Copyright 2002 by Siemens Energy & Automation, Inc.2810840--0001
Product Information
SIMATIC ET 200S
2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module
New Relay Output Module Available
The 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module has beenadded to the ET 200S family. The order number for this module is6ES7 132-4HB10-0AB0.
This product information includes details about the characteristics and technicalspecifications of the 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A RelayModule. Refer to the ET 200S Distributed I/O Manual for more information aboutthe ET 200S product family.
You will also learn how to start up the Module.
Additional Assistance
For assistance in answering technical questions, for training on this product, or forordering, contact your Siemens distributor or sales office.
X 23Release 4
2Product Information ET 200S 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module
2810840--0001
2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A
Order Number
6ES7 132-4HB10-0AB0
Features
The 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module has thefollowing characteristic features:
! Digital electronic module with two relay outputs
! Output current 5 A per output
! Substitute value
! Parameterization length: 3 bytes
! Suitable for solenoid valves, DC contactors, and indicator lights
! Isolated from the supply voltage
! Normally open (N.O.) and normally closed (N.C.) contacts
Note
If you connect an extra-low voltage system (SELV/PELV) on one channel of theRelay module, you can only use an extra-low voltage system (SELV/PELV) on theother channel.
Configuration Tool Support
Support for the 2RO NO/NC DC24..120V / 5 A AC24..230 V / 5 A Relay Modulecan be found in the following:
! Step7 V5.1 SP4
! GSD File Siem806a V1.11
! GSD File Siem806b V1.6
3Product Information ET 200S 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module2810840--0001
Terminal Assignment
Table1 shows the terminal assigment of the different terminal modules.
Table 1 Terminal Assignment of the 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 ARelay Module
View Terminal Assignment Remarks
N.O.
AUX1 (PE)
2
3
4
6
7
8
1 5
AUX1 (PE)
! !
TM-E15S24-A1 and 2RO NO/NC DC24..120 V/ 5 A AC24..230 V / 5 A Relay
CH1CH0
The AUX1 bus mustbe applied to PE.
Common
N.C.
Common
N.O.
N.C.
Channel 0: Terminals 1 to 3
Channel 1: Terminals 5 to 7
1, 2: normally open contactchannel 0
1, 3: normally closedcontact channel 0
5, 6: normally open contactchannel 1
5, 7: normally closedcontact channel 1
2
3
4
6
7
8
1 5
!
TM-E15S24-01 and 2RO NO/NC DC24..120 V/ 5 A AC24..230 V / 5 A Relay
CH1CH0
N.O.
Common
N.C.
Common
N.O.
N.C.
Channel 0: Terminals 1 to 3
Channel 1: Terminals 5 to 7
1, 2: normally open contactchannel 0
1, 3: normally closedcontact channel 0
5, 6: normally open contactchannel 1
5, 7: normally closedcontact channel 1
2
3
6
7
1 5
!
TM-E15S23-01 and 2RO NO/NC DC24..120 V/ 5 A AC24..230 V / 5 A Relay
CH1CH0
Common Common
N.O.
N.C.
N.O.
N.C.
Channel 0: Terminals 1 to 3
Channel 1: Terminals 5 to 7
1, 2: normally open contactchannel 0
1, 3: normally closedcontact channel 0
5, 6: normally open contactchannel 1
5, 7: normally closedcontact channel 1
4Product Information ET 200S 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module
2810840--0001
View RemarksTerminal Assignment
2
3
4
6
7
8
1 5
CH1CH0
AUX1 AUX1
AUX1 AUX1
8
7
4
3
AA
A A
!
TM-E15S26-A1 and 2RO NO/NC DC24..120 V/ 5 A AC24..230 V / 5 A Relay
Common
N.O.
N.C.
N.O.
Common
N.C.
