    Gas Well Inspection Report

    1st Quarter 2014

    EnerVest

    Operating, INC

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    2/20

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    3/20

    INTRODUCTION

    Purpose:

    The exploration, development, and production of gas in the City of Arlington are activities whichnecessitate reasonable regulation to ensure that all property owners, mineral and otherwise, havethe right to peaceably enjoy their property and its benefits and revenues. During the 1

    st

    Quarter of 2014, the City of Arlington, Community Development and Planning Department(CD&P) and the City of Arlington Fire Department (AFD) conducted inspections of gas well padsites within the city limits to ensure compliance with the following: the City of Arlington GasDrilling and Production Ordinance, the Fire Prevention Ordinance and provide gas wellpermittees notice of violations on gas well pad sites.

    Authority:

    In accordance with City of Arlington Gas Drilling and Production Ordinance, Section 3.01 of

    the Inspector of the Ordinance, the City Manager shall designate officials who shall enforce the

    provisions of the Ordinance. The Inspector shall have the authority to enter and inspect anypremises covered by the provisions of the Ordinance to determine compliance with the

    provisions of the Ordinance and all applicable laws, rules, regulations, standards or directives of

    the State. The Inspector shall have the authority to issue any orders or directives required to carryout the intent and purpose of the Ordinance and its particular provisions. Failure of any person to

    comply with an y such order or directive shall constitute a violation of the Ordinance. In accordance

    with the City o f Arlington Fire Prevention Ordinance, Section 1.03, IFC 104.3 Right of Entry,whenever necessary to make an inspection to enforce any of the provisions of the Fire Code.

    Inspectors:

    Jessica Minley- Gas Well Specialist (CD&P)

    J ay White Fire Prevention Specialist (AFD)

    Collin Gregory Gas W ell Coordinator (CD&P)

    Maria Carbajal Gas Well Coordinator (CD&P)

    Page 3 of 20

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    4/20

    NOTICE OF VIOLATION LETTER

    During the dates in the reports listed below, the City of Arlington Gas Well Specialist and FirePrevention Specialist conducted compliance inspections to identify and inform EnerVest

    Operating, LLC (EnerVest) of violations on gas well pad sites within the City of Arlington.Each EnerVest site was inspected and violations documented in the reports attached.

    Section 10.01 and IFC 109.3 Penalty

    A. It shall be unlawful and an offense for any person to do the following:

    1. Engage in any activity not permitted by the terms of a Gas Well Permit issuedunder this Chapter; or the Fire Prevention Chapter.

    2. Fail to comply with any condition set forth in a Gas Well Permit issued under thisChapter or the Fire Prevention Chapter

    B. A person who violates any provision of these Chapters by performing an act prohibitedor by failing to perform an act required is guilty of a misdemeanor; each day theviolation continues shall be a separate offense.

    1. If the definition of an offense under this Chapter does not prescribe a culpablemental state, then a culpable mental state is not required. Such offense shall bepunishable by a fine not to exceed Five Hundred Dollars and No Cents ($500.00).Although not required, if a culpable mental state is in fact alleged in the charge ofthe offense and the offense governs fire safety, zoning, or public health andsanitation, including dumping of refuse, such offense shall be punishable by a fine

    not to exceed Two Thousand Dollars and No Cents ($2,000.00).

    3. If the definition of an offense under these Chapters prescribes a culpable mental stateand the offense governs fire safety, zoning, or public health and sanitation, includingdumping of refuse, then a culpable mental state is required and the offense shall bepunishable by a fine not to exceed Two Thousand Dollars and No Cents ($2,000.00).(Amended Gas Drilling and Production Ord 10-012, 1/12/10) (Amended FirePrevention Ord 12-021, 4/24/2012 )

    EnerVest Operating, LLC is hereby required, per section 5.06 (A) and (B) of the Gas

    Drilling and Production Ordinance and IFC 109.3 of the Fire Prevention Ordinance, to

    correct any noted violations on each corresponding pad site report. Failure to complywith the following stated instructions, and/ or failure to comply with the

    following stated instructions in the future will result in penalties or fines in

    accordance with the Ordinances.

