Product Specification 03250 ESDR 4T Current Differential Relay APPLICATIONS The ESDR 4T unit offers three-phase current differential protection for generators, motors and transformers in unit connection. Current transformers at both sides of the protection object(s) measure the individual conductor currents. Any two-phases of three-phase short circuits and earth leakages are recognized by the ESDR 4T as fault currents. The ESDR 4T affords design simplification of the switchgear cabinet, facilitates the commissioning, ensures the operation of the system is user friendly and increases the availability of the system. DESCRIPTION ESDR 4T functions & features include: 6 x I measurement, 3-phase system at both sides of the protected zone Microprocessor based design. Transformer ratio of the measuring CT for every primary value separately adjustable. Adjustable transformer ratio of the transformer Minimal command time: 40 ms Selectable transformer vector group. 4 programmable relays outputs 4 metallically separated discrete inputs for blocking and remote acknowledgement. An internal test routine monitors cyclically the readiness for operation 5 mm LCD display (green illuminated) ESDR 4T Protective Functions ANSI # Generator current differential 87G Block current differential 87GT Motor current differential 87M Restraint current protection 10 bit measuring 3-phase Current differential protection Configurable transformer ratio for transformer Configurable CT ratio for measuring transformer Selectable vector group for transformer phase shift Digital input for blocking or remote acknowledgement Discrete Out permissive PC configurable and Front panel configurable Microprocessor technology for accurate, repeatable and reliable operation Programmable relay outputs Example: Generator / transformer Block protection Monitoring Differential Current Protection ON Alarm Is Ia Ib + 2 = Ia Ib Id= Protected Object Ia Ib [ ] Operating and Alarm Messages L1 L2 L3 Release Variable Release Characteristic X Y 10% I d N I I s N I Lock Is Id GCB G ESDR 4 Block Protection

Transcript of ESDR 4T.pdf

  • Product Specification

    03250

    ESDR 4T Current

    Differential Relay

    APPLICATIONS

    The ESDR 4T unit offers three-phase current differential protection for generators, motors and transformers in unit connection.

    Current transformers at both sides of the protection object(s) measure the individual conductor currents.

    Any two-phases of three-phase short circuits and earth leakages are recognized by the ESDR 4T as fault currents.

    The ESDR 4T affords design simplification of the switchgear cabinet, facilitates the commissioning, ensures the operation of the system is user friendly and increases the availability of the system.

    DESCRIPTION

    ESDR 4T functions & features include: 6 x I measurement, 3-phase

    system at both sides of the protected zone

    Microprocessor based design. Transformer ratio of the measuring

    CT for every primary value separately adjustable.

    Adjustable transformer ratio of the transformer

    Minimal command time: 40 ms Selectable transformer vector

    group. 4 programmable relays outputs 4 metallically separated discrete

    inputs for blocking and remote acknowledgement.

    An internal test routine monitors cyclically the readiness for operation

    5 mm LCD display (green illuminated)

    ESDR 4T

    Protective Functions ANSI #

    Generator current differential 87G Block current differential 87GT Motor current differential 87M Restraint current protection

    10 bit measuring

    3-phase Current differential protection

    Configurable transformer ratio for transformer

    Configurable CT ratio for measuring transformer

    Selectable vector group for transformer phase shift

    Digital input for blocking or remote acknowledgement

    Discrete Out permissive

    PC configurable and Front panel configurable

    Microprocessor technology for accurate, repeatable and reliable operation

    Programmable relay outputs

    Example: Generator / transformer Block protection

    Monitoring

    Differential CurrentProtection

    ON

    Alarm

    IsIa Ib+

    2=

    Ia IbId =

    ProtectedObject

    Ia Ib

    [ ]

    Operating and Alarm Messages

    L1 L2 L3

    Release

    Variable Release Characteristic

    X

    Y

    10%

    IdNI

    IsNI

    Lock

    Is

    Id

    GCB

    G

    ESDR 4 Block Protection

  • PART NUMBERS AND OPTION PACKAGES

    ESDR 4T 5448-897

    TRIPPING CHARACTERISTIC

    Monitoring step 1(X12 = 100 % / Y1 = 10 %)

