Enclosed switches PLASTIC - 1SCC340005C0201
Click here to load reader
-
Upload
olatunji-oluwagbenga -
Category
Documents
-
view
58 -
download
3
Transcript of Enclosed switches PLASTIC - 1SCC340005C0201
Plastic enclosed switchesand safety switches
Low Voltage Products
Catalogue OTP10GB 03_111SCC340005C0201
Kansikuva
2
S01
087A • Pull stoppers for
two rubber cables
Easy to install
N
S01
074A
S01
072A
• Knock-outopenings forM or Pg threadson the Top andBottom
• Terminals for 5-wiresystem: three phases +N + PE terminals
3
S01
077A
• Separate threaded knock-out openingfor control wires on the top andbottom
Easy to mount•
•
•
•
••
••
•
•
Material standards: IEC 60529 andUL 50 for the enclosureStandard IEC 60947-3 for Switch-DisconnectorsEuropean Standard EN60204Safety of machinery
Cable outlets M or Pg sizedthreaded knock-outsAlso blank end plates availableThe biggest size knock-out forB-flange3-, 4- and 6-pole versionsHandle indication O-I as well asON-OFFIP65-rating, IP20 when a coveropenedSuitable for 4-wire as well as5-wire systems
Other features:
Standards:
ABB
S01
080A
• Optional sealingof the lid
I ON
OOFFS
0107
6A
S01
079A
• Knock-out opening on thebase for incoming cables
S01
078A
• Enclosure mountingscrews isolated fromthe inside housing
•
•
•
•
The rated impulse withstand voltageand air gap exceed the requirementsfor disconnectors in isolation classesIII and/or IV.The position indication is in all casesreliable.It is not possible to lock a handle ofan ABB-switch in the O-position,unless the required isolation isensured.The rated impulse withstand voltageUimp not less than 8 kV is printed inthe type plate.
• Option for two early-break auxiliary contacts
1 N.O. +1 N.C.2 N.O.2 N.C.
In safety switchesauxiliary contacts areincluded to the deliveryaccording to the orderinginformation tables.
4
Safety for personnel
• Door Interlock inON-position
• Door Interlockdefeatable (withrectangular handle)
• Cover cannot beremoved if a handleis padlocked
I ON
O OFF
I ON
O OFF
I ON
O OFF
OO
FF
I ON
OO
FF
I ON
ABB Control
ABB Control
S01
073A
Reliable position indication
• Handle options• Black / white• Red / yellow• Round / rectangular legend plate • Three and four-pole isolation
in same enclosure
The position of the handle indicates with complete reliability the exact position of thecontacts in all circumstances. The switch mechanism is constructed so that thehandle cannot indicate the off position if one of the contacts has been weldedtogether.
O O
FF
I ON
O O
FF
I ON
OO
FF
I ON
OO
FF
I ON
S01
088A
Padlocking with three padlocks againstunintentional star-up.
The handle can not be padlocked in theO-position if one of the contacts is not in theOFF-position.It is not possible to lock the handle in theO-position if one of the contacts is not inthe open (OFF)position.
OOFF
I ON
OOFF
I ON
S01
075A
5
O O
FF
I ON
S01
082A
Plastic enclosed installation switches, white enclosure, 3-pole, IP65Cable entries from top and bottom
Type Rated operational Cable outlets Enclosure Weight Order numbercurrent [A] / side W / H / D
AC-22A AC-23A AC-23A [mm] [kg]≤500V ≤415V 500V
White round handleIncludes white round handle (O-I and ON-OFF indication), N- and PE-terminals and in typeOTP 16HB3P and _B3M_ membrane cable glands (2 pcs) and pull stoppers (2pcs).OTP16HB3M 16 16 16 2xM20 85 / 120 / 60 0.40 1SCA022401R2970OTP16HB3M25 16 16 16 2 x M25 85 / 120 / 60 0.40 1SCA022699R3690OTP16HB3P 16 16 16 2xPg16 85 / 120 / 60 0.40 1SCA022389R6700OTP16HB3U 16 16 16 - 85 / 120 / 60 0.40 1SCA022401R3010
Knock-out flanges, flanges have to be ordered separately.
