Enabling Wellbeing 1. Halton - Enabling Wellbeing Halton was established in 1969 Family owned...

25
Enabling Wellbeing 1

Transcript of Enabling Wellbeing 1. Halton - Enabling Wellbeing Halton was established in 1969 Family owned...

Enabling Wellbeing

1

Halton - Enabling Wellbeing 

Halton was established in 1969 Family owned company, operating in 23 countries. We are passionate about indoor environments. We offer business enhancing products, systems, and services for

comfortable, energy efficient, and safe environments. .

Enabling Wellbeing

Strategic Business Areas

• Halton Foodservice: Inspiring kitchen environments • Halton Indoors: Makes work a breeze• Halton Marine: Safe and seaworthy• Halton Clean Air: A clean advantage• Halton New Ventures: Ensuring wellbeing

Enabling Wellbeing

HaltonHalton’’s Duct Monitoring and s Duct Monitoring and Safety System - KGSSafety System - KGS

KGS – Kitchen Grease Sensor

Energy efficiency

IEQ

Airpurification Safety

HPK

Capture Jet technology

Capture Ray technology

Water Wash technology

Low velocity supply

Fire suppressionShow kitchen solutions

KDS Systems

Ecology Units

Capture Jet hoods and ceilings

KSA Filters M.A.R.V.E.L.F.O.R.M.

Halton Strategy for High Performance Kitchen

KGS – Kitchen Grease Sensor

Grease Sensor

KGS – Kitchen Grease Sensor

System Layouts 6

What is the Duct Monitoring and Safety System (KGS)?

• A signaling device that monitors the grease deposition levels in all monitored duck work and hood exhaust plenums.

• Once the level of grease exceeds the set point threshold an alarm is displayed on the system console alerting the operator that the ductwork needs to be cleaned based on NFPA96 guidelines.

• Provides an indication whether the cleaning was done satisfactorily.• System consists of one or more panels containing the controls and

a display console; grease sensors located in the exhaust plenum of a hood and the exhaust ducts.

• Compatible for use with new or existing ductwork

KGS – Kitchen Grease Sensor

Listings

Grease Sensor Assembly•UL710 / ULC S646•Covers grease penetration in ductwork•Label will be stamped to the outer surface of the the reflector

KGS Duct Safety Monitoring System•ETL listed to UL 2017 general purpose signaling device and systems•Covers system as a whole•There is no label as each part follows individual certification markings

KGS – Kitchen Grease Sensor

Control Panel – Inside View

KGS – Kitchen Grease Sensor

Grease Sensor in Duct – Outside View

Glass for demonstration purposes only

KGS – Kitchen Grease Sensor

Grease Sensor in Duct – Inside View

Grease Sensor

KGS – Kitchen Grease Sensor

Grease Sensor Assembly

KGS – Kitchen Grease Sensor

Sensor Access13

KGS – Kitchen Grease Sensor

Grease Sensor

Duct “by others”

Hex NutM 18 Internal Tooth Lock Washer

Reflector

To KGS Control Panel – Maximum 100 feet from control panel

Grease Sensor

Hex Nut

Gasket

18 mm (45/64” Hole

Air Flow

KGS – Kitchen Grease Sensor

Grease Sensor Cable Connections

KGS – Kitchen Grease Sensor

Console Interface

Power Light Sensor Lights Active Sensor Button

Cleaning Due Button

Active Sensor Alarm Light Cleaning Due

Alarm Light

Connect to PDA

Button

Connection Alarm Light

KGS – Kitchen Grease Sensor

Sensors

Active sensors will remain a steady light when no alarms are active.

KGS – Kitchen Grease Sensor

Active Sensor Alarm Light

If Active Sensor Alarm Light is on, this indicates that there is a problem with an actual sensor.

KGS – Kitchen Grease Sensor

Cleaning Due

If Cleaning Due Alarm light is solid red, then cleaning is required. Once the Cleaning Due Button is pressed, all active sensors that require cleaning will begin to flash green.

KGS – Kitchen Grease Sensor

KGS – Kitchen Grease Sensor

Master Display Panel Slave Panel

Remote Display Panel

KGS – Kitchen Grease Sensor

Installation• From design layout, locate each grease sensor and drill a 18mm hole in the duct

work.

– Location should be in the vertical section of the ductwork. If you have to put in horizontal sections in the ductwork, avoid the bottom area.

– If access panels are not available, you may need to cut an opening in the ductwork to accommodate a UL listed access panel

• Locate and position Master Control Panel and the Slave and/or Remote Display if equipped. Keep in mind that the distance between the sensors and/or Master/Slave can not exceed 100 ft. The maximum distance between the Master, Slave, and/or Remote Display Panel is 300 ft.

• Run and connect each grease sensor cable to the panel. Each sensor will be labeled to match terminal location in panel

• Connect 120V power to the panel

• Test system for power as well as ensuring that each sensor is online

KGS – Kitchen Grease Sensor

KGS – Kitchen Grease Sensor

System Layouts

Duct Monitoring and Safety System for Ecology

KGS – Kitchen Grease Sensor

Service and Maintenance

• The KGS system should only be cleaned when the entire duct system is cleaned.  Always inspect at cleaning each grease sensor and insure reflective surface and lens are clean.  When cleaning, do not use steel wool or other abrasive materials that would scratch the reflective material or lens.

• The KGS system must be inspected after each 12 months of service.  To schedule inspection, contact your authorized service agent or consult the factory for additional details.

• The grease sensors have a typical life span of three years.  After three years, the grease sensors must be replaced.  For replacements, contact your authorized service agent or consult the factory for additional details .

KGS – Kitchen Grease Sensor