using phase

    cancellation method using twelve pulse converters instead of six pulse

    converters.

    Similar application using filters for utility at higher voltage level such as

    distribution network requires extensive economic consideration. This is due to

    the size and cost of the equipment while most of harmonic pollutant is caused

    by consumer. There is little study on a feasible and cost effective means for

    utility to mitigate harmonic, especially harmonic voltage. A study was conducted

    on method using shunt harmonic impedance (Ryckaert et. al., 2004 ) which can

    act like a central damper to reduce harmonic at distribution network. This

    17

  • 8/7/2019 example of thesis format

    17/44

    method is considered to be less expensive compared to active filter. The

    method uses power electronic to emulate resistive behavior for harmonic.

    However, the method is still under further study. Currently, all harmonic

    mitigation techniques involve equipment required to be installed on the system.

    There is yet a study on using other factors which can affects harmonic voltage

    distortion such as network impedance. Optimizing network impedance to

    mitigate harmonic can be cost effective for utility to apply. Because of mitigating

    harmonic is expensive, many utility company have resorted in imposing penalty

    to consumer for injecting current harmonic above the standard steady state limit

    into the system. This process requires method on determining harmonic

    contribution by the consumers (Li, et. al., 2004) and the equipment need to be

    installed at all consumers feeder which is very costly.

    1.4 Time-Varying Harmonic

    Many recent studies on harmonic limit focus on development of time

    varying limit and probabilistic aspects of harmonics in power system (Baghzouz,

    2005). This includes the probabilistic modeling of power system (Carbone, et.

    al., 2000) and probabilistic aspects of harmonic impedance (Testa, et. al.,

    2002). In order to comply with time varying harmonic limits, prediction of the

    systems time varying harmonic characteristic is crucial. Simulation is still the

    best method of assessment but calculation based on steady state design value

    does not reflect the actual fluctuation of harmonic. This is due to the fact that

    current harmonic and network impedance changes over time. Therefore it is

    imperative for utility to be able to predict the time varying characteristic of

    harmonic voltage of a distribution network at PCC based on the varying factors

    18

  • 8/7/2019 example of thesis format

    18/44

    within distribution system, especially factor that within its influence where they

    can be controlled or managed. The factors which can contribute to harmonic

    voltage fluctuation will be discussed in detail in section 1.6.

    1.5 Industrial Area

    Setting up of an industrial area or industrial zone has become a common

    practice in many countries where all industrial plant is located within a certain

    geographical area. There are many reasons for the set up such as economic

    consideration, safety issues and environmental concern. The development of

    industrial area has also caused a unique electrical distribution system with

    unique electrical characteristic, power quality and system stability requirements.

    Due to the strict requirements from consumer to utility, consumers are provided

    with redundant incoming feeders and the distribution network is supplied by

    several sources from transmission system. The network is also operated by

    extensive network control system to provide stable and reliable supply to

    consumers.

    Utility monitors power supply quality of an industrial area at the

    incoming feeder after the step down transformer from transmission system. For

    harmonic monitoring, this point is the point of common coupling. The reason for

    choosing the point is to ensure harmonic pollution from the industrial area is not

    being transmitted into transmission system and vice versa, and to ensure

    harmonic pollution from one branch does not affect another branches

    connected on the feeder. Harmonic level on the feeder is the best indication of

    harmonic quality in the network.

    19

  • 8/7/2019 example of thesis format

    19/44

    1.6 Factors Contributing to Harmonic Fluctuation

    Analysis into factors contributing to harmonic voltage fluctuation at

    industrial area shows that changes in non-linear loads, network configuration

    and number of linear loads within the network are the main factors. However,

    utility has no control over the number and operational of non-linear load within

    industrial plant which caused changes in production of current harmonic. The

    only factors within utilitys control are configuration of the network and number

    of consumer plants in the network. These two factors affect the network

    impedance. Looking in detail into network components, network total

    impedance comprises of transmission system impedance, step down

    transformer impedance, cable impedance and consumers plant network

    impedance.

    Transmission system network impedance looking from the low voltage

    side of a step down transformer varies slightly over time because of the

    impedance of a step down transformer dominates and does not vary much.

    Cables impedance is also constant and can be assume steady. However,

    number of consumer plant in the network and their load demand changes over

    time depending on plant operation and unforeseen tripping. Overall network

    configuration can also change due to switching process. These two factors,

    consumer load variability and network configuration changes, are the main

    factors which utility can use to mitigate harmonic voltage.

    20

  • 8/7/2019 example of thesis format

    20/44

    1.7 Evaluating Harmonic Characteristic

    In order to determine the effect of the above factors on harmonic voltage,

    network harmonic characteristic is important as a baseline for comparison. The

    characteristic must be able to indicate the effect of time varying nature of

    harmonic. Since major contribution of harmonic voltage is the fluctuation of load

    impedance under normal operation, development of harmonic characteristic of a

    network due to load variability is crucial. There is currently no specific method

    been developed to determine or predicting harmonic characteristic of a certain

    network, other than frequency scan for resonance analysis which only

    applicable for steady state analysis. For this study, since utility is able to

    determine the statistical loading pattern of a network, the probability of loading

    can be used to develop and estimate the probabilistic aspect of harmonic.

    1.8 Objectives and Scope of Research

    The objectives of this study were to determine methods for utility to

    reduce harmonic voltage in meeting standards steady state limit of 5% voltage

    THD and time varying limit of 95th percentile voltage THD within steady state

    limit at PCC. The second objective is to determine methods of reducing

    harmonic voltage with little or no cost. The study focused on distribution network

    for industrial area which has the capability of switching into other configuration

    since the network normally has different possible sources, backup and

    redundant feeders to ensure reliability of the supply system. Action plan for this

    study were as follows:

    1. To determine whether varying consumer load increases harmonic

    voltage.

