Essentials of Fire Fighting, 6th Edition Fire Protection Systems
Chapter 20Fire Protection Systems
Lesson GoalAfter completing this lesson, the student shall be able to explain the fundamentals of fire protection systems.
ObjectivesUpon successful completion of this lesson, the student shall be able to:
1. Describe fire alarm systems. [NFPA® 1001, 6.5.3]2. Identify alarm initiating devices. [NFPA® 1001, 6.5.3]3. Explain the ways automatic sprinkler systems work. [NFPA® 1001, 6.5.3]4. Describe standpipe and hose systems. [NFPA® 1001, 6.5.3]5. Explain the ways smoke management systems work. [NFPA® 1001, 6.5.3]
Fire Protection Publications Firefighter II 20-1Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
Instructor InformationThis is the lesson covering fire protection systems. This lesson describes the components and classifications of various fire suppression and detection systems.
Important instructor information is provided in shaded boxes throughout the lesson plan. Carefully review the instructor information before presenting the lesson.
This lesson includes an activity that guides students through the steps to prepare a preincident survey. The activity is developed for the student to identify occupancy information, note items of concern, and prepare any sketches or diagrams need for the survey. This activity will meet the requirements of NFPA® 1001, 6.5.3. All required documents and directions are provided in the curriculum package.
MethodologyThis lesson uses lecture, discussion and a learning activity. The level of learning is application.
Fire Protection Publications Firefighter II 20-2Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
Outline Contents
Section Outline Pages
Text Pages
Section I: Fire Alarm Systems 5 1178Section II: Alarm-Initiating Devices 12 1184Section III: Automatic Sprinkler Systems 22 1194Section IV: Standpipe and Hose Systems 41 1209Section V: Smoke Management Systems 46 1213Section VI: Summary and Review 52 1216
Audiovisuals Visuals 20.1 to 20.66 (PowerPoint® Presentation)
Evaluation Chapter 20 Quiz Chapter 20 Test
Fire Protection Publications Firefighter II 20-3Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
Presentation ToolsInteractive Objects allow instructors to present information a piece at a time by clicking on hot spots in a larger image.
Each object is labeled in the Lesson Outline and indicated in the PowerPoint® presentation by a RED arrow in the top left corner of the image. This lets instructors know to use the mouse to explore all of the information on the slide.
After all of the information is displayed a reset arrow will appear in the bottom right corner of the image. Instructors can use this to remove the text and quiz students on content just covered or simply move on to the next slide.
To move to the slide after an interactive object, select the Click for next slide arrow on the left side of the slide.
Videos are used as discussion starters or to illustrate a concept or process discussed in the chapter.
These are labeled in the Lesson Outline and indicated in the PowerPoint® presentation by the Click image to play arrow on the left side of the slide.
Fire Protection Publications Firefighter II 20-4Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
Section I: Fire Alarm Systems
I. FIRE ALARM SYSTEMSpp. 1178-1184 Objective 1 — Describe fire alarm
systems.A. Fire Alarm Systems
1. Provide notification of emergency condition to building occupants; possibly local response organization
2. Requirements established by authority having jurisdiction (AHJ)
B. Alarm System Components
1. Fire alarm control panel (FACP)a. Contains electronics that
control, monitor fire alarm system
b. Serves as “brain” for alarm systemi. Receives signals from
alarm initiating devicesii. Processes signalsiii. Produces output signals
c. Power, fire alarm circuits directly connected to panel
Fire Protection Publications Firefighter II 20-5Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
d. Power boosters, power supplies for notification system are part of
e. Controls for alarm system located in FACP
f. Other functions for FACPi. Control of remote
annunciator panelii. Operation of relays that
capture, recall elevatorsiii. Public address, mass
notifications2. Power supplies
a. Primary i. Usually obtained from
building’s main connect to local utility provider
ii. If interrupted, alarm signal must be activated
b. Secondaryi. Ensures system will
operate even if primary fails
ii. Sources can include batteries with chargers, auxiliary generators
3. Initiating devices
Fire Protection Publications Firefighter II 20-6Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
a. May be manually operated or automatic
b. Automatic – Sense presence of products of combustion, other hazardous conditions
c. Send signal to FACP – May be hard wired or connected over special radio frequency
4. Notification appliancesa. Activated by control unit
once initiating device sends signal to FACP
b. System may include ability to send signal to central alarm monitoring center or directly to fire department
c. Local devicesi. Bellsii. Buzzersiii. Hornsiv. Recorded voice messagesv. Strobe lightsvi. Speakers
d. Audible notification signaling appliances – Most common types of alarm-signaling systems used
Fire Protection Publications Firefighter II 20-7Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
e. Local alarm may sound only in area of activated detector, or in entire facility – Depends on design
f. Notification appliance categoriesi. Audible – Approved
sounding devices (horns, bells, speakers) that indicate fire or emergency condition
ii. Visual – Approved lighting devices (strobes or flashing lights) that indicate fire or emergency condition
iii. Textual – Visual text or symbols indicating fire or emergency condition
iv. Tactile – Indication of fire or emergency condition through sense of touch or vibration
5. Fire command centera. Consolidates all fire
protection system controls for structure in one room
b. Allows systems to be monitored, controlled as needed
c. May include
Fire Protection Publications Firefighter II 20-8Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
i. Fire alarm control panelii. Smoke control stationiii. Fire pump status
indicatorsiv. Emergency elevator
controlsv. Emergency
communication systemsvi. Spare sprinklers, fusesvii.Building plans, system
diagramsReview Question: What are the basic components of an alarm system?See pp. 1178-1181 of the manual for answers.