Channel 0: Terminals 1 to 3
Channel 1: Terminals 5 to 7
1, 2: normally open contactchannel 0
1, 3: normally closedcontact channel 0
5, 6: normally open contactchannel 1
5, 7: normally closedcontact channel 1
Block Diagram
Bac
kpla
nebu
s
ET 200Sbackplane bus
interfacemodule
L+
1MP1P2
Reversepolarityprotection
1
2
5
6
22
3
7
Figure 1 Block Diagram of the 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay
Module
5Product Information ET 200S 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module2810840--0001
Hazardous Location Information
“Power, input and output (I/O) wiring must be in accordance with Class I, Division 2wiring methods [Article 501-4 (b) of the National Electric Code, NFPA 70] and inaccordance with the authority having jurisdiction.”
Peripheral equipment must be suitable for the location it is used in.
The equipment must be suitable for use in Class I, Div. 2, Groups A, B, C, and DHazardous Locations and nonhazardous locations only.
!WarningExplosion HazardSubstitution of components may impair suitability for Class I, Div. 2 Hazardous Locations.Different or lesser quality components may cause an explosion or other hazardous situation,which could result in death or serious injury, and/or damage to equipment.
To avoid potentially hazardous situations, always use the appropriate components.
!WarningExplosion HazardNever disconnect equipment before powering off or before ascertaining that the area isnonhazardous. Disconnecting equipment before powering off in a hazardous area may causean explosion, which could result in death or serious injury, and/or damage to equipment.
To avoid potentially hazardous situations, always power off equipment and assure that the areais nonhazardous before disconnecting.
6Product Information ET 200S 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module
2810840--0001
Technical Specification of the 2RO NO/NC DC24..120 V / 5 A AC24..230 V /5 A Module
Dimensions and Weight
Dimensions W×H×D(mm)
15×81×52
Weight Approximately 50 g
Data for Specific Module
Number of outputs 2
Cable length
! Unshielded max. 600 m
! Shielded max. 1000 m
Voltage, Currents, Potentials
Rated supply voltage L+(from the power module)
24 VDC
Reverse polarity protectionCurrent per channel
Yes
! Up to 50 °C max. 5 A
! Up to 60 °C max. 4 A
Isolation
! Between the channels Yes
! Between the channelsand backplane bus
Yes
! Between the channelsand supply voltage
Yes
! Between the supplyvoltage and backplanebus
Yes
Permitted potentialdifference
! Between the supplyvoltage and backplanebus
75 VDC, 60 VAC
! Between the channelsand backplane bus
240 VAC
! Between the channelsand supply voltage
240 VAC
Insulation tested Yes
! Between the supplyvoltage and backplanebus
500 VDC
! Between the channelsand backplane bus
2500 VDC
! Between the channelsand supply voltage
2500 VDC
Current input
! From supply voltage L+ max. 30 mA
! From backplane bus max. 10 mA
Power dissipation of themodule
typ. 0.6 W
Status, Diagnostics
Status display Green LEDs perChannel
Diagnostic functions
! Group fault display onthe module
Parameters can beassigned
Red LEDs (SF)
7Product Information ET 200S 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module2810840--0001
Data for Selecting an Actuator
Output current
! Continuous thermalcurrent
max. 5 A
! Minimum load current 8 mA
Parallel connection of twooutputs
! For redundant control ofa load
No
! For performanceimprovement
No
Control of a digital input Yes
Switching frequency
! With resistive load 2 Hz
! With inductive load 0.5 Hz
! With lamp loadLimitation (internal) of thevoltage induced on circuitinterruptionShort-circuit protection ofthe outputUser Supplied(Required)
2 HzNo
No
YesFast Acting6 A/Fuse 250 V
Note: “Outputs must be fused with a 6A, 250 VAC,fast acting fuse. When installed in a HazardousLocation as defined by the National Electric Code,the fuse must be removable only by use of a tooland the area must be determined to benon--hazardous before removal/replacement.”
8Product Information ET 200S 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module
2810840--0001
Assigning Parameters to the 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A RelayModule
To find a description of the general procedure for assigning parameters to digitalmodules, see Section 3.3 of the S7--300 and M7--300 Programmable ControllersModule Specifications Manual.
For details of the parameters of the digital output module, see Appendix A.3 of theS7--300 and M7--300 Programmable Controllers Module Specifications Manual.
Parameters of the 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module
Table 2 shows the parameters that you can set and their default setting for the2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module.