    Page 4 of 20

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    5/20

    PAD SITE INSPECTION REPORTSThe following infractions are found in the Gas Drilling and Production Ordinance Chapter of the Code of the City

    Of Arlington and/ or the Fire Prevention Ordinance Chapter of the Code of the City of Arlington.

    Page 5 of 20

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    6/20

    Gas Well Inspection Form

    Signage (IFC 3406.3.7/Section 7.02) Nearest Receptor

    Address properly displayed Yards

    Well Name

    Well Number Tank Batteries/Well Head/Pipes/Other:

    Name of Operator Tank batteries 25' from well head(IFC 3406.3.1.1/ Section 7.01)

    (2) Emergency Phone Numbers Well Head 75' from street or railway( IFC 3406.3.1.1)

    No smoking signage(IFC 2703.3.1/Section 7.02) Secondary Containment System(IFC 2704.2.2/ Section 7.01)

    Hazmat Identification (IFC 3406.3.3) Lightning Arrestor System(IFC 3406.3.4.1/ Section 7.01)

    Suppression system as required by(Fire Dept IFC 3406.3.8.4)

    Security (IFC: 3406.3.9/ Section 7.01) Fire Extinguisher(IFC 3406.3.8.4)

    Fencing intact Pipe supports, bracing, foundations and anchoring(IFC 3406.3.1.5)

    Gate Locked Soundproof material non-combustible (IFC 3406.3.6)

    Gate width Dust, Odors, Vibrations(Section 7.01)

    Knox Lock Equipment Painted(Section 7.02)

    Vehicle Impact Protection(IFC 3406.3.12) Gas Lift Compressor(Section 7.01)

    Gas Processing Onsite(Section 7.01)

    Accessibility (IFC:3406.3.1.2.1/ Section 7.01) Storage of Equipment(Section 7.01)

    Entry/Approach maintained Muffling Exhaust(Section 7.01)

    24' width 8' Height Requirement (Section 7.01)

    14' high clearance Grass, Weeds, Trash(Section 7.02)

    Unobstructed access

    Fracture Stimulation Earthen Pit (Section 7.01)

    Landscaping & Perimeter Fencing(Section 7.01) Tier 1

    Tier 1 Tier2

    Tier 2

    Monitoring

    Meteorological Data Gas Detection(IFC 3406.3.8.2)

    Wind Direct GFIR Observation (IFC 3406.3.8.2)

    Temp TVA Readings in PPM (Section 7.01)

    Security Camera(IFC 3406.3.9)

    Wind Speed

    Average

    Current

    Max

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    PHASE

    Drilling Fracking Flowback Production Abandoned

    Company:

    Contact Info:

    Inspection Date:

    Time:

    SITE NAME:

    ADDRESS:

    Page 6 of 20

    Fannin Farms

    2322 Eden Rd. EnerVest

    817-477-9955

    3/10/2014

    3:50PM

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    PASS

    N/A

    PASS

    PASS

    PASS

    N/A

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    N/A

    S

    75.9F

    6.0MPH

    10.4MPH

    12.0MPH

    PASS

    N/A

    PASS

    PASS

    (IFC 3406.3.1.2.2)

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    7/20

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    8/20

    Gas Well Inspection Form

    Signage (IFC 3406.3.7/Section 7.02) Nearest Receptor

    Address properly displayed Yards

    Well Name

    Well Number Tank Batteries/Well Head/Pipes/Other:

    Name of Operator Tank batteries 25' from well head(IFC 3406.3.1.1/ Section 7.01)

    (2) Emergency Phone Numbers Well Head 75' from street or railway( IFC 3406.3.1.1)

    No smoking signage(IFC 2703.3.1/Section 7.02) Secondary Containment System(IFC 2704.2.2/ Section 7.01)

    Hazmat Identification (IFC 3406.3.3) Lightning Arrestor System(IFC 3406.3.4.1/ Section 7.01)

    Suppression system as required by(Fire Dept IFC 3406.3.8.4)

    Security (IFC: 3406.3.9/ Section 7.01) Fire Extinguisher(IFC 3406.3.8.4)

    Fencing intact Pipe supports, bracing, foundations and anchoring(IFC 3406.3.1.5)

    Gate Locked Soundproof material non-combustible (IFC 3406.3.6)

    Gate width Dust, Odors, Vibrations(Section 7.01)

    Knox Lock Equipment Painted(Section 7.02)