C. Types of Alarm Signaling Systems
1. Protected premises (Local)a. Designed to provide
notification only to building occupants on immediate premises
b. When allowed – No automatic off-site reporting
c. May be activated manually or automatically
d. May be capable of alerting of supervisory or trouble condition – Ensure service
Fire Protection Publications Firefighter II 20-9Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
interruptions do not go unnoticed
e. Basic typesi. Noncoded alarm
(a)Simplest type of local alarm
(b)All alarm-signaling devices operate simultaneously
(c) Signaling continuously until FACP reset
(d)Not capable of identifying initiating device that triggered
(e)Only practical in small occupancies
ii. Zoned/annunciated alarm(a)Enables responders to
identify general location of alarm activation
(b)Alarm-signaling devices arranged in zones – Each with own indicator light or display
(c) Indicators on FACP illuminate for particular zone, giving responders better idea
Fire Protection Publications Firefighter II 20-10Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
of where problem is located
iii. Addressable alarm systems(a)Display location of
each initiating device on FACP or annunciator panel
(b)Responder can pinpoint specific device activated – Reduces amount of time needed to respond
(c) Allow for quick location and correction of malfunctions in the system
2. Supervising station alarm systems – Remote location monitored continuously a. Auxiliary alarm system –
Connected to municipal fire alarm systemi. Local energy system –
Has own power supply; ability to transmit during power interruption depends on design of system
ii. Shunt system – Municipal alarm circuit extends into protected property
Fire Protection Publications Firefighter II 20-11Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
b. Proprietary systemsi. Used to protect large
area; each building has own system wired into common receiving point in separate structure
ii. Trained personnel staff receiving station; should be able to automatically summon fire department response
c. Central station systems – Monitored by contracted services at receiving point; required to have ability to quickly remedy issues with system
d. Remote receiving systemsi. Not connected through
municipal alarm box system – Connected by another means (telephone line or dedicated radio frequency)
ii. Do not incorporate use of runner service
Review Question: How do protected premises and station alarm systems differ?See pp. 1182-1184 of the manual for answers.
Fire Protection Publications Firefighter II 20-12Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
Section II: Alarm-Initiating Devices
II. ALARM-INITIATING DEVICESpp. 1184-1194 Objective 2 — Identify alarm
initiating devices.A. Alarm-Initiating Devices
1. Identify presence of fire or products of combustion, send signal to alarm system
2. Type used depends on type of occupancy, contents
Fire Protection Publications Firefighter II 20-13Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
B. Pull Stations
1. Devices that allow occupants to initiate fire signaling system
2. Required to be red with white lettering – Must specifya. What device isb. How it is used
3. May be reset by firefighters or may require building owner, representative
C. Heat Detectors – Activate when temperature in monitored area reaches predetermined threshold
1. Fixed-temperaturea. Activate when heated to
temperature for which are rated
b. Installed in highest portions of rooms – Should have activation slightly above highest temperature normally expected
c. Least prone to false activations
d. Depending on installation location can be slowest to activate
e. Activation mechanisms
Fire Protection Publications Firefighter II 20-14Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
i. Expansion of heated material
ii. Melting of heated materialiii. Changes in resistance of
heated materialf. Fusible devices/frangible
bulbsi. Fusible link
(a)Metal strip held in place by solder with known melting temperature
(b)Device holds open spring-operated contact inside detector, when closed sends signal to FACP
ii. Frangible bulb(a)Holds electrical
contacts apart (b)Small glass vial holds
liquid with small air bubble – Designed to break when heated to predetermined temperature
(c) Manufacture has been discontinued; may still be in service
Fire Protection Publications Firefighter II 20-15Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
g. Continuous line detector – Detects heat over linear line parallel to detectori. Cable with conductive
metal inner core sheathed in tubing(a)Separated by
semiconductor material that keeps from touching – When current flow increases, signal is transmitted to FACP
(b)Restores itself when ambient temperature reached
ii. Two insulated wires with outer covering(a)When rated
temperature reached – Melts
(b)Wires complete circuit, send signal to FACP
(c) To restore, fused portion of wires must be cut out and replaced
h. Bimetallic detector i. Two metals with different
thermal expansion, bonded together; also attached to alarm circuit
Fire Protection Publications Firefighter II 20-16Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
ii. When heated – One expands faster, causing to arch; makes/breaks circuit, sends signal
iii. Most will reset automatically but must be inspected post-fire
