Esbed297701en (Web)

download Esbed297701en (Web)

of 46

Transcript of Esbed297701en (Web)

  • http://www.panelbuilders.schneider-electric.com

    Solution guide2011

    BloksetHigh dependability and low voltage switchboard

  • Presentation 2Solution overview 10

    Functional units 15

    Cubicles 28

    Example 38

    Installation 40

    Blokset performances 42

    1

    Contents

  • 2Presentation Fields of applicationsRequirements and solutions

    Refinery, gas, petrochemical

    Mines, metallurgy, cement works

    Food-processing

    Requirements Continuity of supply and safety

    Environment and safety Avaibility and performance

    Solutions > Intelligence in the motor control and the electrical distribution.> Dependability.> Rapid restarting after an incident.> Internal arc protection.

    > Specific anti-corrosion treatment on conductive parts.> Tightness ensured by IP54 guaranteed parts.

    > Tightness ensured by IP54 elements.> Fault prevention by intelligent motor control centers (iMCC).

    Infrastructure, tunnel, subway

    Water treatment

    Requirements Continuity of supply and safety

    Continuity of supply and environment

    Solutions > Internal arc protection.> Withdrawable solutions

    > Feeders on fix or withdrawable systems.> Specific anti-corrosion treatment on conductive parts.

  • 3Presentation Fields of applicationsFunctions

    High power incomings Electrical distribution Power factor compensation

    Motor control Variable speed drive

    and soft starters

  • Intelligent solutions for fast and easy access to information from anywhere, around the clock

    Information for local operation, maintenance and upgrading of your installation Information on electrical distribution, motor operation and power consumption can be accessed.

    > MotorSys iPMCC solutions can integrate a dedicated human-machine interface (HMI) or communicate via a personal computer directly on the motor starters.

    2

    Our MotorSys iPMCC solutions help your teams optimise the energy efficiency of your assets, offering the following benefits:

    bDependability, even in severe industrial environments, b Safety of personnel

    and assets, maintainability and upgradability, b Lead time management

    and risk as well as cost reduction throughout your installation's entire lifecycle.

    Remote control and monitoring of your installationA continuous, real-time communication interface with your control and monitoring systems for energy management and process control.

    > MotorSys iPMCC solutions communicate with the major industrial local area networks on the market (Ethernet TCP/IP, Profibus-DP, DeviceNet, Modbus, etc.).> With data delivered in real time, your operational and maintenance staff will have immediate access to the relevant information to control your motors and electrical distribution locally or remotely.> Warning messages can be sent automatically to a mobile phone in the event of an alarm or group of alarms.

    1

    Our MotorSys iPMCC solutions for continuous and critical processes were developed through our specific expertise in energy and industrial process control management. Forming the keystone of the energy efficiency of your process units, they incorporate a range of functions to supply power (intelligent Power Control Centre - iPCC), start up, control, protect and monitor your LV network electric motors and loads (intelligent Motor Control Centre - iMCC). The breadth of the range ensures that all types of continuous and critical process as well as specific requirements are covered.

    1

    4

    Presentation Blokset solutionMotor Sys intelligent Power & Motor Control Center (iPMCC)

  • MotorSysTM iPMCC

    solutions integrate

    perfectly into your site

    network infrastructure,

    whatever the

    communication

    protocol, but also into

    energy management

    control systems

    and process

    control systems

    Example of a MotorSysTM iPMCC solution integrated into a site infrastructure

    Information for site engineeringWith information delivered to ensure the traceability of electrical distribution, motor operation and power consumption data, installations are constantly improved.

    > MotorSys iPMCC solutions make it easy to collect all the statistics you need to develop effective plans covering the operation, maintenance, optimisation and upgrading of your installations, as well as energy efficiency.

    3

    3

    2

    5

    Presentation Blokset solutionMotor Sys intelligent Power & Motor Control Center (iPMCC)

  • 6Presentation Blokset solutionInnovation

    Mw2 cubicles

    Draw-in b The functional unit is operational. b Power and auxiliaries are connected.

    Test b The functional unit is not operational. b Only auxiliaries are connected. b Padlocking is possible to keep the drawer in this position. b Allows the functional unit testing. b Allows maintenance on the process.

    Draw out b The functional unit is not operational. b Power and auxiliaries are disconnected. b Padlocking is possible to keep the drawer in this position. b Allows maintenance on the process.

    Withdrawn b The drawer can be fully extracted. b Allows quick replacement. b Allows switchboard live change. b Padlocking is possible on the fixed part.

    Drawers operation is very simple. Using the indexing pushbutton, the operator can simply move the drawer in the draw-in, test, draw-out positions. Each position are mechanically marked with a mechanical indicator on the drawer sides.

    Drawer positions

    Distribution busbar

    Installed in a partitioned compartment at the rear of the drawers area, it consists of 8 mm thick bars whose cross-section depend upon the current to be distributed in the cubicle.

    The distribution busbar system can be single or double. The architecture depends on the electrical performance and on the functional unit size (full width or half width).

    The distribution busbar is extremely safe: the tap-off outlets make the busbar unaccessible to operators. Tap-off outlets open and close when the functional unit moves between connected and test position.

    Up to 630 A, functional units are directly connected to the vertical busbar.

    In double busbar architecture, the current flow is balanced in both vertical busbars thanks to the link system.

    Schneide

    r Electric

    patent

  • 7Presentation Blokset solutionInnovation

    Auxiliaries connection

    Schneide

    r Electric

    patent

    The innovative mechanism guarantees the auxiliary contacts to be connected: b from the test position when the drawer is drawn in, b to the test position when the drawer is drawn out.

  • 8Presentation Blokset solutionImplementation

    Reliability and flexibility> The switchboards are type tested assemblies. They have a complete electrical and mechanical inspection in factory.> The modularity of the cubicle makes the installation of a new functional unit easy.

    Continuity of supply> Withdrawable feeders for quick maintenance operations.> Schneider Electric devices association guarantees the continuity of supply.

    Safety of people and equipments> Internal arc protection, in compliance with the requirements of the international regulations (technical reports IEC 61641).> Continuity of supply guaranteed by limitation of harmful effects of the internal arc in the switchboard.> Quick repair of the area where the arc was confined.> Safety of people and equipment guaranteed during the occurrence of the fault.> Insulated busbars prevents flashover and propagation of the arc.

