Energy savings in industrial cooling systems

30
Rational use of energy in cooling @ LABORELEC – 13 July 2006 – 1 13/07/2006 RATIONAL USE OF ENERGY in cooling © LABORELEC

Transcript of Energy savings in industrial cooling systems

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 1

13/07/2006RATIONAL USE OF ENERGY

in cooling

© LABORELEC

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 2

Introduction

Introduction to coolingDifferent types of cooling

Dry CoolingEvaporative CoolingCompression Cooling (chiller)

Energy savings potential on cooling installationsExamplesConclusions

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 3

Why cooling?

Cooling of spaces (persons, products,…)Removing waste heat (process cooling)

INTRODUCTION

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 4

Introduction

Cooling towers

(Twater ≈ 20 °C)

Chilled water

(Twater ≈ 5 °C)

Cold rooms, etc.

(Tair ≈ -10 … - 30 °C)

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 5

Expensive form of energyMore expensive as required T° drops

⇒ Produce with the most efficient method

INTRODUCTION

=

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 6

Dry cooling

Wet cooling (by evaporation)

Compression cooling

(Absorption cooling)

(Gas expansion)

(Thermo-electric cooling)

TYPES OF COOLING

90% of applications

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 7

TYPES OF COOLING

40

35

25

20

T (°C)

EVAPORATIVE COOLING (open, closed, hybrid,…)

DRY COOLING

COMPRESSION COOLING (CHILLER)

(aircooled, watercooled)

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 8

Outside air is used to cool the mediumLimited by outside air temperature

AdvantagesNo water treatment necessary

No additional costs for water consumption

Less maintenance costs

DRY COOLING

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 9

AdvantagesReduced ground area (higher thermal power/m²)

More efficient heat exchange

Less electrical consumption

Limits set by wet bulb temperature

DisadvantagesSubstantial water consumption

Water treatment may be necessary

EVAPORATIVE COOLING

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 10

Types of cooling towersOpen cooling tower

Closed cooling tower

Evaporative condenser

Hybrid cooling tower (combination of dry and wet cooling principles)

EVAPORATIVE COOLING

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 11

Open cooling tower

EVAPORATIVE COOLING

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 12

Closed cooling tower and Evaporative condensor

EVAPORATIVE COOLING

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 13

Hybrid cooling towerDry mode (as much as possible)

Adiabatic mode (dry air temperature too high for dry cooling)

Combined dry/wet mode (max power)

AdvantagesNo water use when in dry mode, so savings on water cost

In combined dry/wet mode there is no visible plume

DisadvantagesHigh initial cost

No energy savings on electricity

EVAPORATIVE COOLING

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 14

expansion valve

evaporator

compressor

condensor

High Pressure

Liquid Gas

Low pressure

COMPRESSION COOLING

4 main components

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 15

Increase efficiency: T1 , T2

Performance of a cooling machine : COP

c

evcd

ev

electrical

evaporator

TTT

WQf

PP

COP η×−

===

With:Qf : thermal power at evaporator (kWth)W: electrical power at compressor (kW)Tev : evaporating temperature (K)Tcd: condensing temperature (K)

ηc : rendement of Carnot

Example:Tev = -5 °C (=> 268 K)Tcd = 35 °C (=> 308 K)

ηc = 0,5

COP = 3,35

COMPRESSION COOLING

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 16

ENERGY SAVINGS - 1

Optimise condensing and evaporating temperatures

Condensing temperature as low as possibleEvaporating temperature as high as possible

c

evcd

ev

electrical

evaporator

TTT

WQf

PP

COP η×−

===

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 17

ENERGY SAVINGS - 2

No exaggerated overdimensioning

Why?• To cope with reduced efficiency throughout the years• To much reserve taken in design point

Consequences:• Installation working under nominal working point• Reduced efficiency

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 18

ENERGY SAVINGS - 3

Use of frequency drivesMost of the time the drives have a reduced loadApplicable on pumps, compressors, fans