Fire Protection Publications Firefighter II 20-17Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
2. Rate-of-rise heat detectors – Designed to initiate signal when rise in temperature exceeds 12°F to 15°F (7°C to 8°C) in one minute a. Benefits
i. Alarm can be initiated at temperature far below those required for fixed-temperature device
ii. Reliable, not subject to false activations
b. Pneumatic rate-of-rise line heat detectori. Used to monitor large
areas of building ii. System of pressurized
pneumatic tubing arranged over area of coverage
iii. Increased pressure of heated air activates alarm
c. Pneumatic rate-of-rise spot detectori. Same principle as line
heat detector ii. Spot is self-contained,
monitors specific locationd. Rate-compensated detector
Fire Protection Publications Firefighter II 20-18Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
i. Designed for areas normally subject to regular temperature changes slower than those under fire conditions
ii. System of two bowed struts that do not touch – When heated rapidly outer sleeve expands releasing tension, allowing to touch
e. Electronic spot-type heat detector – Uses system of thermistors that produce change in electrical resistance when exposed to heat
D. Smoke Detectors/Alarms
1. Both detect presence of smoke, other products of combustion
2. Detectorsa. Only capable of detection,
must transmit signal to another device that sounds alarm
b. In most cases, devices are installed in nonresidential and large multi-family residential occupancies
3. Alarms
Fire Protection Publications Firefighter II 20-19Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
a. Self-contained units capable of both detecting and sounding alarm
b. Typically installed in single-family residences, smaller multi-family residential occupancies
4. Smoke detector can initiate alarm more quickly than heat detector
5. Photoelectric smoke detectors – Also called visible products-of-combustion detectora. Works well on all types of
fires b. Usually responds more
quickly to smoldering fires than ionization-type
c. Automatically reset when conditions return to normal
d. Consist of photoelectric cell coupled with specific light sourcei. Projected-beam – Beam of
light focused across monitored area into cell; when beam obscured initiate alarm when current change threshold is reached
ii. Refractory application – Beam from light-emitting
Fire Protection Publications Firefighter II 20-20Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
diode passes through chamber at point away from light source; when light strikes particles device generates alarm signal
Fire Protection Publications Firefighter II 20-21Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
6. Ionization smoke detectorsa. Invisible products of
combustion detected by devices that use tiny amount of radioactive material to ionize molecules that enter chamber in detector
b. When air in chamber becomes less conductive, decrease in current transmits alarm-initiating signal
c. Generally respond faster to flaming than smoldering fires
d. Automatically reset when atmosphere cleared
7. Power sourcesa. Batteries or household
current can be usedb. Battery operated
i. Advantages – Easy installation, reliability
ii. Only as reliable as batteries used
c. Be aware of state/provincial, local laws that deal with smoke alarmsi. May designate power
source to be used
Fire Protection Publications Firefighter II 20-22Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
ii. Hard-wired systems may be required – Usually more reliable; except in areas with frequent power failures
E. Flame Detectors
1. Basic types – Detect light ina. Ultraviolet wave spectrum
(UV detectors) b. Infrared wave spectrum (IR
detectors)c. Light in ultraviolet and
infrared wave spectrums2. Among the fastest to respond to
fires3. Non-fire conditions may initiate
false activationsa. Located in areas where other
light sources unlikelyb. If blocked by opaque object,
will not activate4. Some single-band infrared (IR)
detectors sensitive to sunlight – Usually installed in fully enclosed area; require flicker motion to initiate alarm
5. Ultravioleta. Virtually insensitive to
sunlight
Fire Protection Publications Firefighter II 20-23Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
b. Can be used in areas not suitable for IR
c. Not suitable for areas where arc welding is done or where intense mercury-vapor lamps are used
F. Fire-Gas Detectors
1. Gases that may be released when fire burns in confined spacea. Released from all fires
i. Water vapor (H2O)ii. Carbon dioxide (CO2)iii. Carbon monoxide (CO)
b. Released based on chemical makeup of fueli. Hydrogen chloride (HCl)ii. Hydrogen cyanide (HCN)iii. Hydrogen fluoride (HF)iv. Hydrogen sulfide (H2S)
2. Initiate signal somewhat faster than heat detector, not as quickly as smoke detector
3. Can be designed to be sensitive to only gases produced by specific types of hostile fires; ignore those produced by friendly fires
Fire Protection Publications Firefighter II 20-24Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
G. Combination Detectors
1. Combine various systems into single device – Depends on design of system
2. Make detectors more versatile, responsive to fire conditions
Review Question: What are the major categories of alarm-initiating devices?See pp. 1184-1190 of the manual for answers.
