Rack and PDP300DFT Installation Guide

Doc. Code L2 GK87 1000 04 13 00

Page 2: En Rack PDP300DFT Installation V1.3
Page 3: En Rack PDP300DFT Installation V1.3

Copyright © 2008 - 2012 NEC. All rights reserved.

Page 4: En Rack PDP300DFT Installation V1.3

Revision History

Manual

Version Revision Date Section Affected Change Description

Rack and Components Add ETSI-compliant rack description. V1.3 July 29, 2012

Cabling in the Rack Add the MN5200 cabling example.

V1.2 December 30, 2011 PDP300DFT Description Modify PDP300DFT spec and DIP Switch description.

V1.1 June 30, 2011 PDP300DFT Description Eight outputs are in two groups, each group corresponding to one input respectively.

V1.0 November 11, 2008 All New document

Page 5: En Rack PDP300DFT Installation V1.3

Rack and PDP300DFT Installation Guide

Contents

About This Guide ........................................................................................................1 

Introduction........................................................................................................................1 

Conventions.......................................................................................................................1 

Notice Icons...................................................................................................................1 

Figures and Screen Captures .......................................................................................1 

1  Rack Components and Installation ..................................................................3 

Rack and Components ......................................................................................................3 

Installing the Rack .............................................................................................................6 

Drilling Holes in the Floor ..............................................................................................6 

Anchoring a Rack ..........................................................................................................6 

Installing Alarm LED ..........................................................................................................6 

Installing SAICEXT ............................................................................................................8 

Installing MUTE/ACO Button...........................................................................................12 

Removing Rack Top/Bottom Covers ...............................................................................14 

2  PDP300DFT Description and Installation.......................................................15 

PDP300DFT Description .................................................................................................15 

Function Descriptions..................................................................................................15 

Front Panel ..................................................................................................................16 

Interface Descriptions..................................................................................................17 

DIP Switch SW2 Settings ............................................................................................18 

PDP300DFT Specification...........................................................................................19 

Installing PDP300DFT.....................................................................................................20 

3  Power Supply and Grounding.........................................................................23 

Rack Grounding...............................................................................................................23 

Power Supply to PDP300DFT.........................................................................................24 

PDP300DFT Grounding ..................................................................................................28 

4  Cabling in the Rack..........................................................................................31 

Installing the Cable Blocks ..............................................................................................31 

Page 6: En Rack PDP300DFT Installation V1.3

ii

Installation Guide Rack and PDP300DFT

Cabling in the Rack..........................................................................................................32 

Sending Alarm to SAICEXT.............................................................................................35 

Sending Alarm to PDP300DFT........................................................................................36 

A  Appendix .......................................................................................................... 37 

Installation Accessories ...................................................................................................37 

Page 7: En Rack PDP300DFT Installation V1.3

iii

Rack and PDP300DFT Installation Guide

List of Tables

Table 1 Rack LEDs .....................................................................................................................6 

Table 2 PDP300DFT LED and Button Descriptions..................................................................16 

Table 3 PDP300DFT Interface Descriptions .............................................................................17 

Table 4 PDP300DFT Alarm Input/output Connector Pins Description......................................18 

Table 5 PDP300DFT SW2 Settings ..........................................................................................19 

Table 6 PDP300DFT Technical Specifications .........................................................................19 

Table 7 PDP300DFT Power Cable Label Descriptions.............................................................26 

Table 8 IEC 19-inch Rack Installation Accessories...................................................................37 

Table 9 ETSI 600 Rack Installation Accessories ......................................................................38 

Page 8: En Rack PDP300DFT Installation V1.3

iv

Installation Guide Rack and PDP300DFT

List of Figures

Figure 1 IEC-compliant 19-inch Rack and Components.............................................................4 

Figure 2 ETSI-compliant Rack and Components........................................................................5 

Figure 3 Removing LED Bracket.................................................................................................7 

Figure 4 Fixing LEDs onto Bracket .............................................................................................8 

Figure 5 SAICEXT Box Position..................................................................................................8 

Figure 6 Removing SAICEXT Box ..............................................................................................9 

