Evidence of Performance Airborne sound insulation of building
elements
Test report 162 35851 / 3e
This test repor t is a t rans lat ion of tes t report 162 35851/3
dated 14 August 2009
06-11 / 585
Basis
EN ISO 140-1:1997+A1:2004
EN 20140-3 :1995+A1:2004
EN ISO 717-1 : 1996+A1:2006
Representation
Instructions for use
This test report serves to dem-onstrate the sound insulation of building elements.
Applicable for Germany:
- Rw,R as per DIN 4109: (Rw corresponds to Rw,P, Rw,R = Rw,P – 5 dB)
- Rw,R for "Bauregelliste" (Construction Products List)
Validity
The data and results given re-late solely to the tested and de-scribed specimen.
Testing the sound insulation does not allow any statement to be made on further characteris-tics of the present structure re-garding performance and qual-ity.
Notes on publication
The ift Guidance Sheet "Condi-tions and Guidance for the Use of ift Test Documents" applies.
The cover sheet can be used as abstract.
Contents
The test report contains a total of 13 pages:
1 Object 2 Procedure 3 Detailed results 4 Instructions for use Data sheet (3 pages)
Client Reynaers Aluminium N.V./S.A.
Oude Liersbaan 266
2570 Duffel Belgium
Product
External pedestrian doorset, single leaf, outward open-ing
System designation CS 86-HI
External Dimen-sions (W x H) 985 mm × 2120 mm
Material aluminium profiles with thermal break, uncoated
Type of opening turn
Rebate seals 2 seals
Infill panel
Insulating glass unit, 3 variants Variant 1: 6/15/4 Variant 2: 8/15/11 LG Variant 3: 9 LG Acoustic /20/ 13 LG Acoustic
Special features -/-
Weighted sound reduction index Rw Spectrum adaptation terms C and Ctr
Variant 1: Rw (C; Ctr) = 37 (-2;-5) dB Variant 2: Rw (C; Ctr) = 39 (-2;-4) dB Variant 3: Rw (C; Ctr) = 43 (-1;-4) dB
ift Rosenheim 02. November 2009
Bernd Saß, Dipl.-Ing. (FH) Assistant Head of Testing Department ift Centre for Acoustics
Dr. Joachim Hessinger, Dipl.-Phys. Head of Testing Department ift Centre for Acoustics
Evidence of Performance Airborne sound insulation of building elements
Page 2 of 13
Test Report 162 35851 / 3e dated 2. November 2009
Client Reynaers Aluminium N.V./S.A., B-2570 Duffel, Belgium
Q:\LSW\Projekte\162_Türen\35851_Reynaers\PB\Hillebrecht\162 35851-3e Reynaers.doc
1 Object
1.1 Description of test specimen
Product External pedestrian doorset, single leaf, outward opening
Product designation CS 86-HI
Type of opening turn
Opening direction to outside
Mass of the door Variant 1: 64.7 kg
Variant 2: 91.7 kg
Variant 3: 100.4 kg
Area related mass Variant 1: 31.0 kg/m²
Variant 2: 43.9 kg/m²
Variant 3: 48.1 kg/m²
Frame member
Frame member size (W x H) 985 mm × 2120 mm
Material aluminium profiles with thermal break, uncoated
Profile number* frame 108.0869.XX,
threshold 108.0874.XX
Profile section (W x T) 68 mm × 77 mm, threshold 18 mm × 778 mm
Casement member
Casement member size (W x H) 889 mm × 2062 mm
Material aluminium profiles with thermal break, uncoated
Profile number* 108.1014.XX
Profile section (W x T) 102 mm × 77 mm
Rebate design
Rebate seal 2 seals
external (type / material / manufac-
turer)*
080.9080.04 / EPDM / Atel
Position continuous around perimeter of casement member
internal (type / material / manufac-
turer)*
080.9080.04 / EPDM / Atel
Position on sides and at top of frame member
Floor threshold
Floor threshold* Threshold profile 108.0874.XX
Sealing unit of casement member
internal (type / material / manufac-
turer)*
080.9440.04 / EPDM / Atel
Position at bottom of casement member
Infill panel Insulating glass unit, 3 variants
Type, manufacturer* Variant 1: Phonibel 2534, AGC Kempenglas
Variant 2: Phonibel S3441, AGC Kempenglas
Variant 3: Phonibel ST 4248,AGC Kempenglas
Evidence of Performance Airborne sound insulation of building elements
Page 3 of 13
Test Report 162 35851 / 3e dated 2. November 2009
Client Reynaers Aluminium N.V./S.A., B-2570 Duffel, Belgium
Q:\LSW\Projekte\162_Türen\35851_Reynaers\PB\Hillebrecht\162 35851-3e Reynaers.doc
Sound insulation of glazing * Variant 1: 34 dB
Variant 2: 41 dB
Variant 3: 50 dB
Visible size (W x H) 684 mm × 1860 mm
Total thickness at edge Variant 1: 25 mm
Variant 2: 35 mm
Variant 3: 41 mm