Section III: Automatic Sprinkler Systems
III. AUTOMATIC SPRINKLER SYSTEMS
pp. 1194-1208 Objective 3 — Explain the ways automatic sprinkler systems work.A. Automatic Sprinkler Systems
1. Integrated system of pipes, sprinklers (sprinkler heads), control valvesa. Designed to activate during
fires byi. Discharging enough water
or extinguishing agent to extinguish fire
ii. Prevent fire spread until firefighters arrive
Fire Protection Publications Firefighter II 20-25Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
b. Systematically arranged to adequately distribute enough water or agent in protected area
c. May extend from exposed pipes, protrude through ceiling or walls from hidden pipes
2. Two general typesa. Complete coverage –
Protects entire buildingb. Partial coverage – Protects
only certain areasi. High-hazard areasii. Exit routesiii. Places designated by code
or AHJ3. Standards for primary design,
installation criteria in most occupanciesa. NFPA® 13, 13D, 13Rb. Include requirements on
i. Spacing of sprinklers in building
ii. Size of pipe to be usediii. Proper method of hanging
pipe
Fire Protection Publications Firefighter II 20-26Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
iv. All other details concerning installation of sprinkler system
c. Specify minimum design area that should be used to calculate system – Based oni. Maximum number of
sprinklers that might be expected to activate at one time
ii. Assumption that only portion of sprinklers will operate during fire
4. Failures generally not due to sprinklers – Other reasonsa. Partially or completely closed
main water control valveb. Interruption to municipal
water supplyc. Damaged or painted-
over sprinklersd. Frozen or broken pipese. Excess debris or
sediment in pipesf. Failure of secondary
water supplyg. Tampering, vandalismh. Sprinklers obstructed by
objects stacked too close
Fire Protection Publications Firefighter II 20-27Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
5. All components should be tested, certified by nationally recognized testing lab
6. Recognized as the most reliable of all fire protection devices
B. Effects of Sprinkler Systems on Life Safety
1. Safety greatly enhanceda. Discharges water directly
onto fire while still small – Products of combustion limited
b. Effective in preventing spread of fire upwards in multistory buildings, protecting lives of occupants in other parts of building
2. May not be effective when used alone in some situationsa. Fires are too small to
activate systemb. Smoke generation
reaches occupants before system activates
c. Building occupants are sleeping, handicapped, impaired, or incarcerated
3. Important to life safety of firefighters – Controlling fire in early stages increases safety of
Fire Protection Publications Firefighter II 20-28Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
environment during search and rescue, suppression activities
C. Sprinkler System Components
1. Starts with water main – Continues into control valve
2. Riser – Vertical piping to which components are attacheda. Sprinkler valveb. One-way check valvec. Fire department connection
(FDC)d. Alarm valvee. Main drainf. Other components
3. Feed main – Pipe connecting riser to cross mains
4. Cross mainsa. Directly service number of
branch lines on which sprinklers installed
b. Extend past last branch linesc. Capped to facilitate flushing
5. Piping decreases in size from riser outward
6. Entire system supported by hangers, clamps
Fire Protection Publications Firefighter II 20-29Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
7. Sprinklers – Fixed spray nozzles opened individuallya. Operates when heat-
responsive element activates, cap or plug opens allowing water discharge
b. Open type common in deluge systems
c. Early-suppression fast-response (ESFR) sprinkleri. React 5 to 10 times faster
than traditionalii. Quickly identified because
are larger than traditionald. Rated according to
temperature at which designed to operate – Identified in several waysi. Color-coding sprinkler
frame armsii. Color-coding liquid in
frangible bulb-type sprinklers
iii. Stamping temperature into sprinkler
e. Common release mechanisms – All open in response to heati. Fusible link
Fire Protection Publications Firefighter II 20-30Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
(a) Frame that is screwed into sprinkler piping
(b)Link melts under heat from fire releasing water
ii. Frangible bulb (a)Small bulb filled with
heat sensitive alcohol or glycerol liquid; air bubble to hold orifice shut
(b)Heat expands liquid until bulb shatters – Valve cap released, water flows
iii. Chemical pellet(a)Valve cap held in place
by plunger, small pellet made of solder
(b)Pellet melts releasing pressure, opening valve
8. Sprinkler deflectorsa. Attached to sprinkler frame,
create discharge pattern of water
b. Patterns vary depending on style, selected based on occupancy risk factors
Fire Protection Publications Firefighter II 20-31Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
c. Direct flow downward – Controls fire more quickly, protects structural elements effectively
d. Orientation typesi. Upright – Deflects spray
downward in hemispherical pattern; cannot be inverted; typically used in dry systems
ii. Pendant – Breaks water into circular pattern of small droplets directed downward; used where impractical or unsightly to use upright