Figure 7 Fixing SAICEXT and Buzzer.......................................................................................10 

Figure 8 Plugging Alarm LEDs into SAICEXT Ports .................................................................10 

Figure 9 SAICEXT Interfaces for Connecting LEDs .................................................................11 

Figure 10 Installing LEDs in Place ............................................................................................11 

Figure 11 Installing SAICEXT in Place .....................................................................................12 

Figure 12 MUTE and ACO Button Positions.............................................................................13 

Figure 13 Installing MUTE and ACO Buttons ...........................................................................13 

Figure 14 Removing Rack Top Cover.......................................................................................14 

Figure 15 Removing Rack Bottom Cover .................................................................................14 

Figure 16 PDP300DFT Front Panel ..........................................................................................16 

Figure 17 PDP300DFT View without Front Cover ....................................................................17 

Figure 18 PDP300DFT Alarm Input/output Connector .............................................................18 

Figure 19 PDP300DFT SW2.....................................................................................................18 

Figure 20 Installing Air Breaker.................................................................................................20 

Figure 21 Installing Mounting Nuts ...........................................................................................21 

Figure 22 Mounting PDP300DFT in Rack.................................................................................21 

Figure 23 Rack Ground Cable ..................................................................................................23 

Figure 24 Rack Grounding ........................................................................................................24 

Figure 25 Removing PDP300DFT Front Panel.........................................................................25 

Figure 26 Connecting Copper Lugs to Power Cable ................................................................26 

Figure 27 PDP300DFT Power Supply ......................................................................................26 

Figure 28 PDP300DFT Power Cabling .....................................................................................27 

Figure 29 PDP300DFT Ground Cable ......................................................................................28 

Page 9: En Rack PDP300DFT Installation V1.3

v

Rack and PDP300DFT Installation Guide

Figure 30 Connecting Ground Cable to Copper Plate ..............................................................28 

Figure 31 Connecting Ground Cable to Rack Inner Grounding Point ......................................29 

Figure 32 Connecting Rack Inner Grounding Point to Mounting Bar .......................................29 

Figure 33 Connecting Rack Inner Grounding Point to PDP300DFT ........................................30 

Figure 34 Removing Cable Block .............................................................................................31 

Figure 35 Positioning Cable Block ............................................................................................32 

Figure 36 SpectralWave MN5200 Cabling in the Rack ............................................................32 

Figure 37 SpectralWave MN3100 E1 cabling in Rack..............................................................33 

Figure 38 SpectralWave MN3100 and MN4100 cabling in ETSI rack......................................34 

Figure 39 Sending Alarm to SAICEXT......................................................................................35 

Figure 40 Sending Alarms to PDP300DFT...............................................................................36 

Page 10: En Rack PDP300DFT Installation V1.3
Page 11: En Rack PDP300DFT Installation V1.3

Rack and PDP300DFT Installation Guide

About This Guide

Introduction

This installation guide provides an overview of the Rack and PDP300DFT for the SpectralWave series, and describes the installation procedures and cabling methods.

Conventions

This guide may contain notice icons, figures, screen captures, and certain typographical conventions. These conventions are described below.

Notice Icons

The following table lists notice icons used in this guide.

Icon Notice Type Description

Note

A note providing important information or instructions but is not hazard-related.

Caution

Information to alert of potential damage to a program, data, system, or device. If not avoided, may result in minor or moderate damage. It may also alert against unsafe practices and potential program, data, system, or device damage.

Warning

Information to alert of operations that may cause an accident, personal injury, fatality or potential electrical hazard. If not avoided, could result in serious injury or even death.

ESD

Special handling instructions for components sensitive to electrostatic discharge damage.

Figures and Screen Captures

This guide provides figures and screen captures as examples. These examples contain sample data which may differ from the actual data on an installed system.

Page 12: En Rack PDP300DFT Installation V1.3
Page 13: En Rack PDP300DFT Installation V1.3

Rack and PDP300DFT Installation Guide

1 Rack Components and Installation

This chapter contains the following topics:

Rack and components

Installing the Rack

Installing the Alarm LED

Installing the SAICEXT module

Installing the MUTE/ACO button

Removing rack top/bottom covers

Rack and Components

NEC provides two kinds of racks for SpectralWave product family, one is an IEC-compliant 19-inch rack, and the other is an ETSI-compliant rack. The dimensions of the two kinds of racks are: 2200 mm height, 600 mm width and 600 mm depth.

