EW-401_3

download EW-401_3

of 10

Transcript of EW-401_3

  • 8/7/2019 EW-401_3

    1/10

    GAS LEAK DETECTOR

    MODEL: EW-401

    Expl anati ons

    EWOO ENG NEERI NG CO. , LTD.

  • 8/7/2019 EW-401_3

    2/10

    Tabl e of Contents

    1. Speci fi cati ons1-1. Speci fi cati ons of the I ndi cator (EW401)

    1-2. Speci fi cati ons of the Detector

    2. Functi on of Each Devi ce and T tl e Expl anati ons2-1. I ndi cator

    2-2. Detector

    3. Wri ng D agram

    4. Operati on System D agram

    5. I nstal l ati on P ace and I nstal l ati on Drawng

    6. Operati on Method and I nstructi ons

  • 8/7/2019 EW-401_3

    3/10

    1. Product Speci fi cati ons1-1. Speci fi cati ons of the I ndi cator

    Name Gas Leak Detector (MODEL:EW401)

    Detector GasesLPG LNG Ci ty Gas (Methane, Butane, Propane)

    Combusti bl e Gas

    Power AC 220V. 60 (AC 230V 50 AC110V/ 50 opti on)

    Power Consumpti on Normal : 2. 5W. Al arm: 3W

    Operati ng Temperature Range

    and Humi di ty-10~ 50, 0~95% RH

    Readout Range 0 ~ 100% LEL

    Al arm Poi nt Wi thi n 25% (user adj ustabl e*Vari abl e setti ng)

    Response Ti me Wi thi n 20 seconds

    Vi sual Al arm and Audi o Al arm Fl i ckeri ng of LED LAMP (yel l ow) and above 70Db of buzzer sound

    Operati ng I ndi cator Li ghti ng of LED LAMP (green)

    Troubl e I ndi cator Li ghti ng of LED LAMP (Red)

    Warm up Ti me 60 seconds

    Connecti on Cabl e VCT or CVVS above O. 75mm SQ Use over

    Di mensi on 114*250*80

    Outer OutputDC 12V(20~30mA Output). Contact poi nt of non-vol tage

    contact poi nt NO. NC. COM(Rel ay contact poi nt)

    Capaci ty of Contact Poi nt AC 110/1A. DC 12~24 2A

    Wei ght Some 1,840g

    1-2. Speci fi cati ons of the Detector

    Type Expansi on Type

    Detector Gases LPG LNG Ci ty Gas (Methane, Butane, Propane) Combusti bl e Gas

    Sensor Type Catal yti c, Combusti on (Hot-wi re type) Di ffusi on Type

    Operati ng Temperature Rang

    and Humi di ty-20~ 50, 0~95% RH

    Expl osi on-proof Type ExdBT

    Cabl e Connector I nsi de Di a 16mm/ Outer Di a 23mm

    Di mensi on 137*142*75

    Wei ght 1,036g

    Readout Range 0~100%(LEL)

    Response Ti me Wi thi n 20 seconds

  • 8/7/2019 EW-401_3

    4/10

    2. Functi on of Each Part and T tl e Expl anati ons2-1. I ndi cator (EW401)

    Power Lamp Troubl e Si gnal

    - Lamp to confi rm el ectri ci ty status - Li ghted i n case of abnormal detecti on devi ce or i ts l i ne

    (Green LED) (Red LED)

    Ci rcui t Test Swi tch Reset Swi tch

    - To confi rm operati on status of recei ver - As al arm i s kept i n case of gas l eakage or l i ne test,

    uni t i nternal ci rcui t i t wi l l be reversed when reversi on swi tch i s pushed after

    (Al arm, l evel meter, buzzer, rel ay) i t drops on the densi tometer.

    Buzzer stop Lamp Gas Densi ty I ndi cator

    - I n case of pushi ng the swi tch agai nst - Expanded gas densi ty i s marked by l amp l evel meter.

    Al arm, buzzer turns off, and l amp around LEL I ndi cati on

    swi tch and etc. turn off. - Tabl e i ndi cati ng l amp l evel meter and LEL conversi on

    Buzzer Stop Swi tch

    -I n case of pushi ng the buzzer stop swi tch agai nst al arm, al arm

    sound stops and i n case numeri cal val ue of re-pushi ng, al arm i s sounded.