iii. Sidewall – Discharges most of water to one side; used when necessary to install on wall at side of room or save space
iv. Concealed – Hidden by removable decorative cover that releases when exposed to specific heat level
v. Flush – Mounted in ceiling with body of sprinkler (including threaded shank) above plane of ceiling
Fire Protection Publications Firefighter II 20-32Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
vi. Recessed – Installed in housing within ceiling of compartment or space; all or part (other than threaded shank) in housing
vii.In-Rack – Incorporates protective disk that shields heat-sensing element from water discharged from sprinklers above
Fire Protection Publications Firefighter II 20-33Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
9. Sprinkler storagea. Cabinet location
i. Usually installed near riser, water control valve
ii. May be found in fire command center
b. Contain minimum – In accordance with NFPA® 13i. Six sprinklersii. Sprinkler wrench
c. Responsibility for changing depend on jurisdiction
10. Control valvesa. Every system has main water
control valveb. Used to stop supplying water
to system in order to replace sprinklers, perform maintenance, interrupt operations
c. Most are indicating valves, manually operated
d. Indicating valve types – Show at a glance if it is open or closedi. Outside stem and yoke
(OS&Y) – Yoke on outside with threaded stem;
Fire Protection Publications Firefighter II 20-34Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
threaded portion visible beyond yoke when open, not when closed
ii. Post indicator valve (PIV) – Hollow metal post houses valve stem; moveable plate with OPEN or SHUT visible through small glass window on side of housing; operating handle locked into valve housing when not in use
iii. Wall post indicator valve (WPIV) – Similar to PIV; extends horizontally through wall with target, valve operating nut outside of building
iv. Post indicator valve assembly (PIVA) – Uses circular disk inside flat plate on top of valve housing; perpendicular to plate when open, in line with when closed; operated by built-in crank
11. Operating valvesa. Alarm test valve
i. Located on pipe that connects supply side of alarm check valve to retard chamber
Fire Protection Publications Firefighter II 20-35Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
ii. Can be used to simulate actuation of system
b. Inspector’s test valvei. Located in remote part of
sprinkler systemii. Equipped with same size
orifice as one sprinkleriii. Used to simulate
activation of one sprinkleriv. Normally discharges
outside buildingc. Main drain valve – Primary
purpose to allow personnel to drain water from system for maintenance; may be used to check system water supply
NOTE: The water contained in sprinkler systems may be extremely dirty and contaminated. You should wear full PPE including eye protection when operating test valves or drains. Care should also be taken to direct the flow of water away from areas that can be damaged.
12. Waterflow alarmsa. Waterflow device initiates
alarm when water begins to flow in system
b. Consists of vane or paddle that protrudes into waterway
Fire Protection Publications Firefighter II 20-36Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
i. Connected to switch on outside of riser – Initiates alarm when vane moves
ii. Must be thin, pliable so can flatten against riser providing clear waterway
D. Water Supply
1. Minimum supply has to deliver required volume of water to highest sprinkler in building at pressure of 15 psi (105 kPa)a. Flow depends on hazard to
be protected, occupancy, building contents
b. Connection to public water system with adequate volume, pressure, reliability is good source of water
2. Fire pump typically incorporated into system to ensure adequate water volume, pressure during periods of demanda. Powered by electric, diesel,
or steam pump driverb. Activates when system
pressure falls below predetermined level
3. May be designed to only supply portion of sprinklers on system
4. Fire department pump connected to sprinkler fire
Fire Protection Publications Firefighter II 20-37Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
department connect (FDC) can provide additional water, pressure – Either a. Siamese inlet with at least
two 2½ inch (65 mm) female connections with clapper valve in each
b. One large-diameter connection attached to clappered inlet
5. Sprinkler FDCs should be supplieda. From pumpers with capacity
of at least 1,000 gpm (4 000 L/min) or greater
b. Attached to minimum of two 2½ inch (65 mm) or larger hoses
c. Pumpers should operate from hydrants connected to mains other than main supply when possible
6. Once in system – Passes through check valvea. Prevents water flowing from
system back into FDC – Allows flow from FDC to system
b. Proper flow direction usually indicated by arrow on valve or by observing appearance of valve casing
Fire Protection Publications Firefighter II 20-38Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
7. Departmental preincident plansa. May identify pressure at
which system should be supported, any special circumstances
b. Cannot be established until personnel are familiar with properties protected by systems
c. Plan of operation should cover buildings in jurisdiction, type of occupancy, system, extent of system
Review Question: What are the fundamental aspects of a sprinkler system?See pp. 1194-1203 of the manual for answers.