    Withstand to the most demanding environments> The conductive parts treated against corrosive atmospheres (according to IEC 721-3-3 standard).> IP54 tightness for the dusty and / or damp environments.> Earthquake safety versions*.> Forced ventilation for environments with ambient temperatures exceeding 45 C or for devices with high heat loss.

    * consult us for spectrum analysis

    Type tested

    Blokset is totally type-tested in accordance with CEI 60439-1 and 61439-2 Certified by independant labs: LOVAG, ASEFA and KEMA. As well as by a permanent control in Schneider Electric test laboratories. Type-tests carried out:o temperature-rise limit,o dielectric properties,o short-circuit withstand,o effectiveness of the protective circuit,o conformity of the clearance and creepage distances,o mechanical operation,o degree of protection.

  • 9Available forms 2b 3b 4a 4bBusbars / fonctional units separation b b b b

    Busbars / terminal blocks(1) separation for external conductors b b b b

    Separation between functional units - b b b

    Separation between terminal blocks(1) for external conductors - - b b

    Terminal blocks separation for external conductors / functional units - - - b(1) They are integral part of the functional unit.

    Presentation Blokset solutionImplementation

    3 specific compliances

    StandardFor all applications.

    Earthquake safetyFor seismic zones up to Richter 9.

    2 levels of safety against internal arc

    Cubicle partitioningProtective screens (side partition + vertical busbar screen) prevent tracking of an arc in the cubicle.

    Type-tested solutionAt functional unit level, the drawers are type tested against internal arc at both broken unit sides.

    3 levels of service

    Operation

    FFF WWWShutting down only the concerned functional unit. Shutting down only the concerned functional unit, but test

    of the control system possible before the resumed operation.

    MaintenanceShutting down the whole switchboard. Shutting down only the concerned functional unit without

    connections handlings.

    EvolutionShutting down the whole switchboard. Addition of a functional unit without shutting down the

    switchboard, free addition in non-equiped spare slots.

    4 levels of functional unit (FU) partitioning

    Service Index

    IndustryInternal arc protection

  • 10

    Solution overview PCC device cubicles

    y 630A

    > 630A

    Type of cubicle

    In distribution busbar

    Incomers

    Feeders

    Very high power

    incomers/feede

    rs

    cubicle

    Dis

    trib

    utio

    n

    D

    4000/5700 A

    NW40b/63b

    NW40b/63b

    -

    D

    3000/3600 A

    NW40/NW32/NS3200

    NW40 /NW32/ NS3200

    -

    High power

    incomers/feede

    rs

    cubicle

  • 11

    D

    800/3300 A

    NW08-25 /NT06-16/NS630b-2500

    NW08-25/NT06-16/NS630b-2500

    -

    High power

    incomers/feede

    rs

    cubicleIncomer

    s/feeders

    cubicle

    D

    800/3300 A

    NW08-25/NT06-16/NS630b-2500

    NW08-25/NT06-16/NS630b-2500

    C60/EZC100/NSX100-630/

    NS100L/NS400L

    DC

    800/3300 A

    -

    -

    Power factor

    correction

    Power factor

    correction

    Solution overview PCC device cubicles

  • 12

    Solution overview

    Type of cubicle

    In distribution busbar

    Incomers

    Feeders

    MCC device cubicles

    Ms

    800/3300 A

    -

    b fixed mounting plates VSD y 55 kW b fixed mounting plates SS y 250 kW

    Mf

    800/3300 A

    -

    b fixed mounting plate y 250 kW

    Variable speed

    drive & soft

    starter cubicle

    Feeders cubicle

    MC

    C

  • 13

    Optimized for

    MCC drawers

    Mw2

    400/2000 A

    -

    b drawer y 250 kW

    Blokset Mw2For MCC application drawers, Mw2 is an optimized solution, robust, reliable and secure.The Mw2 satisfy the motor control needs of the most demanding processes.

    Solution overview MCC device cubicles

  • 14

    Feeders Service IndexFunctional units

    The switchboard must permit

    The applications continuity of service is:

    Making the right choice

    FFFSetting, padlocking may disturb remaining part of switchgear

    FFFSwitchgear shut down shall be foreseen

    FFFSwitchgear extension is only possible when shut down

    DDDFunctional unit shut down possible without disturbnce on the remaining parts

    DDDFunctional unit shut down possible with no operation on cablesFunctional unit replacement in a short time

    DDD-

    WWWFunctional unit shut down possible without disturbance on the remaining parts Test position offered ith power disconnected

    WWWFunctional unit shut down possible with no operation on cablesFunctional unit replacement in a short time

    WWW-

    OperationSetting

    Padlocking

    MaintenanceCheckingCleaningRepairing

    EvolutionAddition

    ModificationExpansion

    Expected

    Not required

    Mandatory

    p p pComposition

    3rd letter: auxiliaries connection (coils, contacts, )

    2nd letter: Power downstream connection

    1st letter: Power upstream connection

    Letters and signification

    FFF Connection is fixed

    DDD Connection is deconnectable

    WWW Connection is withdrawable

    Blokset offers several options to answer the installation needs and the service continuity required.FFF power upstream and downstream connections are fixed, auxiliaries are fixed.DDD power upstream and downstream connections are disconnectable, auxiliaries are disconnectable.WWW power upstream and downstream connections are withdrawable, auxiliaries is withdrawable.

