EST Network Applications Installation Sheets

20
EST Network Applications Installation Sheets P/N 3100766 • Rev 1.0 • 19JAN04

description

configuracion de red EST

Transcript of EST Network Applications Installation Sheets

Page 1: EST Network Applications Installation Sheets

EST Network Applications Installation Sheets

P/N 3100766 • Rev 1.0 • 19JAN04

Page 2: EST Network Applications Installation Sheets

DEVELOPED BY Edwards Systems Technology 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300

COPYRIGHT NOTICE Copyright © 2000–2004. All rights reserved.

This manual and the products it describes are copyrighted by Edwards Systems Technology, Inc. (EST). You may not reproduce, translate, transcribe, or transmit any part of this manual without express, written permission from EST.

This manual contains proprietary information intended for distribution to authorized persons or companies for the sole purpose of conducting business with EST. If you distribute any information contained in this manual to unauthorized persons, you have violated all distributor agreements and we may take legal action.

CREDITS This manual was designed and written by the EST Technical Services - Documentation Department, Sarasota.

DOCUMENT HISTORY

Date Revision Reason for change

19JAN04 1.0 Initial release

Page 3: EST Network Applications Installation Sheets

EST Network Applications Installation Sheets i

Content

Installation sheet title P/N

NETCOM-16D Mulitport Device Server 3100573

NETCOM-1F Device Server 3100572

NETCOM-1S Device Server 3100571

NETCOM-BRKT Mounting Bracket 3100575

NETSW-EIS6-MM and NETSW-EIS6-SM Switching Hub 3100574

Page 4: EST Network Applications Installation Sheets

Content

ii EST Network Applications Installation Sheets

Introduction

About this manual This manual contains copies of the EST Network Applications installation sheets. The sheets are arranged in alphabetical order by title. The part number listed in Content is the installation sheet part number.

Page 5: EST Network Applications Installation Sheets

Installation Sheet 02APR03 P/N: 3100573 REV: 1.0NETCOM-16D - Multiport Device Server 1 / 3

NETCOM-16DMultiport Device Server

Product description

xmtlnk pol ok net rcvpwrtest

The NETCOM-16D is a multiport device server that providesshared network access to terminals, devices, console ports,and printers for a variety of network protocols and operatingsystems. The NETCOM-16D will network-enable up to 16peripheral serial devices in one location.

SpecificationsPower requirements

Voltage: 95 to 250 Vac, 3-wire single phase, auto-rangingFrequency: 47 to 63 HzOperating current: 300 mA @ 120 VPower consumption: 40 watts (maximum)Fuse rating: 1.6 A, 250 V

Supported serial protocols: RS-232, RS-423, RS-422Operating environment

Temperature: 32 to 120 °F (0 to 49 °C)Humidity: 93% RH, noncondensing

LEDs and switches

LED Function

PWR Lights to indicate the unit has power

LNK Lights to indicate a functional 10Base-T network link

POL Lights to indicate a swapped 10Base-T cable

OK Blinks to indicate that the unit is functioning properly

NET Blinks to indicate Ethernet activity

RCV Blinks periodically to indicate serial charactersentering the unit

XMT Blinks periodically to indicate serial charactersexiting the unit

Switch Function

Test/Reset

When pressed for 5 seconds during power up,flushes NVR (non volatile RAM)

Power Turns the NETCOM-16D on and off

Installation instructionsTo install the NETCOM-16D, complete these steps in order.

1. Select a desktop location for the NETCOM-16D.

2. Connect one or more serial (RS-232) devices to theRJ-45 ports. See "Wiring diagram."

Note: To provide a proper interface for theNETCOM-16D, EST2 and IRC-3 panels require anIOP3-A and FCC panels require an FCOM-232 card.

3. Connect an Ethernet cable to the 10Base-T port on theNETCOM-16D and then to your Ethernet networkconnection. See "Wiring diagram."

4. Attach one end of the power cable to the NETCOM-16Dand plug the other end into a surge protected electricaloutlet or UPS (recommended). See "Wiring diagram."

5. Turn on the NETCOM-16D.

The NETCOM-16D goes through a set of power-updiagnostics for 12 seconds. The LEDs show varyingpatterns corresponding to the tests being run.

6. Install the EZWebCon software on your PC.

7. Assign the NETCOM-16D an IP address usingEZWebCon. See "Assigning an IP address to theNETCOM-16D." Also see the "System setup proceduresand worksheets" topic in the Network ApplicationsManual (P/N 3100576) for obtaining an IP address.

8. Configure the serial RS-232 ports using EZWebCon.See "Configuring a NETCOM-16D RS-232 port."

9. Configure the communication ports on each controlpanel and FireWorks computer to communicate with theNETCOM-16D. See "Configuring a control panel orFireWorks computer" for required configuration settings.

10. After all installation, wiring, and communication settingsare complete, test the communication of theNETCOM-16D with each component.

Wiring diagramThe back panel of the NETCOM-16D has a power plug, RJ-4510Base-T Ethernet port, and sixteen RJ-45 serial ports.