E. Types of Sprinkler Systems
1. Wet-pipe systems – Also known as straight sticka. Used in locations where
temperatures remain above 40°F (4°C)
b. Simplest type – Generally requires little maintenance
c. Contains water under pressure at all times
d. Connected to public or private water supply so will
Fire Protection Publications Firefighter II 20-39Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
immediately discharge water spray, activate alarm
e. Includes i. Minimum – Alarm valve,
OS&Y valve, fire department connection
ii. May also have – Electronic waterflow alarm
f. May be equipped with retard chamber as part of check valve – Catches excess water sent during momentary water pressure surges
2. Dry-pipe systemsa. Used in locations where
piping may be subjected to temperatures below 40°F (4°C)
b. All pipes are pitched to help drain water back toward main drain
c. Air or nitrogen under pressure replaces water in sprinkler above dry-pipe valve – Air escapes first when sprinkler activates
d. Have larger surface area on air side of clapper than water side
Fire Protection Publications Firefighter II 20-40Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
e. Required air pressure – Usually about 20 psi (140 kPa) above trip pressure
f. Normally air pressure gauge reads at pressure lower than water-pressure – If gauges read same then system tripped, water has entered pipes
g. Valve must be located in heated area of structure maintained at temperature of 40°F (4°C) or greater
h. Equipped with either electric or hydraulic alarm-signaling equipment
i. In large system – May take several minutes to expel airi. Quick-opening device
required in systems with over 5000 gallon (2 000 L) capacity
ii. Accelerator – Redirects system air to accelerate opening of dry-pipe valve
iii. Exhauster – Expel air from system quickly
3. Deluge systemsa. No water in piping before
activation
Fire Protection Publications Firefighter II 20-41Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
b. All sprinklers open all the time (also known as open-head sprinklers)
c. Deluge valve controls flow into system – Controlled by fire detection devices
d. Designed to quickly supply large volume of water to protected area
e. Variationsi. Partial deluge system –
Some sprinklers open while others are not
ii. Water curtain system – Designed to provide exposure protection
4. Preaction systemsa. Dry systems that employ
deluge-type valve, fire detection devices, closed sprinklers
b. Used when especially important to prevent water damage – Even if pipes broken
c. Will not discharge water into piping except in response to smoke- or heat-detection system actuation
Fire Protection Publications Firefighter II 20-42Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
i. Opens release switch located in system actuation unit
ii. Opens deluge valve – Water only discharges through activated sprinklers
5. Special extinguishing systemsa. Use extinguishing agents
other than water – Unique to application in specific occupancies
b. Typesi. Wet chemicalii. Dry chemicaliii. Clean-agentiv. Carbon dioxidev. Water-mist, hybrid
systemsvi. Foam
6. Residential systemsa. Design
i. Prevent flashover in room of fire origin
ii. Improve chance for occupants to escape or be evacuated
Fire Protection Publications Firefighter II 20-43Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
iii. For one- and two-family dwellings
iv. Smaller, more economical than commercial systems
v. Generally supplied by domestic water supply
b. Changes in design, operation, water supply, flow requirementsi. Modification of sprinkler
design, development of fast-response residential sprinklers
ii. Minimum flow requirements of 18 gpm (68 L/min) from individual sprinkler
iii. Alarms are simpler, better designed for residential applications
c. Differences between residential and standardi. Sensitivity, speed of
operation – Residential operates more quickly; fusible link activates when ceiling temperature reaches 165°F (74°C)
ii. Coverage not as extensive – Will vary depending on local codes
Fire Protection Publications Firefighter II 20-44Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
iii. Designed to discharge water higher on walls of room
iv. Installed with variety of materials not found in commercial – Piping may be multipurpose or combination
d. Must be continually in service – One valve should control both sprinklers, domestic water service for residence
e. Water supply sourcesi. Connection to public
water system – Very reliable; usually provides adequate volume
ii. On-site pressure tank – Often found at rural homes that do not have public water service
iii. Storage tank with automatic pump – May be found at rural homes or large homes in urban areas where public system must be augmented for size; may also need fire pump
Review Question: How do the application methods for sprinkler systems differ?