    21

  • 8/7/2019 example of thesis format

    21/44

    2. To determine amount of changes in harmonic voltage due to size

    of varying consumer load.

    3. To determine amount of change in harmonic voltage due to

    location of varying consumer load.

    4. To determine changes in harmonic voltage due to switching

    network configuration.

    5. To determine changes in harmonic voltage due to adding

    consumer load into existing network.

    1.9 Methodology

    In order to achieve the objectives, the following protocol had been set up.

    Select and gather data on industrial area distribution

    network configuration and components

    Decide method on modeling of equipment for harmonic

    analysis and method of simulation

    Model the selected industrial area distribution network

    Simulate identified factors affecting harmonic voltage

    Analyze data using statistical technique and compare with

    calculation based on design values

    Conclude the research, suggest and recommend mitigating

    action

    Base on protocol and action plan a flow diagram of research

    methodology was drawn and shown in Figure 1.1.

    22

  • 8/7/2019 example of thesis format

    22/44

    Figure 1.1 Methodology flow chart

    1.10 Contribution of This Study

    The outcome of this study is important to utility in controlling harmonic

    voltage and improving power quality without huge investment in mitigating

    equipment. Components which are affected by harmonic voltage will have

    longer life and cost of maintenance is reduced. Consumers will also benefit from

    the method since utility is able to provide better power quality. System design

    engineers can use the method in planning of electrical system and control

    engineers will be able to use the method in controlling harmonic voltage.

    23

  • 8/7/2019 example of thesis format

    23/44

    1.11 Overview of Thesis

    This thesis discusses and analyzes harmonic voltage distortion at a utility

    distribution network supplying to industries due to changes in consumer load

    and network configuration. The analysis determines the condition which can

    reduce total harmonic voltage distortion THDv at point of common coupling.

    Recommendation to reduce harmonic voltage distortion was proposed which

    can be integrated into the network control system.

    The content in Chapter 2 provides reader with the applicable standards

    for harmonic, harmonic mitigation, probabilistic aspects of harmonic, economic

    consideration and effect of network impedance on harmonic. Reviews from past

    studies by researchers related to those issues were presented.

    Chapter 3 discusses the method of simulation and the process flow of the

    simulation. Each factors contributing to the changes to harmonic voltage at PCC

    were taken into consideration for simulation. Method of calculations and

    analysis were also presented in this chapter.

    Chapter 4 contains information on test distribution network system

    together with component data and test values that were used for analysis.

    Methods for modeling and calculation of each component in the network were

    described in details.

    Chapter 5 exhibits the simulation results and analysis together with

    discussion of the overall situation. A conclusion of the thesis was presented in

    Chapter 6 which includes recommendation for future studies.

    24

  • 8/7/2019 example of thesis format

    24/44

    CHAPTER TWO

    LITERATURE SURVEY

    2.1Background

    The studies required broad knowledge of the issues regarding harmonic

    in power system, the standard limit and requirements, modeling and simulation,

    issues related to utility and consumers especially at an industrial area, and

    result from studies by other researchers. All this information is necessary to

    address the changes and dynamic of harmonic voltage at an industrial area.

    The following sections include brief knowledge of harmonics and reviews

    on papers related to relevant harmonic standards and requirements, mitigation,

    probabilistic aspects, cost of mitigation and effect of harmonic impedance

    variability. The review focus on studies related to harmonic in power system

    with regards to relation between utility and consumers. The reviews also

    pointed out the differences and similarities between previous studies and this

    research.

    2.2 Basic on Harmonics

    IEEE PES Winter Meeting 1998 provides basic harmonic theory which

    according to Fourier theorem, periodic non-sinusoidal or complex voltage

    (Figure 2.1) or current waveforms can be represented by the sum of a series of

    25

  • 8/7/2019 example of thesis format

    25/44

    multiple frequency terms of varying magnitudes and phases as shown in

    equation (2.1).

    ++= )]cos([)( 0 nn qtnaatf (2.1)

    where: na is the magnitude of the nth harmonic frequency

    oa is the d.c. component

    nq is the phase angle of the nth harmonic frequency

    is the fundamental frequency

    n =1,2,3,

    Harmonic is measured using total harmonic distortion (THD) which is

    also known as distortion factor and can be applied to current and voltage. It is a

    26

    Figure 2.1 Harmonic Current and Voltage Distortiona) Non-linear load draws non-sinusoidal current from the system.b) Resulting voltage distortion due to non-sinusoidal current

    Non-linear current

    Supply

    voltage

    (a)(b)

    V

    time

    Distorted

    Voltage

    waveform

    time

  • 8/7/2019 example of thesis format

    26/44

    square-root of sum of all harmonic magnitudes over the fundamental. Equation

    (2.2) shows the calculation for voltage total harmonic distortion (THDv).

    1

    2

    2

    V

    V

    THDn

    n

    V

    ==

    (2.2)

    where: 1V is the magnitude of fundamental frequency voltage

    nV is the magnitude of nth harmonic frequency voltage

    For a balanced three-phase network with three-phase non-linear loads,

    harmonic current or voltage has phase sequences. Equations (2.3) until (2.7)

    describe the equation for each phase for the first three harmonics.