The IEC-compliant 19-inch rack is shown in Figure 1, and the ETSI-compliant rack is shown in Figure 2. Both kinds of racks have several optional components, including the Alarm LED, SAICEXT module, and MUTE/ACO button.

1

Page 14: En Rack PDP300DFT Installation V1.3

4 Chapter 1 Rack Components and Installation

Installation Guide Rack and PDP300DFT

Figure 1 IEC-compliant 19-inch Rack and Components

Page 15: En Rack PDP300DFT Installation V1.3

Chapter 1 Rack Components and Installation 5

Rack and PDP300DFT Installation Guide

Figure 2 ETSI-compliant Rack and Components

Page 16: En Rack PDP300DFT Installation V1.3

6 Chapter 1 Rack Components and Installation

Installation Guide Rack and PDP300DFT

Installing the Rack

In addition to the information provided in this section, follow the manufacturer's instructions for drilling holes in the floor and installing the rack.

Drilling Holes in the Floor

Follow the anchor bolt manufacturer's instructions and these precautions when drilling anchor holes in the floor:

Before attempting to drill the mounting holes into the floor, set up the drilling rig according to the manufacturer's instructions.

Safety goggles, dust masks, and ear plugs must be worn by all installation personnel, including those in the vicinity of personnel operating the drill equipment.

To prevent personal injury, follow the manufacturer's instructions when using any power tools.

Dust from concrete floor is harmful to the equipment and wiring. Use a tarpaulin, cloth, or plastic sheeting to cover exposed equipment.

Carefully clean up any accumulated debris remaining from drilling holes before anchoring the rack.

Anchoring a Rack

After the rack is secured to the floor, verify that it is balanced and level. Racks that are not level may prevent side-by-side racks from seating properly on the floor and create a tipping hazard.

Installing Alarm LED

There are four LEDs on the top of the rack. They are: Power, Critical, Major and Minor. The LED colors and their corresponding meanings are listed in Table 1.

Table 1 Rack LEDs

Symbol Color Description

OFF The NE in the rack has failed or is not powered on. Power

Green ON The NE has powered on.

OFF No critical alarms. Critical

Red ON The NE has a critical alarms

OFF No major alarm. Major

Red ON The NE has a major alarm.

Page 17: En Rack PDP300DFT Installation V1.3

Chapter 1 Rack Components and Installation 7

Rack and PDP300DFT Installation Guide

Symbol Color Description

OFF No minor alarm. Minor

Yellow ON The NE has a minor alarm.

The installation procedure is as follows:

1 Remove the bracket that will hold the LEDs, as shown in Figure 3.

Figure 3 Removing LED Bracket

2 Fix the LEDs onto the bracket, as shown in Figure 4. The colors of the alarm LED indicators and their corresponding labels are listed in Table 1. Ensure that the LEDs are installed in the correct sequence.

Page 18: En Rack PDP300DFT Installation V1.3

8 Chapter 1 Rack Components and Installation

Installation Guide Rack and PDP300DFT

Figure 4 Fixing LEDs onto Bracket

Installing SAICEXT

Usually, the external alarms of the NE are sent to the rack through a SAICEXT module. Follow the steps below to connect the cables accordingly.

Or, the external alarms of the NE can be sent to the PDP300DFT. Please refer to the section Sending Alarm to PDP300DFT on page 36.

