Evolution Fan Units - Caice · Evolution Fan Unit Technical Data HD1 Fan Performance Curves 0 200...
Transcript of Evolution Fan Units - Caice · Evolution Fan Unit Technical Data HD1 Fan Performance Curves 0 200...
-
Evolution Fan Units
Technical Data
Physical Data
Quick Selection Performance Curves
Data for Typical Duty Points
Construction Code Description
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
2
Plan View (shown with close coupled rectangular attenuators)
Side View
Evolution Fan Unit Technical Data
Physical Data
Model Width 1
(mm) Height 1
(mm) Length (mm)
Duct connection Optional Circular
connection (mm) Weight (kg)
Width 2 (mm)
Height 2 (mm)
HA1 500 275 550 440 215 200Ø 20
HA2 850 275 550 790 215 N/A 30
HA3 1200 275 550 1140 215 N/A 39
HB1 500 335 425 440 275 200Ø 18
HB2 850 335 425 790 275 N/A 26
HC1 550 360 500 490 300 250Ø 23
HC2 1000 360 500 940 300 N/A 36
HD1 700 400 650 640 340 355Ø 33
HD2 1200 400 650 1140 340 N/A 50
Length
Wid
th 2
Wid
th 1
Control Panel
Heig
ht
2
Heig
ht
1
Access Panel
Access Zone
500m
m
30mm Doby/Mez
compatible flange
Access Zone (Height 1+200mm)
For attenuator data, please see pages 19 to 22.
Filters, Heating and Cooling Coils are available upon request, for more detailed dimensional data,
please contact Caice for specific fan selections.
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
3
Plan View (shown with close coupled rectangular attenuators)
Evolution Fan Unit Technical Data
Quick Selection
Selection Guide
0
200
300
500
400
600
700
0 400 1400 1800
Sta
tic P
ressure
(P
a)
Airflow (l/s)
100
200 600 800 1000 1200 1600
HD2 HD1
HB2 HB1
HC2
HC1
HA3 HA2
HA1
HA1, HA2 and HA3 are particularly suited to acoustically sensitive locations. With their available pressure
they are commonly used for localised ventilation and transfer fans. Remaining models offer higher pressure
capacity for more complex ventilation systems and also facilitate the option of filters and coils as part of the
fan assembly.
Upon request Caice can provide a detailed acoustic analysis for its entire range against specified noise
targets. All models are for internal installation only.
Fixed speed control via the local (on-board) speed setting potentiometer.
Remote speed control using a 0-10v signal from a BMS.
Remote speed control using a 0-10v signal from another external control device (e.g. wall mounted potentiometer).
A 10v reference signal for this purpose is available from
the controller.
Remote enable using a volt-free contact (e.g. wall switch, occupancy sensor).
Boost speed activation using a volt-free contact.
230vAC / 2A output
24vAC / 2A output when fitted with optional transformer.
EC Fan Interface Panel
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
4
Evolution Fan Unit Technical Data
HA1 Fan Performance Curves
0
40
60
100
80
120
140
160
0 50 100 150 200 250
Sta
tic P
ressure
(P
a)
Airflow (l/s)
20
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 57 54 49 47 40 36 30 17
Discharge 57 54 48 48 48 43 36 25
Casing 47 46 44 42 37 31 24 15
Free field hemispherical radiated noise: 25 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
80 50 980 22 0.15 0.27
Data for Typical Duty Points
80l/s at 50Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 60 59 55 55 49 45 43 31
Discharge 62 62 56 56 59 55 52 45
Casing 51 52 51 50 48 42 36 28
Free field hemispherical radiated noise: 34 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
150 50 1133 44 0.33 0.29
150l/s at 50Pa
Additional data for other specific duty points is available on request
180 10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
5
Evolution Fan Unit Technical Data
HA2 Fan Performance Curves
0
40
60
100
80
120
140
160
0 100 200 300 400 500
Sta
tic P
ressure
(P
a)
Airflow (l/s)
20
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 59 56 51 49 42 37 31 18
Discharge 60 56 49 49 50 44 37 26
Casing 49 48 45 43 38 32 26 16
Free field hemispherical radiated noise: 26 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
150 50 978 43 0.34 0.28
Data for Typical Duty Points
150l/s at 50Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 60 60 55 55 49 45 41 29
