EXTERNAL STATIC PRESSURE CALCULATION Project : MSE Hotel Location : Roof Floor Job No Ref :TX/8/17 (Toilet Extract Date : :24/06/2013 Drawing No Rev : 0 Sl No Eq. length EA DUCT 1 200x150 126 3 1.545 4.635 2 Total Length 20 1.545 30.90 Sub Total 35.54 Add 30 % for fittings like Elbows, collars, vanes etc 10.66 3 Fire Damper 15 4 Diffuser 35 TOTAL 131.73 Rectangular Duct Size (mm) Air Qty (Lps) Pr. Drop (Pa/m) Total Pr. Drop (Pa)

description

ESP CALCULATION

Transcript of ESP calculation for EXTRACT FANS 4STAR .xls

Page 1: ESP calculation for EXTRACT FANS  4STAR .xls

EXTERNAL STATIC PRESSURE CALCULATION

Project : MSE Hotel Location : Roof FloorJob No Ref :TX/8/17 (Toilet Extract Fan)Date : :24/06/2013 Drawing NoRev : 0

Sl No Eq. length RemarksEA DUCT

1 200x150 126 3 1.545 4.6352 Total Length 20 1.545 30.90

Sub Total 35.54Add 30 % for fittings like Elbows, collars, vanes etc 10.66

3 Fire Damper 154 Diffuser 35

TOTAL 131.73

Rectangular Duct Size (mm)

Air Qty (Lps)

Pr. Drop (Pa/m)

Total Pr. Drop (Pa)

Page 2: ESP calculation for EXTRACT FANS  4STAR .xls

EXTERNAL STATIC PRESSURE CALCULATION

Project : MSE Hotel Location : Roof FloorJob No Ref :KX/8/11 (Kitchen Extract Fan)Date : :24/06/2013 Drawing NoRev : 0

Sl No Eq. length RemarksEA DUCT

1 250x200 240 3 1.435 4.3052 Total Length 25 1.435 35.88

Sub Total 40.18Add 30 % for fittings like Elbows, collars, vanes etc 12.05

3 Fire Damper 154 Diffuser 355 Kitchen Hood Details Not Available

TOTAL 142.41

Rectangular Duct Size (mm)

Air Qty (Lps)

Pr. Drop (Pa/m)

Total Pr. Drop (Pa)