European Technical Assessment ETA-14/0293 Of /0 /201 Trade name of the construction product Firetect ® C Product family to which the construction product belongs Fire protective products: Fire protective board Manufacturer KLF Building Products Edisonweg 5 4207 HE Gorinchem The Netherlands Tel.: +31 (0) 345 – 63 97 97 E-mail: [email protected] Web: www.klf.nl Manufacturing plants This European Technical Assessment contains A001 pages including 1 Annex which form an integral part of this assessment. This European Technical Assessment is issued in accordance with regulation (EU) No 305/2011, on the basis of ETAG 018-4, edition 2011, used as European Assessment Document (EAD) Translations of this European Technical Assessment in other languages shall fully correspond to the original issued document and should be identified as such. Communication of this European Technical Assessment, including transmission by electronic means, shall be in full. However, partial reproduction may be made, with the written consent of the issuing Technical Assessment Body. Any partial reproduction has to be identified as such.

Transcript of European Technical ETA-14/0293 · ETAG 018-4, edition 2011, used as European Assessment Document...

European Technical Assessment

ETA-14/0293 Of /0 /201

Trade name of the construction product Firetect® C

Product family to which the construction product belongs

Fire protective products:Fire protective board

Manufacturer KLF Building Products Edisonweg 5 4207 HE Gorinchem The Netherlands Tel.: +31 (0) 345 – 63 97 97 E-mail: [email protected] Web: www.klf.nl

Manufacturing plants

This European Technical Assessment contains

A001

pages including 1 Annex which form an integral part

of this assessment.

This European Technical Assessment is issued in accordance with regulation (EU) No 305/2011, on the basis of

ETAG 018-4, edition 2011, used as European Assessment Document (EAD)

Translations of this European Technical Assessment in other languages shall fully correspond to the original issued document and should be identified as such.

Communication of this European Technical Assessment, including transmission by electronic means, shall be in full. However, partial reproduction may be made, with the written consent of the issuing Technical Assessment Body. Any partial reproduction has to be identified as such.

1 Technical description of the product:

Firetect® C is an autoclaved calcium silicate fire resistant board.

Product Properties Firetect® C board Autoclaved calcium silicate board

Dimensions: 1200 mm x 2400 mm Thickness: 10, 12, 15, 18, 20, 22, 25 and 27 mm

The applicant has submitted a written declaration that Firetect® C does not contain substances which have to be classified as dangerous according to Directive 67/548/EEC and Regulation (EC) No 1272/2008 and listed in the "Indicative list on dangerous substances" of the EGDS - taking into account the installation conditions of the construction product and the release scenarios resulting from there.

According to the manufacturer’s declaration the fire protective boards comply with all relevant European and national provisions - known at the date of issuing – applicable for the uses for which they are brought to the market. Firetect® C has no formaldehyde containing components and is 100% asbestos-free.

In addition to the specific clauses relating to dangerous substances contained in this European technical Assessment, there may be other requirements applicable to the products falling within its scope (e.g. transposed European legislation and national laws, regulations and administrative provisions). In order to meet the provisions of the Construction Products Regulation, these requirements need also to be complied with, when and where they apply.

2 Specification of the intended uses in accordance with the applicable Assessment Document (hereinafter EAD) ETAG 018-4.

2.1 The fire protective boards are intended for internal use, designated as type Z2 in ETAG 018-4.

The intended use of Firetect® C is to protect elements to be used in assemblies as specified in table 1.

Protection of ETAG 018-1 reference Load-bearing steel elements Type 4 Fire separating assemblies with no load-bearing requirements

Type 8

Table 1: intended use

Detailed information and data of the assemblies is given in Annex A.

2.2 Working life The assumed working life of the board for the intended use is 25 years, provided that the assembled product is subject to appropriate installation, use and maintenance. For the intended use type Z2 no more than accidental wetting and no frost inside the building is to be expected. With this assumed intended working life it is expected that when this working life has elapsed, the real working life may be, in normal use conditions, considerably longer without major degradation affecting the essential requirements. The indication of 25 years cannot be interpreted as a guarantee given by KLF Building Products, but should only be regarded as a means for selecting the appropriate fire protective board in relation to the expected, economically reasonable working life of the works.

3. Performance of the product and references to the methods used for itsassessment

The assessment of fitness for use has been made in accordance with ETAG 018-4 (used as European Assessment Document, EAD).