    )3sin()2sin()sin()( 332211 +++++= tItItIti oooa (2.3)

    )3

    63sin()

    3

    42sin()

    3

    2sin()( 332211

    +++++= tItItIti

    ooob (2.4)

    )3

    63sin()

    3

    42sin()

    3

    2sin()( 332211

    ++++++++= tItItIti

    oooc (2.5)

    where: nI is the nth current harmonic magnitude

    o is the fundamental frequency

    n is the nth harmonic phase angle

    n = 1,2,3

    Equation (2.4) and (2.5) can also be described as follows:

    )03sin()322sin()

    32sin()( 332211 ++++++= tItItIti ooob (2.6)

    27

  • 8/7/2019 example of thesis format

    27/44

    )03sin()3

    22sin()

    3

    2sin()( 332211 +++++++=

    tItItIti

    oooc (2.7)

    Current magnitude of all phases for all harmonic frequencies is equal for

    a balanced system. Looking at equations (2.3), (2.6) and (2.7), the first

    harmonic or the fundamental is positive sequence since ib(t) lags ia(t) by 120o

    and ic(t) leads ia(t) by 120o. The second harmonic is negative sequence since

    and ib(t) leads ia(t) by 120o and ic(t) lags ia(t) by 120

    o. The third harmonic is zero

    sequence since ib(t) and ic(t) are in phase with ia(t). The sequence pattern for

    each harmonic order is shown in Table 2.1.

    Table 2.1Harmonic Phase Sequence

    Harmonic Phase Sequence

    1 +

    2 -

    3 0

    4 +

    5 -

    6 0

    7 +

    8 -

    9 0

    10 +

    11 -

    12 0

    13 +

    14 -15 0

    CHAPTER SIX

    CONCLUSIONS AND RECOMMENDATIONS

    28

  • 8/7/2019 example of thesis format

    28/44

    6.1 Conclusions

    This study has succeeded in developing methods to reduce harmonic

    voltage at industrial area. The simulations have showed a reduction of 10.6%

    voltage THD by switching configuration at design condition and 3.5% voltage

    THD by switching in additional 5MVA load into the network. The simulation also

    produced reduction of time varying 95th percentile level from between 3.5% and

    4.0% to between 3.0% and 3.5% which was about 10% reduction.

    The main purpose of this research was to obtain methods for utility to

    mitigate harmonic voltage at the point of common coupling using minimum cost

    by looking at load and network management. The study did not only address

    steady state limit but also include time varying characteristic of harmonic. Focus

    was made on optimizing harmonic impedance of an industrial area distribution

    network in order to reduce the effect of impedance variability on voltage THD.

    Consumer load variability has been determined as the main contribution to time

    varying harmonic voltage in the system. Based on the study, several factors

    have been identified which could be manipulated to reduce the effect such as

    consumer load fluctuation size, consumer load location within the network

    relative to PCC, difference network configuration and introduction of additional

    load into the system. The test distribution network was described in detail

    including components data and modeling required for harmonic analysis.

    Methods of simulation to observe the effect of the various factors had also been

    explained.

    29

  • 8/7/2019 example of thesis format

    29/44

    Based on the results, it is concluded that the following mitigating actions

    can be an alternative means available for utility company to use in managing

    and complying with standards requirement on harmonic voltage distortion

    especially at industrial area distribution network. These methods are able to

    reduce the effect of load variability on harmonic voltage and also reduce the

    level of harmonic voltage level at PCC. Depending on the availability of

    switching facilities of the network, one or combination of the following criteria

    can be performed to change network configuration:

    1. Switching the network by locating large consumer plant or large

    fluctuating load to the end of network branch and locating smaller load or

    less fluctuating load closer to PCC to reduce the effect of consumer load

    variability on THDv.

    2. Increase load demand of the sub network by switching other linear load

    into the network.

    3. Combining two short branches into a longer branch by switching the

    branch with lower total load demand to the end of the other branch which

    has higher load demand.

    These actions could be incorporated into the automated network

    distributed control system together with other power quality control scheme and

    during planning or designing of a new system. The amount of reduction was

    significant, whether comparing with steady state limit or time-varying limit, since

    the implementation cost is trivial where it uses existing switching facilities of the

    network system.

    30

  • 8/7/2019 example of thesis format

    30/44

    6.2 Recommendation for Future Study

    The research was performed with assumption that there is only one

    current harmonic source from a single consumer in the system while others are

    linear loads. It is important to note that changing network configuration with

    several harmonic sources in the system can change the location of other

    harmonic source. Further study is required to determine the effect of changing

    current harmonic source location in the system on harmonic voltage which

    includes impedance variability of the network. Software on handling simulation

    of several harmonic sources with randomly varying load can be developed to

    assist utility and consumer in analyzing and estimating the probability of the

    system in complying with harmonic standards.

    31

  • 8/7/2019 example of thesis format

    31/44

    REFERENCES

    Baghzouz,Y.; An overview on Probabilistic Aspects of Harmonics in PowerSystems, IEEE Power Engineering Society General Meeting, 2005 Vol. 3, pp.2394 2396, 2005

    Carbone, R.; Castaldo, D.; Langella, R.; Testa, A.; Probabilistic modeling ofindustrial systems for voltage distortion analyses, Ninth International

    Conference on Harmonics and Quality of Power, 2000,Volume 2, 1-4 Oct. 2000 Page(s):608 - 613 vol.2

    Halpin, S.M.; Comparison of IEEE and IEC Harmonic Standards, IEEE PowerEngineering Society General Meeting, 2005, Vol. 3, Page(s) 2214-2216

    IEEE std. 519-1992 IEEE Recommended Practices and Requirements forHarmonic Control in Electrical Power Systems

    IEEE PES Winter meeting 1998, Tutorial on Harmonic Modeling and Simulation,Available: http://www.ee.ualberta.ca/pwrsysIEEE/download.html24/12/2005

    Izhar, M.; Hadzer, S.M.;Masri, S.; Idris, S.; A Study of The FundamentalPrinciples to Power System Harmonic, Proceedings on National Power andEnergy Conference, 2003, Page(s) 223 - 231

    Li, C.; Xu, W.; Tayjasanant, T.; A critical impedance-based method for

    identifying harmonic sources, IEEE Transactions on Power Delivery, Volume19, Issue 2, April 2004 Page(s):671 678