    Vehicle Impact Protection(IFC 3406.3.12) Gas Lift Compressor(Section 7.01)

    Gas Processing Onsite(Section 7.01)

    Accessibility (IFC:3406.3.1.2.1/ Section 7.01) Storage of Equipment(Section 7.01)

    Entry/Approach maintained Muffling Exhaust(Section 7.01)

    24' width 8' Height Requirement (Section 7.01)

    14' high clearance Grass, Weeds, Trash(Section 7.02)

    Unobstructed access

    Fracture Stimulation Earthen Pit (Section 7.01)

    Landscaping & Perimeter Fencing(Section 7.01) Tier 1

    Tier 1 Tier2

    Tier 2

    Monitoring

    Meteorological Data Gas Detection(IFC 3406.3.8.2)

    Wind Direct GFIR Observation (IFC 3406.3.8.2)

    Temp TVA Readings in PPM (Section 7.01)

    Security Camera(IFC 3406.3.9)

    Wind Speed

    Average

    Current

    Max

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    PHASE

    Drilling Fracking Flowback Production Abandoned

    Company:

    Contact Info:

    Inspection Date:

    Time:

    SITE NAME:

    ADDRESS:

    Page 8 of 20

    Lonestar

    2234 Carter St. EnerVest

    817-477-9955

    3/17/2014

    12:55PM

    N/A

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    PASS

    N/A

    PASS

    PASS

    PASS

    N/A

    PASS

    N/A

    PASS

    PASS

    N/A

    N/A

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    NW

    53.1F

    9.0MPH

    8.1MPH

    14.0MPH

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    9/20

    Gas Well Inspection Form

    Valves Site Inventory

    Automatic shut-off valve/BOP (IFC 3406.3.4) # of Wellheads

    Emergency shut-off valve(IFC 3406.3.8.2) # of Separators

    # of Storage Tanks

    Well Head Status After Fracing (Section 7.01) # of Fire Hydrants (If Applicable)

    Covered

    Completed

    Cellar filled or Closed

    Bradenhead Gauge Installed

    Vehicle Impact Protection(IFC 3406.3.12)

    Administrative

    Emergency Action Plan (IFC 3406.3.10)

    Hazardous Material Plan (IFC 3406.3.11)

    Personnel on site (if applicable)

    Credentials.

    Fire extinguisher (Applicable if personnel on-site)

    Explosives (if on site)

    Permit from Fire Marshal (Required)

    Summa Sample

    Canister #

    GPS coordinates

    Time

    Start

    Finish

    Notes:

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    SITE NAME:

    TCEQ Investigator Contacted

    Referred to Rail Road Commission

    Site Representative

    Time Date Gas Well Specialist (CD&P)

    Time Date Fire Prevention

    Specialist (Fire Department)

    Page 9 of 20

    Lonestar

    5

    5

    4

    Full Compliance

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    N/A

    12:55PM 3/17/2014 Jessica Minley

    N/A 1/21/2014 Jay White

    Inspection Verification

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    10/20

    Gas Well Inspection Form

    Signage (IFC 3406.3.7/Section 7.02) Nearest Receptor

    Address properly displayed Yards

    Well Name

    Well Number Tank Batteries/Well Head/Pipes/Other:

    Name of Operator Tank batteries 25' from well head(IFC 3406.3.1.1/ Section 7.01)

    (2) Emergency Phone Numbers Well Head 75' from street or railway( IFC 3406.3.1.1)

    No smoking signage(IFC 2703.3.1/Section 7.02) Secondary Containment System(IFC 2704.2.2/ Section 7.01)

    Hazmat Identification (IFC 3406.3.3) Lightning Arrestor System(IFC 3406.3.4.1/ Section 7.01)

    Suppression system as required by(Fire Dept IFC 3406.3.8.4)

    Security (IFC: 3406.3.9/ Section 7.01) Fire Extinguisher(IFC 3406.3.8.4)

    Fencing intact Pipe supports, bracing, foundations and anchoring(IFC 3406.3.1.5)

    Gate Locked Soundproof material non-combustible (IFC 3406.3.6)

    Gate width Dust, Odors, Vibrations(Section 7.01)

    Knox Lock Equipment Painted(Section 7.02)