OTP80BA3B 80 55 32 Flange I 200 / 400 / 140 2.40 1SCA022389R7340OTP80BA3U 80 55 32 - 200 / 400 / 140 2.40 1SCA022401R3860OTP125BA3B 125 90 70 Flange I 200 / 400 / 140 2.40 1SCA022389R7420OTP125BA3U 125 90 70 - 200 / 400 / 140 2.40 1SCA022401R3940
Includes selector-type rectangular red-yellow handle (O-I and ON-OFF indication), N- and PE-terminals. Threaded knock-outs, compression glands have to be ordered separately.OTP25BA3M 25 20 20 2xM25 + M16 130 / 150 / 60 0.50 1SCA022401R3430OTP25BA3P 25 20 20 2xPg21+Pg11 130 / 150 / 60 0.50 1SCA022389R6960OTP32BA3M 32 23 23 2xM25 + M16 130 / 150 / 60 0.50 1SCA022401R3510OTP32BA3P 32 23 23 2xPg21+Pg11 130 / 150 / 60 0.50 1SCA022389R7000OTP45BA3M 45 30 30 2xM32 + M16 145 / 200 / 90 0.90 1SCA022401R3600OTP45BA3P 45 30 30 2xPg29 + Pg11 145 / 200 / 90 0.90 1SCA022389R7180OTP63BA3M 63 38 32 2xM32 + M16 145 / 200 / 90 0.90 1SCA022401R3780OTP63BA3P 63 38 32 2xPg29 + Pg11 145 / 200 / 90 0.90 1SCA022389R7260
Knock-out flanges, flanges have to be ordered separately.
OTP80B3B 80 55 32 Flange I 200 / 400 / 140 2.40 1SCA022389R7690OTP80B3U 80 55 32 - 200 / 400 / 140 2.40 1SCA022401R3190OTP125B3B 125 90 70 Flange I 200 / 400 / 140 2.40 1SCA022383R3700OTP125B3U 125 90 70 - 200 / 400 / 140 2.40 1SCA022401R3270
Includes selector-type rectangular black handle (O-I and ON-OFF indication), N- and PE-terminals.Threaded knock-outs, compression glands have to be ordered separately.OTP25B3M 25 20 20 2xM25 + M16 130 / 150 / 60 0.5 1SCA022383R2640OTP25B3P 25 20 20 2xPg21+Pg11 130 / 150 / 60 0.5 1SCA022383R2560OTP32B3M 32 23 23 2xM25 + M16 130 / 150 / 60 0.5 1SCA022389R8400OTP32B3P 32 23 23 2xPg21 + Pg11 130 / 150 / 60 0.5 1SCA022389R7510OTP45B3M 45 30 30 2xM32 + M16 145 / 200 / 90 0.9 1SCA022383R3020OTP45B3P 45 30 30 2xPg29 + Pg11 145 / 200 / 90 0.9 1SCA022383R2990OTP63B3M 63 38 32 2xM32 + M16 145 / 200 / 90 0.9 1SCA022383R3450OTP63B3P 63 38 32 2xPg29 + Pg11 145 / 200 / 90 0.9 1SCA022383R3370
Black handleIncludes selector-type rectangular black handle (O-I and ON-OFF indication), N- and PE-terminals.In types OTP 16B3_ also membrane cable glands (2 pcs) and pull stoppers (2 pcs) are included.OTP16B3M 16 16 16 2xM20 85 / 120 / 60 0.40 1SCA022383R2130OTP16B3M25 16 16 16 2 x M25 85 / 120 / 60 0.40 1SCA022699R2880OTP16B3P 16 16 16 2xPg16 85 / 120 / 60 0.40 1SCA022383R0940
Plastic enclosed load break switches, grey enclosure, 3-pole, IP65Cable entries from top and bottom
Type Rated operational Cable outlets Enclosure Weight Order numbercurrent [A] / side W / H / D
AC-22A AC-23A AC-23A [mm] [kg]≤500V ≤415V 500V
SafeLineEnclosed Load Break SwitchesOrdering Information
OO
FF
I ON
S01
085A
OTP 16H_
OTP 16B_
OTP 80...125B_
OTP 25...32B_
O O
FF
I ON
S006
96A
O O
FF
I ON
S009
87A
OTP 45...63B_
O O
FF
I ON