    Ryckaert, W.R.A.; Ghijselen, J.A.L.; Melkebeek, J.A.A.; Desmet, J.J.M.;Driesen, J.; The influence on harmonic propagation of the resistive shuntharmonic impedance location along a distribution feeder and the influence ofdistributed capacitors, 11th International Conference on Harmonics and Qualityof Power, 2004. 12-15 Sept. 2004 Page(s):129 135

    32

    http://www.ee.ualberta.ca/pwrsysIEEE/download.htmlhttp://www.ee.ualberta.ca/pwrsysIEEE/download.html
  • 8/7/2019 example of thesis format

    32/44

    Testa, A.; Castaldo, D.; Langella, R.; Probabilistic aspects of harmonicimpedances, Power Engineering Society Winter Meeting, 2002. IEEE Volume2, 27-31 Jan. 2002 Page(s):1076 - 1081 vol.2

    Wakileh, George J.; Power Systems Harmonics, Fundamentals, Analysis andFilter Design, Springer, 2001 Page(s) 275 286

    Xu, W.; Liu, X.; Liu, Y.; An investigation on the validity of power-directionmethod for harmonic source determination, IEEE Transactions on PowerDelivery, Volume 18, Issue 1, Jan 2003 Page(s):214 219

    Xu, W.; Component Modeling Issues for Power Quality AssessmentIEEE Power Engineering Review, November 2001 Page(s): 12 15

    33

  • 8/7/2019 example of thesis format

    33/44

    APPENDIX A

    Table of Random Load Level

    Load1

    Load2

    Load3

    Load4

    Load5

    Load6

    Load7

    Load8

    Load9

    Load10

    15% 55% 33% 0% 0% 0% 0% 15% 66% 105%33% 0% 33% 0% 33% 105% 66% 15% 66% 0%0% 15% 105% 85% 33% 85% 0% 85% 105% 0%85% 15% 15% 105% 105% 105% 0% 55% 85% 105%15% 66% 15% 15% 15% 33% 0% 0% 33% 15%55% 33% 85% 0% 15% 15% 85% 33% 66% 105%0% 85% 105% 55% 55% 33% 85% 55% 85% 15%0% 0% 66% 105% 0% 15% 15% 85% 85% 33%85% 55% 85% 0% 0% 33% 105% 55% 33% 15%

    105% 105% 33% 0% 33% 0% 33% 55% 33% 66%0% 105% 66% 55% 105% 0% 0% 85% 105% 15%15% 33% 66% 105% 66% 15% 33% 15% 55% 85%33% 55% 85% 105% 85% 85% 0% 105% 15% 85%15% 0% 15% 55% 55% 0% 15% 85% 66% 33%85% 66% 66% 85% 15% 85% 55% 33% 105% 85%66% 105% 66% 0% 105% 33% 105% 33% 55% 66%15% 85% 0% 66% 15% 0% 33% 55% 66% 55%15% 105% 15% 55% 55% 15% 0% 85% 85% 105%66% 15% 55% 15% 85% 55% 66% 15% 33% 33%

    105% 85% 15% 33% 0% 105% 33% 66% 55% 0%0% 15% 0% 0% 66% 85% 0% 33% 66% 15%55% 66% 105% 105% 0% 33% 85% 15% 0% 66%85% 55% 66% 85% 0% 0% 66% 55% 105% 33%15% 55% 66% 66% 105% 55% 66% 0% 105% 33%105% 66% 105% 0% 55% 66% 55% 55% 0% 66%85% 105% 15% 85% 0% 33% 0% 66% 15% 33%15% 55% 85% 55% 15% 105% 55% 55% 33% 85%85% 55% 33% 66% 85% 85% 85% 55% 15% 55%15% 55% 0% 15% 33% 105% 85% 66% 66% 85%33% 55% 105% 55% 15% 33% 55% 66% 0% 0%

    0% 105% 85% 55% 15% 66% 85% 15% 105% 33%105% 105% 66% 15% 15% 66% 15% 85% 66% 66%0% 33% 66% 0% 66% 85% 33% 15% 0% 33%15% 0% 0% 85% 105% 105% 85% 33% 0% 0%0% 66% 66% 0% 66% 66% 105% 85% 85% 33%66% 33% 33% 66% 0% 66% 33% 55% 33% 0%85% 85% 66% 85% 0% 0% 33% 33% 105% 55%85% 15% 55% 55% 55% 15% 15% 33% 33% 85%

  • 8/7/2019 example of thesis format

    34/44

    Table of Random Load Level continued

    Load1

    Load2

    Load3

    Load4

    Load5

    Load6

    Load7

    Load8

    Load9

    Load10

    0% 66% 105% 33% 15% 105% 33% 0% 85% 0%0% 0% 33% 85% 33% 15% 55% 33% 0% 0%

    66% 66% 33% 66% 15% 33% 33% 0% 66% 55%105% 85% 0% 15% 15% 66% 33% 15% 33% 85%55% 66% 55% 66% 15% 15% 0% 0% 55% 85%105% 105% 85% 85% 55% 55% 0% 105% 0% 0%15% 0% 15% 33% 33% 55% 85% 85% 105% 15%85% 33% 66% 85% 0% 0% 105% 15% 66% 66%66% 55% 15% 55% 55% 85% 0% 66% 33% 15%85% 85% 85% 85% 0% 105% 66% 66% 15% 85%66% 15% 0% 85% 66% 33% 15% 33% 33% 33%15% 66% 105% 33% 105% 105% 33% 15% 15% 33%66% 105% 33% 66% 105% 33% 33% 55% 33% 0%