Discharge 63 61 56 57 59 54 50 43
Casing 52 53 51 50 47 41 35 28
Free field hemispherical radiated noise: 34 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
260 50 1068 71 0.52 0.27
260l/s at 125Pa
Additional data for other specific duty points is available on request
180
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
6
Evolution Fan Unit Technical Data
HA3 Fan Performance Curves
0
40
60
100
80
120
140
160
0 150 300 450 600 750
Sta
tic P
ressure
(P
a)
Airflow (l/s)
20
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 63 62 57 56 49 45 41 29
Discharge 64 62 56 57 58 53 48 39
Casing 54 54 52 51 47 40 34 25
Free field hemispherical radiated noise: 34 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
320 60 1090 87 0.64 0.27
Data for Typical Duty Points
320l/s at 60Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 67 66 62 60 54 50 47 36
Discharge 67 66 60 61 63 59 55 48
Casing 57 58 56 54 52 46 38 27
Free field hemispherical radiated noise: 38 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
400 80 1312 138 1.05 0.35
400l/s at 80Pa
Additional data for other specific duty points is available on request
180 10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
7
Evolution Fan Unit Technical Data
HB1 Fan Performance Curves
Airflow (l/s)
0
200
300
500
400
600
700
Sta
tic P
ressure
(P
a)
100
Additional data for other specific duty points is available on request
Data for Typical Duty Points
0 50 100 150 200 250 300
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 70 74 73 76 65 65 60 55
Discharge 71 71 71 75 69 72 67 65
Casing 65 66 65 69 53 54 47 43
Free field hemispherical radiated noise: 49 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
175 200 3557 100 0.84 0.57
175l/s at 200Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 64 67 72 61 56 55 51 42
Discharge 64 65 69 63 60 61 58 51
Casing 56 59 63 54 45 42 37 33
Free field hemispherical radiated noise: 39 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
125 150 2750 49 0.42 0.40
125l/s at 150Pa
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
8
Evolution Fan Unit Technical Data
HB2 Fan Performance Curves
0
200
300
500
400
600
700
Sta
tic P
ressure
(P
a)
Airflow (l/s)
100
Additional data for other specific duty points is available on request
Data for Typical Duty Points
0 100 200 300 400 500 600
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 74 77 78 78 68 68 63 58
Discharge 75 75 75 78 72 74 69 68
Casing 68 69 70 71 57 56 49 46
Free field hemispherical radiated noise: 52 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
350 150 3448 174 1.48 0.50
350l/s at 150Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 66 68 73 62 57 56 52 40
Discharge 66 66 70 64 62 62 58 50
Casing 58 60 64 55 47 43 37 33
Free field hemispherical radiated noise: 40 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
200 200 2712 98 0.83 0.49
200l/s at 200Pa
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
9
Evolution Fan Unit Technical Data
HC1 Fan Performance Curves
0
100
150
250
200
300
350
400
0 100 200 300 400 450
Sta
tic P
ressure
(P
a)
Airflow (l/s)
50
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 58 67 58 49 49 44 32 22
Discharge 58 63 59 54 53 55 43 36
Casing 61 61 52 45 38 36 32 33
Free field hemispherical radiated noise: 31 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
175 125 1675 49 0.39 0.28
Data for Typical Duty Points
175l/s at 125Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 66 68 74 61 63 62 52 50
Discharge 66 68 72 65 66 67 61 61
Casing 64 63 68 57 51 50 43 41
Free field hemispherical radiated noise: 37 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
260 150 2149 104 0.82 0.40
260l/s at 150Pa
Additional data for other specific duty points is available on request
450
500
350 250 150 50
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
10
Evolution Fan Unit Technical Data
HC2 Fan Performance Curves
0
100
150
250
200
300
350
400
0 200 400 600 800 900
Sta
tic P
ressure
(P
a)
Airflow (l/s)
50
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 62 70 62 53 57 46 35 24
Discharge 62 66 63 58 56 56 45 37
Casing 64 64 57 49 40 38 34 33