S00
692A
Red-yellow handleIncludes selector-type rectangular red-yellow handle (O-I and ON-OFF indication), N- and PE-termi-nals. In types OTP 16BA3_ also membrane cable glands, (2 pcs) and pull stoppers (2pcs) areincluded.OTP16BA3M 16 16 16 2xM20 85 / 120 / 60 0.40 1SCA022401R3350OTP16BA3M25 16 16 16 2 x M25 85 / 120 / 60 0.40 1SCA022699R2960OTP16BA3P 16 16 16 2xPg16 85 / 120 / 60 0.40 1SCA022389R6880
O O
FF
I ON
S01
083A
OTP 16BA_
6
SafeLineEnclosed Load Break SwitchesOrdering Information
OTP 16...32B_
O O
FF
I ON
S006
96A
O O
FF
I ON
S009
87A
OTP 45...63B_
OTP 80...125B_
O O
FF
I ON
S00
692A
Plastic enclosed load break switches, grey enclosure, 4-pole, IP65Cable entries from top and bottomType Rated operational 1) Cable outlets Enclosure Weight Order number
current [A] / side W / H / DAC-22A AC-23A AC-23A [mm] [kg]≤500V ≤415V 500V
Includes selector-type rectangular black handle (O-I and ON-OFF indication), N- and PE-terminalsThreaded knock-outs, compression glands have to be ordered separatelyOTP16B4M 16 16 16 2xM25 + M16 130 / 150 / 60 0.60 1SCA022401R4160OTP16B4P 16 16 16 2xPg21+Pg11 130 / 150 / 60 0.60 1SCA022419R8620OTP25B4M 25 20 20 2xM25 + M16 130 / 150 / 60 0.60 1SCA022401R4320OTP25B4P 25 20 20 2xPg21 + Pg11 130 / 150 / 60 0.60 1SCA022401R4240OTP32B4M 32 23 23 2xM25 + M16 130 / 150 / 60 0.60 1SCA022401R4590OTP32B4P 32 23 23 2xPg21+Pg11 130 / 150 / 60 0.60 1SCA022401R4410OTP45B4M 45 30 30 2xM32 + M16 145 / 200 / 90 1.00 1SCA022401R4750OTP45B4P 45 30 30 2xPg29 + Pg11 145 / 200 / 90 1.00 1SCA022401R4670OTP63B4M 63 38 32 2xM32 + M16 145 / 200 / 90 1.00 1SCA022401R4910OTP63B4P 63 38 32 2xPg29 + Pg11 145 / 200 / 90 1.00 1SCA022401R4830Knock-out flanges, flanges have to be ordered separatelyOTP80B4B 80 55 32 Flange I 200 / 400 / 140 2.50 1SCA022401R5050OTP80B4U 80 55 32 - 200 / 400 / 140 2.50 1SCA022401R5130OTP125B4B 125 90 70 Flange I 200 / 400 / 140 2.50 1SCA022401R5210OTP125B4U 125 90 70 - 200 / 400 / 140 2.50 1SCA022401R5300Includes selector-type rectangular red-yellow handle (O-I and ON-OFF indication), N- and PE-terminalsThreaded knock-outs, compression glands have to be ordered separatelyOTP16BA4M 16 16 16 2xM25 + M16 130 / 150 / 60 0.60 1SCA022459R6510OTP25BA4M 25 20 20 2xM25 + M16 130 / 150 / 60 0.60 1SCA022459R6600OTP32BA4M 32 23 23 2xM25 + M16 130 / 150 / 60 0.60 1SCA022459R6780OTP45BA4M 45 30 30 2xM32 + M16 145 / 200 / 90 1.00 1SCA022459R6860OTP63BA4M 63 38 32 2xM32 + M16 145 / 200 / 90 1.00 1SCA022459R6940
Plastic enclosed load break switches, grey enclosure, 6-pole, IP65Cable entries from top and bottomType Rated 1) Cable outlets Enclosure Weight Order number
operational current [A] / side W / H / DAC 22A AC 23A AC 23A [mm] [kg]
≤500V ≤415V 500V