    Vehicle Impact Protection(IFC 3406.3.12) Gas Lift Compressor(Section 7.01)

    Gas Processing Onsite(Section 7.01)

    Accessibility (IFC:3406.3.1.2.1/ Section 7.01) Storage of Equipment(Section 7.01)

    Entry/Approach maintained Muffling Exhaust(Section 7.01)

    24' width 8' Height Requirement (Section 7.01)

    14' high clearance Grass, Weeds, Trash(Section 7.02)

    Unobstructed access

    Fracture Stimulation Earthen Pit (Section 7.01)

    Landscaping & Perimeter Fencing(Section 7.01) Tier 1

    Tier 1 Tier2

    Tier 2

    Monitoring

    Meteorological Data Gas Detection(IFC 3406.3.8.2)

    Wind Direct GFIR Observation (IFC 3406.3.8.2)

    Temp TVA Readings in PPM (Section 7.01)

    Security Camera(IFC 3406.3.9)

    Wind Speed

    Average

    Current

    Max

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    PHASE

    Drilling Fracking Flowback Production Abandoned

    Company:

    Contact Info:

    Inspection Date:

    Time:

    SITE NAME:

    ADDRESS:

    Page 10 of 20

    Matlock Thorton

    6001 Coping Lane EnerVest

    817-477-9955

    3/10/2014

    2:40PM

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    PASS

    N/A

    PASS

    PASS

    PASS

    N/A

    PASS

    N/A

    PASS

    PASS

    N/A

    N/A

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    SSE

    75.0F

    6.0MPH

    10.4MPH

    12.0MPH

    N/A

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    11/20

    Gas Well Inspection Form

    Valves Site Inventory

    Automatic shut-off valve/BOP (IFC 3406.3.4) # of Wellheads

    Emergency shut-off valve(IFC 3406.3.8.2) # of Separators

    # of Storage Tanks

    Well Head Status After Fracing (Section 7.01) # of Fire Hydrants (If Applicable)

    Covered

    Completed

    Cellar filled or Closed

    Bradenhead Gauge Installed

    Vehicle Impact Protection(IFC 3406.3.12)

    Administrative

    Emergency Action Plan (IFC 3406.3.10)

    Hazardous Material Plan (IFC 3406.3.11)

    Personnel on site (if applicable)

    Credentials.

    Fire extinguisher (Applicable if personnel on-site)

    Explosives (if on site)

    Permit from Fire Marshal (Required)

    Summa Sample

    Canister #

    GPS coordinates

    Time

    Start

    Finish

    Notes:

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    SITE NAME:

    TCEQ Investigator Contacted

    Referred to Rail Road Commission

    Site Representative

    Time Date Gas Well Specialist (CD&P)

    Time Date Fire Prevention

    Specialist (Fire Department)

    Page 11 of 20

    Matlock Thorton

    8

    8

    3

    1

    Full Compliance

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    N/A

    2:16PM

    3/10/2014

    3/12/2014

    Jessica Minley

    Jay White

    2:40PM

    Inspection Verification

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    12/20

    Gas Well Inspection Form

    Signage (IFC 3406.3.7/Section 7.02) Nearest Receptor

    Address properly displayed Yards

    Well Name

    Well Number Tank Batteries/Well Head/Pipes/Other:

    Name of Operator Tank batteries 25' from well head(IFC 3406.3.1.1/ Section 7.01)

    (2) Emergency Phone Numbers Well Head 75' from street or railway( IFC 3406.3.1.1)

    No smoking signage(IFC 2703.3.1/Section 7.02) Secondary Containment System(IFC 2704.2.2/ Section 7.01)

    Hazmat Identification (IFC 3406.3.3) Lightning Arrestor System(IFC 3406.3.4.1/ Section 7.01)

    Suppression system as required by(Fire Dept IFC 3406.3.8.4)

    Security (IFC: 3406.3.9/ Section 7.01) Fire Extinguisher(IFC 3406.3.8.4)

    Fencing intact Pipe supports, bracing, foundations and anchoring(IFC 3406.3.1.5)

    Gate Locked Soundproof material non-combustible (IFC 3406.3.6)

    Gate width Dust, Odors, Vibrations(Section 7.01)

    Knox Lock Equipment Painted(Section 7.02)

