Energy Saving Using Mitsubishi VFD

download Energy Saving Using Mitsubishi VFD

of 4

Transcript of Energy Saving Using Mitsubishi VFD

  • 8/11/2019 Energy Saving Using Mitsubishi VFD

    1/4

    Energy saving using Mitsubishi Inverters for Fan and Pump Application

    Automation Objective

    The reasons and benefits of energy saving are numerous and pointless to repeat here. Simply, energy

    is to be saved if it is just wasted because of inefficient process, methods of use or use of conventional

    control mechanisms. When Induction Motor is run above the required speed, energy is wasted. If

    speed is reduced to required operating condition, energy wastage is prevented.

    The induction motor is used in industries mainly for following applications:

    Centrifugal Fan (Blower)

    Pump

    Compressor

    Plastic Injection Molding Machine

    Mechanical Press

    Figure 1 Total Cost of Running Motor

    The total cost of running motor if considered (Figure 1), the more than 70 % is spend for energy bill

    and rest is for investment and maintenance cost. The core objective is to reduce the running cost by

    using Mitsubishi Inverters.

    Basic Principle

    The relationship between Power and speed of induction motor is the base of energy saving. This is

    known as Cube Low. This is derived as below:

    The 10% reduction in speed reduces 25 % power requirements which results in energy saving.

    Centrifugal Fan Application

    The centrifugal Fan is used as a blower and conventionally, flow is controlled by throttling device like

    http://www.messung.com/images/distri_ener_sav_img_01_big.jpg
  • 8/11/2019 Energy Saving Using Mitsubishi VFD

    2/4

    inlet vanes or damper while motor is running at maximum speed. The energy is wasted at flow

    regulating devices.

    Figure 2 Conventional Method

    Figure 2 Air Flow Control using VFD

    Using VFD from Mitsubishi, the induction motor speed is regulated as per the input received from flow

    sensor. Figure 3 shows the mechanism.

    Pump Application

    Similar to blower applications, conventionally, pumps are run at constant speed and flow is regulated

    by control valve as per the demand. The excess flow is bypassed to the reservoir or tank (Figure 4).

    The energy used to generate this excess flow is totally lost. The inverter controlled system removes

    the control valve and flow itself is controlled by manipulating speed of pump as per the input of flow

    sensor and desired set point (Figure 5). Here, no need to bypass or divert excess flow and hence there

    is an energy saving.

    Figure 3 Conventional Flow Control Figure 4 Flow Control using Inverter

  • 8/11/2019 Energy Saving Using Mitsubishi VFD

    3/4

    Inverter Selection

    Centrifugal Fan and Pump are used for variable torque loads and need low starting torque. Hence VFD

    with 110% overload capacity is adequate. Further, while selecting the drive, motor Full Load Ampere

    (FLA) should be considered rather than motor KW.

    Application Area

    The major potential areas of energy saving using Mitsubishi drives are:

    HVAC systems AHUs, Pumps and Chillers, Cooling Towers (Pharmaceutical and Bio-Tech

    Installations, IT Parks, Hospitals, Theaters, Commercial Malls, etc)

    Paint Shops in Automotive Industries

    All utility management centers across the Industry

    Cold storage installations

    Boilers (ID,FD Fans)

    Advantages of Mitsubishi Inverters

    The Mitsubishi VFDs are perfect selection for energy saving applications since it offers following

    features:

    Electronic protection of motor

    High Starting Torque

    Soft Starting & Stopping reduces mechanical

    stresses

    Optimum excitation control

    Energy saving mode

    PID control

    Energy/Cost saving monitoring

    Electronic bypass for changeover

    Built-in PLC in A700 series

    Multiple overload rating according to

    application

    Diagnostic Capabilities in VFD

    Interface With Main SCADA System

    Supports all major Field Buses

    - Profibus- DP,- DeviceNet,

    - CC link,

    - LonWorks

    Modbus RTU as standard feature

    Achievements

    Over 4000 installations for energy saving for Fan and Pump applications are completed for Automotive

    (Paint Shops of all major automotive manufacturers), Sugar, Pharmaceuticals and others.

    Case study: Cooling Tower Pump

    This is the case study of energy saving using Mitsubishi Drive for cooling tower pump for leading dairy

    product manufacturer.

    Inverter Model : FR-A540-11K

    Power Rating : 11KW

    Parameter Settings : LOAD PATTERN SELECTION Pr 14 = 1 (for Variable Torque Load)

  • 8/11/2019 Energy Saving Using Mitsubishi VFD

    4/4

    Following readings are taken for actual operation at full load for calculation of power demand

    reduction:

    Frequency

    (Hz)

    I/P POWER

    (kW)

    O/P CURRENT (A) % Speed

    Reduction

    %Power

    Reduction

    50 8.32 18.9 0 0

    47.5 7.15 18.3 5 14

    45

    42.5

    6

    5.05

    16.6

    15.7

    10

    15

    27

    39

    40 4.16 14.4 20 50

    37.5 3.42 13.7 25 59

    35 2.73 12.5 30 67

    32.5 2.19 11.5 35 73

    30 1.68 10 40 79

    The actual load is operated with 40 HZ frequency and hence there is a 20% reduction in speed

    resulting in 50% reduction in power demand.

    Calculation of saving and payback period:

    Per Hour power saving for 20 hour per day run = (Full Load Actual Load)x20 KWH

    = (8.32 4.16)x20 KWH

    = 83.2 KWH

    Power saving per year for 300 days operation = 83.2 x 300

    = 24960 KWH

    Using per unit charges for energy bill, per year saving can be calculated.

    The investment cost is recovered within 9 moths for this application.