The procedures for SAIXEXT installation and external alarm sending are as follows:

1 The position of the SAICEXT box is as shown in Figure 5.

Figure 5 SAICEXT Box Position

Page 19: En Rack PDP300DFT Installation V1.3

Chapter 1 Rack Components and Installation 9

Rack and PDP300DFT Installation Guide

2 Loosen the screws and remove the box, as shown in Figure 6.

Figure 6 Removing SAICEXT Box

Page 20: En Rack PDP300DFT Installation V1.3

10 Chapter 1 Rack Components and Installation

Installation Guide Rack and PDP300DFT

3 Install SAICEXT in the box and fix a buzzer onto the box, as shown in Figure 7.

Figure 7 Fixing SAICEXT and Buzzer

4 Connect the LEDs to the corresponding port on SAICEXT, as shown in Figure 8 and Figure 9.

Figure 8 Plugging Alarm LEDs into SAICEXT Ports

Page 21: En Rack PDP300DFT Installation V1.3

Chapter 1 Rack Components and Installation 11

Rack and PDP300DFT Installation Guide

Figure 9 SAICEXT Interfaces for Connecting LEDs

5 Connect the buzzer to the BUZZER port on SAICEXT.

6 Install the LEDs in place, as shown in Figure 10.

Figure 10 Installing LEDs in Place

Page 22: En Rack PDP300DFT Installation V1.3

12 Chapter 1 Rack Components and Installation

Installation Guide Rack and PDP300DFT

7 Install the SAICEXT box in place, as shown in Figure 11.

Figure 11 Installing SAICEXT in Place

Installing MUTE/ACO Button

The installation procedure is as follows:

1 The positions of the MUTE and ACO buttons in the rack are as shown in Figure 12.

Page 23: En Rack PDP300DFT Installation V1.3

Chapter 1 Rack Components and Installation 13

Rack and PDP300DFT Installation Guide

Figure 12 MUTE and ACO Button Positions

2 Install the MUTE and ACO buttons on the rack, as shown in Figure 13.

Figure 13 Installing MUTE and ACO Buttons

3 Connect MUTE and ACO Buttons to the MUTE and ACO ports on SAICEXT.

Page 24: En Rack PDP300DFT Installation V1.3

14 Chapter 1 Rack Components and Installation

Installation Guide Rack and PDP300DFT

Removing Rack Top/Bottom Covers

For overhead cabling, remove the left and right covers on the top of the rack for cabling, as shown in Figure 14. For under-floor cabling, remove the left and right covers at the bottom of the rack for cabling, as shown in Figure 15.

Figure 14 Removing Rack Top Cover

Figure 15 Removing Rack Bottom Cover

Page 25: En Rack PDP300DFT Installation V1.3

Rack and PDP300DFT Installation Guide

2 PDP300DFT Description and

Installation

This chapter contains the following topics:

PDP300DFT Description

PDP300DFT Installation

PDP300DFT Description

Function Descriptions

The PDP300DFT Power Distribution Panel is used for the -48 VDC power supply system, providing DC power supply and overload protection for the NEs. PDP300DFT has two -48 VDC inputs and eight -48 VDC outputs. Individual outputs are overload protected by replaceable circuit breakers.

PDP300DFT has a single replaceable alarm/control module. This module is used to indicate the PDP300DFT SPD (Surge Protection Device) status and monitors the over/under-voltage status. This module can also receive alarm status signals from the system and in turn displays these alarms on the front panel LED indicators. PDP300DFT also transmits its alarms to the rack for remote alarm management.

PDP300DFT has the following features:

Eight -48 VDC power output terminals, each with circuit breaker protection. Each output has a maximum current capacity of 50 A. The eight output terminals are in two groups, one is A1 - A4 and the other is B1 - B4.

Dual power input terminals (A and B), each with circuit breaker protected. Each input terminal has a maximum current capacity of 80A. Each input terminal corresponds to one output group. That is, input A corresponds to output terminals A1 - A4, and input B corresponds to output terminal B1 - B4 (Refer to Figure 17). When PDP300DFT provide power supply to an NE, the user must use two output terminals in different groups to achieve a 1+1 power input protection.

Receives alarms from NE or sends out alarms.

Audible and visual alarm status indicators for connected NEs and the PDP300DFT itself.

Mute/test buttons for turning off the audible alarm or testing the LEDs.

Two power inputs with over-voltage/under-voltage detection:

- -48 V mode: Input voltage range is -39.5 2% VDC to -60 VDC

- -60 V mode: Input voltage range is -52 VDC to -71.5 2% VDC

Note: The measurement error is ± 2%.