Includes selector-type rectangular black handle (O-I and ON-OFF indication), N- and PE-terminalsThreaded knock-outs, compression glands have to be ordered separatelyOTP16B6M 16 16 16 2xM25 + M16 130 / 150 / 85 0.70 1SCA022401R5560OTP16B6P 16 16 16 2xPg21+Pg11 130 / 150 / 85 0.70 1SCA022401R5480OTP25B6M 25 20 20 2xM25 + M16 130 / 150 / 85 0.70 1SCA022401R5720OTP25B6P 25 20 20 2xPg21 + Pg11 130 / 150 / 85 0.70 1SCA022401R5640OTP32B6M 32 23 23 2xM25 + M16 130 / 150 / 85 0.70 1SCA022401R5990OTP32B6P 32 23 23 2xPg21+Pg11 130 / 150 / 85 0.70 1SCA022401R5810Includes pistol-type black handle (O-I and ON-OFF indication), N- and PE-terminalsThreaded knock-outs, compression glands have to be ordered separatelyOTP45B6M 45 30 30 2xM32 + M16 145 / 200 / 90 1.20 1SCA022401R6110OTP45B6P 45 30 30 2xPg29 + Pg11 145 / 200 / 90 1.20 1SCA022401R6020OTP63B6M 63 38 32 2xM32 + M16 145 / 200 / 90 1.20 1SCA022401R6370OTP63B6P 63 38 32 2xPg29 + Pg11 145 / 200 / 90 1.20 1SCA022401R6290Knock-out flanges, flanges have to be ordered separatelyOTP80B6B 80 55 32 Flange I 200 / 400 / 140 3.20 1SCA022401R6450OTP80B6U 80 55 32 - 200 / 400 / 140 3.20 1SCA022401R6530OTP125B6B 125 90 70 Flange I 200 / 400 / 140 3.20 1SCA022401R6610OTP125B6U 125 90 70 - 200 / 400 / 140 3.20 1SCA022401R6700Includes selector-type rectangular red-yellow handle (O-I and ON-OFF indication), N- and PE-terminalsThreaded knock-outs, compression glands have to be ordered separatelyOTP16BA6M 16 16 16 2xM25 + M16 130 / 150 / 85 0.70 1SCA022401R6880OTP16BA6P 16 16 16 2xPg21+Pg11 130 / 150 / 85 0.70 1SCA022394R5330OTP25BA6M 25 20 20 2xM25 + M16 130 / 150 / 85 0.70 1SCA022401R6960OTP25BA6P 25 20 20 2xPg21+Pg11 130 / 150 / 85 0.70 1SCA022394R5410OTP32BA6M 32 23 23 2xM25 + M16 130 / 150 / 85 0.70 1SCA022401R7000OTP32BA6P 32 23 23 2xPg21+Pg11 130 / 150 / 85 0.70 1SCA022394R5680Includes pistol-type red-yellow handle (O-I and ON-OFF indication), N- and PE-terminalsThreaded knock-outs, compression glands have to be ordered separatelyOTP45BA6M 45 30 30 2xM32 + M16 145 / 200 / 90 1.20 1SCA022401R7180OTP45BA6P 45 30 30 2xPg29 + Pg11 145 / 200 / 90 1.20 1SCA022394R5840OTP63BA6M 63 38 32 2xM32 + M16 145 / 200 / 90 1.20 1SCA022401R7260OTP63BA6P 63 38 32 2xPg29 + Pg11 145 / 200 / 90 1.20 1SCA022394R5760Knock-out flanges, flanges have to be ordered separatelyOTP80BA6B 80 55 32 Flange I 200 / 400 / 140 3.20 1SCA022401R7340OTP80BA6U 80 55 32 - 200 / 400 / 140 3.20 1SCA022401R7420OTP125BA6B 125 90 70 Flange I 200 / 400 / 140 3.20 1SCA022401R7510OTP125BA6U 125 90 70 - 200 / 400 / 140 3.20 1SCA022401R7690
OTP 80...125B_
OTP 45...63B_
S00
768A
NOI
OO
FF
O O
FF
I ON
S00
560A
b
NOI
OO
FF
7
Includes N- and PE-terminals, 2 membrane cable glands, 2 pull stoppers, round white handle and auxiliarycontacts according to table. Type _/10 = 10 pcs package.