    Vehicle Impact Protection(IFC 3406.3.12) Gas Lift Compressor(Section 7.01)

    Gas Processing Onsite(Section 7.01)

    Accessibility (IFC:3406.3.1.2.1/ Section 7.01) Storage of Equipment(Section 7.01)

    Entry/Approach maintained Muffling Exhaust(Section 7.01)

    24' width 8' Height Requirement (Section 7.01)

    14' high clearance Grass, Weeds, Trash(Section 7.02)

    Unobstructed access

    Fracture Stimulation Earthen Pit (Section 7.01)

    Landscaping & Perimeter Fencing(Section 7.01) Tier 1

    Tier 1 Tier2

    Tier 2

    Monitoring

    Meteorological Data Gas Detection(IFC 3406.3.8.2)

    Wind Direct GFIR Observation (IFC 3406.3.8.2)

    Temp TVA Readings in PPM (Section 7.01)

    Security Camera(IFC 3406.3.9)

    Wind Speed

    Average

    Current

    Max

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    PHASE

    Drilling Fracking Flowback Production Abandoned

    Company:

    Contact Info:

    Date:

    Time:

    SITE NAME:

    ADDRESS:

    Page 12 of 20

    Perr

    2825 S. Cooper St EnerVest

    817-477-9955

    3/17/2014

    2:15PM

    N/A

    PASS

    PASS

    PASS

    FAIL

    PASS

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    N/A

    PASS

    N/A

    PASS

    PASS

    N/A

    N/A

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    NW

    54.0F

    9.0MPH

    8.1MPH

    14.0MPH

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    13/20

    Gas Well Inspection Form

    Valves Site Inventory

    Automatic shut-off valve/BOP (IFC 3406.3.4) # of Wellheads

    Emergency shut-off valve(IFC 3406.3.8.2) # of Separators

    # of Storage Tanks

    Well Head Status After Fracing (Section 7.01) # of Fire Hydrants (If Applicable)

    Covered

    Completed

    Cellar filled or Closed

    Bradenhead Gauge Installed

    Vehicle Impact Protection(IFC 3406.3.12)

    Administrative

    Emergency Action Plan (IFC 3406.3.10)

    Hazardous Material Plan (IFC 3406.3.11)

    Personnel on site (if applicable)

    Credentials.

    Fire extinguisher (Applicable if personnel on-site)

    Explosives (if on site)

    Permit from Fire Marshal (Required)

    Summa Sample

    Canister #

    GPS coordinates

    Time

    Start

    Finish

    Notes:

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    SITE NAME:

    TCEQ Investigator Contacted

    Referred to Rail Road Commission

    Site Representative

    Time Date Gas Well Specialist (CD&P)

    Time Date Fire Prevention

    Specialist (Fire Department)

    Page 13 of 20

    Perr

    5

    5

    4

    Full Compliance

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    N/A

    N/A

    2:15PM

    N/A 1/22/2014 Angie Lopez

    3/17/2014 Jessica Minley

    Inspection Verification

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    14/20

    Gas Well Inspection Form

    Signage (IFC 3406.3.7/Section 7.02) Nearest Receptor

    Address properly displayed Yards

    Well Name

    Well Number Tank Batteries/Well Head/Pipes/Other:

    Name of Operator Tank batteries 25' from well head(IFC 3406.3.1.1/ Section 7.01)

    (2) Emergency Phone Numbers Well Head 75' from street or railway( IFC 3406.3.1.1)

    No smoking signage(IFC 2703.3.1/Section 7.02) Secondary Containment System(IFC 2704.2.2/ Section 7.01)

    Hazmat Identification (IFC 3406.3.3) Lightning Arrestor System(IFC 3406.3.4.1/ Section 7.01)

    Suppression system as required by(Fire Dept IFC 3406.3.8.4)

    Security (IFC: 3406.3.9/ Section 7.01) Fire Extinguisher(IFC 3406.3.8.4)

    Fencing intact Pipe supports, bracing, foundations and anchoring(IFC 3406.3.1.5)

    Gate Locked Soundproof material non-combustible (IFC 3406.3.6)

    Gate width Dust, Odors, Vibrations(Section 7.01)

    Knox Lock Equipment Painted(Section 7.02)

    Vehicle Impact Protection(IFC 3406.3.12) Gas Lift Compressor(Section 7.01)