Free field hemispherical radiated noise: 35 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
300 150 1696 100 0.67 0.33
Data for Typical Duty Points
300l/s at 150Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 68 69 76 63 63 62 52 49
Discharge 68 70 73 66 66 67 61 59
Casing 66 65 70 58 52 51 44 40
Free field hemispherical radiated noise: 45 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
450 200 2134 204 1.35 0.45
450l/s at 200Pa
Additional data for other specific duty points is available on request
450
500
700 500 300 100
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
11
Evolution Fan Unit Technical Data
HD1 Fan Performance Curves
0
200
300
400
500
Sta
tic P
ressure
(P
a)
Airflow (l/s)
100
Additional data for other specific duty points is available on request
600
Data for Typical Duty Points
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 60 69 53 44 48 44 39 28
Discharge 56 64 51 47 55 52 46 39
Casing 58 57 46 40 42 34 30 30
Free field hemispherical radiated noise: 29 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
300 150 1470 90 0.68 0.3
300l/s at 150Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 66 75 67 57 61 57 53 49
Discharge 64 71 63 61 68 66 60 61
Casing 63 66 61 52 53 47 40 38
Free field hemispherical radiated noise: 38 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
450 200 1919 195 0.96 0.43
450l/s at 200Pa
0 100 200 300 400 600 500 700 800 900
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
12
Evolution Fan Unit Technical Data
HD2 Fan Performance Curves
0
200
300
400
500
0 200 400 600 800 1200
Sta
tic P
ressure
(P
a)
Airflow (l/s)
100
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 66 76 63 53 56 52 47 38
Discharge 63 71 60 57 63 60 54 50
Casing 64 65 56 49 50 42 36 34
Free field hemispherical radiated noise: 37 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
600 200 1650 248 1.22 0.41
600l/s at 200Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 74 79 78 67 67 63 59 54
Discharge 72 76 74 71 73 72 66 66
Casing 71 71 72 62 58 52 45 42
Free field hemispherical radiated noise: 48 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
900 250 2070 494 2.18 0.55
900l/s at 250Pa
Additional data for other specific duty points is available on request
600
Data for Typical Duty Points
1000 1400 1600 1800
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
13
Plan View (shown with close coupled rectangular attenuators)
Side View
Evolution Twin Fan Unit Technical Data
Physical Data
Model Width 1
(mm) Height 1
(mm) Length (mm)
Duct connection Optional Circular
connection (mm) Weight (kg)
Width 2 (mm)
Height 2 (mm)
HAT 850 275 550 440 215 200Ø 31
HBT 850 335 625 440 275 200Ø 35
HCT 1000 360 700 490 300 250Ø 45
HDT 1200 400 850 640 340 355Ø 61
Length
Wid
th 2
Wid
th 1
Control Panel
Heig
ht
2
Heig
ht
1
Access Panel
For attenuator data, please see pages 19 to 22.
Access Zone
500m
m
30mm Doby/Mez
compatible flange
Access Zone (Height 1+200mm)
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
14
Evolution Twin Fan Unit Technical Data
Quick Selection
Selection Guide
0
200
300
400
500
600
0 100 200 300 400 900
Sta
tic P
ressure
(P
a)
Airflow (l/s)
100
600 700 500 800
HDT
HCT
HBT
HAT
HAT is particularly suited to acoustically sensitive locations. With its available pressure it is commonly used for
localised ventilation.
Remaining models offer higher pressure capacity for more complex ventilation systems.
Upon request Caice can provide a detailed acoustic analysis for its entire range against specified noise targets.
All Models are for internal installation only in horizontal orientation.
Fixed speed control via the local (on-board) speed setting potentiometer.
Remote speed control using a 0-10v signal from a BMS.
Remote speed control using a 0-10v signal from another external control device (e.g. wall mounted potentiometer).
A 10v reference signal for this purpose is available from
the controller.
Remote enable using a volt-free contact (e.g. wall switch, occupancy sensor).
Boost speed activation using a volt-free contact.
Run-on timer of 0-15 minutes.
Remote display/alarm panel (optional).