    Monitoring step 2(X12 = 100 % / Y2 = 35 %)

    Protectedobject

    100 200

    Characteristic gradient = 10 %

    Monitoring step 2, fixed limit (100 %)

    X12, Y2 and Y1: adjustable

    NI

    100

    P (X12/Y2)

    P (X12/Y1)

    Y =Id [%]

    aI

    300 400

    2000-12-08ESDR 4T Auslsekennlinie e4tleo-5000-kenn.skf

    500

    S

    I[%]I

    N

    X =

    -+ IbaIb

    I =I

    S II=I bad2

    Monitoring step 1fixed limit(85 %-Y2+Y1)

    Monitoring step 2fixed limit (85 %)

    1

    21 2=

    35

    10

  • DIMENSIONS

    27

    1

    34

    35

    36

    63

    28

    29

    30

    31

    32

    33

    42

    50

    65.0

    55.8

    4.0

    4.6

    46.5

    4.0

    14

    3.

    0

    50.0

    Leonhard - ReglerbauStuttgart

    24

    variable release characteristic

    Section A

    operation and error messages

    I

    25

    26

    37

    38

    39

    40

    41

    Y

    N

    d

    I

    X

    10 %release

    lock

    Id

    ISL1

    bad

    4.0

    IN

    IS

    error

    ONmonitoring

    select digit

    message display

    4.0

    cursor

    clear

    differential currentprotection

    protectedobject

    I=I

    L2

    Ia=IS

    Ia

    [ ]L3ESDR 4

    I-

    +2

    bI

    bI

    180.0

    132.0A

    8.0

    14

    4.

    0

    110.045.0

    16.5

    A Mounting clamp

    Snapp track mounting

    72.0

    SPECIFICATIONS

    Measuring current .............................. /1 A or../5 A Measuring frequency.............................. 4070 Hz Power supply................................. 24 Vdc (25 %) Power consumption ................................ max. 6 W Ambient temperature ............................ -2070 C Ambient humidity................. 95%, non-condensing

    Measuring input current.. consumption < 0.15 VA Current-carrying capacity...................... 5.0 IN Rated short-time current (1 s)100.0 IN (for 1 s) ........................................ 30.0 IN (for 10 s) Accuracy ............................... maximal 1 % IN Reference voltage............................... 0.15 % Max. temperature deviation .............. 12 ppm/K

    Digital inputs ..................... metallically separated Insulation voltage ............................... 2200 Veff Input range......................... 18250 V (dc or ac) Input resistance....................................... 68 kW

    Potential free outputs .... contact material: AgCdO Electrical life cycle (ohmic load) .................................

    ................. min. 100.000 cycles at 2 A / 250 Vac

    Load................. max. 2 A at 250 Vac or 24 Vdc Max. switching voltage ........................ 250 Vac Insulation voltage................................ 2200 Veff Switching capacity DC............................. 45 W

    Protection functions............................................................................ minimum command time 40 ms

    Housing ................ type APRANORM DIN 43 700 Dimensions (snap-on rail) . 144 72 199 mm Dimensions (front) ............. 144 72 162 mm Front cutout ...................................138 67 mm Connection ............ screw terminals depending ......... on plug connector 2,5 mm or 4 mm

    Front foil .................................... insulated surface

    Protection system .................... IP 21, front IP 54 Weight ......... depending on model, ca. 1,000 g

    Disturbance test ......................................... (CE)........ tested according to applicable EN guidelines

  • Woodward Industrial Controls PO Box 1519 Fort Collins CO, USA

    80522-1519 1000 East Drake Road Fort Collins CO 80525 Ph: +1 (970) 482-5811 Fax: +1 (970) 498-3058 Distributors & Service Woodward has an international network of distributors and service facilities. For your nearest representative, call the Fort Collins plant or see the Worldwide Directory on our website. Corporate Headquarters Rockford IL, USA Ph: +1 (815) 877-7441 www.woodward.com This document is distributed for informational purposes only. It is not to be construed as creating or becoming part of any Woodward Governor Company contractual or warranty obligation unless expressly stated in a written sales contract. Woodward Governor Company, 2001 All Rights Reserved

    TYPICAL APPLICATIONS