    Gas Processing Onsite(Section 7.01)

    Accessibility (IFC:3406.3.1.2.1/ Section 7.01) Storage of Equipment(Section 7.01)

    Entry/Approach maintained Muffling Exhaust(Section 7.01)

    24' width 8' Height Requirement (Section 7.01)

    14' high clearance Grass, Weeds, Trash(Section 7.02)

    Unobstructed access

    Fracture Stimulation Earthen Pit (Section 7.01)

    Landscaping & Perimeter Fencing(Section 7.01) Tier 1

    Tier 1 Tier2

    Tier 2

    Monitoring

    Meteorological Data Gas Detection(IFC 3406.3.8.2)

    Wind Direct GFIR Observation (IFC 3406.3.8.2)

    Temp TVA Readings in PPM (Section 7.01)

    Security Camera(IFC 3406.3.9)

    Wind Speed

    Average

    Current

    Max

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    PHASE

    Drilling Fracking Flowback Production Abandoned

    Company:

    Contact Info:

    Date:

    Time:

    SITE NAME:

    ADDRESS:

    Page 14 of 20

    Rice Loh

    1801 E. Arkansas Lane EnerVest

    817-477-9955

    3/17/2014

    1:00PM

    N/A

    PASS

    PASS

    PASS

    PASS

    N/A

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    NW

    53.1F

    9.0MPH

    8.1MPH

    14.0MPH

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    15/20

    Gas Well Inspection Form

    Valves Site Inventory

    Automatic shut-off valve/BOP (IFC 3406.3.4) # of Wellheads

    Emergency shut-off valve(IFC 3406.3.8.2) # of Separators

    # of Storage Tanks

    Well Head Status After Fracing (Section 7.01) # of Fire Hydrants (If Applicable)

    Covered

    Completed

    Cellar filled or Closed

    Bradenhead Gauge Installed

    Vehicle Impact Protection(IFC 3406.3.12)

    Administrative

    Emergency Action Plan (IFC 3406.3.10)

    Hazardous Material Plan (IFC 3406.3.11)

    Personnel on site (if applicable)

    Credentials.

    Fire extinguisher (Applicable if personnel on-site)

    Explosives (if on site)

    Permit from Fire Marshal (Required)

    Summa Sample

    Canister #

    GPS coordinates

    Time

    Start

    Finish

    Notes:

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    SITE NAME:

    TCEQ Investigator Contacted

    Referred to Rail Road Commission

    Site Representative

    Time Date Gas Well Specialist (CD&P)

    Time Date Fire Prevention

    Specialist (Fire Department)

    Page 15 of 20

    Rice Loh

    7

    7

    3

    N/A

    Full Compliance

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    N/A

    1:00PM 3/17/2014 Jessica Minley

    9:00AM 3/24/2014 Jay White

    Inspection Verification

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    16/20

    Gas Well Inspection Form

    Signage (IFC 3406.3.7/Section 7.02) Nearest Receptor

    Address properly displayed Yards

    Well Name

    Well Number Tank Batteries/Well Head/Pipes/Other:

    Name of Operator Tank batteries 25' from well head(IFC 3406.3.1.1/ Section 7.01)

    (2) Emergency Phone Numbers Well Head 75' from street or railway( IFC 3406.3.1.1)

    No smoking signage(IFC 2703.3.1/Section 7.02) Secondary Containment System(IFC 2704.2.2/ Section 7.01)

    Hazmat Identification (IFC 3406.3.3) Lightning Arrestor System(IFC 3406.3.4.1/ Section 7.01)

    Suppression system as required by(Fire Dept IFC 3406.3.8.4)

    Security (IFC: 3406.3.9/ Section 7.01) Fire Extinguisher(IFC 3406.3.8.4)

    Fencing intact Pipe supports, bracing, foundations and anchoring(IFC 3406.3.1.5)

    Gate Locked Soundproof material non-combustible (IFC 3406.3.6)

    Gate width Dust, Odors, Vibrations(Section 7.01)

    Knox Lock Equipment Painted(Section 7.02)

    Vehicle Impact Protection(IFC 3406.3.12) Gas Lift Compressor(Section 7.01)

    Gas Processing Onsite(Section 7.01)