  • 8/7/2019 EW-401_3

    5/10

    2-2. Detector

    Sensor fi xi ng hol e Sti cker

    - The hol e for fi xi ng the detector by bol ts or nai l s -4m*6m

    Si ntered Fi l ter Ground earth

    - Sensor protecti on fi l ter (bronze 300mesh) -M4*6mm

    Cover Fi xi ng bol t Mol ded Cover

    - The bol t for fi xi ng cover and body of Detector

    Cabl e grand Mol ded Body

    Cabl e I nsert Devi ce Wi re

    -Cabl e pi pe or fi exi bl e screw(Femal e screw) -VCTF 0. 75x3C (Bl ue, Brown, Green)

  • 8/7/2019 EW-401_3

    6/10

    3. Wri ng D agram

    110/220 I nput: To fi x the power suppl y sel ecti on swi tch to AC110V or 220V

    and then to connect the l i ne. (AC230V 50 AC110V/ 50 opti on)

    Non-vol tage contact poi nt (NO. NC. COM): Contact (Swi tch) COM termi nal and

    NC termi nal are connected at ordi nary ti mes. I n case of al armi ng, COM termi nal and

    NO termi nal are connected.

    Sensor Connecti on Termi nal (Bl ue, Brown, Green): I t i s connected to be

    matched wi th wi re col ors arranged i n detecti on devi ce. Bl ue (El ectri c Li ne +),

    Brown (El ectri c Li ne +), Green (Si gnal Li ne)

    Si gnal Output (+. -): I n case of al armi ng, i t can be used for shut-off devi ce or

    other vari ous devi ces wi th DC12V 30mA output.

  • 8/7/2019 EW-401_3

    7/10

    4. Operati on System D agram

  • 8/7/2019 EW-401_3

    8/10

    5. I nstal l ati on P ace and I nstal l ati on drawng5-1. I nstal l ati on Pl ace1. Detecti on devi ce shal l be i nstal l ed i n the pl ace where the l eaked

    gas easi l y stays, as the pl ace where gas i s easi l y l eaked among

    storage faci l i ti es and gas faci l i ti es.

    2. The l ocati on where detecti on devi ce i s i nstal l ed, shal l be deci ded

    as per the condi ti ons such as characteri sti cs of gas, i nstructi ons,

    structure of each devi ce and etc.

    3. As for i nstal l ati on hei ght of detecti on devi ce, i f the gas heavi er than

    ai r, i t shal l be i nstal l ed wi thi n 30cm above the fl oor whi l e i f the one

    l i ghter than ai r, i t shal l be i nstal l ed wi thi n 30cm bel ow the cei l i ng.

    4. I nstal l ati on pl ace for recei ver devi ce of gas l eak al arm devi ce shal l

    be i nstal l ed i n the proper pl ace to take every measure after al arm i s

    sounded, as the pl ace where the rel evant person resi des or the al arm

    can be i denti fi ed.

  • 8/7/2019 EW-401_3

    9/10

    5-2. I nstal l ati on Drawi ng

    I nstal l ati on Pl ace: Ki tchen of the restaurant, boi l er room, governor room

    and gas storage room.

    6. Operati on Method and I nstructi onsOperati on Method

    1. To open the front case and to fi x the swi tch to the operati on vol tage

    after fi ni shi ng the connecti on of recei ver devi ce and detecti on devi ce.

    2. I n case power suppl y swi tch turns on, power suppl y l amp wi l l

    be fl i ckered for some one mi nute, and i n case earl y stabi l i zati on

    ti me i s passed, power suppl y l amp wi l l stops fl i ckeri ng and be l i ghted

    and ci rcui t wi l l be operated i n normal way.

    3. I n case detecti on devi ce i s di sconnected, buzzer i s sounded and

    troubl e si gnal i s l i ghted.

  • 8/7/2019 EW-401_3

    10/10

    4. As for test operati on of gas l eak al arm devi ce, i n case of pushi ng the

    ci rcui t test button, densi ty si gnal l amp i s sl owl y up as gas i s

    detected, and then when al arm setti ng devi ce i s abnormal , al arm si gnal

    l amp i s l i ghted and al arm i s sounded.

    5. I n case of pushi ng the buzzer button i n order to stop the al arm sound,

    normal operati on wi l l be made as i t becomes i n normal .

    6. I n case di sconnecti on si gnal and troubl e l amp are l i ghted, to confi rm

    the detecti on devi ce and connecti on status.

    I nstructi ons

    1. Opti onal di sassembl y, repai r or al terati on i s not al l owed by an

    person except the rel evant personnel of our company.

    2. As for the product equi pped wi th earthi ng termi nal , earthi ng

    l i ne shal l be surel y i nstal l ed

    3. I n case of connecti ng recei ver devi ce and detecti on devi ce, the same

    manufacturi ng number shal l be connected.

    4. To confi rm the vol tage before i nstal l ati on, to match 110V/220V

    conversi on swi tch to operati on vol tage.

    5. Do not use any other gas except appl i cati on objecti ve gas.

    6. Do not use i t i n the pl ace where there i s hi gh vapor or strong wi nd.

    7. Pl ease check the detecti on el ement more than one ti me per year.