  • 15

    Fixed on mounting plate

    fixed device

    Main functional units typesFunctional units

    MCC drawers

    Mw2 half width drawer

    Mw2 full width drawer

    PCC drawers

    Mw2 full width drawer

    Drawer

    height

    250

    200

    110

    75

    45

    30

    18.5

    15

    KW

    2 modules

    (100 mm)

    4 modules

    (200 mm)

    6 modules

    (300 mm)

    8 modules

    (400 mm)

    10 modules

    (500 mm)

    12 modules

    (600 mm)

    Half size

    Full size

    Full size

    Full size

    Full size

    Full size

    Full size

    Half size

    MCC drawer sizes

    Drawer

    size

    630

    400

    160

    125

    100

    57

    25

    In (A)

    2 modules

    (100 mm)

    4 modules

    (200 mm)

    6 modules

    (300 mm)

    8 modules

    (400 mm)

    Half width

    Full width

    Full width

    Full width

    Half width

    C60

    NG125

    NSX100

    NSX160

    NG125

    NSX100

    NSX250

    NSX400-630

    PCC drawer sizes

    device on base

  • 16

    Functional units Electrical distributionIn > 630 A

    Selection of the functional unit - rated 415 V - 50 / 60 Hz - IP31 / 35 CIn (A) Icw max (kA) Max. qty of circuit breakers

    per cubicleType of circuit breaker Cubicle In distribution

    busbar (A)4000 < In < 5700 100 1 NW40b-63b

    type D3000 < In < 3600 85 / 100

    8585

    111

    NW40NW32NS3200

    type D800 < In < 3300 85

    858585

    2322

    NW20-25NW16NS2000 - NS2500NS1600bNS630bNT06-16

    type D

    3200

    800 < In < 1600 8550 / 8550 / 85

    42 / 85

    346

    4

    NW08-16 NS630b - NS1600NS630b - NS1000 (horizontal position)NT06-16

    type D

    1600

    (1) These are recommended configurations. For extended one, please consult us.

  • 17

    Functional units Electrical distributionIn y 630 A

    Selection of the functional unit - rated 415 V - 50 / 60 Hz - IP31 / 35 C

    Withdrawability In (A) Device Max. qty of devices

    Max. modularity (1 module = 50 mm)

    Cubicle

    Drawer In < 63 C60 1 2 modules half width

    Mw2

    63 < In < 125 NG125 1 4 modules half or full width (1)16 < In < 100 NSX100 1 4 modules half or full width

    125 < In < 160 NSX160 1 4 modules full width200 < In < 400 NSX 250-400 1 6 modules full width

    400 < In < 630 NSX630 1 8 modules full width

    Drawer 100 < In < 250 NSX100-250vertical position

    1 6 modules

    type D

    100 < In < 250 NSX100-250horizontal position

    2 8 modules

    400 < In < 630 NSX400-630vertical position

    1 8 modules

    Plug-in 100 < In < 250 NSX100-250vertical position

    4 6 modules

    type D

    100 < In < 250 NSX100-250horizontal position

    1 3 modules

    100 < In < 250 NSX100-250horizontal position

    2 3 modules

    400 < In < 630 NSX400-630horizontal position

    1 4 modules

    Fixed In < 63 C60 24 3 modules

    type D

    63 < In < 100 EZC100 vertical position

    6 6 modules

    100 < In < 250 NSX100-250 vertical position

    4 6 modules

    100 < In < 250 NSX100-250 horizontal position

    1 3 modules

    100 < In < 250 NSX100-250 horizontal position

    2 3 modules

    400 < In < 630 NSX400-630 horizontal position

    1 4 modules

    (1) Depending on Iq.

    Selection of the functional unit - rated 690 V - 50 / 60 Hz - IP31 / 35 CWithdrawability In (A) Device Max. qty of

    devicesMax. modularity (1 module = 50 mm)

    Cubicle

    Drawer In < 100 NS100L 1 4 modules

    Mw2

    100 < In < 400 NS400L 1 6 modules

    Fixed In < 100 NSX160 / NS100L 1 3 modules

    type D

    100 < In < 250 NSX 250 1 3 modules400 < In

  • 18

    Power factor correction

    U max = 415 V U max = 690 V

    few polluted network

    polluted network

    very polluted network

    few polluted network

    polluted network

    Varplus2 and

    Varplus Box Compact

    Varplus2 components and

    Varplus Box Compact

    Selection

    Functional units

    A wide selection for sensitive applications

    Statistical studies determine the frequency of the solutions used, according to the applications.

    Classic Comfort Harmony

    Pollution rate Gh / Sn y 15 % 15% < Gh / Sn y 25% 25% < Gh / Sn y 50%

    Automotive

    Water treatment

    Mines & Minerals

    Infrastructures

    Tertiary

    Agri-food

    very frequently

    usually

    occasionally

    Sn: apparent power of the transformer. Gh: apparent power of harmonics-generating loads (variable speed motors, static converters, power electronics, etc.).

    A source of energy savingsPower factor correction means using your transformer and your facility at maximum efficiency by reducing losses (iron, heat, etc.)

    Power output by your transformer (kVA)

    Cos 250 400 630 1000 1600

    0.5 125 200 315 500 800

    0.7 175 280 441 700 1120

    0.9 225 360 567 900 1440

    0.95 238 380 598 950 1520

    It is however recommended that measurements be carried out on site to check that the correct solution is adopted.

  • 19

    Selection of cubicle

    Rated voltage (V) Type Ventilation Power (kVAR) Qty of mounting plates

    415 without self (50Hz) natural up to 192 6forced up to 516 6

    without self (60Hz) natural up to 192 6forced up to 456 6

    440 without self (60Hz) natural up to 182 5

    forced up to 538 6

    480 without self (60Hz) natural up to 168 4

    forced up t o 396 6

    690 without self (50Hz) natural up to 199 3

    forced up to 398 6

    without self (60Hz) natural up to 160 3

    forced up to 422 6

    Many configuration possibilities

    b The power factor correction solution within Blokset has been designed to fit the switchgear dimensions.

    b The power factor correction elements can be protected as follows: v externally, by an NSX630 circuit breaker in an adjacent cubicle, v internally, by an NSX100-250 separate circuit breaker on each mounting plate.

    b The choice affects the number of mounting plates per column. Up to 6 capacitor plates can be installed.

    b Capacitors elements can be protected either from internal or external part of cubicle with the Compact NSX circuit breaker range.

    b The quantity of capacitor plates per cubicle depends upon electrical performance as well as ambient temperature and IP degree of protection.

    Power factor correctionFunctional units

  • 20

    Solutions that integrate into your installation, simply

    Our MotorSysTM iPMCC solutions integrate perfectly into your site network infrastructure, whatever the communication protocol, but also into all energy management control systems and process control systems.

    Example of an Ethernet communication architecture of a MotorSysTM iPMCC solution, at a process unit level

    > Given the complexity of data flows and communication network infrastructures, from instrumentation to corporate management systems, simple to integrate and scalable solutions are the natural choice.

    > Based on architectures that have been pre-tested and pre-validated for an integration in the leading communication protocols used in process industry and infrastructures, our solutions help you rapidly and efficiently optimise the energy efficiency of your assets.