    Accessibility (IFC:3406.3.1.2.1/ Section 7.01) Storage of Equipment(Section 7.01)

    Entry/Approach maintained Muffling Exhaust(Section 7.01)

    24' width 8' Height Requirement (Section 7.01)

    14' high clearance Grass, Weeds, Trash(Section 7.02)

    Unobstructed access

    Fracture Stimulation Earthen Pit (Section 7.01)

    Landscaping & Perimeter Fencing(Section 7.01) Tier 1

    Tier 1 Tier2

    Tier 2

    Monitoring

    Meteorological Data Gas Detection(IFC 3406.3.8.2)

    Wind Direct GFIR Observation (IFC 3406.3.8.2)

    Temp TVA Readings in PPM (Section 7.01)

    Security Camera(IFC 3406.3.9)

    Wind Speed

    Average

    Current

    Max

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    PHASE

    Drilling Fracking Flowback Production Abandoned

    Company:

    Contact Info:

    Inspection Date:

    Time:

    SITE NAME:

    ADDRESS:

    Page 16 of 20

    Rolling Hills

    401 E. Lamar Blvd EnerVest

    817-477-9955

    2/5/2014

    1:34PM

    N/A

    PASS

    PASS

    PASS

    PASS

    N/A

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    NW

    30.0F

    17.0MPH

    18.4MPH

    25.0MPH

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    17/20

    Gas Well Inspection Form

    Valves Site Inventory

    Automatic shut-off valve/BOP (IFC 3406.3.4) # of Wellheads

    Emergency shut-off valve(IFC 3406.3.8.2) # of Separators

    # of Storage Tanks

    Well Head Status After Fracing (Section 7.01) # of Fire Hydrants (If Applicable)

    Covered

    Completed

    Cellar filled or Closed

    Bradenhead Gauge Installed

    Vehicle Impact Protection(IFC 3406.3.12)

    Administrative

    Emergency Action Plan (IFC 3406.3.10)

    Hazardous Material Plan (IFC 3406.3.11)

    Personnel on site (if applicable)

    Credentials.

    Fire extinguisher (Applicable if personnel on-site)

    Explosives (if on site)

    Permit from Fire Marshal (Required)

    Summa Sample

    Canister #

    GPS coordinates

    Time

    Start

    Finish

    Notes:

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    SITE NAME:

    TCEQ Investigator Contacted

    Referred to Rail Road Commission

    Site Representative

    Time Date Gas Well Specialist (CD&P)

    Time Date Fire Prevention

    Specialist (Fire Department)

    Page 17 of 20

    Rolling Hills

    6

    12( 6 sand sep.)

    4

    1

    Full Complinace

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    N/A

    3:15PM 3/17/2014 Jessica Minley

    1:34PM 2/5/2014 Jay White

    Inspection Verification

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    18/20

    Gas Well Inspection Form

    Signage (IFC 3406.3.7/Section 7.02) Nearest Receptor

    Address properly displayed Yards

    Well Name

    Well Number Tank Batteries/Well Head/Pipes/Other:

    Name of Operator Tank batteries 25' from well head(IFC 3406.3.1.1/ Section 7.01)

    (2) Emergency Phone Numbers Well Head 75' from street or railway( IFC 3406.3.1.1)

    No smoking signage(IFC 2703.3.1/Section 7.02) Secondary Containment System(IFC 2704.2.2/ Section 7.01)

    Hazmat Identification (IFC 3406.3.3) Lightning Arrestor System(IFC 3406.3.4.1/ Section 7.01)

    Suppression system as required by(Fire Dept IFC 3406.3.8.4)

    Security (IFC: 3406.3.9/ Section 7.01) Fire Extinguisher(IFC 3406.3.8.4)

    Fencing intact Pipe supports, bracing, foundations and anchoring(IFC 3406.3.1.5)

    Gate Locked Soundproof material non-combustible (IFC 3406.3.6)

    Gate width Dust, Odors, Vibrations(Section 7.01)

    Knox Lock Equipment Painted(Section 7.02)

    Vehicle Impact Protection(IFC 3406.3.12) Gas Lift Compressor(Section 7.01)

    Gas Processing Onsite(Section 7.01)

    Accessibility (IFC:3406.3.1.2.1/ Section 7.01) Storage of Equipment(Section 7.01)