Fire Protection Publications Firefighter II 20-45Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
See pp. 1203-1208 of the manual for answers.
Section IV: Standpipe and Hose Systems
IV. STANDPIPE AND HOSE SYSTEMS
pp. 1208-1212 Objective 4 — Describe standpipe and hose systems.A. Standpipe and Hose Systems
1. Designed to provide means for rapidly deploying fire hoses, operating fire streams at locations remote from fire apparatus
2. Value a. In large area one-story
structures – Reduces time, effort needed to manually advance hoseline to reach seat of fire
b. During overhaul – Reduce amount of hose need to reach areas already controlled by sprinklers
c. In high-rise buildings – Primary means for manual extinguishment, overhaul of fire; essential in building design
Fire Protection Publications Firefighter II 20-46Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
3. May be operated by firefighters or residents – Depending on design
4. Water supply may be provided by fire department or augmented with FDC
5. May be part of or separate from automatic sprinkler, water spray, water mist, or foam-water system
6. Do not take the place or lessen need for automatic sprinkler systems
B. Components and Classifications of Standpipe Systems
1. Componentsa. Hose stations b. Water supplyc. Waterflow control valves d. Risers e. Pressure-regulating devices f. FDC
2. NFPA® Standardsa. 14 – Describes design,
installation; establishes three classes based on intended use
Fire Protection Publications Firefighter II 20-47Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
b. 13 – Contains information on hose stations
3. Class Ia. Primarily used by personnel
trained in handling large hoselines
b. Must be capable of supplying effective fire streams during advanced stages of fire within building
c. Provides 2½ inch (65 mm) hose connections or stations attached to standpipe riser
d. May be equipped with reducer on cap that allows connection of 1½ inch (38 mm) hose coupling
4. Class IIa. Designed for use by trained
building occupants or fire department personnel
b. Equipped with 1½ inch (38 mm) hose, nozzle; stored on hose rack system
c. Hose typically single-jacket type, equipped with lightweight, twist-type shut-off nozzle
d. May be referred to as house lines
Fire Protection Publications Firefighter II 20-48Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
e. May give occupants false sense of security
5. Class IIIa. Provide 1½ inch (38 mm)
hose stations to supply water for use by trained building occupants; 2½ inch (65 mm) hose for use by fire departments, those trained in heavy fire streams
b. Must allow both Class I, Class II services to be used simultaneously
C. Types of Standpipe Systems
1. Automatic weta. Contains water at all times b. Water supply capable of
meeting system demand automatically
c. Water-supply control valve open, pressure maintained in system at all times.
d. Cannot be used in cold environments
2. Automatic drya. Contains air under pressure
to maintain integrity of piping
Fire Protection Publications Firefighter II 20-49Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
b. Water is admitted to system through dry-pipe valve upon opening of hose valve
c. Have permanently attached water supply
d. Disadvantage of greater cost, maintenance requirements
3. Semiautomatic dry a. System attached to water
supply capable of supplying system demand at all times
b. Requires activation of control device to provide water at hose connections
c. Designed to admit water into system when dry-pipe valve is activated at hose station
4. Manual dry – Does not have permanent water supply; designed to have water only when system is being supplied through FDC
5. Manual wet a. Maintained full of water but
has no water supply b. Water is maintained to
identify leaksc. Fire department must
provide water to system
Fire Protection Publications Firefighter II 20-50Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
Review Question: How are standpipe systems classified?See pp. 1209-1211 of the manual for answers.