EC Fan Auto–Changeover Panel
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
15
Evolution Twin Fan Unit Technical Data
HAT Twin Fan Performance Curves
0
40
60
100
80
120
140
160
250
Sta
tic P
ressure
(P
a)
0 50 100 150 200
Airflow (l/s)
20
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 58 57 52 52 45 41 37 25
Discharge 60 58 52 53 55 50 46 38
Casing 48 49 47 46 43 35 30 24
Free field hemispherical radiated noise: 29 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
120 50 1033 31 0.23 0.26
Data for Typical Duty Points
120l/s at 50Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 63 62 58 57 52 48 45 35
Discharge 63 63 58 58 61 57 53 48
Casing 52 53 52 51 49 42 35 27
Free field hemispherical radiated noise: 35 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
160 75 1344 59 0.45 0.37
160l/s at 75Pa
Additional data for other specific duty points is available on request
180
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
16
Evolution Twin Fan Unit Technical Data
HBT Twin Fan Performance Curves
0
200
300
500
400
600
700
Sta
tic P
ressure
(P
a)
Airflow (l/s)
100
Additional data for other specific duty points is available on request
Data for Typical Duty Points
0 50 100 150 200 250 300
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 70 74 73 76 65 65 60 55
Discharge 71 71 71 75 69 72 67 65
Casing 64 65 64 68 52 52 46 43
Free field hemispherical radiated noise: 48 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
175 200 3557 100 0.84 0.57
175l/s at 200Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 63 66 72 61 54 53 50 39
Discharge 63 65 70 62 58 60 56 47
Casing 54 58 62 53 42 39 33 33
Free field hemispherical radiated noise: 37 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
125 100 2547 37 0.32 0.30
125l/s at 100Pa
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
17
Evolution Twin Fan Unit Technical Data
HCT Twin Fan Performance Curves
0
100
150
250
200
300
350
400
0 100 200 300 400 450
Sta
tic P
ressure
(P
a)
Airflow (l/s)
50
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 59 67 59 50 48 43 32 21
Discharge 59 63 60 55 53 53 42 34
Casing 60 60 53 45 36 33 30 30
Free field hemispherical radiated noise: 31 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
150 150 1696 50 0.40 0.33
Data for Typical Duty Points
150l/s at 150Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 66 68 74 61 62 61 51 48
Discharge 66 68 72 65 65 67 60 60
Casing 63 62 67 56 50 48 41 38
Free field hemispherical radiated noise: 42 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
250 200 2247 120 0.95 0.48
250l/s at 200Pa
Additional data for other specific duty points is available on request
450
500
350 250 150 50
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
18
Evolution Twin Fan Unit Technical Data
HDT Twin Fan Performance Curves
0
200
300
400
500
0 100 200 300 400 600
Sta
tic P
ressure
(P
a)
Airflow (l/s)
100
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 62 72 58 49 55 52 48 41
Discharge 59 68 56 53 62 60 54 53
Casing 59 61 51 44 48 40 35 35
Free field hemispherical radiated noise: 34 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
400 150 1684 132 0.76 0.33
400l/s at 150Pa
Octave Band Sound Power Levels (dB)
63 125 250 500 1k 2k 4k 8k
Inlet 76 79 83 71 71 66 62 61
Discharge 73 76 79 74 77 75 69 73
Casing 71 70 76 65 59 53 47 49
Free field hemispherical radiated noise: 51 dB(A) at 3m
l/s Pa n
(rpm) P
(W) I
(A) SFP
(W/l/s)
600 150 2170 249 1.14 0.42
600l/s at 150Pa
Additional data for other specific duty points is available on request
600
Data for Typical Duty Points
500 700 800 900
10 Volts
8 Volts
6 Volts
4 Volts
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
19
Evolution Fan Unit Technical Data
Rectangular Attenuator Data
Insertion Losses
Insertion Loss (dB)
Fan Model Length
(mm) 63 125 250 500 1k 2k 4k 8k
HA1
HA2
HA3
HAT
650 2 5 9 15 26 35 31 27
950 3 6 14 22 36 43 36 31
1250 4 7 18 30 46 50 41 35
1565 4 8 22 37 55 55 45 38
1865 5 9 27 44 55 55 50 42
Insertion Loss (dB)
Fan Model Length
(mm) 63 125 250 500 1k 2k 4k 8k
HB1
HB2
HBT
650 3 5 7 15 26 24 18 13
950 4 7 10 20 34 32 23 16
1250 5 9 13 25 42 39 29 20
1565 6 11 16 31 51 47 34 23
1865 8 13 19 36 55 54 39 27
Insertion Loss (dB)
Fan Model Length
(mm) 63 125 250 500 1k 2k 4k 8k
HC1
HC2
HCT
650 3 5 7 14 24 20 14 9
950 4 6 9 18 31 27 18 11
1250 5 8 11 22 39 33 22 13
1565 6 10 14 27 47 39 26 15
1865 7 11 16 31 54 45 30 18
Insertion Loss (dB)
Fan Model Length
(mm) 63 125 250 500 1k 2k 4k 8k
HD1
HD2
HDT
650 3 6 8 14 22 23 18 12
950 4 8 13 22 33 31 23 14
1250 5 11 18 30 44 39 27 16
1565 6 13 23 38 55 47 32 19
1865 6 16 27 46 55 55 37 21
Rectangular attenuators should be connected directly to the fan box in order to minimise radiated
noise levels.
Only Caice attenuators are recommended for use with Caice fan units.