    105% 15% 66% 105% 15% 105% 66% 85% 0% 33%15% 0% 55% 15% 105% 15% 66% 0% 15% 66%66% 33% 85% 33% 15% 66% 55% 85% 55% 66%105% 33% 66% 33% 0% 105% 55% 15% 0% 85%15% 15% 0% 66% 0% 85% 55% 85% 33% 85%15% 0% 0% 66% 55% 15% 66% 85% 105% 55%105% 85% 55% 0% 15% 85% 0% 33% 0% 85%55% 33% 33% 15% 55% 0% 55% 33% 33% 33%66% 0% 33% 0% 33% 33% 66% 0% 66% 66%105% 105% 0% 105% 66% 15% 15% 85% 33% 66%

    15% 66% 55% 85% 85% 15% 105% 66% 0% 15%66% 66% 33% 66% 105% 33% 85% 0% 33% 55%85% 33% 66% 85% 55% 55% 15% 66% 0% 105%85% 33% 33% 85% 15% 105% 0% 33% 15% 33%85% 55% 105% 15% 85% 66% 66% 85% 33% 85%0% 33% 105% 33% 66% 66% 15% 55% 33% 66%85% 15% 15% 15% 105% 33% 66% 33% 105% 55%105% 33% 15% 105% 33% 66% 66% 55% 33% 15%15% 105% 0% 15% 105% 105% 66% 66% 85% 66%0% 66% 15% 33% 105% 0% 85% 85% 0% 15%15% 85% 105% 66% 15% 33% 0% 33% 0% 33%

    66% 55% 0% 85% 55% 33% 85% 33% 33% 0%105% 0% 105% 33% 85% 105% 33% 85% 15% 85%105% 33% 55% 105% 105% 66% 85% 105% 85% 0%0% 15% 15% 55% 105% 55% 15% 85% 66% 55%33% 0% 105% 55% 33% 33% 85% 66% 0% 66%105% 105% 85% 105% 33% 55% 0% 0% 33% 85%55% 55% 55% 105% 55% 15% 33% 0% 66% 66%

  • 8/7/2019 example of thesis format

    35/44

    Table of Random Load Level continued

    Load1

    Load2

    Load3

    Load4

    Load5

    Load6

    Load7

    Load8

    Load9

    Load10

    0% 85% 33% 55% 0% 55% 0% 105% 15% 15%0% 85% 15% 33% 0% 85% 105% 105% 105% 105%

    33% 33% 55% 66% 15% 0% 55% 105% 55% 85%85% 0% 15% 55% 85% 85% 0% 105% 105% 15%85% 66% 0% 55% 0% 66% 0% 15% 105% 33%66% 85% 0% 55% 85% 55% 0% 85% 0% 66%33% 85% 85% 15% 55% 15% 85% 0% 33% 55%15% 15% 15% 15% 66% 85% 66% 55% 66% 0%0% 66% 66% 15% 85% 105% 85% 105% 66% 33%85% 85% 0% 55% 66% 105% 66% 0% 105% 15%105% 55% 105% 33% 85% 33% 33% 33% 0% 0%105% 66% 85% 66% 55% 85% 55% 85% 33% 55%33% 66% 66% 66% 33% 105% 55% 15% 55% 0%

    105% 33% 15% 85% 33% 33% 15% 0% 66% 15%105% 55% 15% 66% 33% 33% 66% 105% 85% 85%66% 55% 85% 55% 15% 33% 15% 105% 105% 85%85% 55% 66% 55% 85% 66% 105% 66% 85% 33%105% 55% 33% 66% 105% 15% 33% 33% 85% 105%66% 55% 66% 55% 0% 85% 85% 85% 33% 85%66% 55% 85% 55% 55% 33% 33% 15% 33% 55%105% 0% 85% 85% 55% 15% 85% 66% 105% 15%

  • 8/7/2019 example of thesis format

    36/44

    APPENDIX B

    Results for Effect of Load Variability in Configuration A

    No.TotalMVA

    THDvNo.

    TotalMVA

    THDvNo.

    TotalMVA

    THDv

    1 22.25 5.23% 41 34.72 4.42% 81 51.66 3.71%2 30.51 4.61% 42 37.50 4.27% 82 40.86 4.13%3 42.90 4.04% 43 32.40 4.57% 83 48.70 3.79%4 57.08 3.49% 44 51.03 3.71% 84 34.95 4.42%5 16.79 5.61% 45 37.51 4.27% 85 42.64 4.03%6 39.92 4.16% 46 41.51 4.08% 86 37.50 4.28%7 46.97 3.87% 47 38.56 4.21% 87 34.84 4.39%8 32.37 4.56% 48 55.35 3.54% 88 53.60 3.62%9 39.29 4.17% 49 32.20 4.53% 89 49.08 3.77%

    10 38.92 4.22% 50 44.61 3.95% 90 42.06 4.05%11 45.03 3.98% 51 45.38 3.93% 91 58.46 3.44%

    12 38.90 4.22% 52 50.35 3.70% 92 40.96 4.10%13 54.69 3.58% 53 29.83 4.66% 93 33.40 4.48%14 28.84 4.75% 54 46.79 3.86% 94 54.20 3.59%15 55.29 3.56% 55 41.27 4.07% 95 51.04 3.72%16 53.45 3.62% 56 35.89 4.34% 96 59.55 3.41%17 30.92 4.65% 57 38.50 4.23% 97 53.14 3.64%18 43.43 4.04% 58 38.99 4.19% 98 50.64 3.71%19 37.95 4.22% 59 29.38 4.70% 99 40.07 4.15%20 42.62 4.03% 60 30.36 4.63% 100 52.10 3.66%21 24.84 4.98% 61 49.69 3.76%

    22 41.74 4.07% 62 42.30 4.04%23 44.65 3.97% 63 45.24 3.92%24 46.89 3.87% 64 47.05 3.84%25 49.01 3.76% 65 36.74 4.28%26 35.85 4.36% 66 58.04 3.46%27 45.37 3.92% 67 39.41 4.18%28 52.69 3.62% 68 45.59 3.91%29 43.65 3.99% 69 44.44 3.93%30 34.65 4.41% 70 53.27 3.63%31 44.90 3.96% 71 34.89 4.39%32 50.80 3.72% 72 30.74 4.65%