    Innovation Bypass switch in a Daisy Chain Loop for an optimum dependability

    Motor controlFunctional units

  • 21

    Overview of the MotorSysTM iPMCC solutions

    We design with you the solution which meets your needs as well as your process requirements.

    Motor controlFunctional units

    Short-circuit, Thermal overload, Overcurrent, Ground currentCurrent phase imbalance & phase lossCurrent phase reversalUndercurrentLong start (stall) & Jam (locked rotor)Motor temperature sensorRapid cycle lockoutLoad sheddingVoltage phase imbalance, phase loss, & phase reversalUndervoltage & Overvoltage, Underpower & Overpower, Under & Over power factor

    MotorSysTM iPMCC Solutions Range iPMCC MCC

    Protection

    Measurements

    Line currents, Ground current, Average current, Current phase imbalance, Thermal capacity level Motor temperature sensor Frequency Line-to-line voltage, Line voltage imbalance, Average voltageActive & Reactive power, Power factor, Active & Reactive power consumption

    Connectivity & Communication architectures

    Schneider Electric Process Control System, Energy Management and Control System, PLCs (1) Third-party Process Control System, Energy Management and Control System, PLCs (1)

    Native Ethernet Modbus/TCP in Daisy Chain Loop, Star, Proxy Native Profibus-DP, Native DeviceNet, Native Modbus-SL Other protocols

    interop. testedinterop. tested

    Operational modes

    ConsignmentStarters test position Maintenance & Upgrade liveControl at motor levelPC set-upRemote management Local HMI "Nominal current only" set-up (screwdriver)

    High level functions

    Custom logic at starter levelAdvanced motor starting modes Automatic restarting of motorsFast Device Replacement

    Standard

    Optional

    (1) PLC: Programmable Logic Controller

  • 22

    Motor controlFunctional units

    Circuit breaker-contactor combination TeSys U b Advantages

    v easy installation: - easy to order: 1 power base + 1 protection (control unit) - easy to install: only one device must be wired, reduced installation times - easy to set: locally via the LCD and keypad built into the control unit or remotely v continuity of service:

    - total coordination between protection devices - protection functions modified by simply changing the control unit - manual or automatic reset following a thermal fault v upgradeability: modular design. Functional modules (communication and

    protection) can be easily changed at any time without having to rewire the entire assembly.

    b Applications v manufacturing and continuous and semi-continuous processes.

    1-component motor feeder

    2-component motor feeder

    Thermomagnetic circuit-breaker + contactor

    b Advantages v very economic solutions v suitable for all types of diagrams v manual reset following a thermal fault v type 2 coordination

    b Applications v manufacturing and continuous and semi-continuous processes.

    3-component motor feeder

    Advantages b Wide choice of solutions. b Suitable for all types of diagrams. b Manual or automatic reset following a thermal fault. b 2 starting classes (10 and 20). b Type 2 coordination. b Segregation of thermal and magnetic faults.

    Magnetic circuit-breaker + contactor + thermal protection b For manufacturing and continuous and semi-continuous processes.

    Switch-disconnector fuse + contactor + thermal protection b For all types of machines. b For manufacturing and continuous and semi-continuous processes.

  • 23

    Motor controlFunctional units

    Withdrawability Starter Circuit breaker Power (kW) Dimensions (1) (2) Cubiclemin max

    Drawer DOL Tesys U 0 to 15 2M half 2M full

    Mw2

    DOL Tesys U 0 to 15 4M half 4M half

    Selection of the functional unit -MotorSys iMCC 1 component - rated 415 V - 50 / 60 Hz - IP31 / 35 C

    Withdrawability Starter Circuit breaker Power (kW) Dimensions (1) (2) Cubiclemin max

    Drawer DOL GV2P 0 to 15 2M half 4M half

    Mw2

    GV3P 18.5 to 30 4M half 4M fullReverse GV2P 0 to 15 4M half 4M full

    GV3P 18.5 to 30 4M half 4M fullStar-delta GV2P 0 to 15 4M full 4M full

    GV3P 18.5 to 30 6M full 6M full

    Selection of the functional unit -MotorSys MCC 2 components - rated 415 V - 50 / 60Hz - IP31 / 35 C

    Withdrawability Starter Circuit breaker Power (kW) Dimensions (1) (2) Cubiclemin max

    Drawer DOL GV2L 0 to 15 2M half 4M half

    Mw2

    GV3L 18.5 to 30 2M full 4M fullNS80HMA 18.5 to 30 4M half 4M full

    37 4M full 4M fullNSX100SMA 18.5 to 30 4M full 6M fullNSX100*MA 37 4M full 4M full

    45 4M full 6M fullNSX160*MA 55 4M full 4M full

    75 6M full 6M fullNSX250*MA 90 to 110 8M full 8M fullNSX400*MA 132 to 160 10M full 10M fullNSX630*MA 200 10M full 10M full

    220 to 250 12M full 12M fullReverse GV2L 0 to 15 4M half 4M full

    GV3L 18.5 to 30 4M half 4M fullNS80HMA 18.5 to 30 4M full 4M full

    37 6M full 6M fullNSX100SMA 18.5 to 30 6M full 6M fullNSX100*MA 37 to 45 6M full 8M fullNSX160*MA 55 6M full 6M full

    75 6M full 8M fullNSX250*MA 90 to 110 10M full 10M fullNSX400*MA 132 to 160 12M full 12M fullNSX630*MA 200 to 250 12M full 12M full

    Star-delta GV2L 0 to 15 4M full 4M fullGV3L 18.5 to 30 6M full 6M fullNS80HMA 18.5 to 30 6M full 6M full

    37 8M full 8M fullNSX100*MA 18.5 to 45 8M full 8M fullNSX160*MA 55 to 75 8M full 8M full

    (1) Depending on additional equipments.(2) In number of vertical modules (1 module = 50 mm).