LISTED6J40

UL1950

LR89493

geprufteSicherheit

EN60950

TUVS E R V I C E

1 2 3 4 5 6 7 8 Serial ports

10BASE-T

9 10 11 12 13 14 15 16

Power plug connection [1]

RJ-45 10Base-T Ethernetnetwork connection

Not used

RJ-45 serial RS-232 ports

[1] An AC surge protector (6 kV, 0.5 µsec rise time) is required

Page 6: EST Network Applications Installation Sheets

P/N: 3100573 REV: 1.0 02APR03 Installation Sheet2 / 3 NETCOM-16D - Multiport Device Server

PinoutsRJ-45 Ethernet connector

1 2 3 4 5 6 7 8 1 RX+2 RX-3 TX+6 TX-

RJ-45 serial connectors

RS-232 limits: 15 m (50 ft) in length at 9600 K baud and2 m (6 ft) at 115.2 K baud

1 RTS (out)2 DTR (out)3 TX+ (out)4 TX-5 RX-6 RX+ (in)7 DSR (in)8 CTS (in)

1 2 3 4 5 6 7 8

Control panelsRJ-45

3-CPU1(TB2)

2-MCM(TB6)

CM1N(TB1)

FCOM-232(TB1)

IOP3-A(TB2/3)

3 (TX+) RXD RXD TB1-3(RXD)

RXD TB2/3-4(RXD)

6 (RX+) TXD TXD TB1-4(TXD)

TXD TB2/3-3(TXD)

4 (TX-) COM COM TB1-2(COM)

COM TB2/3-2(COM)

5 (RX-) COM COM TB1-2(COM)

COM TB2/3-2(COM)

RJ-45 to DB-25

RJ-45serialport Cable

6

5

4

3

2

6

5

4

8

7

3

2

1

DTR

RX+

TX+

RX-

TX-

(out)

(out)

(in)

DSR(in)

CTS(in)

RTS(out)

1

2

3

4

5

6

DCD

TXD

SG

RXD

DTR

RJ-45 to DB-25adapter

RJ-45(server)

DB-25(modem)

7

8 RTS

CTS5

8

3

7

2

20

4

3

4

5

1

2

6

7

8

6

5

4

8

7

3

2

1

DCE - DB-25 adapter pinout

RJ-45serialport Cable

6

5

4

3

2

6

5

4

8

7

3

2

1

DTR

RX+

TX+

RX-

TX-

(out)

(out)

(in)

DSR(in)

CTS(in)

RTS(out)

1

2

3

4

5

6

DTR

RXD

SG

TXD

DSR

RJ-45 to DB-25adapter

RJ-45(server)

DB-25(terminal)

7

8 CTS

RTS4

20

2

7

3

6

5

3

4

5

1

2

6

7

8

6

5

4

8

7

3

2

1

DTE - DB-25 adapter pinout

If you are connecting an RJ-45 port to a DTE device (such as aterminal) that has a DB-25 connector, you will need to use anRJ-45-DTE DB-25 adapter. To connect an RJ-45 port to aDB-25 connector on a DCE device, you will need an RJ-45 toDCE DB-25 adapter.

RJ-45 to DB-9

1

2

3

4

5

6

DTR

RXD

SG

TXD

DSR

4

2

5

3

6

RJ-45serialport Cable

RJ-45 to DB-9adapter

RJ-45(server)

DB-9(terminal)

3

4

5

1

2

6

7

8

7

8

6

5

4

8

7

3

2

1

6

5

4

3

2

6

5

4

8

7

3

2

1

DTR

RX+

TX+

RX-

TX-

(out)

(out)

(in)

DSR(in)

CTS(in)

RTS(out)

8

7

CTS

RTS

Note: The arrows represent the direction of the signal. Thepinouts assume that the 8-conductor cable connecting the unitand the adapter block is a swapped cable. Both the transmitand receive ground signals on the unit connector are wired tothe signal ground on a DB-9 adapter.

Page 7: EST Network Applications Installation Sheets

Installation Sheet 02APR03 P/N: 3100573 REV: 1.0NETCOM-16D - Multiport Device Server 3 / 3

Assigning an IP address to theNETCOM-16DThe EZWebCon configuration software is the easiest way toconfigure the NETCOM-16D. Follow these steps to assign anIP address to the NETCOM-16D.

Note: For more details on using the EZWebCon software, referto its online help system.

1. From the Action menu, click Assign IP Address.

2. Enter or change the IP-related settings:

a. For Ethernet Address, enter the number that appearson the bottom label of your NETCOM-16D.

b. For IP Address, enter the desired IP address for yourNETCOM-16D. [1]

c. For Subnet Mask, change the values provided only ifyou wish to use a mask other than the default. [1]

[1] Refer to the topic "System setup procedures andworksheets" in the Network Applications Manual (P/N3100576) for obtaining an IP address and subnet mask.

3. Click OK.

4. Follow the onscreen instructions.

Configuring a NETCOM-16D RS-232 portYou need to configure each serial port that is being connectedto a control panel.

1. From the File menu, click Browse Network.

Your NETCOM-16D will be listed with its IP address.