Type Max.motor output/ Cable outlets/side Includes Weight Order numberAC 23A auxiliary
230V 400V 500V 690V contacts[kW] [kW] [kW] [kW] [kg]
OTP 16H3P1 5.5 7.5 7.5 7.5 2xPg16 -* 0.4 1SCA022371R2400OTP 16H3P1/10 5.5 7.5 7.5 7.5 2xPg16 -* 4.0 1SCA022373R1700OTP 16H3P 5.5 7.5 7.5 7.5 2xPg16 1no* 0.4 1SCA022371R2310OTP 16H3P/10 5.5 7.5 7.5 7.5 2xPg16 1no* 4.0 1SCA022373R1610OTP16H3M1 5.5 7.5 7.5 7.5 2xM20 -* 0.4 1SCA022432R1090OTP16H3M1/10 5.5 7.5 7.5 7.5 2xM20 -* 4.0 1SCA022608R9750OTP16H3M 5.5 7.5 7.5 7.5 2xM20 1no* 0.4 1SCA022608R8190OTP16H3M/10 5.5 7.5 7.5 7.5 2xM20 1no* 4.0 1SCA022608R9240OTP16H3M25 5.5 7.5 7.5 7.5 2xM25 1no* 0.4 1SCA022699R3000OTP16H3M25/10 5.5 7.5 7.5 7.5 2xM25 -* 4.0 1SCA022699R3180OTP16H3M251 5.5 7.5 7.5 7.5 2xM25 1no* 0.4 1SCA022699R3340OTP16H3M251/10 5.5 7.5 7.5 7.5 2xM25 -* 4.0 1SCA022699R3420
Plastic enclosed safety switches, 3-pole, IP 65
OTP 16K_
O O
FF
I ON
S006
96A
O O
FF
I ON
S01
082A
OTP 16T_OTP 25T_OTP 36T_OTP 63T_
OTP 16H_
OO
FF
I ON
ABB Control
S00
691A
O O
FF
I ON
S00
692A
OTP 75T_OTP 90T_
OO
FF
I ON
S006
94A
OTP 16HT_
Installation safety switches, white enclosure (RAL9001)
SafeLineSafety SwitchesOrdering Information
Cable entries from top and bottom
Includes N- and PE-terminals, 2 membrane cable glands, 2 pull stoppers, handle and auxiliary contactsaccording to table. Type _/10 = 10 pcs/package.Round black handle
OTP 16HT3P1 5.5 7.5 7.5 7.5 2xPg16 -* 0.4 1SCA022385R5180OTP 16HT3P1/10 5.5 7.5 7.5 7.5 2xPg16 -* 4.0 1SCA022385R5260OTP 16HT3P 5.5 7.5 7.5 7.5 2xPg16 1no* 0.4 1SCA022385R5340OTP 16HT3P/10 5.5 7.5 7.5 7.5 2xPg16 1no* 4.0 1SCA022385R5420OTP16HT3M 5.5 7.5 7.5 7.5 2xM20 1no* 0.4 1SCA022400R9410OTP16HT3M/10 5.5 7.5 7.5 7.5 2xM20 1no* 4.0 1SCA022641R7510OTP16HT3M1 5.5 7.5 7.5 7.5 2xM20 -* 0.4 1SCA022400R9320OTP16HT3M1/10 5.5 7.5 7.5 7.5 2xM20 -* 4.0 1SCA022641R7600OTP16HT3M25 5.5 7.5 7.5 7.5 2xM25 1no* 0.4 1SCA022699R3770OTP16HT3M25/10 5.5 7.5 7.5 7.5 2xM25 1no* 4.0 1SCA022699R3850OTP16HT3M251 5.5 7.5 7.5 7.5 2xM25 -* 0.4 1SCA022699R4070OTP16HT3M251/10 5.5 7.5 7.5 7.5 2xM25 -* 4.0 1SCA022699R4150
Rectangular black selector-type handleOTP 16K3P1 5.5 7.5 7.5 7.5 2xPg16 -* 0.4 1SCA022371R2230OTP 16K3P 5.5 7.5 7.5 7.5 2xPg16 1no* 0.4 1SCA022371R2150OTP16K3M1 5.5 7.5 7.5 7.5 2xM20 -* 0.4 1SCA022400R9750OTP16K3M 5.5 7.5 7.5 7.5 2xM20 1no* 0.4 1SCA022400R9830OTP16K3M25 5.5 7.5 7.5 7.5 2xM25 1no* 0.4 1SCA022699R4310OTP16K3M251 5.5 7.5 7.5 7.5 2xM25 -* 0.4 1SCA022699R4400
Includes N- and PE-terminals, black selector-type handle (I-O, ON-OFF indication) and auxiliary contactsaccording to table.