Fire Protection Publications Firefighter II 20-51Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
Section V: Smoke Management Systems
V. SMOKE MANAGEMENT SYSTEMS
pp. 1213-1215 Objective 5 — Explain the ways smoke management systems work.A. Smoke Management Systems
1. Purpose – Remove smoke and/or control spread
2. May reduce a. Injuries, fatalities due to
smoke inhalationb. Property losses due to smoke
damage3. Functions
a. Maintaining tenable environment in area of egress during time required for evacuation
b. Controlling, reducing migration of smoke from fire area
c. Providing conditions outside the fire zone that will assist emergency response personnel in conducting search-and-rescue operations; also assist in locating, controlling fire
Fire Protection Publications Firefighter II 20-52Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
d. Contributing to protection of life, reduction of property loss
4. Includesa. Compartmentationb. Pressurizationc. Exhaustiond. Ejectione. Dilutionf. Buoyance elementsg. Smoke barriersh. Exhaust fans, vents
5. Smoke control – Any effort to change pressure in spaces adjacent to fire area or to compartmentalize, exhaust smoke from area of origin
B. Smoke Control Strategies
1. Different strategiesa. Passive (compartmentation)b. Pressurizationc. Zonedd. Dilutione. Exhaustf. Opposed airflow
Fire Protection Publications Firefighter II 20-53Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
2. Dedicated smoke control systems – Intended, specifically listed for smoke control purposesa. Allow for separate air
movement, distribution; do not function under normal operating conditions, only when activated
b. Advantagesi. Operation, control
generally simpler than other systems
ii. Modification of controls during system maintenance is less likely to occur
iii. Is less likely to be affected by modification or failures of other building systems
3. Non-dedicated – Those that share components with other systemsa. Activation causes to change
mode of operation from heating-cooling to smoke control
b. Advantagesi. Less chance for
component failure due to regular use, maintenance
Fire Protection Publications Firefighter II 20-54Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
ii. Lower costiii. Less space needed for
mechanical equipmentc. Disadvantages
i. Elaborate nature of system control, possibility of modification that might affect function
ii. All features may not be exercised in day-to-day operations
C. Types of Smoke Control Systems and Methods
1. Passive systemsa. Barriers with sufficient fire
endurance to provide protection against fire spread
b. Examples – Fire stops around barrier penetrations; door gasket, drop seals; stair, elevator vestibules; smoke dampers in HVAC ductwork; automatic door devices
2. Pressurization systemsa. Use mechanical fans,
ventilation to create pressure difference across barrier – Prevent smoke from infiltrating into high-pressure side
Fire Protection Publications Firefighter II 20-55Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
b. Both positive, negative pressure used
c. Must be designed to not impede safe egress
3. Zoned smoke controla. Designed to limit movement
of smoke from one compartment of building to another
b. Building divided into zones – During fire mechanical fans used to contain smoke in zone of fire origini. Each floor may be
separate smoke control zone
ii. Zone can be multiple floors or division of single floor
iii. All nonsmoke zones or those adjacent to fire may be pressurized
4. Dilutiona. Systems may be designed to
dilute contaminantsb. Fresh air dilutes to
acceptable level for breathing
5. Exhaust method
Fire Protection Publications Firefighter II 20-56Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
a. Uses mechanical ventilation along with properties of smoke to collect smoke at highest point in large space
b. Should allow smoke to be maintained at level of 6 to 10 feet (2 m to 3 m) above highest occupied floor
Fire Protection Publications Firefighter II 20-57Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
6. Opposed airflow methoda. Used in large spaces where
smoke migration is limited by opposed airflow
b. High velocity air aimed at area of origin keeps smoke from migrating into unaffected areas
c. Must not result in airflow toward fire
d. Used in – Subway, railroad, highway tunnels
D. Firefighters’ Smoke Control Station (FSCS)
1. Provides full monitoring, manual control of all smoke control systems, equipment
2. Can be used to control all smoke control equipment or zones – When practical should allow control of individual zones
3. Should be located in Fire Command Center or other location approved by AHJ
4. Only authorized individuals should have access
5. Should contain building diagram a. Clearly indicate location of all
smoke control equipment, as well as areas affected
Fire Protection Publications Firefighter II 20-58Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
b. Status of systems, equipment should be clearly indicated
6. Manual override switches should be provided to restart or shut down operation of equipment
Review Question: What types of smoke control systems can be used at an incident?See pp. 1213-1215 of the manual for answers.
Section VI: Summary and Review
VI. SUMMARY AND REVIEWA. Chapter Summary
1. Many buildings are protected, partially or fully, by fire protection systems that range from simple to complex.
2. These systems can perform a variety of functions and it is important that these are identified during preincident surveys to ensure firefighters understand how to operate in these structures.
B. Review Questions
1. What are the basic components of an alarm system? (1178-1182)
Fire Protection Publications Firefighter II 20-59Oklahoma State University
Essentials of Fire Fighting, 6th Edition Fire Protection Systems
2. How do protected premises and station alarm systems differ? (1182-1184)
3. What are the major categories of alarm-initiating devices? (1184-1194)
4. What are the fundamental aspects of a sprinkler system? (1194-1203)
5. How do the application methods for sprinkler systems differ? (1203-1208)
6. How are standpipe systems classified? (1209-1211)
7. What types of smoke control systems can be used at an incident? (1213-1215)