Total thickness in pane centre Variant 1: 26 mm
Variant 2: 35 mm
Variant 3: 42 mm
Construction Variant 1: 6/15/4
Variant 2: 8/15/11 LG
Variant 3: 9 LG Acoustic /20/ 13 LG Acoustic
Configuration of laminated glass * Variant 2: Stratobel 55.2 Planibel
Variant 3: Stratophone 44.2 Planibel
Stratophone 66.2 Planibel
Gas filling in cavity according to Analysis at ift
Gas Variant 1, 2 and 3 : each Air
Volume in % Variant 1, 2 and 3 : each 100 %
Mounting of infill panels
Sealing system external and internal gaskets
internal: type / material / manufac-
turer*
Variant 1 and 2: 080.9106.04 / EPDM / Hutchinson
Variant 3: 080.8904.04 / EPDM / Hutchinson
external: type / material / manufac-
turer*
080.9114.04 / EPDM / Polecex.
Glazing beads aluminium profiles, Company Reynaers N.V./S.A.
Position interior / exterior interior
Type* Variant 1: 030.3616.XX
Variant 2: 030.3613.XX
Variant 3: 030.3611.XX
Ventilation of glazing rebate 3 holes ∅ 8 mm in casement member at bottom to outside
Fittings
Hinges / manufacturer 2 hinges, type 065.6813.XX / Dr. Hahn
Lock / manufacturer Latch lock with 1 locking device type 061.7650.ZC / Sobinco
test with latch engaged and locked
The description is based on inspection of the test specimen at ift. Article designa-
tions/numbers as well as material specifications were given by the client. (Additional data
provided by the client are marked with *)
Evidence of Performance Airborne sound insulation of building elements
Page 4 of 13
Test Report 162 35851 / 3e dated 2. November 2009
Client Reynaers Aluminium N.V./S.A., B-2570 Duffel, Belgium
Q:\LSW\Projekte\162_Türen\35851_Reynaers\PB\Hillebrecht\162 35851-3e Reynaers.doc
1.2 Mounting in test rig
Test rig Door test rig „Z-Wall“ with suppressed flanking transmission
acc. to EN ISO 140-1; the test rig includes a mounting frame
with 5 cm continuous acoustic break which is sealed in the test
opening with plastic sealant.
Mounting of specimen Specimen mounted by ift Centre for Acoustics and by staff from
client.
Mounting conditions Mounting in test opening, connecting joints filled with foam and
sealed on both sides by application of elastic sealant
Mounting position The test opening with bottom door edge is positioned close to
the floor, the floor seal operates against the system threshold.
Opening direction To receiving room
Preparation The element was opened and closed repeatedly.
1.3 Representation of the test specimen
The structural details were examined solely on the basis of the characteristics to be classi-
fied. The illustrations are based on unchanged documentation provided by the client.
Fig 1 Photography of the mounted element, left from source room, right from receiving room,
taken by ift Centre for Acoustic
Evidence of Performance Airborne sound insulation of building elements
Page 5 of 13
Test Report 162 35851 / 3e dated 2. November 2009
Client Reynaers Aluminium N.V./S.A., B-2570 Duffel, Belgium
Q:\LSW\Projekte\162_Türen\35851_Reynaers\PB\Hillebrecht\162 35851-3e Reynaers.doc
Fig 2 elevation drawing and sectional drawing for glazing variant 1
Evidence of Performance Airborne sound insulation of building elements
Page 6 of 13
Test Report 162 35851 / 3e dated 2. November 2009
Client Reynaers Aluminium N.V./S.A., B-2570 Duffel, Belgium
Q:\LSW\Projekte\162_Türen\35851_Reynaers\PB\Hillebrecht\162 35851-3e Reynaers.doc
Fig 3 elevation drawing and sectional drawing for glazing variant 2
Evidence of Performance Airborne sound insulation of building elements
Page 7 of 13
Test Report 162 35851 / 3e dated 2. November 2009
Client Reynaers Aluminium N.V./S.A., B-2570 Duffel, Belgium
Q:\LSW\Projekte\162_Türen\35851_Reynaers\PB\Hillebrecht\162 35851-3e Reynaers.doc
Fig 4 elevation drawing and sectional drawing for glazing variant 3
Evidence of Performance Airborne sound insulation of building elements
Page 8 of 13
Test Report 162 35851 / 3e dated 2. November 2009
Client Reynaers Aluminium N.V./S.A., B-2570 Duffel, Belgium
Q:\LSW\Projekte\162_Türen\35851_Reynaers\PB\Hillebrecht\162 35851-3e Reynaers.doc
2 Procedure
2.1 Sampling
Sampling The samples were selected by the client
Quantity One door, three glass panes
Manufacturer Reynaers N.V./S.A.