Advantages:Energy savings on electricityBetter regulation off required process value (more stable)

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 19

ENERGY SAVINGS - 4

Higher COP with direct coolingDirect cooling is the method where the evaporation is present in the medium to be cooled (for example: evaporator in cold storage rooms). No secundary fluids if possible

EVAPORATOR

HEAT EXCHANGER

-10°C

- 5°C

-5°C

0°C

Primary circuit (refrigerant)

Secundary circuit (glycol-water)

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 20

ENERGY SAVINGS - 5

Central systems often consume less energyBase load is likely to be more stable, so frequent regime changes are avoidedSometimes less efficient due to large losses in the conduits resulting from important distances between user and cold production.

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 21

ENERGY SAVINGS - 6

Use of “free cooling” if possible

Use of cooling towers during periods with lower outside temperatures. Especially interesting if cooling temperature is above 15°C

Proces

Chiller

Cooling

Tower

TsetpointOnly when outside Twb < T setpoint

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 22

ENERGY SAVINGS - 7Heat recovery (where possible)

In cooling a lot of heat is pumped from one place to another (mostly to the environment)If there are other processes which need (pre-) heating, the cooling and heating process can be combined. Example: slaughterhouse• cooling is required to cool the animal carcasses • heating of water for cleaning purposes.

Energy savings through heat recuperation: • Electrical savings as condenser load diminishes• Gas bill is smaller due to less heat required for heating

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 23

ENERGY SAVINGS - 8

Intelligent defrosting systemsDefrosting is necessary when there is ice buildup on the evaporator (for example in cold rooms on the evaporators). Ice insulates and ice buildup thus quickly reduces efficiency

2 TypesClock regulated defrosting with set durationIntelligent systems which determines moment and duration of defrost cycle

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 24

ENERGY SAVING EXAMPLES - 1Changing setpoint of cooling towers

Cooling towers

Process Process

20°CProcess

Initial situationInitial situationCooling towers

Process Process

24°CProcess

New situationNew situation

Energy savings depending Energy savings depending on size and design of on size and design of cooling tower!cooling tower!(40% in this particular case)

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 25

ENERGY SAVING EXAMPLES - 2Frequency regulation on fans of cooling tower

Cooling towers

Process Process

22°CProcess

Initial situationInitial situation

Regulation on/offCooling towers

Process Process

22°CProcess

New situationNew situation

Frequency regulation

Energy savings, depending Energy savings, depending on load profile, of up to 50%on load profile, of up to 50%

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 26

ENERGY SAVING EXAMPLES - 3Centralised regulation of chiller compressors

Compressor load = 61 % (7 CP)Compressor load = 61 % (7 CP)

All pumps ON (7 pumps)All pumps ON (7 pumps)

1

Process ProcessProcess Process

CH 1 CH 2 CH 3 CH 4 CH 5 CH 6 CH 7

Initial situationInitial situation

1

Process ProcessProcess Process

CH 1 CH 2 CH 3 CH 4 CH 5 CH 6 CH 7

Compressor load = 100 % (5 CP)Compressor load = 100 % (5 CP)

Only 5 pumps ON Only 5 pumps ON

New situationNew situation

Energy savings, dependingEnergy savings, dependingon initial load profile, of up to 10%on initial load profile, of up to 10%

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 27

ENERGY SAVING EXAMPLES - 4“Floating” condensing pressure

HP = fixed

Minimised kWh fans.Maximum kWh Compressor

HP = floating

Maximised kWh fansMinimum kWh Compressor

Energy savings of up to 30%Energy savings of up to 30%

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 28

Conclusions

Important to choose the best setpoints to control the installationNot all regulation techniques have the same energetical impactModification to current circuit can sometimes bring up significant energy savings

=> In general, the ways to optimise cooling installations are numerous

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 29

Thank you for your attention!

LABORELECRational use of energy in cooling @ LABORELEC – 13 July 2006 – 30

Questions?