    Entry/Approach maintained Muffling Exhaust(Section 7.01)

    24' width 8' Height Requirement (Section 7.01)

    14' high clearance Grass, Weeds, Trash(Section 7.02)

    Unobstructed access

    Fracture Stimulation Earthen Pit (Section 7.01)

    Landscaping & Perimeter Fencing(Section 7.01) Tier 1

    Tier 1 Tier2

    Tier 2

    Monitoring

    Meteorological Data Gas Detection(IFC 3406.3.8.2)

    Wind Direct GFIR Observation (IFC 3406.3.8.2)

    Temp TVA Readings in PPM (Section 7.01)

    Security Camera(IFC 3406.3.9)

    Wind Speed

    Average

    Current

    Max

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    PHASE

    Drilling Fracking Flowback Production Abandoned

    Company:

    Contact Info:

    Inspection Date:

    Time:

    SITE NAME:

    ADDRESS:

    Page 18 of 20

    Swapo II

    5408 US 287 HWY EnerVest

    817-477-9955

    1/28/2014

    9:45AM

    N/A

    PASS

    PASS

    PASS

    FAIL

    N/A

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    N/A

    N/A

    PASS

    PASS

    PASS

    N/A

    N/A

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    PASS

    N/A

    S

    53.1F

    13.0MPH

    12.7MPH

    18.0MPH

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    19/20

    Gas Well Inspection Form

    Valves Site Inventory

    Automatic shut-off valve/BOP (IFC 3406.3.4) # of Wellheads

    Emergency shut-off valve(IFC 3406.3.8.2) # of Separators

    # of Storage Tanks

    Well Head Status After Fracing (Section 7.01) # of Fire Hydrants (If Applicable)

    Covered

    Completed

    Cellar filled or Closed

    Bradenhead Gauge Installed

    Vehicle Impact Protection(IFC 3406.3.12)

    Administrative

    Emergency Action Plan (IFC 3406.3.10)

    Hazardous Material Plan (IFC 3406.3.11)

    Personnel on site (if applicable)

    Credentials.

    Fire extinguisher (Applicable if personnel on-site)

    Explosives (if on site)

    Permit from Fire Marshal (Required)

    Summa Sample

    Canister #

    GPS coordinates

    Time

    Start

    Finish

    Notes:

    Gas well inspections are conducted jointly by Community Development and Planning and the Fire Department.

    The section of the Fire Code and/ or Gas Well Ordinance is noted on each item.

    SITE NAME:

    TCEQ Investigator Contacted

    Referred to Rail Road Commission

    Site Representative

    Time Date Gas Well Specialist (CD&P)

    Time Date Fire Prevention

    Specialist (Fire Department)

    Page 19 of 20

    Swapo II

    1

    2

    2

    1

    All listed failures represent the condition

    of the site at the time of the inspection.

    Corrective actions taken after the ins ection

    will reflect on next quarters report.

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    N/A

    PASS

    PASS

    PASS

    PASS

    N/A

    PASS

    PASS

    PASS

    PASS

    N/A

    N/A

    N/A

    1:03PM 3/5/2014 Jessica Minley

    9:45AM 1/28/2014 Jay White

    Inspection Verification

  • 8/11/2019 EnerVest 1st Quarter Inspection Reports 2014

    20/20

    CONTACT INFORMATION

    Community Development and Planning

    101 W. Abram St.

    PO Box 90231 MS 01-0241

    Arlington, TX 76004-3231

    www.arlingtontx.gov

    Bridgett White, AICP

    Assistant Director

    817-459-6660

    [email protected]

    Collin Gregory

    Gas Well Coordinator817-459-6593

    [email protected]

    Maria Carbajal

    Gas Well Coordinator

    817-459-6661

    [email protected]

    Jessica Minley

    Gas Well Specialist

    817-459-6520Jessica. [email protected]

    Jay White

    Fire Prevention Specialist

    817-459-5523

    [email protected]

    http://www.arlingtontx.gov/http://www.arlingtontx.gov/mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:Jessica.%[email protected]:Jessica.%[email protected]:[email protected]:[email protected]:[email protected]:Jessica.%[email protected]:[email protected]:[email protected]:[email protected]://www.arlingtontx.gov/