SFPE Handbook of Fire Protection Engineering 4th Edition
Errata
Chapter 1-4
On page 1-78, the equation for the 2 parallel surfaces (2nd from bottom) the X in X / sqrt (1 + X2) on the second line should be Y / sqrt (1 + X2).
Chapter 2-1
On page 2-3, Figure 2-1.3 - on the scale for Q*, the right most value should read 106 not 105.
Chapter 2-3
In equation 19 on page 3-68, in the numerator, the measured mole fraction of oxygen in the exhaust duct should be multiplied by the second term, not the first.
Chapter 2-12
Equation 6 on page 2-282 should have a coefficient of 4 before " .
Chapter 3-1
Page 3-37 - the equation for calculating heat release rate from liquid pool fires (in the upper right-hand corner of the page) - the exponential term (kβD) should have a negative sign.
Chapter 3-4
In Table 3-4.3, the multiplier for "k" should be 103 (not 10-3).
Chapter 4-3
On page 4-76, the exponent for "Q" in the first equation should be 1.85.
Chapter 4-9
Page 4-235, in table 4-9.2, the entry for "735< Tst < 900" should be 545 + 17820/( Tst -731).
Chapter 4-11
On page 4-299, in the table in the lower right-hand corner, the first entry should read "k = -0.022T +48 for 0≤T≤900 ⁰C"
Chapter 4-14
On page 4-381, replace equation 17 and everything after it until just before the title "Elevator Smoke Control" with the text in the attached file.
Chapter 4-15
Equation (43) p.4-399 should read
2/12/1
202/12
02 dAT
TTgm v
Chapter 5-3
On page 5-61, the unnumbered equation in the lower left should read [1-R(t)] in both places.
Appendix C
In Table C.1, the units for Heat of combustion should be MJ/kg.