Manufacturing plant Reynaers N.V./S.A., B 2570 Duffel, Belgium
Date of manufacture /
date of sampling
17 March 2009
Production line Prototype production
Responsible for sampling Mrs. Monica Hiciu
Delivery at ift Frame: 30 March 2009 by client via forwarding agency
Glazing: 3. November 2008 by client via forwarding agency
ift- registry number 25704/1 frame
24873/ 1 to /3 glazing
2.2 Process
Technical basis
EN ISO 140-1:1997 + A1:2004 Acoustics; Measurement of sound insulation in buildings
and of building elements - Part 1: Requirements for laboratory
test facilities with suppressed flanking transmission
EN 20140-3:1995 + A1:2004 Acoustics; Measurement of sound insulation in buildings
and of building elements - Part 3: Laboratory measurements of
airborne sound insulation of building elements
EN ISO 717-1 : 1996 + A1:2006 Acoustics; Rating of sound insulation in buildings and of
building elements - Part 1: Airborne sound insulation
Corresponds to national german version:
DIN EN ISO 140-1:2005-03, DIN EN ISO 140-3:2005-03 and DIN EN ISO 717-1 : 2006-11
Methods and scope of testing according to the principles of the "Arbeitskreis der bauakus-
tischen Prüfstellen" (Working group of acoustic centres) in agreement with NA 005-55-75- AA
(UA 1 to DIN 4109)
Boundary conditions Up to the standard
Deviations There are no deviations from the test procedure and test condi-
tions.
Test noise Pink noise
Measuring filter One-third-octave band filter
Test limits
Background noise level The background noise level in the receiving room was deter-
mined during measurement and the receiving room level L2 cor-
rected by calculation as per DIN EN ISO 140-3 Clause 6.5.
Evidence of Performance Airborne sound insulation of building elements
Page 9 of 13
Test Report 162 35851 / 3e dated 2. November 2009
Client Reynaers Aluminium N.V./S.A., B-2570 Duffel, Belgium
Q:\LSW\Projekte\162_Türen\35851_Reynaers\PB\Hillebrecht\162 35851-3e Reynaers.doc
Maximum sound insulation Maximum sound insulation of the test set-up was at least 15 dB
higher than the measured sound reduction index of the test
specimen. Not corrected by calculation.
Measurement of arithmetical mean: two measurements each of 2 loudspeaker
reverberation time and 3 microphone positions (total of 12 independent measure-
ments).
Measurement equation A T
V16,0A ⋅= m²
Measurement of sound level
difference At least 2 speaker positions and microphones moved on circulat
paths.
Measurement equation A
Slg10LLR 21 ⋅+−= dB
Key A equivalent absorption area in m² L1 Sound pressure level source room in dB L2 Sound pressure level receiving room in dB R Sound reduction index in dB T Reverberation time in s V Volume of receiving room in m³ S Testing area of the specimen in m²
2.3 Measuring and test equipment
Device Type Hersteller
Integrating sound meter Type Nortronic 830 Norsonic-Tippkemper
Microphone preamplifiers Type 1201 Norsonic-Tippkemper
Microphone units Type 1220 Norsonic-Tippkemper
Calibrator Type 1251 Norsonic-Tippkemper
Dodecahedron loudspeakers Own design -
Amplifier Type E120 FG Elektronik
Rotating microphone boom Own design / Type 231-N-360 Norsonic-Tippkemper
The ift Centre for Acoustics participates in comparative measurements at the Physikalisch-
Technische Bundesanstalt (PTB) in Braunschweig every three years, the last one was in Ja-
nuary 2007. The sound level meter used, Series No. 17956 was calibrated by the Dortmund
Eichamt (calibration agency) on 16 May 2007. The calibration is valid until 31 Decem-
ber 2009.