2. Click the NETCOM-16D in the list.

3. Click OK.

Your NETCOM-16D is displayed with its assigned IPaddress.

4. Click the NETCOM-16D to highlight it.

5. From the Action menu, click Manage.

6. Click Maintenance.

7. Double-click Ports.

8. Select the port you want to edit. You must set up each portthat you are connecting a device to (e.g. a control panel).

9. On the General tab, set the Serial Port GeneralParameters using the following:

CM1N, DCPU, and 2-MCMCharacter size: 8Parity: EvenAccess: RemoteFlow control: NoneStop bits: 1Speed: 1200 to 9600

3-CPU1Character size: 8Parity: NoneAccess: RemoteFlow control: NoneStop bits: 1Speed: 19200

10. Click OK.

11. Click Menu.

12. Click Extract Configuration from Server.

This allows you to save the NETCOM-16D configuration ina file. If there is a problem, you can download this file tothe NETCOM-16D and avoid repeating the configurationsteps.

13. Follow the instructions in the Save Configuration window.

14. Click OK.

15. Click Close.

You have now finished setting up the NETCOM-16D.

16. From the File menu, click Exit.

Configuring a control panel or FireWorkscomputer

EST3 panel settings

In the SDU, set the RS-232 communication port to"Gateway 3" for FireWorks communications.

FireWorks settings

The following settings must be configured in the FireWorksCommunications Manager for each NETCOM-16D serial portthat is connected to a control panel.

• IP address: xx.xx.xx.xx• IP port number: 3001 to 3016• Network type: any• EST3 port type: Gateway 3

Page 8: EST Network Applications Installation Sheets
Page 9: EST Network Applications Installation Sheets

Installation Sheet 02APR03 P/N: 3100572 REV: 1.0NETCOM-1F - Device Server 1 / 3

NETCOM-1FDevice Server

IntroductionThis installation checklist is a supplement to the NETCOM-1FUser Guide. Use this checklist to set up and install yourNETCOM-1F. Make sure you follow the procedures in theorder shown.

Parts you will need:

• NETCOM-1F• NETCOM-BRKT mounting bracket• NETCOM-1F User Guide (P/N 900-290)• Network Applications Manual (P/N 3100576)• NETCOM-CD

Steps for setting up and installing aNETCOM-1F

Step 1: Review Section 1, "Introduction," in theNETCOM-1F User Guide. This will help you tobecome familiar with the NETCOM-1F'sspecifications, LEDs, RJ-45 connection, and fiberoptic connections.

Step 2: Follow the procedures in Section 2, "GettingStarted," in the NETCOM-1F User Guide forconnecting the NETCOM-1F to a computerand/or Ethernet network and for assigning an IPaddress to the NETCOM-1F. Also refer to thetopic "System setup procedures and worksheets"in the Network Applications Manual(P/N 3100576) for obtaining IP addresses.

Step 3: Follow the procedures in Section 3, "Configuringthe Unit," in the NETCOM-1F User Guide forconfiguring the NETCOM-1F to communicate ona network.

Note: See pages 2 and 3 of this installation sheetfor device configuration settings. Refer to boththe "Overview" and "Application" settings.

Step 4: Disconnect the NETCOM-1F from your PC ornetwork.

Step 5: Install the NETCOM-1F in a cabinet using theNETCOM-BRKT mounting bracket. Seeinstallation sheet P/N 3100575.

Step 6: Connect all wiring. See Figure 1.

- Connect the 24 Vdc power wiring- Connect the RJ-45 or fiber optic network wiring- Connect the DB-25 RS-232 wiring

Note: To provide a proper interface for the deviceserver, EST2 and IRC-3 panels require anIOP3-A and FCC panels require an FCOM-232card.

Caution: When using a NETCOM-1F between aFireWorks computer and CCTV controllers, ifeither of the two transmit or receive wires areshorted, you will lose communications. Toreestablish communications, shut down andrestart FireWorks.

Step 7: Configure the communication ports on eachcontrol panel, FireWorks, and ACDB computer tocommunicate with the NETCOM-1F. See pages 2and 3 of this installation sheet for configurationsettings. Refer to both the "Overview" and"Application" settings.

Note: If you are using the NETCOM-1F with anACDB computer or FireWorks computer withCCTV controllers, you need to install theNETDIRECT software and set it up tocommunicate on your network. Follow theprocedures in Section 4, "NETDIRECT," in theNETCOM-1F User Guide for installation andsetup information. Refer to both the "Overview"and "Application" settings on pages 2 and 3 ofthis installation sheet for configuration settings.

Step 8: After all installation, wiring, and communicationsettings are complete, test the communication ofeach NETCOM-1F with each component they areconnected to.

RJ-45 Ethernet 10Base-Tnetwork connection [4]

10Base-FL (fiber optic)Ethernet network connection(transmit) [4]

10Base-FL (fiber optic)Ethernet network connection(receive) [4]

24 Vdc fromcontrol panel [1]

DB-9 and DB-25 serial port (RS-232)from control panel [2] [3]

Figure 1: Wiring connections

Notes

[1] Remove the transformer from the supplied power cableand connect the wires to a 24 Vdc power source on thecontrol panel.

