“Enhanced Housekeeping Requirements in Egress Paths in Buildings with Polystyrene”
ES&H Tier 1 Working Group Meeting Presentation
MICHAEL KRETSCHMANN PEFIRE PROTECTION ENGINEERING
February 8, 2011
JULY 2010 REPORT: ASSESSMENT OF BROOKHAVEN NATIONAL LABORATORY’S
FIRE PROTECTION PROGRAM
Finding 201 O-FP-L 1-1: Egress paths in buildings with elevated fire risks (facilities that lack automatic sprinkler protection or have exposed polystyrene foam insulation* on the HVAC ducts) are not being maintained to assure access to exits are clear, unobstructed, and unencumbered (not to hinder or impede the action or performance of).
Polystyrene
Polystyrene produces a highly intense fire and a thick black smoke. The intensity of a polystyrene fire has been proven to be
able to outrun sprinkler protection in tests.
BLDG Building Description0197 NNSD/Graphic Arts/NNDC
0459 Information Technology Division
0463 Biology
0477 Research Library
0480* Materials Science
0488 Berkner Hall
0490 Medical Research Center
0510 Physics
0515 Information Technology Division
0526 Energy Efficiency & Conservation
0535 Instrumentation Division
0555** Chemistry
0815 EENS Multiprogram Laboratory
0830 Environmental Waste Technical Center
0901 Radioisotope and Radiotracer C
0902 Magnet Division
0911 Collider Accelerator Department
0930 200 Mev Linac
NOTES
* Bldg 480 should have the Polystyrene removed with the completion of RSL I project.
** Chemistry should have the poly removed and sprinkler installed with the end of RSl II project.
Buildings with Polystyrene
Once seven foot wide, now 5 foot. What happens when doors are open and materials
are being loaded into the cabinets?
“Assure Access to Exits are Clear, Unobstructed, and Unencumbered”
When three floors of people come down the stairs, does their safety have to rely on
the bicycles staying under the stairs?
“Assure Access to Exits are Clear, Unobstructed, and Unencumbered”
Problems are not always visible from the inside.
“Assure Access to Exits are Clear, Unobstructed, and Unencumbered”
A temporary blockage can occur during a temporary fire leading to a temporary life loss.
“Assure Access to Exits are Clear, Unobstructed, and Unencumbered”
Is this worse?
(door can only swing 90 degree due to the tanks)
“Assure Access to Exits are Clear, Unobstructed, and Unencumbered”