2.4 Testing
Date 2. April 2009
Test engineer Dr. Joachim Hessinger
Evidence of Performance Airborne sound insulation of building elements
Page 10 of 13
Test Report 162 35851 / 3e dated 2. November 2009
Client Reynaers Aluminium N.V./S.A., B-2570 Duffel, Belgium
Q:\LSW\Projekte\162_Türen\35851_Reynaers\PB\Hillebrecht\162 35851-3e Reynaers.doc
3 Detailed results
The values of the measured airborne sound reduction index of the tested door are drawn-up
in the diagram of the annexed data sheets as a function of the frequency and are given in a
table.
As per EN ISO 717-1 the weighted sound reduction index Rw and the spectrum adaptation
terms C and Ctr for the frequency range from 100 Hz to 3150 Hz obtained by calculation are
as follows:
Variant 1 (measurement Z70, data sheet 1): Rw (C;Ctr) = 37 (-2;-5) dB
Variant 2 (measurement Z71, data sheet 2): Rw (C;Ctr) = 39 (-2;-4) dB
Variant 3 (measurement Z69, data sheet 3): Rw (C;Ctr) = 43 (-1;-4) dB
4 Instructions for use
4.1 Requirement in Germany
Basis
DIN 4109:1989-11 Schallschutz im Hochbau, Anforderungen und Nachweise
For requirements according to DIN 4109 : 1989-11 (“Eignungsprüfung I”) the weighted sound
reduction index Rw is equivalent to Rw,P. After deduction of 5 dB safety margin the Rw,R value
is given by
Variant 1: Rw,R = 32 dB
Variant 2: Rw,R = 34 dB
Variant 3: Rw,R = 38 dB
4.2 Laminated glass
The sound reduction of laminated glass depends on the temperature of the environment. If
the temperature is lower than the test temperature the sound reduction index may be re-
duced.
ift Rosenheim
Centre for Acoustics
2. November 2009
Sound reduction index according to ISO 140 - 3 Laboratory measurement of airborne sound insulation of building elements
Client: Reynaers Aluminium N.V./S.A., 2570 Duffel, Belgium
Product designation CS 86-HI
Design of test specimen
External pedestrian doorset, single leaf, outward opening
External dimensions 985 mm × 2120 mm
Material aluminium profiles with thermal break, uncoated
Type of opening turn
Rebate seals 2 seals
Infill panel Insulation glass
Pane construction 6/15/4
Gas filling in cavity Air
Test date 2. April 2009
Test surface S 1.01 m × 2.13 m = 2.15 m2
Test rig as per EN ISO 140-1
Partition wall Double-leaf concrete wall, mounting frame
Test noise pink noise
Volumes of test rooms VS = 104 m³ VR = 67.5 m³
Maximum sound insulation Rw,max = 62 dB (related to test surface)
Mounting conditions Door flush inserted in test opening and mounted using wedges. Joints are completely stuffed with plastic foam and sealed with elastic sealant on both sides.
Climate in test rooms 22 °C / 35 % RF
f in Hz R in dB
50 - 63 - 80 -
100 22.3 125 23.5 160 20.3
200 26.1 250 24.1 315 31.5
400 35.4 500 38.4 630 39.0
800 40.5 1000 40.7 1250 41.0
1600 39.0 2000 37.0 2500 35.8
3150 36.4
4000 40.2 5000 44.3
Rating according to EN ISO 717-1 (in third octave bands): Rw (C;Ctr) = 37 (-2;-5) dB C50-3150 = - dB; C100-5000 = -1 dB; C50-5000 = - dB
Ctr,50-3150 = - dB; Ctr,100-5000 = -5 dB; Ctr,50-5000 = - dB
Test report No.: 162 35851 / 3e, page 11 of 13
Data sheet 1, Test No. Z70
ift Rosenheim
Centre for Acoustics
2. November 2009
Bernd Saß, Dipl.-Ing. (FH)
Assistant Head of Testing Department
Shifted reference curve Measurement curve Frequency range corresp. to reference curve as per EN ISO 717-1
400063 125 250 500 1000 200010
20
30
40
50
60
Frequency f in Hz
Sound reduction index R in dB
Sound reduction index according to ISO 140 - 3 Laboratory measurement of airborne sound insulation of building elements
Client: Reynaers Aluminium N.V./S.A., 2570 Duffel, Belgium
Product designation CS 86-HI
Design of test specimen
External pedestrian doorset, single leaf, outward opening
External dimensions 985 mm × 2120 mm
Material aluminium profiles with thermal break, uncoated
Type of opening turn
Rebate seals 2 seals
Infill panel Insulation glass
Pane construction 8/15/11 LG
Gas filling in cavity Air
Test date 2. April 2009
Test surface S 1.01 m × 2.13 m = 2.15 m2
Test rig as per EN ISO 140-1
Partition wall Double-leaf concrete wall, mounting frame
Test noise pink noise
Volumes of test rooms VS = 104 m³ VR = 67.5 m³
Maximum sound insulation Rw,max = 62 dB (related to test surface)
Mounting conditions Door flush inserted in test opening and mounted using wedges. Joints are completely stuffed with plastic foam and sealed with elastic sealant on both sides.