• Solid black wire = positive (+)• White striped wire = negative (-)

[2] Pinout requirements can be found in the NETCOM-1FUser Guide in Section 1, "Introduction" and in the tablebelow.

[3] The NETCOM-1F can be configured to operate on CH1 orCH2.

[4] Either the Ethernet connection or the fiber opticconnection can be used, but not both simultaneously.

Page 10: EST Network Applications Installation Sheets

P/N: 3100572 REV: 1.0 02APR03 Installation Sheet2 / 3 NETCOM-1F - Device Server

Control panelsDB-9andDB-25 3-CPU1

(TB2)2-MCM(TB6)

CM1N(TB1)

FCOM-232 (TB1)

IOP3-A(TB2/3)

Pin 2(TXD)

RXD RXD TB1-3(RXD)

RXD TB2/3-4(RXD)

Pin 3(RXD)

TXD TXD TB1-4(TXD)

TXD TB2/3-3(TXD)

DB-9:Pin 5(COM)DB-25:Pin 7(COM)

COM COM TB1-2(COM)

COM TB2/3-2(COM)

Overview of configuration settingsNETCOM-1F configuration settings are dependent on twofactors, the panel you are connecting to and the applicationyou are setting up.

EST3 panel settings

• RS-232 port: set to "Gateway 3" for FireWorks• RS-232 port: set to "none" for the ACDB• RS-232 port: set to "printer" for a data terminal

FireWorks settings (Communications Manager)

• IP address: set to address of device server• IP port number: set to 10001 or 10002 for CH1 or CH2• EST3 port type: set to Gateway 3 for TCP/IP

communications

ACDB settings

• Outbound port: set to virtual port (configured inNETDIRECT)

NETDIRECT settings

If you are using the NETCOM-1F with an ACDB computer orFireWorks computer with CCTV controllers, you need to installthe NETDIRECT software and set it up to communicate withyour network. Follow the procedures in Section 4,"NETDIRECT," in the NETCOM-1F User Guide for installationand setup information.

• Create a virtual COM port (one that does not physicallyexist)

• Add the IP address TCPPort = 3001

Device server settings

• Baud rate: set to baud rate of the panel• I/F Mode: set to 4C for EST3, 7C for IRC-3, EST2, FCC,

and Pelco (CCTV)• Flow: set to 00• Port number: set to 10001; if using NETDIRECT add

11000 to the TCPPort value that was entered inNETDIRECT (e.g. 11000 + 3001 = 14001) (acceptablerange = 14001 to 14009)

• Connect mode: set to C0 for most panels and applications,set to C1 for device servers connected to a control panelin the data terminal application

• Remote IP: set to 0.0.0.0; if connecting to another deviceserver (e.g. data terminal application) set to the IP addressof the device server connected to the data terminal

• Remote port: set to 0 for most panels and applications; setto 10001 (CH1) or 10002 (CH2) for device serversconnected to a control panel in a data terminal application

• DisConnMode: set to 00• FlushMode: set to 80 if the device server is connected to

an EST3 panel and 00 for all others• PackControl: set to 23 (on only if Flush Mode is enabled)• DisConnTime: set to 00:00• SendChar1: set to 0D if device server is connected to an

EST3 panel; 00 for all others• SendChar2: set to 0D if device server is connected to an

EST3 panel; 00 for all others

Application specific configuration settingsThe following settings are application specific and should beused for each of the listed applications. See the NetworkApplications Manual (P/N 3100576).

Fireworks with EST3 using a NETCOM-1F

• Panel RS-232 port configured as Gateway 3 (this is set inthe SDU)

• FireWorks Communications Manager = TCP/IP port:

- IP address: xx.xx.xx.xx- IP port number: 10001 or 10002 (CH1 or CH2)- Network type: any- EST3 port type: Gateway 3

• Device server settings:

- Baud rate: baud rate of the panel (that was set in theSDU, either 19.2 K or 9600)- I/F mode: 4C- Flow: 00- Port number: 10001 (CH1) or 10002 (CH2)- Connect mode: C0- Remote IP address: 00.00.00.00- Remote port: 0- DisConnMode: 00- FlushMode: 80- Pack control: 23- DisConnTime: 00:00- SendChar1: 0d- SendChar2: 0d

Fireworks with EST2, IRC-3, or FCC using a NETCOM-1F

• FireWorks Communications Manager – TCP/IP port:

- IP address: xx.xx.xx.xx- IP port number: 10001 or 10002 (CH1 or CH2)- Network type: any- EST3 port type: N/A

• Device server settings:

- Baud rate: baud rate of the panel (usually 2400 to 9600)- I/F mode: 7C- Flow: 00- Port number: 10001 (CH1) or 10002 (CH2)- Connect mode: C0- Remote IP address: 00.00.00.00- Remote port: 0- DisConnMode: 00- FlushMode: 00- DisConnTime: 00:00- SendChar1: 00- SendChar2: 00

Page 11: EST Network Applications Installation Sheets

Installation Sheet 02APR03 P/N: 3100572 REV: 1.0NETCOM-1F - Device Server 3 / 3

ACDB with EST3 using a NETCOM-1F

• EST3 port set to none (set in the SDU)• NETDIRECT:

Install the NETDIRECT software on the ACDB computerand set it up to communicate with your network. Follow theprocedures in Section 4, "NETDIRECT," in the NETCOM-1F User Guide for installation and setup information.