    Selection of the functional unit -MotorSys MCC 3 components - rated 415 V - 50 / 60 Hz - IP31 / 35 C

  • 24

    Withdrawability Starter Circuit breaker or fuse Power (kW) Dimensions (1) (2) Cubiclemin max

    Drawer DOL GV2L 0 to 4 2M half 2M full

    Mw2

    5.5 to 15 2M half 4M fullGV3L 18.5 to 30 2M full 4M fullNS80HMA 18.5 to 37 4M full 4M fullNSX100*MA 18.5 to 30 4M full 6M full

    37 4M full 4M full45 4M full 6M full

    NSX160*MA 55 to 75 6M full 6M fullNSX250*MA 90 to 110 8M full 8M fullNSX400*MA 132 to 160 10M full 10M fullNSX630*MA 200 10M full 10M full

    220 to 250 12M full 12M fullReverse GV2L 0 to 15 4M half 4M full

    GV3L 18.5 to 30 4M full 4M fullNS80HMA 18.5 to 37 6M full 6M fullNSX100*MA 18.5 to 30 6M full 6M full

    37 to 45 6M full 8M fullNSX160*MA 55 to 75 6M full 8M fullNSX250*MA 90 to 110 10M full 10M fullNSX400*MA 132 to 160 12M full 12M fullNSX630*MA 200 to 250 12M full 12M full

    Star-delta GV2L 0 to 15 4M full 4M fullGV3L 18.5 to 30 6M full 6M fullNS80HMA 18.5 to 37 6M full 8M fullNSX100*MA 18.5 to 45 8M full 8M fullNSX160*MA 55 to 75 8M full 8M full

    Fixed DOL GV2 0.37 to 15 3M 3M

    Mf

    NS80 0.18 to 37 3M 3MNSX100 0.37 to 30 3M 3M

    37 to 45 6M 6MNSX160 55 to 75 6M 6MNSX250 90 to 110 9M 9MNSX400 132 to 160 12M 12MNSX630 200 to 250 15M 15M

    REV GV2 0.37 to 15 6M 6MNS80 0.18 to 37 6M 6MNSX100 0.37 3M 3M

    0.55 to 37 6M 6MNSX160 55 to 75 9M 9MNSX250 90 to 110 12M 12MNSX400 132 to 160 16M 16MNSX630 200 to 250 16M 16M

    Star-delta GV2 1.5 to 11 6M 6MNS80 1.5 to 15 6M 6M

    18.5 to 37 9M 9MNSX100 3 to 11 6M 6M

    15 to 37 9M 9M45 12M 12M

    NSX160 55 to 75 12M 12MNSX250 90 to 110 16M 16MNSX400 132 to 160 20M 20MNSX630 200 to 250 20M 20M

    (1) Depending on additional equipments.(2) In number of vertical modules (1 module = 50 mm).

    Selection of the functional unit - MotorSys MCC and iMCC 3 components - rated 415 V - 50 / 60 Hz - IP31 / 35C

    Motor controlFunctional units

  • Withdrawability Starter Circuit breaker or fuse Power (kW) Dimensions (1) (2) Cubiclemin max

    Drawer DOL GV2L 0 to 15 2M full 2M full

    Mw2

    18.5 to 22 2M full 4M fullNS100LMA 0 to 55 6M full 6M full

    75 8M full 8M fullNS400LMA 90 to 250 10M full 10M full

    Reverse GV2L 0 to 22 4M full 4M fullNS100LMA 0 to 1.5 6M full 6M full

    2.2 to 55 8M full 8M full75 10M full 10M full

    NS400LMA 90 to 250 12M full 12M fullStar-delta GV2L 0 to 15 4M full 4M full

    18.5 to 22 6M full 6M fullNS100LMA 0 to 1.5 6M full 6M full

    2.2 to 55 8M full 8M full75 10M full 10M full

    (1) Depending on additional equipments.(2) In number of vertical modules (1 module = 50 mm).

    Motor control - MotorSys MCC and iMCC 3 components - rated 690 V - 50 Hz - IP31 / 35C

    Withdrawability Starter Circuit breaker or fuse Power (kW) Dimensions (1) (2) Cubiclemin max

    Drawer DOL Tesys U 0 to 18.5 2M full 2M full

    Mw2

    Motor control - MotorSys MCC and iMCC 1 component - rated 690 V - 50 Hz - IP31 / 35C

    Withdrawability Starter Circuit breaker or fuse Power (kW) Dimensions (1) (2) Cubiclemin max

    Drawer DOL GV2P 0 to 22 2M full 2M full

    Mw2

    18.5 to 22 4M full 4M fullReverse GV2P 0 to 22 4M full 4M fullStar-delta GV2P 0 to 15 4M full 4M full

    18.5 to 22 6M full 6M full

    Motor control - MotorSys MCC and iMCC 2 components - rated 690 V - 50 Hz - IP31 / 35C

    25

    Motor controlFunctional units

  • 26

    Variable speed drive and soft starter

    Functional units

    Altistart ATS 48

    Altistart ATS 48

    b The Altistart ATS 48 soft start - soft stop unit is a controller with 6 thyristors, which is used for the torque-controlled soft starting and stopping of three-phase squirrel cage asynchronous motors.

    b The Altistart ATS 48 must be selected on the basis of 3 main criteria: v the power supply voltage range (this catalogue deals only whith the devices

    connected to a 415V or 690V network), v the power and the nominal current of the motor, v the type of application and the operating cycle.

    Altivar ATV 61 Altivar ATV 71

    They have been designed for the following main applications:

    ATV61 ATV71

    ventilation,air conditioning,pumping,

    hoisting,handling,packing,process machines,lifts, ...

    This catalogue deals only with 415V and 690V voltage.

    Altivar ATV61 and 71

    From 75 kW, equipment configuration is different.

    Speed drive is powered, either through a drawer located in the 70-2 adjoining cubicle (fig. 1 and 2), or through a dedicated 450 mm cubicle (fig. 3).

    The speed drive cubicle can be either 650 mm (fig. 1) or 1150 mm wide (fig. 2 and 3).

    Installation can be performed only in IP31 maximum.