Firetect® CBasic requirement for

construction work Characteristic Assessments of characteristics

BWR 1 Mechanical resistance and stability

- none Not relevant BWR 2 Safety in case of fire

EN 13501-1 Reaction to fire Class A1

EN 13501-2 Resistance to fire Annex A BWR 3 Hygiene, health and environment

ETAG 018-4 Air permeability Not relevant ETAG 018-4 Water permeability Not relevant Declaration of manufacturer Release of dangerous substances Declaration of manufacturer BWR 4 Safety in use

Mechanical resistance and stability

Flexural strength EN 12467

7,46 MPa* The boards have sufficient strength to support their own mass. The boards are not intended to support additional loads.

Pull-through resistance of mechanical fasteners ETAG 018-4

1025 N **

Shear load resistance of mechanical fastening systems ETAG 018-4

606 N **

Pull-out resistance of mechanical fasteners ETAG 018-4

0,93 kN **

Resistance to impact / movement

Resistance to impact with soft body impact-load EOTA TR001

Pass

Resistance to impact with hard body impact-load EOTA TR001

Pass

ETAG 018-4 Adhesion Not relevant BWR 5 Protection against noise

EN10140-2/ EN ISO 717-1 Airborne sound insulation No performance determined EN ISO 11654 Sound absorption No performance determined EN ISO 717-2 Impact sound insulation No performance determined BWR 6 Energy economy and heat retention

EN 12664, EN 12667 or EN 12939

Thermal properties No performance determined

EN ISO 12572 EN12056

Water vapour permeability No performance determined

General aspects relating to fitness for use

ETAG 018-4 Durability and serviceability Z2

Compressive strength 8.6 N/mm2 *

Tensile strength perpendicular to the plane of the board

0.372 N/mm2 *

* Tests have been performed on 12 mm Firetect® C board. ** Tests have been performed on 12 mm Firetect® C board with phosphate drylining screws Ø 3.5

mm. *** Tests have been performed on phosphate drylining screws Ø 3.5 mm on metal stud profile

U70F, steel sheet thickness 0,6 mm.

4 Assessment and verification of consistency of performance (hereinafter AVCP) system applied, with reference to its legal base

According to the decision 1999/454/EC – Commission Decision of date 22nd June 1999 on the procedure for attesting the conformity of construction products pursuant to Article 20(2) of Council Directive 89/106/EEC as regards fire stopping, fire sealing and fire protective products, published in the Official Journal of the European Union (OJEU) L178/52 of 14/07/1999, see http://eur-lex.europa.eu/JOIndex.do) of the European Commission1, as amended, the system(s) of assessment and verification of constancy of performance (see Annex V to Regulation (EU) No 305/2011) given in the following table(s) applies (apply).

Product(s) Intended use(s) Level(s) or class(es) System(s)

Fire stopping and fire sealing products

For fire compartmentation

and/or fire protection or fire performance

Any 1

5 Technical details necessary for the implementation of the AVCP system, as provided for in the applicable EAD

Tasks of the manufacturer:

Factory production control The manufacturer shall exercise permanent internal control of production. All the elements, requirements and provisions adopted by the manufacturer shall be documented in a systematic manner in the form of written policies and procedures, including records of results performed. This production control system shall ensure that the product is in conformity with this European Technical Assessment. The manufacturer may only use initial / raw / constituent materials stated in the technical documentation of this European Technical Assessment. The factory production control shall be in accordance with the Control Plan of 201 relating tothe European technical assessment ETA 14/0293 issued on /0 /201 which is part of the technicaldocumentation of this European technical approval. The "Control Plan" is laid down in the context of the factory production control system operated by the manufacturer and deposited at IKOB-BKB. The results of factory production control shall be recorded and evaluated in accordance with the provisions of the Control Plan.

Other tasks of the manufacturer

Additional information The manufacturer shall provide a technical data sheet and an installation instruction with the following minimum information: (a) Technical data sheet:

• Field of application:

• Building elements for which the fire protective board is suitable, type and properties of thebuilding elements like minimum thickness, density, and the construction requirements.

• Limits in size, minimum thickness etc. of the fire protective board

• Assembly of the fire separating constructions including the necessary components andadditional products (e.g. backfilling material) with clear indication whether they are generic orspecific.

(b) Installation instruction:

• Steps to be followed

• Procedure in case of retrofitting

• Stipulations on maintenance, repair and replacement

6 Issued on

201