2
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707 www.lvscontrols.com Project: Model No.: Comments: APPLICATION FEATURES MOUNTING Patented Automatic Diagnostic Feature The unique feature of the EPC-A-1 is the ability to place the unit above the accessible ceiling tile because the unit does not require an accessible test switch. Instead, when the room switch is turned off, the emergency luminaires stay on for 2.5 seconds and indicate that an emergency power source was available and that the EPC-A-1, ballast, and lamp(s) are all functioning correctly. This feature replaces a test switch and is approved for this purpose. Power indicator LED for utility power (green) LED COMPATIBILE U L ® UL924 LISTED C US 5 YEAR WARRANTY In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model EPC-A-1, to convert regular light fixtures into approved emergency lights. The EPC-A-1 saves energy and money while ensuring compliance with both life safety and energy codes. During normal operation, the same room switch, occupancy sensor, relay panel, or lighting control switches regular and emergency fixtures on and off simultaneously. During a utility power interruption, the EPC-A-1 automatically bypasses the regular lighting controls, turning the emergency lights ON, regardless of switch position. The EPC-A-1 is ceiling or wall mounted in a junction box with a single gang plaster ring and is usually located in the area where the emergency fixtures are installed. Winner LFI Innovation Award EPC-A-1 20A Emergency Power Control (Junction Box/Fixture Mount)

Transcript of EPC-A-1 Spec Sheet - LVS Inc. · specifications single line drawing wiring diagram ordering...

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707

www.lvscontrols.com

Project:

Model No.:

Comments:

APPLICATION

FEATURESMOUNTING

Patented Automatic Diagnostic Feature

The unique feature of the EPC-A-1 is the ability to place the unit above the accessible ceiling tile because the unit does not require an accessible test switch. Instead, when the room switch is turned off, the emergency luminaires stay on for 2.5 seconds and indicate that an emergency power source was available and that the EPC-A-1, ballast, and lamp(s) are all functioning correctly. This feature replaces a test switch and is approved for this purpose.

Power indicator LED for utility power (green)

LED COMPATIBILE

UL®UL924 LISTEDC US

5YEAR

WARRANTY

In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model EPC-A-1, to convert regular light fixtures into approved emergency lights. The EPC-A-1 saves energy and money while ensuring compliance with both life safety and energy codes.

During normal operation, the same room switch, occupancy sensor, relay panel, or lighting control switches regular and emergency fixtures on and off simultaneously.

During a utility power interruption, the EPC-A-1 automatically bypasses the regular lighting controls, turning the emergency lights ON, regardless of switch position.

The EPC-A-1 is ceiling or wall mounted in a junction box with a single gang plaster ring and is usually located in the area where the emergency fixtures are installed.

Winner LFI Innovation

Award

EPC-A-120A Emergency Power Control(Junction Box/Fixture Mount)

SPECIFICATIONS

SINGLE LINE DRAWING

WIRING DIAGRAM

ORDERING INFORMATION ADDITIONAL RESOURCES

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707

www.lvscontrols.com20160706_E001_Spec

For canadian version, see EPC-A-1-cUL

EPC-A-1 Installation SheetFAQ SheetAlternative Wiring Sheet

Terms & Conditions/Warranty Information

EMERGENCY HOT

#4 WHITE

REGULAR PANEL

20A

#3 RED

#2 ORANGE

#1 BLACK

*

Relay Panel, Power Pack, Sensor, or other (optional)*

Regular Light (optional)

EMERGENCY PANEL OR INVERTER

20AREGULAR HOT

REGULAR NEUTRALEMERGENCY NEUTRAL

#6 YELLOW

#5 BLUE

Emergency Light

Note: Emergency Light is also called N/E Light or Normal/Emergency

Light by many specifiers

120V

277V

UTILITY PO

WER

DESIGNATEDEMERGENCY

LIGHTS

REGULAR ROOM LIGHTS

EPC-A-1 CONTROL

UL 1008Transfer SwitchOr Equivalent

RegularUtility Power

Emergency Power Source

Neutral Not Shown

EPC-A-1 CONTROL

REGULARPANEL

RegularUtility Power

EMERGENCYPANEL

$

EPC-A-1

TO ADDITIONAL EPC-A-1 CONTROLS

MODEL NO.

SENSING INPUT

LOAD RATING

BALLAST LOAD RATING

INCANDESCENT LOAD

WARRANTY

EPC-A-1

120V / 277V

120V - 277V (20A)

20A (120-277V)

1200W (120V) / 1500W (277V)

5 Year Replacement Warranty

ELECTRICAL

MOUNTING

RATING

SHIPPING WEIGHT

TEMPERATURE

COLOR

SIZE (WITH MOUNTING EARS)

4-11/16” Junction Box w/ blank cover

UL94V-0 Flame Rating

8 oz.

32ºF - 140ºF (0ºC - 60ºC)

BLACK

3-3/4” x 1-3/4” x 1-1/2”