    Circuit breaker and variable speed drive combination

  • 27

    Variable speed drive and soft starter in fixed mounting plateSwitchgears Rated voltage (V) Power (kW) Circuit breaker or fuse Modularity (1 M = 50mm) CubicleATS 48

    (standard application whitout bypass contactor)

    415 7.5 to 15 GV2 9

    Ms

    7.5 to 22 Compact NS80 930 to 37 Compact NS80 1245 Compact NSX100 1855 to 75 Compact NSX160 1890 to 110 Compact NSX250 24132 to 160 Compact NSX400 24220 to 250 Compact NSX630 36

    440 7.5 to 22 Compact NS80 9Compact NSX100 9

    30 to 37 Compact NS80 12Compact NSX100 12

    45 to 55 Compact NSX100 1875 Compact NSX160 1890 Compact NSX160 24110 Compact NSX250 24132 to 160 Compact NSX400 24220 to 250 Compact NSX630 36

    690 15 to 22 GV2 1215 to 37 Compact NS100L 1245 to 75 Compact NS100L 1890 to 200 Compact NS400L 24250 Compact NS400L 36

    ATV 61

    (without braking resistor)

    415 0.75 to 7.5 GV2 97.5 to 11 Compact NS80 915 to 18.5 Compact NS80 1222 to 37 Compact NS80 2445 to 55 Compact NSX100-160 24

    440 0.75 to 11 GV2 911 Compact NS80 915 to 18.5 Compact NS80 1222 to 37 Compact NS80 2445 to 55 Compact NSX100 24

    690 3 to 15 GV2 1218.5 to 22 Compact NS100L 1230 to 75 Compact NS100L 2490 Compact NS400L 24

    ATV71 415 0.75 to 5.5 GV2 9

    (without braking resistor)

    7.5 to 11 Compact NS80 915 to 18.5 Compact NS80 1222 to 30 Compact NS80 2437 to 55 Compact NSX100-160 24

    440 0.75 to 5.5 GV2 97.5 to 11 Compact NS80 915 Compact NS80 1218.5 Compact NSX100 1222 to 55 Compact NSX100-160 24

    690 2.2 to 15 GV2 1218.5 to 22 Compact NS100L 1230 to 75 Compact NS100L 2490 Compact NS400L 24

    Variable speed drive and soft starter

    Functional units

  • 28

    Cubicles Associating cubicles and compartments

    Device installation zone:

    Device cubicles architecture

    horizontal busbar

    vertical busbar

    device installation zone

    Particular case of the Mw2 device cubicle:

    Double vertical busbar topCubicle height 2200 mmNo. of poles 3P 3P+NModularity 30 modules 28 modules

    Single vertical busbarCubicle height 2200 mmNo. of poles 3P 3P+NModularity 34 modules 32 modules

    Note: 1 module = 50 mm.

    Link cover double horizontal busbarDouble horizontal busbar topBottom link cover dimension 62.5 mm 162.5 mm

    Link cover single horizontal busbarSingle horizontal busbar topTop link cover dimension 52.5 mm 152.5 mmSingle horizontal busbar bottomBottom link cover dimension 62.5 mm 162.5 mm

    Device installation zoneSingle horizontal busbarModularity 34 modulesDouble horizontal busbarModularity 28 modules

    Note: 1 module = 50 mm.

  • 29

    RC columns panoramaswitchboard depth 600 mm switchboard depth 1000 mm

    device cubicle width 700 mm

    device cubicle width 900 mm

    device cubicle width 1200 mm

    Type of connection

    RC: rear connectionBDC: bottom direct connection SC: side connectionTDC: top direct connection

    For rear connection (RC), a solution depth 600 mm is possible for small In (y 630 A).An additional compartment depth 400 mm is added for In > 630 A.

    Columns for rear connection (RC)

    In case of a side connection switchboard, the depth is unique allthrough its length: 600 mm. To the right of the device cubicle, compartments (width 200, 400 or 700 mm) are added in order to give way for the cables and device connections, according to the size and the quantity of cables to be connected.Due to the position of the horizontal busbar, device connection can be made indifferently from the top or from the bottom of the switchboard.

    Columns for side connection (SC)

    SC columns panorama (switchboard depth: 600 mm)column width 900 / 1100 mm column width 900 mm

    A / C 600

    700

    A / C 600

    700

    V

    200

    A / C 600

    1200

    A 600

    700

    C 400

    A 600

    700

    C 400

    V

    200

    A 600

    1200

    C 400

    A 600

    700

    C

    200 / 400

    A 600

    700

    C

    200 / 400

    V

    200

    A device cubicle

    C cable compartment

    V vertical busbar compartment

    A device cubicle

    C cable compartment

    V vertical busbar compartment

    Cubicles Associating cubicles and compartments

  • 30

    Horizontal busbarSelection tableAllowable intensity at 35 C IP31 (A) Icw max. Qty of barsHorizontal busbar (kA) 100 x 5 mm 125 x 5 mmSingle busbars1500A 50 1from 1500 to 2550 50 / 85 2from 2550 to 3250 50 / 85 3from 3250 to 3800 50 / 85 4from 3800 to 4100 50 / 85 5Double busbarsfrom 4100 to 6000 100 2 x 4from 6000 to 6600 100 2 x 5

    Cubicles Presentation

    CubicleThe Blokset switchboards consist of a framework and busbar assembly designed to combine in the same cubicle functional units of varying technologies, grouping both distribution and motor control applications.

    A complete range of configurations to satisfy the requirements of each site: b cubicles available in 1 height, 8 widths and 3 depths, to allow integration in all

    environments and ensure optimum installation modularity, b switchboard supplied by busbar trunking and / or cables, b front or rear, top and / or bottom connections, b choice of functional unit output partitioning: v incomers: forms 3b, 4b, v feeders: forms 2b, 3b, 4a, 4b.

    BusbarsBusbar coatingBusbar coating none silver tin nickel epoxyhorizontal busbar b b b bvertical busbar D b b b bvertical busbar Mw2 b b bprotection against ... corrosive

    environmentcorrosive environment

    internal arc

  • 31

    Cubicles Type D For NW40b-63 devices

    Functional unit

    DimensionsType of distribution Type of connection Qty of cubicle

    1 incomer or 1 distribution feeder b direct connection from the bottom b front or rear connection

    1

    2 incomers + 1 coupling b direct connection from the bottom b front or rear connection

    3

    1 source changeover b direct connection from the bottom b front or rear connection

    2

    Busbar for type D cubicle

    b very high power, b dedicated to NW40b-63 devices, b height-reduced busbar.