- Create a virtual COM port (one that does not physicallyexist) with NETDIRECT- Set the IP address to that of the device server xx.xx.xx.xx- Set the TCPPort to 3001 (acceptable range: 3001 to 3009)

• ACDB settings:

- Set the outbound port to the port you configured inNETDIRECT

• Device server settings:

- Baud rate: 9600- I/F mode: 4C- Flow: 00- Port number: 11000 + TCPPort value set in NETDIRECT(acceptable range: 14001 to 14009)- Connect mode: C0- Remote IP address: 00.00.00.00- Remote port: 0- DisConnMode: 00- FlushMode: 00- DisConnTime: 00:00- SendChar1: 00- SendChar2: 00

Fireworks with CCTV (TCP/IP) using a NETCOM-1F

• FireWorks Communications manager = serial port:

- COM port set to virtual COM port in NETDIRECT- Baud rate: 9600- Parity: even- Stop Bits: 1- EST3 port type: N/A

• NETDIRECT settings:

Install the NETDIRECT software on the ACDB computerand set it up to communicate with your network. Follow theprocedures in Section 4, "NETDIRECT," in the NETCOM-1F User Guide for installation and setup information.

- Create a virtual COM port (one that does not physicallyexist)- Set the IP address to the device server xx.xx.xx.xx- Set the TCPPort to 3001 (acceptable range: 3001 to 3009)

• Device server settings:

- Baud rate: 9600- I/F mode: 7C- Flow: 00- Port number: 11000 + TCPPort value set in NETDIRECT(acceptable range: 14001 to 14009)- Connect mode: C0- Remote IP address: 00.00.00.00- Remote Port: 00- DisConMode: 00- Flush mode: 00- DisConnTime: 00:00- Send char: 00- Send char: 00

Data terminal device server connecting to an EST3 deviceserver (such as the printer and 3-VDUT applications)

• Device server connected to a panel:

- Baud rate: baud rate of the panel (set in the SDU)- I/F mode: 4C- Flow: 00- Port number: 10001- Connect mode: C1- Remote IP address: IP address of the device serverconnected to the DTE device- Remote port: 10001 (CH1) or 10002 (CH2)- DisConnMode: 00- FlushMode: 80- Pack control: 23- DisConnTime: 00:00- SendChar1: 0d- SendChar2: 0d

• Device server connected to the DTE device:

- Baud rate: baud rate of the panel (set in the SDU)- I/F mode: 4C- Flow: 00- Port number: 10001 (CH1) or 10002 (CH2)- Connect mode: C0- Remote IP address: 00.00.00.00- Remote port: 00- DisConnMode: 00- FlushMode: 00- DisConnTime: 00:00- SendChar1: 00- SendChar2: 00

Data terminal device server connecting to an EST2, IRC-3,or FCC device server (such as the printer and VDU-3applications)

• Device server connected to the panel:

- Baud rate: baud rate of the panel- I/F mode: 7C- Flow: 00- Port number: 10001- Connect mode: C1- Remote IP address: IP address of the device server- Remote port: 10001 (CH1) or 10002 (CH2)- DisConnMode: 00- FlushMode: 00- DisConnTime: 00:00- SendChar1: 00- SendChar2: 00

• Device Server connected to the DTE device:

- Baud rate: baud rate of the panel- I/F mode: 7C- Flow: 00- Port number: 10001 (CH1) or 10002 (CH2)- Connect mode: C1- Remote IP address: IP address of the device serverconnected to the panel- Remote port: 00- DisConnMode: 00- FlushMode: 00- DisConnTime: 00:00- SendChar1: 00- SendChar2: 00

Page 12: EST Network Applications Installation Sheets
Page 13: EST Network Applications Installation Sheets

Installation Sheet 02APR03 P/N: 3100571 REV: 1.0NETCOM-1S - Device Server 1 / 3

NETCOM-1SDevice Server

IntroductionThis installation checklist is a supplement to the NETCOM-1SUser Guide. Use this checklist to set up and install yourNETCOM-1S. Make sure you follow the procedures in theorder shown.

Parts you will need:

• NETCOM-1S• NETCOM-BRKT mounting bracket• NETCOM-1S User Guide (P/N 900-291)• Network Applications Manual (P/N 3100576)• NETCOM-CD

Setting up and installing a NETCOM-1S Step 1: Review Section 1, "Introduction," in the

NETCOM-1S User Guide. This will help you tobecome familiar with the NETCOM-1S'sspecifications, LEDs, DB-25 connection, andRJ-45 connection.