    33 28.38 4.74% 73 37.39 4.25%34 37.26 4.23% 74 56.50 3.49%35 48.36 3.81% 75 64.22 3.27%36 32.45 4.51% 76 40.03 4.15%37 43.71 4.02% 77 39.35 4.16%38 37.23 4.28% 78 48.84 3.80%39 36.05 4.35% 79 40.49 4.15%40 20.78 5.24% 80 30.04 4.68%

  • 8/7/2019 example of thesis format

    37/44

    APPENDIX C

    Results for Effect of Load Variability in Configuration A at 2/3 Current Harmonic

    No.TotalMVA

    THDvNo.

    TotalMVA

    THDvNo.

    TotalMVA

    THDv

    1 22.25 3.51% 41 34.72 2.94% 81 51.66 2.45%2 30.51 3.09% 42 37.50 2.92% 82 40.86 2.74%3 42.90 2.66% 43 32.40 3.04% 83 48.70 2.57%4 57.08 2.33% 44 51.03 2.51% 84 34.95 2.98%5 16.79 3.74% 45 37.51 2.83% 85 42.64 2.72%6 39.92 2.80% 46 41.51 2.69% 86 37.50 2.84%7 46.97 2.54% 47 38.56 2.84% 87 34.84 2.92%8 32.37 2.97% 48 55.35 2.36% 88 53.60 2.41%9 39.29 2.83% 49 32.20 3.01% 89 49.08 2.52%

    10 38.92 2.91% 50 44.61 2.62% 90 42.06 2.76%11 45.03 2.64% 51 45.38 2.63% 91 58.46 2.32%

    12 38.90 2.74% 52 50.35 2.47% 92 40.96 2.70%13 54.69 2.37% 53 29.83 3.08% 93 33.40 3.00%14 28.84 3.15% 54 46.79 2.61% 94 54.20 2.43%15 55.29 2.37% 55 41.27 2.76% 95 51.04 2.51%16 53.45 2.43% 56 35.89 2.86% 96 59.55 2.28%17 30.92 3.06% 57 38.50 2.79% 97 53.14 2.45%18 43.43 2.69% 58 38.99 2.90% 98 50.64 2.48%19 37.95 2.84% 59 29.38 3.16% 99 40.07 2.77%20 42.62 2.75% 60 30.36 3.13% 100 52.10 2.45%21 24.84 3.34% 61 49.69 2.53%

    22 41.74 2.66% 62 42.30 2.63%23 44.65 2.64% 63 45.24 2.59%24 46.89 2.53% 64 47.05 2.58%25 49.01 2.58% 65 36.74 2.87%26 35.85 2.93% 66 58.04 2.35%27 45.37 2.59% 67 39.41 2.78%28 52.69 2.42% 68 45.59 2.64%29 43.65 2.66% 69 44.44 2.62%30 34.65 2.92% 70 53.27 2.42%31 44.90 2.59% 71 34.89 2.90%32 50.80 2.56% 72 30.74 3.07%

    33 28.38 3.15% 73 37.39 2.81%34 37.26 2.76% 74 56.50 2.38%35 48.36 2.54% 75 64.22 2.19%36 32.45 3.02% 76 40.03 2.75%37 43.71 2.68% 77 39.35 2.75%38 37.23 2.89% 78 48.84 2.54%39 36.05 2.87% 79 40.49 2.72%40 20.78 3.38% 80 30.04 3.11%

  • 8/7/2019 example of thesis format

    38/44

    APPENDIX D

    Results for Effect of Load Variability in Configuration A at 1/3 Current Harmonic

    No.TotalMVA

    THDvNo.

    TotalMVA

    THDvNo.

    TotalMVA

    THDv

    1 22.25 1.76% 41 34.72 1.47% 81 51.66 1.23%2 30.51 1.55% 42 37.50 1.46% 82 40.86 1.37%3 42.90 1.33% 43 32.40 1.52% 83 48.70 1.29%4 57.08 1.17% 44 51.03 1.26% 84 34.95 1.49%5 16.79 1.87% 45 37.51 1.42% 85 42.64 1.36%6 39.92 1.40% 46 41.51 1.35% 86 37.50 1.42%7 46.97 1.27% 47 38.56 1.42% 87 34.84 1.46%8 32.37 1.48% 48 55.35 1.18% 88 53.60 1.20%9 39.29 1.42% 49 32.20 1.51% 89 49.08 1.26%

    10 38.92 1.45% 50 44.61 1.31% 90 42.06 1.38%11 45.03 1.32% 51 45.38 1.31% 91 58.46 1.16%

    12 38.90 1.37% 52 50.35 1.24% 92 40.96 1.35%13 54.69 1.19% 53 29.83 1.54% 93 33.40 1.50%14 28.84 1.58% 54 46.79 1.30% 94 54.20 1.21%15 55.29 1.19% 55 41.27 1.38% 95 51.04 1.26%16 53.45 1.22% 56 35.89 1.43% 96 59.55 1.14%17 30.92 1.53% 57 38.50 1.39% 97 53.14 1.22%18 43.43 1.34% 58 38.99 1.45% 98 50.64 1.24%19 37.95 1.42% 59 29.38 1.58% 99 40.07 1.39%20 42.62 1.38% 60 30.36 1.56% 100 52.10 1.22%21 24.84 1.67% 61 49.69 1.26%