    Allowable intensity at 35 C IP31 (A) Icw max. Qty of barsHorizontal busbar (kA) 100 x 5 mm6000 100 2 x 46600 100 2 x 5

  • 32

    Cubicles Type D For NW32-40 and NS3200 devices

    Functional unit

    Dimensions

    Busbar for type D cubicle

    b high power, b dedicated to NW and NS devices, b height-reduced busbar.

    Type of distribution Circuit breaker Type of connection Qty of cubicle1 incomer or 1 distribution feeder

    Masterpact NW32-40Compact NS3200

    b direct connection from the top b direct connection from the bottom b front or rear connection

    1

    2 incomers + 1 coupling Masterpact NW32-40Compact NS3200

    b direct connection from the top b direct connection from the bottom b front or rear connection

    3

    1 source changeover Masterpact NW32-40Compact NS3200

    b direct connection from the top b direct connection from the bottom b front or rear connection

    2

    Allowable intensity at 35 C IP31 (A) Icw max. Qty of barsHorizontal busbar (kA) 125 x 5 mm3250 50 / 85 / 100 34100 50 / 85 / 100 5

  • 33

    Cubicles Type D For NW08-25, NT06-16 and NS630b-2500 devices

    Functional unit

    Dimensions

    Busbar for type D cubicle

    b high power, b dedicated to NW08-25, NT06-16, NS630b-2500 devices, b full height busbar.

    Type of distribution Circuit breaker Type of connection Qty of cubicleIncomer or distribution feeder

    Masterpact NW08-25 (2 or 3) b direct connection from the top b direct connection from the bottom b front or rear connection

    1

    Masterpact NT06-16 (3 or 4)Compact NS630b-2500 (3 or 4)

    b direct connection from the top b direct connection from the bottom b rear connection

    1

    2 incomers + 1 coupling Masterpact NW08-25 (2 or 3) b direct connection from the top b direct connection from the bottom b front or rear connection

    2

    Masterpact NT06-16 (3 or 4)Compact NS630b-2500 (3 or 4)

    b direct connection from the top b direct connection from the bottom b front or rear connection

    2

    1 source changeover Masterpact NW08-25 (2 or 3) b direct connection from the top b direct connection from the bottom b front or rear connection

    1

    Masterpact NT06-16 (3 or 4)Compact NS630b-2500 (3 or 4)

    b direct connection from the top b direct connection from the bottom b front or rear connection

    1

    Allowable intensity at 35 C IP31 (A) Icw max. Qty of barsHorizontal busbar (kA) 100 x 5 mm 125 x 5 mmSingle busbars1500 50 12550 50 / 85 23250 50 / 85 33800 50 / 85 44100 50 / 85 5Double busbars6000 50 / 85 2 x 46600 50 / 85 2 x 5

  • 34

    Cubicles Type D For C60, EZC100 and NSX100-630 devices

    Functional unit

    Dimensions

    Busbar for type D cubicle

    b small power, b dedicated to C60, EZC100, NSX100-630 devices, b full height busbar.

    Type of functional unit Rating (A) No. of pole Type of connectionFixed < 63 3P / 4P b front connection

    63 to 100 3P / 4P b front connectionFixed 100 to 630 3P / 4P b front connection

    b rear connectionPlug-in 100 to 630 3P / 4P b front connection

    b rear connectionWithdrawable 100 to 630 3P / 4P b front connection

    b rear connection

    Allowable intensity at 35 C IP31 (A) Icw max. Qty of barsHorizontal busbar (kA) 100 x 5 mm 125 x 5 mmSingle busbars1500 50 12550 50 / 85 23250 50 / 85 33800 50 / 85 44100 50 / 85 5Double busbars6000 50 / 85 2 x 46600 50 / 85 2 x 5

  • Dimensions

    Vertical Mw2 busbar

    b designed for MCC functional units in drawer, b full height busbar.

    Rated current In (A)IP31 / 35C

    No. of bars / phase Icw max (kA)

    Single vertical busbars

    400 1 x 20 x 8 25

    630 1 x 30 x 8 37.5

    1000 1 x 50 x 8 60

    Double vertical busbars

    800 2 x 20 x 8 50

    1250 2 x 30 x 8 75

    2000 2 x 50 x 8 85

    35

    Cubicles Mw2

    Functional unit

    All functional unitsType of functional unit Type of connectionDrawer b side connection from the front

    b rear connection

  • 36

    Cubicles Mf

    Functional unitBusbar for Mf cubicle

    b designed for MCC fixed functional units, b full height busbar.

    DimensionsAll functional unitsType of functional unit Type of connectionFixed in functional unit b side connection from the front

    b rear connection

    The dimensions of the functional units are in the MCC choice pages, page 23.

    Rated current In (A)IP31 / 35C

    Icw max. Qty of bars

    Horizontal busbar (kA) 100 x 5 mm 125 x 5 mmSingle busbars1500 50 12550 50 / 85 23250 50 / 85 33800 50 / 85 44100 50 / 85 5Double busbars6000 50 / 85 2 x 46600 50 / 85 2 x 5

  • 37

  • 1415 V - 3P+T - 70 kA - 3200 A

    35 kW

    5,5 kW

    1,5 kW

    15 kW

    1,5 kW

    35 kW

    100 kW

    150 kW

    1,5 kW

    1,5 kW

    15 kW

    45 kW

    100 kVAR

    1,5 kW

    1,5 kW

    1,5 kW

    250 A

    250 A

    100 A

    100 A

    100 A

    1250 A

    1250 A

    3200 A

    3200 A

    800 A

    G35 kW

    35 kW

    38

    Example Example of configuration

    Customers needs

    single-wire diagramm of the installation

    Main characteristics of the switchboardReference standards IEC 61439-2Rated insulation voltage 1000 VRated operation voltage 380 / 415 VVertical busbar rating 3200 ARated short-circuit current 70 kARated peak current 154 kARated frequency 50 / 60 HzBusbar number of phases 3

    material copperinsulation air

    Form 3bDegree of pollution external IP 31

    internal IP 20Rated auxiliary circuit voltage 230 VEnergy compensation 100 kVARCable entry top / bottomAccess front / rearTemperature 35 CAltitude 2000 mPanelling colour RAL 9002

  • 415 V - 3P+T - 70 kA - 3200 A

    35 kW

    5,5 kW

    1,5 kW

    15 kW

    1,5 kW

    35 kW

    100 kW

    150 kW

    1,5 kW

    1,5 kW

    15 kW

    45 kW

    100 kVAR

    1,5 kW

    1,5 kW

    1,5 kW

    250 A

    250 A

    100 A

    100 A

    100 A

    1250 A

    1250 A

    3200 A

    3200 A

    800 A

    G35 kW

    35 kW

    23

    39

    Example

    Determine the functional unitsaccording to the following parameters:

    b In current, b voltage, b short-circuit current, b number of pole b type and technology of the functional units.