Type Max.motor output/ Cable outlets/side Includes Weight Order numberAC 23A auxiliary
230V 400V 500V 690V contacts[kW] [kW] [kW] [kW] [kg]
Threaded knock-outs, compression glands have to be ordered separately
OTP 16T3P 5.5 7.5 7.5 7.5 2xPg21+Pg11 1no** 0.5 1SCA022371R1770OTP 25T3P 7.5 15 15 15 2xPg29+Pgg11 1no** 0.9 1SCA022371R2580OTP 36T3P 11 18.5 18.5 15 2xPg29+Pg11 1no** 0.9 1SCA022371R2740OTP16T3M 5.5 7.5 7.5 7.5 2xM25+M16 1no** 0.5 1SCA022400R9910OTP25T3M 7.5 15 15 15 2xM32+M16 1no** 0.9 1SCA022401R0090OTP36T3M 11 18.5 18.5 15 2xM32+M16 1no** 0.9 1SCA022401R0170OTP63T3M 18.5 30 30 30 2xM32+M16 1no** 1.0 1SCA022608R2910Knock-out flanges, flanges have to be ordered separatelyOTP 75T3B 22 37 37 37 I-Flange 1no** 2.4 1SCA022371R2910OTP 90T3B 22 45 45 45 I-Flange 1no** 2.4 1SCA022429R3450
Industrial safety switches, grey enclosure
Installation safety switches, grey enclosure
* Max 1no+1nc ** Max 2no+2nc
The technical data and dimensions are valid at thetime of printing. We reserve the right to subsequentalterations.
The operations of the manufacturing plant have been certified.Low Voltage ProductsP.O. Box 622FIN-65101 VAASA, FinlandTelephone +358 10 22 11Telefax +358 10 22 45708www.abb.com/lvswitches
Cat
alog
ue O
TP
10G
B 0
3_11
1SC
C34
0005
C02
01W
aasa
Gra
phic
s O
y, V
aasa
ABB Oy
O O
FF
I ON
S006
96A
OTP 16T_OTP 25T_OTP 36T_
O O
FF
I ON
S00
692A
OTP 75T_OTP 90T_
Includes N- and PE-terminals, black selector-type handle (I-O, ON-OFF indication) and auxiliary contactsaccording to table.
Type Max.motor output/ Cable outlets/side Includes Weight Order numberAC 23A auxiliary
230V 400V 500V 690V contacts[kW] [kW] [kW] [kW] [kg]
Threaded knock-outs, compression glands have to be ordered separatelyOTP 16T4P 5.5 7.5 7.5 7.5 2xPg21+Pg11 1no** 0.53 1SCA022383R0510OTP 25T4P 7.5 15 15 15 2xPg29+Pg11 1no** 0.96 1SCA022383R0600OTP 36T4P 11 18.5 18.5 15 2xPg29+Pg11 1no** 0.96 1SCA022383R0780OTP16T4M 5.5 7.5 7.5 7.5 2xM25+M16 1no** 0.53 1SCA022401R0500OTP25T4M 7.5 15 15 15 2xM32+M16 1no** 0.96 1SCA022401R0680OTP36T4M 11 18.5 18.5 15 2xM32+M16 1no** 0.96 1SCA022401R0760Knock-out flanges, flanges have to be ordered separatelyOTP 75T4B 22 37 37 37 I-Flange 1no** 2.5 1SCA022383R0860OTP 90T4B 22 45 45 45 I-Flange 1no** 2.5 1SCA022430R1310
Plastic enclosed safety switches, 4-pole, IP 65Cable entries from top and bottom
Plastic enclosed safety switches, 6-pole, IP 65Cable entries from top and bottomIncludes N and PE-terminal, black pistol type handle, selector-type handle in OTP16_ (I-O, ON-OFFindication) and auxiliary contacts according to table.
Type Max.motor output/ Cable outlets/side Includes Weight Order numberAC 23A auxiliary
230V 400V 500V 690V contacts[kW] [kW] [kW] [kW] [kg]
Threaded knock-outs, compression glands have to be ordered separatelyOTP 16T6P 5.5 7.5 7.5 7.5 2xPg21+Pg11 1no* 0.7 1SCA022371R2070OTP 25T6P 7.5 15 15 15 2xPg29+Pg11 1no* 1.2 1SCA022371R2660OTP 36T6P 11 18.5 18.5 15 2xPg29+Pg11 1no* 1.2 1SCA022371R2820OTP16T6M 5.5 7.5 7.5 7.5 2xM25+M16 1no* 0.7 1SCA022401R1730OTP25T6M 7.5 15 15 15 2xM32+M16 1no* 1.2 1SCA022401R1810OTP36T6M 11 18.5 18.5 15 2xM32+M16 1no* 1.2 1SCA022401R1900Knock-out flanges, flanges have to be ordered separatelyOTP 75T6B 22 37 37 37 I-Flange 1no** 3.2 1SCA022371R3040OTP 90T6B 22 45 45 45 I-Flange 1no** 3.2 1SCA022430R2380
SafeLineSafety SwitchesOrdering Information
* Max 1no+1nc ** Max 2no+2nc