Step 2: Follow the procedures in Section 2, "GettingStarted," in the NETCOM-1S User Guide forconnecting the NETCOM-1S to a computer and/orEthernet network and for assigning an IP addressto the NETCOM-1S. Also refer to the topic"System setup procedures and worksheets" in theNetwork Applications Manual (P/N 3100576) forobtaining IP addresses.

Step 3: Follow the procedures in Section 3, "Configuringthe Unit," in the NETCOM-1S User Guide forconfiguring the NETCOM-1S to communicate ona network.

Note: See pages 2 and 3 of this installation sheetfor device configuration settings. Refer to boththe "Overview" and "Application" settings.

Step 4: Disconnect the NETCOM-1S from your PC ornetwork.

Step 5: Install the NETCOM-1S in a cabinet using theNETCOM-BRKT mounting bracket. Seeinstallation sheet P/N 3100575.

Step 6: Connect all wiring. See Figure 1.

- Connect the 24 Vdc power wiring- Connect the RJ-45 network wiring- Connect the DB-25 RS-232 wiring

Note: To provide a proper interface for the deviceserver, EST2 and IRC-3 panels require an IOP3-Aand FCC panels require an FCOM-232 card.

Caution: When using a NETCOM-1S between aFireWorks computer and CCTV controllers, ifeither of the two transmit or receive wires areshorted, you will lose communications. Toreestablish communications, shut down andrestart FireWorks.

Step 7: Configure the communication port(s) on eachcontrol panel, FireWorks, and ACDB computer tocommunicate with the NETCOM-1S. See pages2 and 3 of this installation sheet for configurationsettings. Refer to both the "Overview" and"Application" settings.

Note: If you are using the NETCOM-1S with anACDB computer or FireWorks computer withCCTV controllers, you need to install theNETDIRECT software and set it up tocommunicate on your network. Follow theprocedures in Section 4, "NETDIRECT," in theNETCOM-1S User Guide for installation andsetup information. Refer to both the "Overview"and "Application" settings on pages 2 and 3 ofthis installation sheet for configuration settings.

Step 8: After all installation, wiring, and communicationsettings are complete, test the communication ofeach NETCOM-1S with each component they areconnected to.

RJ-45 Ethernet 10/100Base-Tnetwork connection

24 Vdc fromcontrol panel [1] DB-25 serial

port (RS-232)from control panel [2]

Figure 1: Wiring connections

Notes

[1] Remove the transformer from the supplied power cableand connect the wires to a 24 Vdc power source on thecontrol panel. Polarity:

• Solid black wire = positive (+)• White striped wire = negative (-)

[2] Pinout requirements can be found in the NETCOM-1SUser Guide in Section 1, "Introduction" and in the tablebelow.

Control panelsDB-25

3-CPU1(TB2)

2-MCM(TB6)

CM1N(TB1)

FCOM-232 (TB1)

IOP3-A(TB2/3)

Pin 2(TXD)

RXD RXD TB1-3(RXD)

RXD TB2/3-4(RXD)

Pin 3(RXD)

TXD TXD TB1-4(TXD)

TXD TB2/3-3(TXD)

Pin 7(COM)

COM COM TB1-2(COM)

COM TB2/3-2(COM)

Page 14: EST Network Applications Installation Sheets

P/N: 3100571 REV: 1.0 02APR03 Installation Sheet2 / 3 NETCOM-1S - Device Server

Overview of configuration settingsNETCOM-1S configuration settings are dependent on twofactors, the panel you are connecting to and the applicationyou are setting up.

EST3 panel settings

• RS-232 port: set to "Gateway 3" for FireWorks• RS-232 port: set to "none" for the ACDB• RS-232 port: set to "printer" for a data terminal

FireWorks settings (Communications Manager)

• IP address: set to address of device server• IP port number: set to 10001• EST3 port type: set to Gateway 3 for TCP/IP

communications

ACDB settings

• Outbound port: set to virtual port (configured inNETDIRECT)

NETDIRECT settings

If you are using the NETCOM-1S with an ACDB computer orFireWorks computer with CCTV controllers, you need to installthe NETDIRECT software and set it up to communicate withyour network. Follow the procedures in Section 4,"NETDIRECT," in the NETCOM-1S User Guide for installationand setup information.

• Create a virtual COM port (one that does not physicallyexist)

• Add the IP address TCPPort = 3001

Device server settings

• Baud rate: set to baud rate of the panel• I/F Mode: set to 4C for EST3, 7C for IRC-3, EST2, FCC,

and Pelco (CCTV)• Flow: set to 00• Port number: set to 10001; if using NETDIRECT add

11000 to the TCPPort value that was entered inNETDIRECT (11000 + 3001 = 14001) (acceptable range =14001 to 14009)

• Connect mode: set to C0 for most panels and applications,set to C1 for device servers connected to a control panelin a data terminal application

• Remote IP: set to 0.0.0.0; if connecting to another deviceserver (e.g. data terminal application) set to the IP addressof the device server connected to the data terminal

• Remote port: set to 0 for most panels and applications; setto 10001 for device servers connected to the control panelin a data terminal application

• DisConnMode: set to 00• FlushMode: set to 80 if the device server is connected to

an EST3 panel and 00 for all others• PackControl: set to 23 (on only if Flush Mode is enabled)• DisConnTime: set to 00:00• SendChar1: set to 0D if device server is connected to an

EST3 panel, 00 for all others• SendChar2: set to 0D if device server is connected to an

EST3 panel, 00 for all others

Application specific configuration settingsThe following settings are application specific and should beused for each of the listed applications. See the NetworkApplications Manual (P/N 3100576).