    22 41.74 1.33% 62 42.30 1.32%23 44.65 1.32% 63 45.24 1.29%24 46.89 1.27% 64 47.05 1.29%25 49.01 1.29% 65 36.74 1.44%26 35.85 1.47% 66 58.04 1.17%27 45.37 1.29% 67 39.41 1.39%28 52.69 1.21% 68 45.59 1.32%29 43.65 1.33% 69 44.44 1.31%30 34.65 1.46% 70 53.27 1.21%31 44.90 1.29% 71 34.89 1.45%32 50.80 1.28% 72 30.74 1.53%

    33 28.38 1.58% 73 37.39 1.40%34 37.26 1.38% 74 56.50 1.19%35 48.36 1.27% 75 64.22 1.09%36 32.45 1.51% 76 40.03 1.37%37 43.71 1.34% 77 39.35 1.38%38 37.23 1.44% 78 48.84 1.27%39 36.05 1.43% 79 40.49 1.36%40 20.78 1.69% 80 30.04 1.55%

  • 8/7/2019 example of thesis format

    39/44

    APPENDIX E

    Load Variability Results for Configurations A, B and C

    TotalMVA

    ConfigurationA

    THDv

    ConfigurationB

    THDv

    ConfigurationC

    THDv22.25 5.23% 4.99% 4.96%30.51 4.61% 4.24% 4.24%42.90 4.04% 3.63% 3.70%57.08 3.49% 3.16% 3.17%16.79 5.61% 5.35% 5.37%39.92 4.16% 3.83% 3.82%46.97 3.87% 3.53% 3.55%32.37 4.56% 4.24% 4.22%39.29 4.17% 3.80% 3.85%38.92 4.22% 3.87% 3.92%

    45.03 3.98% 3.65% 3.67%38.90 4.22% 3.88% 3.89%54.69 3.58% 3.23% 3.26%28.84 4.75% 4.43% 4.41%55.29 3.56% 3.22% 3.25%53.45 3.62% 3.27% 3.31%30.92 4.65% 4.34% 4.33%43.43 4.04% 3.73% 3.71%37.95 4.22% 3.85% 3.89%42.62 4.03% 3.65% 3.71%

    24.84 4.98% 4.65% 4.64%41.74 4.07% 3.70% 3.76%44.65 3.97% 3.62% 3.66%46.89 3.87% 3.52% 3.54%49.01 3.76% 3.39% 3.47%35.85 4.36% 4.00% 4.07%45.37 3.92% 3.57% 3.57%52.69 3.62% 3.25% 3.31%43.65 3.99% 3.65% 3.61%34.65 4.41% 4.03% 4.09%44.90 3.96% 3.62% 3.63%

    50.80 3.72% 3.37% 3.42%28.38 4.74% 4.38% 4.40%37.26 4.23% 3.84% 3.87%48.36 3.81% 3.47% 3.46%32.45 4.51% 4.14% 4.19%43.71 4.02% 3.68% 3.73%37.23 4.28% 3.93% 3.97%36.05 4.35% 4.00% 4.03%

  • 8/7/2019 example of thesis format

    40/44

    THDv Simulation Results for Three Different Configurations continued

    TotalMVA

    ConfigurationA

    THDv

    ConfigurationB

    THDv

    ConfigurationC

    THDv

    20.78 5.24% 4.90% 4.92%

    34.72 4.42% 4.08% 4.11%37.50 4.27% 3.90% 3.95%32.40 4.57% 4.24% 4.27%51.03 3.71% 3.32% 3.44%37.51 4.27% 3.93% 3.89%41.51 4.08% 3.73% 3.76%38.56 4.21% 3.84% 3.89%55.35 3.54% 3.18% 3.24%32.20 4.53% 4.17% 4.21%44.61 3.95% 3.57% 3.63%45.38 3.93% 3.55% 3.64%

    50.35 3.70% 3.32% 3.38%29.83 4.66% 4.31% 4.31%46.79 3.86% 3.51% 3.52%41.27 4.07% 3.68% 3.74%35.89 4.34% 4.00% 3.95%38.50 4.23% 3.91% 3.86%38.99 4.19% 3.82% 3.89%29.38 4.70% 4.35% 4.38%30.36 4.63% 4.29% 4.29%49.69 3.76% 3.40% 3.47%

    42.30 4.04% 3.67% 3.71%45.24 3.92% 3.54% 3.60%47.05 3.84% 3.48% 3.53%36.74 4.28% 3.90% 3.97%58.04 3.46% 3.11% 3.15%39.41 4.18% 3.84% 3.84%45.59 3.91% 3.56% 3.57%44.44 3.93% 3.55% 3.62%53.27 3.63% 3.30% 3.29%34.89 4.39% 4.03% 4.05%30.74 4.65% 4.30% 4.36%

    37.39 4.25% 3.88% 3.93%56.50 3.49% 3.14% 3.19%64.22 3.27% 2.93% 2.99%40.03 4.15% 3.82% 3.80%39.35 4.16% 3.80% 3.81%48.84 3.80% 3.43% 3.53%40.49 4.15% 3.79% 3.84%30.04 4.68% 4.34% 4.35%

  • 8/7/2019 example of thesis format

    41/44

    THDv Simulation Results for Three Different Configurations continued

    TotalMVA

    ConfigurationA

    THDv

    ConfigurationB

    THDv

    ConfigurationC

    THDv

    51.66 3.71% 3.40% 3.32%

    40.86 4.13% 3.80% 3.78%48.70 3.79% 3.43% 3.45%34.95 4.42% 4.07% 4.11%42.64 4.03% 3.67% 3.71%37.50 4.28% 3.92% 3.96%34.84 4.39% 4.02% 4.02%53.60 3.62% 3.28% 3.27%49.08 3.77% 3.40% 3.46%42.06 4.05% 3.66% 3.78%58.46 3.44% 3.08% 3.15%40.96 4.10% 3.73% 3.78%