Climate in test rooms 22 °C / 35 % RF
f in Hz R in dB
50 - 63 - 80 -
100 24.9 125 20.6 160 28.2
200 31.1 250 32.2 315 36.3
400 36.8 500 39.6 630 40.0
800 41.3 1000 39.2 1250 36.4
1600 35.3 2000 37.8 2500 41.5
3150 43.8
4000 44.7 5000 49.2
Rating according to EN ISO 717-1 (in third octave bands): Rw (C;Ctr) = 39 (-2;-4) dB C50-3150 = - dB; C100-5000 = -1 dB; C50-5000 = - dB
Ctr,50-3150 = - dB; Ctr,100-5000 = -4 dB; Ctr,50-5000 = - dB
Test report No.: 162 35851 / 3e, page 12 of 13
Data sheet 2, Test No. Z71
ift Rosenheim
Centre for Acoustics
2. November 2009
Bernd Saß, Dipl.-Ing. (FH)
Assistant Head of Testing Department
Shifted reference curve Measurement curve Frequency range corresp. to reference curve as per EN ISO 717-1
400063 125 250 500 1000 200010
20
30
40
50
60
Frequency f in Hz
Sound reduction index R in dB
Sound reduction index according to ISO 140 - 3 Laboratory measurement of airborne sound insulation of building elements
Client: Reynaers Aluminium N.V./S.A., 2570 Duffel, Belgium
Product designation CS 86-HI
Design of test specimen
External pedestrian doorset, single leaf, outward opening
External dimensions 985 mm × 2120 mm
Material aluminium profiles with thermal break, uncoated
Type of opening turn
Rebate seals 2 seals
Infill panel Insulation glass
Pane construction 9 LG Acoustic/20/13 LG Acoustic
Gas filling in cavity Air
Test date 2. April 2009
Test surface S 1.01 m × 2.13 m = 2.15 m2
Test rig as per EN ISO 140-1
Partition wall Double-leaf concrete wall, mounting frame
Test noise pink noise
Volumes of test rooms VS = 104 m³ VR = 67.5 m³
Maximum sound insulation Rw,max = 62 dB (related to test surface)
Mounting conditions Door flush inserted in test opening and mounted using wedges. Joints are completely stuffed with plastic foam and sealed with elastic sealant on both sides.
Climate in test rooms 22 °C / 35 % RF
f in Hz R in dB
50 - 63 - 80 -
100 25.4 125 30.2 160 36.4
200 35.1 250 36.8 315 38.2
400 39.7 500 40.9 630 40.9
800 42.5 1000 42.4 1250 42.4
1600 43.1 2000 43.1 2500 45.1
3150 45.2
4000 45.2 5000 49.0
Rating according to EN ISO 717-1 (in third octave bands): Rw (C;Ctr) = 43 (-1;-4) dB C50-3150 = - dB; C100-5000 = 0 dB; C50-5000 = - dB
Ctr,50-3150 = - dB; Ctr,100-5000 = -4 dB; Ctr,50-5000 = - dB
Test report No.: 162 35851 / 3e, page 13 of 13
Data sheet 3, Test No. Z69
ift Rosenheim
Centre for Acoustics
2. November 2009
Bernd Saß, Dipl.-Ing. (FH)
Assistant Head of Testing Department
Shifted reference curve Measurement curve Frequency range corresp. to reference curve as per EN ISO 717-1
400063 125 250 500 1000 200010
20
30
40
50
60
Frequency f in Hz
Sound reduction index R in dB