Fireworks with EST3 using a NETCOM-1S

• Panel RS-232 port configured as Gateway 3 (this is set inthe SDU)

• FireWorks Communications Manager = TCP/IP port:

- IP address: xx.xx.xx.xx- IP port number: 10001- Network type: any- EST3 port type: Gateway 3

• Device server settings:

- Baud rate: baud rate of the panel (that was set in theSDU, either 19.2 K or 9600)- I/F mode: 4C- Flow: 00- Port number: 10001- Connect mode: C0- Remote IP address: 00.00.00.00- Remote port: 0- DisConnMode: 00- FlushMode: 80- Pack control: 23- DisConnTime: 00:00- SendChar1: 0d- SendChar2: 0d

Fireworks with EST2, IRC-3, or FCC using a NETCOM-1S

• FireWorks Communications manager = TCP/IP port:

- IP address: xx.xx.xx.xx- IP port number: 10001- Network type: any- EST3 port type: N/A

• Device server settings:

- Baud rate: baud rate of the panel (usually 2400 to 9600)- I/F mode: 7C- Flow: 00- Port number: 10001- Connect mode: C0- Remote IP address: 00.00.00.00- Remote port: 0- DisConnMode: 00- FlushMode: 00- DisConnTime: 00:00- SendChar1: 00- SendChar2: 00

Page 15: EST Network Applications Installation Sheets

Installation Sheet 02APR03 P/N: 3100571 REV: 1.0NETCOM-1S - Device Server 3 / 3

ACDB with EST3 using a NETCOM-1S

• EST3 port set to none (set in the SDU)• NETDIRECT settings:

Install the NETDIRECT software on the ACDB computerand set it up to communicate with your network. Follow theprocedures in Section 4, "NETDIRECT," in the NETCOM-1S User Guide for installation and setup information.

- Create a virtual COM port (one that does not physicallyexist) with NETDIRECT- Set the IP address to that of the device server xx.xx.xx.xx- Set the TCPPort to 3001 (acceptable range: 3001 to 3009)

• ACDB settings:

- Set the outbound port to the port you configured inNETDIRECT

• Device server settings:

- Baud rate: 9600- I/F mode: 4C- Flow: 00- Port number: 11000 + TCPPort value set in NETDIRECT(acceptable range: 14001 to 14009)- Connect mode: C0- Remote IP address: 00.00.00.00- Remote port: 0- DisConnMode: 00- FlushMode: 00- DisConnTime: 00:00- SendChar1: 00- SendChar2: 00

Fireworks with CCTV (TCP/IP) using a NETCOM-1S

• FireWorks Communications Manager = serial port:

- COM port set to virtual COM port in NETDIRECT- Baud rate: 9600- Parity: even- Stop Bits: 1- EST3 port type: N/A

• NETDIRECT settings:

Install the NETDIRECT software on the FireWorkscomputer and set it up to communicate with your CCTVcontroller. Follow the procedures in Section 4,"NETDIRECT," in the NETCOM-1S User Guide forinstallation and setup information.

- Create a virtual COM port (one that does not physicallyexist)- Set the IP address to the device server xx.xx.xx.xx- Set the TCPPort to 3001 (acceptable range: 3001 to 3009)

• Device server settings:

- Baud rate: 9600- I/F mode: 7C- Flow: 00- Port number: 11000 + TCPPort value set in NETDIRECT(acceptable range: 14001 to 14009)- Connect mode: C0- Remote IP address: 00.00.00.00- Remote Port: 00- DisConMode: 00- Flush mode: 00- DisConnTime: 00:00- Send char: 00- Send char: 00

Data terminal device server connecting to an EST3 deviceserver (such as the printer and 3-VDUT applications)

• Device server connected to a panel:

- Baud rate: baud rate of the panel (set in the SDU)- I/F mode: 4C- Flow: 00- Port number: 10001- Connect mode: C1- Remote IP address: IP address of the device serverconnected to the DTE device- Remote port: 10001- DisConnMode: 00- FlushMode: 80- Pack control: 23- DisConnTime: 00:00- SendChar1: 0d- SendChar2: 0d

• Device server connected to the DTE device:

- Baud rate: baud rate of the panel (set in the SDU)- I/F mode: 4C- Flow: 00- Port number: 10001- Connect mode: C0- Remote IP address: 00.00.00.00- Remote port: 00- DisConnMode: 00- FlushMode: 00- DisConnTime: 00:00- SendChar1: 00- SendChar2: 00

Data terminal device server connecting to an EST2, IRC-3,or FCC device server (such as the printer and VDU-3applications)

• Device server connected to the panel:

- Baud rate: baud rate of the panel- I/F mode: 7C- Flow: 00- Port number: 10001- Connect mode: C1- Remote IP address: IP address of the device serverconnected to the DTE device- Remote port: 10001- DisConnMode: 00- FlushMode: 00- DisConnTime: 00:00- SendChar1: 00- SendChar2: 00

• Device server connected to the DTE device:

- Baud rate: baud rate of the panel- I/F mode: 7C- Flow: 00- Port number: 10001- Connect mode: C0- Remote IP address: 00.00.00.00- Remote port: 00- DisConnMode: 00- FlushMode: 00- DisConnTime: 00:00- SendChar1: 00- SendChar2: 00

Page 16: EST Network Applications Installation Sheets
Page 17: EST Network Applications Installation Sheets

Installation Sheet 20MAR03 P/N: 3100575 REV: 1.0NETCOM-BRKT - Mounting Bracket 1 / 1

NETCOM-BRKTMounting Bracket

Product descriptionThe NETCOM-BRKT is a metal bracket that is installed in a3-CHAS7 or MFC-A cabinet and is used for mounting aNETCOM-1S or NETCOM-1F device server or a NETSW hub.

Installation instructionsYou must first install the NETCOM-BRKT to either a 3-CHAS7or an MFC-A cabinet before connecting a device to thebracket. Use the instructions below to install the bracket andconnect the device servers.

Mounting the NETCOM-BRKT in a 3-CHAS7

Mount each bracket using the diagram below. Note: Differentmounting holes are used to attach the bracket to the left andright positions on the 3-CHAS7.

3-CHAS7

NETCOM-BRKTs

6-32, 5/16-inchcountersunk screws

Mounting the NETCOM-BRKT in an MFC-A cabinet

Mount the bracket using the diagram below.

MFC-A cabinet

NETCOM-BRKT

6-32, 1/4-inchcountersunk screws

Mounting a NETCOM-1S on the NETCOM-BRKT

Mount up to two NETCOM-1S modules on the bracket usingthe diagram below.

Holes for top device

Holes for bottom device

NETCOM-BRKT

NETCOM-1S

6-32, 1/4-inchpan head screws

Mounting a NETCOM-1F on the NETCOM-BRKT

Mount the NETCOM-1F on the bracket using the diagrambelow.

NETCOM-BRKT

NETCOM-1F

6-32, 1/4-inchpan head screws

Mounting a NETSW on the NETCOM-BRKT

Mount a NETSW on the bracket using the diagram below.

NETCOM-BRKT

NETSW

6-32, 1/4-inchpan head screws

Page 18: EST Network Applications Installation Sheets
Page 19: EST Network Applications Installation Sheets

Installation Sheet 17MAR03 P/N: 3100574 REV: 1.0NETSW-EIS6-MM and NETSW-EIS6-SM - Switching Hub 1 / 1

NETSW-EIS6-MM and NETSW-EIS6-SMSwitching Hub

Product descriptionThis installation checklist is a supplement to the NETSW-EISSeries Technical Reference Manual. Use this checklist to setup and install your switch. Make sure you follow theprocedures in the order shown.

Parts you will need:

• NETSW-EIS6-MM or NETSW-EIS6-SM• NETCOM-BRKT mounting bracket• NETSW-EIS Series Technical Reference Manual

(P/N 3100620)• Network Applications Manual (P/N 3100576)• NETCOM-CD

Steps for setting up and installing anNETSW

Step 1: Review the NETSW-EIS Series TechnicalReference Manual for installation information,wiring diagrams, specifications, LEDs, fiber cableconnections, and RJ-45 connections. Also seethe diagram on this sheet.

Step 2: Install the unit in a cabinet using the NETCOM-BRKT mounting bracket. See installation sheetP/N 3100575.

Step 3: Connect the fiber optic network cables to theswitch using the procedures described in theNETSW-EIS Series Technical Reference Manualand the diagram on this sheet.

Step 4: Using CAT5 cable, connect the device servers,FireWorks, or ACDB computers to the RJ-45connections on the switch. Refer to the NETSW-EIS Series Technical Reference Manual and thediagram on this sheet.

Note: Do not connect the NETCOM-1F fiberports to the NETSW fiber ports.

Step 5: Connect the power wiring to the switch using theprocedures described in the NETSW-EIS SeriesTechnical Reference Manual and the diagram onthis sheet.

Step 6: Turn on the computers. When the computerscome online, they will configure themselvesaccordingly. Refer to the topic "System setupprocedures and worksheets" in the NetworkApplications Manual, for details on getting the IPaddresses and subnet mask of your newnetwork.

Step 7: Configure all device servers (NETCOM-1S orNETCOM-1F). Refer to installation sheet P/N3100571 and 3100572 for detailed instructions.

10 Vdc 36

8 Vac 24 Power connection

Fiber optic RX

Fiber optic TX

RJ-45 Ethernet network connections(to computers and device servers)

Network backboneconnectionsFiber optic RX

Fiber optic TX

5

6

Figure 1: NETSW wiring connections (also refer to theNETSW-EIS Series Technical Reference Manual for moredetails)