The default settings apply if you do not perform parameter assignments in STEP 7.
Table 2 Parameter Assignment of the Relay Module
Parameter Value Range DefaultSettings
ParameterType
Scope
Enable
! Diagnostics interrupts Yes/No No Dynamic Module
Behavior on CPU STOP Apply substitute value(EWS)Hold last value (LWH)
EWS Dynamic Channel
Apply substitute value “1” Yes/No No Dynamic Channel
9Product Information ET 200S 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module2810840--0001
Interrupts of the 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module
The 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module can triggerdiagnostic interrupts.
The OBs and SFCs mentioned below are explained in detail in the online help forSTEP 7.
Enabling Interrupts
The interrupts are inhibited (not present) without appropriate parameterassignment. Assign parameters to the Interrupt Enable in STEP 7.
Diagnostic Interrupt
If you have enabled diagnostic interrupts, then active error events (initialoccurrence of the error) and departing error events (message aftertroubleshooting) are reported by means of an interrupt.
The CPU interrupts the execution of the user program and processes thediagnostics interrupt block (OB82).
In the user program, you can call SFC51 or SFC59 in OB82 to obtain moredetailed diagnostic information from the module.
The diagnostic information is consistent until such time as OB82 is exited. WhenOB82 is exited, the diagnostic interrupt is acknowledged on the module.
10Product Information ET 200S 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module
2810840--0001
Contact Rating and Endurance
With an external suppression circuit, the contacts will last longer than specified inTable 3.
The normally open and normally closed contacts of the relay have differentendurance ratings.
Table 3 Relay Contact and Endurance
Resistive Load Voltage Current Operating Cycles(Typical)
Normally Open
Operating Cycles(Typical)
Normally Closed
For resistive load 24 VDC 5.0 A 0.1 million 0.15 million
4.0 A 0.2 million 0.175 million
2.0 A 0.45 million 0.3 million
0.5 A 1.4 million 1.1 million
0.1 A 1.5 million 1.5 million
48 VDC 2.0 A 0.15 million 0.11 million
1.0 A 0.3 million 0.2 million
0.5 A 0.6 million 0.6 million
0.1 A 0.8 million 0.6 million
48 VAC 2.0 A 0.45 million 0.35 million
60 VAC 2.0 A 0.45 million 0.35 million
120 VAC 5.0 A 0.1 million 0.1 million
3.0 A 0.2 million 0.2 million
2.0 A 0.4 million 0.3 million
1.0 A 0.8 million 0.6 million
0.5 A 1.5 million 1.0 million
230 VAC 5.0 A 0.1 million 0.1 million
3.0 A 0.2 million 0.2 million
2.0 A 0.4 million 0.3 million
1.0 A 0.8 million 0.6 million
0.5 A 1.5 million 1.0 million
11Product Information ET 200S 2RO NO/NC DC24..120 V / 5 A AC24..230 V / 5 A Relay Module2810840--0001
Table 3 Relay Contact Endurance (continued)
Inductive Load Voltage Current Operating Cycles(Typical)
Normally Open
Operating Cycles(Typical)
Normally Closed
For inductivel d i
24 VDC 2.0 A 0.1 million 0.1 millionload inaccordance with 1.0 A 0.2 million 0.2 millionaccordance withIEC 947-5-1DC 13/ AC 15
0.5 A 0.5 million 0.5 millionDC 13/ AC 15
48 VDC 2.0 A 0.07 million 0.05 million
1.0 A 0.15 million 0.1 million
0.5 A 0.4 million 0.25 million
48 VAC 1.0 A 0.5 million 0.3 million
60 VAC 1.0 A 0.5 million 0.3 million
120 VAC 2.0 A 0.1 million 0.1 million
1.0 A 0.3 million 0.1 million
0.5 A 0.9 million 0.6 million
0.1 A 1.5 million 1.0 million
230 VAC 2.0 A 0.1 million 0.1 million
1.0 A 0.5 million 0.3 million
0.5 A 0.9 million 0.6 million
0.1 A 1.0 million 1.0 million
Note: You will achieve a longer service life with an external suppression circuit.