    Deduce the number and the type of necessary cubicles

    Example of configuration

    Type of functional units M

    C

    MC

    MC

    MC

    MC

    MC

    MC

    MC

    MC

    MC

    ED

    ED

    ED

    ED

    INC

    C INC

    ED

    INC

    PC

    C

    PC

    CM

    C

    MC

    MC

    MC

    MC

    VV

    D

    VV

    D

    EC

    Technology

    draw

    er

    draw

    er

    draw

    er

    draw

    er

    draw

    er

    draw

    er

    draw

    er

    draw

    er

    draw

    er

    draw

    er

    fixed

    fixed

    fixed

    chas

    sis

    chas

    sis

    chas

    sis

    chas

    sis

    chas

    sis

    chas

    sis

    draw

    er

    draw

    erdr

    awer

    draw

    er

    draw

    er

    draw

    er

    draw

    er

    fixed

    fixed

    fixed

    No. of vertical modules (1 module = 50 mm) 4 2 2.

    5

    4 8 10 2.5

    2.5

    2.5

    2 3 3 3 12 12 12 4 4 4 4 2 2.5

    2 12 24 20 x

    5.5

    kVA

    R

    Cubicles, rear connection with around 10 % of reserve

    34 modules = 1 cubicle Mw2 1 cubicletype D2 cubicles type D

    1 cubicletype D

    1 cubicle

    type D 22 modules

    = 1 cubicle Mw2

    1 cub

    icle

    type

    Ms

    1 cub

    icle

    type

    Dc

    To determine the dimensions of each functional unit, see the selection table.INC: high power circuit-breaker incoming.C: coupling.EC: Power factor compensation.ED: electrical distribution.MC: motor control.VVD = Variable speed drive and soft starter.

  • 40

    Ground fastening

    b class 8.8 screws: M10 TH screws + washers (external 25 mm, thickness 3 mm) + CS contact washers 10 mm.

    Cubicle installationFixing points

    Installation

    b Mw2 front connection. b Mw2 rear connection.

    122,5 355180697,5

    350

    625

    550

    25 25687,5 737,5

    b Section width 700

    b Section width 1100 (700 + 400)

    b Section width 1100 (200 + 700 + 200)

    b Section width 1300 (200 + 700 + 400)

    322,5125 25

    A

    455 197,5

    122,5 25

    A

    455 205195

    b Section width 900 (200 + 700)

    b Section width 1200

    122,5 25

    A

    955

    322,5125 25

    A

    455

    125 25

    A

    455 195 205322,5

    A: 350 mm for a depth of 400 mm 550 mm for a depth of 600 mm 950 mm for a depth of 1000 mm

    455122,5 25

    A

    Side connection Rear connection b Section width 800 b Section width 900 b Section width 1000 b Section width 600

    687,5 180697,5

    800 900 1000

    737,5

    550

    25

    122,5 355

    600

    350

    1000

    625

    600

    25

    687,5 180697,5

    800 900 1000

    737,5

    550

    25

    122,5 355

    600

    350

    1000

    625

    600

    25

  • (mm)

    (mm)

    (mm)

    41

    Minimum distances around switchboard

    b Provide a minimum space of 500 mm above the switchboard for connection by cables or for fishplating the horizontal busbar.

    Clearance above the switchboard. Rear connection. Front connection.

    Cubicle installationSwitchboard positionning

    Installation

  • 42

    Futher technical informationBlokset performances

    General dataStandard environment

    reference standards IEC 60439-1 / IEC 61439-2IEC 60529

    climatic resistance damp heat withstand IEC 60068-2-30dry heat withstand IEC 60068-2-2low temperature withstand IEC 60068-21salt spray withstand IEC 60068-2-11

    installation indoorearthquake withstand IEC68-3-3 and UBC / CBC

    HN20E53environment (CEM) type 2

    Mechanical datacable entry top / bottomaccess front / reardegree of protection (IP) 20 / 31 / 42 / 54form 2b / 3b / 4a / 4bwithdrawability FFF / WWWdimensions (mm) height 2200

    width 600 / 700 / 800 / 9001000 / 1100 / 1200 / 1300

    depth 400 / 600 / 1000installation modularity in a cubicle

    height 2200 mm 40 modules of 50 mm

    panel coating epoxy / polyester powderpolymerised, > 50

    panelling colour RAL 9002 / 7016

    Electrical datarated insulation voltage (Ui) 1000 Vrated operational voltage (Ue) 415 / 690 V CArated frequency (F) 50 / 60 Hzrated impact withstand voltage (Uimp) 12 kVrated auxiliary circuit voltage 230 V AC max.surge category IVdegree of pollution 3rated current (In) 6300 Avertical busbar rating 3200 Ahorizontal busbar short-term rated current (Icw) 1s 50 / 85 / 100 kA rmsvertical busbar short-term rated current (Icw) 1s 50 / 85 kA rmsrated conditional short-circuit current (lcc) up to 100 kAinternal arcing protection according to IEC 61641 85 kA eff 0.3 searthing diagram TT-IT-TNS-TNCcurrent limit of power incoming and outgoing feeders up to 5650 Apower limit of motor control feeders up to 250 kW 415 / 690 V

  • 03-2011

    Schneider Electric Industries SAS35 rue Joseph MonierCS 30323F-92506 Rueil Malmaison Cedex

    RCS Nanterre B 954 503 439Capital social 896 313 776 www.schneider-electric.com

    As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this document.

    Design: Schneider ElectricPhotos: Schneider ElectricEdition: Altavia ConnexionPrinting: A

    RT.

    9605

    74

    201

    1 - S

    chne

    ider

    Ele

    ctric

    - A

    ll rig

    hts

    rese

    rved

    ESBED297701EN

    PresentationSolution overviewFunctional unitsCubiclesExampleInstallationBlokset performances