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
20
Evolution Fan Unit Technical Data
Rectangular Attenuator Pressure Losses Fan Model A
Rectangular Attenuator Pressure Losses Fan Model B
25
0
0
400 500 600 700 300200100
50
75
100
125
HA1/HAT
HA3
HA2
Airflow (l/s)
Pre
ssure
loss (P
a)
0
25
50
75
100
125
100 200 300 400 5000
HB1/HBT
HB2
Airflow (l/s)
Pre
ssure
loss (P
a)
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
21
Evolution Fan Unit Technical Data
Rectangular Attenuator Pressure Losses Fan Model C
Rectangular Attenuator Pressure Losses Fan Model D
Airflow (l/s)
25
0
0
400 500 600 700 300200100
50
75
100
125
HC2
HC1/HCT
800
Pre
ssure
loss (P
a)
0
25
50
75
100
125
200 400 600 800 1000 0
HD1/HBT
HD2
1200 1400 1600
Airflow (l/s)
Pre
ssure
loss (P
a)
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
22
Evolution Fan Unit Technical Data
Circular Attenuator Data
Insertion Losses
Insertion Loss (dB)
Fan Model OD
(mm)
Length
(mm) 63 125 250 500 1k 2k 4k 8k
ID
(mm)
HD1/HDT 460
615 1 2 4 9 20 10 9 8
355 915 1 2 5 14 26 12 11 10
1215 1 3 7 18 32 14 12 12
Insertion Loss (dB)
Fan Model OD
(mm)
Length
(mm) 63 125 250 500 1k 2k 4k 8k
ID
(mm)
HC1/HCT 355
615 1 2 5 12 27 17 13 13
250 915 1 3 7 17 36 21 15 15
1215 1 4 9 23 45 26 18 17
Insertion Loss (dB)
Fan Model OD
(mm)
Length
(mm) 63 125 250 500 1k 2k 4k 8k
ID
(mm)
HA1/HAT
HB1/HBT 305
615 1 3 7 14 29 21 16 15
200 915 1 4 10 20 38 27 19 18
1215 1 4 12 25 47 33 22 21
Circular attenuator pressure losses are negligible.
Circular Attenuator
ID
OD
Length
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
23
Evolution Fan Unit Technical Data
Construction Code Description
Model Attenuator Components Controls
Casing
H High Acoustic Specification Double Skinned Casing
Fans
A 133mm Diameter Forward Curved Centrifugal Fan
B 190mm Diameter Backward Curved Impellor Fan
C 250mm Diameter Backward Curved Impellor Fan
D 280mm Diameter Backward Curved Impellor Fan
Number Of Fans
1 One Fan Unit
2 Two Fan Unit
3 Three Fan Unit
T Twin Fan Unit
Special Features
X Any Special Features
S Shut Off Damper D DX Coil
P EU4 Panel Filter E Electric Heater
B EU6 Bag Filter R Frost Heater
W EU2 Wire Framed Washable Filter F Frost Coil
H LPHW Heating Coil I Circular Inlet Connection
C CHW Cooling Coil O Circular Discharge Connection
Components Components
H D 2 / A H / S P B C H / 1 / X
A Rectangular 650mm Long
B Rectangular 950mm Long
C Rectangular 1250mm Long
D Rectangular 1565mm Long
E Rectangular 1865mm Long
K Circular 615mm Long
L Circular 915mm Long
M Circular 1215mm Long
Inlet Attenuators
Special Features
Controls
1 EC Fan Interface Control
3 EC Auto Changeover Fan Control
F Rectangular 650mm Long
G Rectangular 950mm Long
H Rectangular 1250mm Long
I Rectangular 1565mm Long
J Rectangular 1865mm Long
N Circular 615mm Long
O Circular 915mm Long
P Circular 1215mm Long
Discharge Attenuators
http://www.twitter.com/CaiceUKhttp://www.linkedin.com/company/caicehttps://plus.google.com/111958683056369215299
-
Telephone
0118 918 6470
Facsimile
0118 918 6480
www.caice.co.uk
Caice Acoustic Air Movement Ltd.
Riverside House
3 Winnersh Fields
Gazelle Close
Winnersh
Wokingham
RG41 5QS
Registered office and
head office
Company Registration Number
2790667
VAT Registration Number
GB614683632
Important Information
All published specifications within this document were accurate as of 27 November 2014. As part of
our policy of continuous product improvement we reserve the right to change the specifications of
our products without prior notice. Our latest product specifications are available from our web site.