EPC-A-1 Spec Sheet - LVS Inc. · specifications single line drawing wiring diagram ordering...
Transcript of EPC-A-1 Spec Sheet - LVS Inc. · specifications single line drawing wiring diagram ordering...
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707
www.lvscontrols.com
Project:
Model No.:
Comments:
APPLICATION
FEATURESMOUNTING
Patented Automatic Diagnostic Feature
The unique feature of the EPC-A-1 is the ability to place the unit above the accessible ceiling tile because the unit does not require an accessible test switch. Instead, when the room switch is turned off, the emergency luminaires stay on for 2.5 seconds and indicate that an emergency power source was available and that the EPC-A-1, ballast, and lamp(s) are all functioning correctly. This feature replaces a test switch and is approved for this purpose.
Power indicator LED for utility power (green)
LED COMPATIBILE
UL®UL924 LISTEDC US
5YEAR
WARRANTY
In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model EPC-A-1, to convert regular light fixtures into approved emergency lights. The EPC-A-1 saves energy and money while ensuring compliance with both life safety and energy codes.
During normal operation, the same room switch, occupancy sensor, relay panel, or lighting control switches regular and emergency fixtures on and off simultaneously.
During a utility power interruption, the EPC-A-1 automatically bypasses the regular lighting controls, turning the emergency lights ON, regardless of switch position.
The EPC-A-1 is ceiling or wall mounted in a junction box with a single gang plaster ring and is usually located in the area where the emergency fixtures are installed.
Winner LFI Innovation
Award
EPC-A-120A Emergency Power Control(Junction Box/Fixture Mount)
SPECIFICATIONS
SINGLE LINE DRAWING
WIRING DIAGRAM
ORDERING INFORMATION ADDITIONAL RESOURCES
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707
www.lvscontrols.com20160706_E001_Spec
For canadian version, see EPC-A-1-cUL
EPC-A-1 Installation SheetFAQ SheetAlternative Wiring Sheet
Terms & Conditions/Warranty Information
EMERGENCY HOT
#4 WHITE
REGULAR PANEL
20A
#3 RED
#2 ORANGE
#1 BLACK
*
Relay Panel, Power Pack, Sensor, or other (optional)*
Regular Light (optional)
EMERGENCY PANEL OR INVERTER
20AREGULAR HOT
REGULAR NEUTRALEMERGENCY NEUTRAL
#6 YELLOW
#5 BLUE
Emergency Light
Note: Emergency Light is also called N/E Light or Normal/Emergency
Light by many specifiers
120V
277V
UTILITY PO
WER
DESIGNATEDEMERGENCY
LIGHTS
REGULAR ROOM LIGHTS
EPC-A-1 CONTROL
UL 1008Transfer SwitchOr Equivalent
RegularUtility Power
Emergency Power Source
Neutral Not Shown
EPC-A-1 CONTROL
REGULARPANEL
RegularUtility Power
EMERGENCYPANEL
$
EPC-A-1
TO ADDITIONAL EPC-A-1 CONTROLS
MODEL NO.
SENSING INPUT
LOAD RATING
BALLAST LOAD RATING
INCANDESCENT LOAD
WARRANTY
EPC-A-1
120V / 277V
120V - 277V (20A)
20A (120-277V)
1200W (120V) / 1500W (277V)
5 Year Replacement Warranty
ELECTRICAL
MOUNTING
RATING
SHIPPING WEIGHT
TEMPERATURE
COLOR
SIZE (WITH MOUNTING EARS)
4-11/16” Junction Box w/ blank cover
UL94V-0 Flame Rating
8 oz.
32ºF - 140ºF (0ºC - 60ºC)
BLACK
3-3/4” x 1-3/4” x 1-1/2”
MECHANICAL