    33.40 4.48% 4.11% 4.18%54.20 3.59% 3.26% 3.27%51.04 3.72% 3.40% 3.40%59.55 3.41% 3.07% 3.11%53.14 3.64% 3.29% 3.33%50.64 3.71% 3.36% 3.37%40.07 4.15% 3.79% 3.85%52.10 3.66% 3.31% 3.35%

  • 8/7/2019 example of thesis format

    42/44

    APPENDIX F

    Difference in Network Branch Load and Difference In THDv BetweenConfiguration B and C

    Branch 1

    Branch 2(MVA)

    Configuration

    BTHDv

    Configuration

    CTHDv

    Difference in

    THDv

    -5.87 4.99% 4.96% 0.02%-12.36 4.24% 4.24% 0.00%-5.35 3.63% 3.70% -0.07%-0.58 3.16% 3.17% -0.02%3.47 5.35% 5.37% -0.02%-7.92 3.83% 3.82% 0.01%1.28 3.53% 3.55% -0.02%-7.11 4.24% 4.22% 0.02%-1.29 3.80% 3.85% -0.05%

    8.67 3.87% 3.92% -0.06%9.98 3.65% 3.67% -0.02%7.37 3.88% 3.89% -0.01%5.14 3.23% 3.26% -0.03%-4.89 4.43% 4.41% 0.02%-3.78 3.22% 3.25% -0.03%6.40 3.27% 3.31% -0.05%-3.08 4.34% 4.33% 0.01%-3.73 3.73% 3.71% 0.02%4.74 3.85% 3.89% -0.04%

    -2.90 3.65% 3.71% -0.07%-9.39 4.65% 4.64% 0.01%10.11 3.70% 3.76% -0.06%2.22 3.62% 3.66% -0.04%5.01 3.52% 3.54% -0.02%8.64 3.39% 3.47% -0.08%

    10.35 4.00% 4.07% -0.07%-9.97 3.57% 3.57% 0.00%3.24 3.25% 3.31% -0.05%

    -23.85 3.65% 3.61% 0.04%7.37 4.03% 4.09% -0.06%

    -4.85 3.62% 3.63% -0.01%0.57 3.37% 3.42% -0.05%0.33 4.38% 4.40% -0.02%-1.51 3.84% 3.87% -0.03%-14.70 3.47% 3.46% 0.02%-0.44 4.14% 4.19% -0.04%7.66 3.68% 3.73% -0.05%8.68 3.93% 3.97% -0.04%-1.73 4.00% 4.03% -0.03%

  • 8/7/2019 example of thesis format

    43/44

    Difference in Network Branch Load and Difference In THDv BetweenConfiguration B and C... continued

    TotalMVA

    ConfigurationB

    THDv

    ConfigurationC

    THDv

    Difference inTHDv

    3.01 4.90% 4.92% -0.01%5.24 4.08% 4.11% -0.04%0.31 3.90% 3.95% -0.04%9.00 4.24% 4.27% -0.03%

    21.18 3.32% 3.44% -0.12%-21.04 3.93% 3.89% 0.04%2.06 3.73% 3.76% -0.03%3.34 3.84% 3.89% -0.05%-0.95 3.18% 3.24% -0.05%7.69 4.17% 4.21% -0.04%

    10.56 3.57% 3.63% -0.06%

    18.43 3.55% 3.64% -0.09%0.12 3.32% 3.38% -0.07%4.93 4.31% 4.31% -0.01%-8.08 3.51% 3.52% -0.01%-1.19 3.68% 3.74% -0.05%-21.55 4.00% 3.95% 0.04%-15.41 3.91% 3.86% 0.05%5.52 3.82% 3.89% -0.07%4.41 4.35% 4.38% -0.03%-5.94 4.29% 4.29% 0.00%

    13.92 3.40% 3.47% -0.07%8.16 3.67% 3.71% -0.04%12.72 3.54% 3.60% -0.06%7.51 3.48% 3.53% -0.05%4.55 3.90% 3.97% -0.06%2.27 3.11% 3.15% -0.04%0.16 3.84% 3.84% -0.01%-1.69 3.56% 3.57% -0.01%4.17 3.55% 3.62% -0.07%

    -11.57 3.30% 3.29% 0.01%3.04 4.03% 4.05% -0.01%

    13.91 4.30% 4.36% -0.06%6.30 3.88% 3.93% -0.05%1.87 3.14% 3.19% -0.05%5.19 2.93% 2.99% -0.06%-6.68 3.82% 3.80% 0.02%-1.98 3.80% 3.81% -0.01%21.76 3.43% 3.53% -0.10%12.71 3.79% 3.84% -0.04%

  • 8/7/2019 example of thesis format

    44/44

    Difference in Network Branch Load and Difference In THDv BetweenConfiguration B and C continued

    TotalMVA

    ConfigurationB

    THDv

    ConfigurationC

    THDv

    Difference inTHDv

    -4.31 4.34% 4.35% -0.01%-31.89 3.40% 3.32% 0.07%-8.60 3.80% 3.78% 0.02%-5.45 3.43% 3.45% -0.02%-1.20 4.07% 4.11% -0.03%7.35 3.67% 3.71% -0.05%8.22 3.92% 3.96% -0.04%

    -12.04 4.02% 4.02% 0.01%-14.04 3.28% 3.27% 0.01%0.72 3.40% 3.46% -0.05%

    24.57 3.66% 3.78% -0.12%

    5.23 3.08% 3.15% -0.07%1.61 3.73% 3.78% -0.05%

    12.40 4.11% 4.18% -0.07%-7.76 3.26% 3.27% -0.01%-5.95 3.40% 3.40% 0.00%0.11 3.07% 3.11% -0.04%

    10.59 3.29% 3.33% -0.04%-11.59 3.36% 3.37% -0.01%13.02 3.79% 3.85% -0.06%4.36 3.31% 3.35% -0.05%