2

Page 26: En Rack PDP300DFT Installation V1.3

16 Chapter 2 PDP300DFT Description and Installation

Installation Guide Rack and PDP300DFT

Front Panel

The front panel of the PDP300DFT has five LED indicators and a button, as shown in Figure 16. Table 2 describes the PDP300DFT LED and button functionalities.

Figure 16 PDP300DFT Front Panel

Table 2 PDP300DFT LED and Button Descriptions

Name Color Status Description

POWER A Green LED ON: Normal operation.

LED OFF: No input power or the power input’s polarity is reversed.

LED Flash (0.3s interval): Over-voltage or under-voltage.

This LED indicates input A‘s power status.

The over/under voltage range depends on which of the two input voltage modes (-48 VDC or -60 VDC) is selectable via DIP switch SW2.

POWER B Green LED ON: Normal operation.

LED OFF: No input power or the power input’s polarity is reversed.

LED Flash (0.3s interval): Over-voltage or under-voltage.

This LED indicates input B‘s power status.

The over/under voltage range depends on which of the two input voltage modes (-48 VDC or -60 VDC) is selectable via DIP switch SW2.

CRITICAL Red LED ON: The power input’s polarity is reversed, or there is a critical alarm on the NE.

LED OFF: Normal operation.

In the following two situations the LED will be ON:

The two power inputs polarities are reversed.

Critical alarm(s) are received from the NE.

MAJOR Red LED ON: Major NE alarm(s).

LED OFF: Normal operation.

The LED will be ON when major alarms are received from the NE.

MINOR Yellow LED ON: Minor NE alarm(s), or there is an SPD alarm

LED OFF: Normal operation.

In the following two situations the LED will be ON:

Minor alarms are received from the NE.

There is an SPD alarm.

ACO/TEST

Button

Clear alarm sound indication or test the LED indicators.

Press this button to temporarily turn OFF a current audible alarm indication.

Under normal operating conditions, when this button is pressed it will test the LED indicators.

Page 27: En Rack PDP300DFT Installation V1.3

Chapter 2 PDP300DFT Description and Installation 17

Rack and PDP300DFT Installation Guide

Interface Descriptions

PDP300DFT input/output connection terminals are on the front of the PDP300DFT behind the front cover panel. All cables connecting to the PDP300DFT are routed from below. Figure 17 shows a front view of the PDP300DFT with the cover panel removed and Table 3 describes its interfaces.

Figure 17 PDP300DFT View without Front Cover

Table 3 PDP300DFT Interface Descriptions

No. Description

1 Lightning protector

2 Indicator and button connector

3 Four alarm input/output connectors

4 Alarm output connector (reserved for future use)

5 Eight power output breakers

6 Eight power output terminals (-48V). Output terminals A1 - A4 correspond to input terminal A, and output terminals B1 - B4 correspond to input terminal B.

7 Power input terminal B (-48V)

8 Power input terminal A (-48V)

9 Two power input return terminals (0V)

10 Eight power output return terminals (0V)

11 Five protection ground terminals (For the NEs)

12 One protection ground terminal (to the rack mounting bar)

PDP300DFT provides the following connection terminals:

Power input terminal A and B: Capable of connecting cable sizes from 12 mm2 to 16 mm2. Total current must not exceed 80 A (Total current of all output connections). To achieve 1+1 power input protection, power supply must be connected to both power input terminal A and B.

Power output terminal: Eight independent output terminals, each with a corresponding circuit breaker for overload protection. When providing power supply to an NE, two power output terminals in different group must be used to achieve 1+1 power input protection. For example, you can use output terminals A1&B1, A2&B2, A3&B3 or A4&B4 for an NE.

Page 28: En Rack PDP300DFT Installation V1.3

18 Chapter 2 PDP300DFT Description and Installation

Installation Guide Rack and PDP300DFT

Alarm input connectors (M, S1, S2, and S3) (Refer to Figure 18): RJ-45 connectors which receive LED/buzzer control signals, connected with the external alarm output interfaces of the NE. The RJ-45 pin descriptions are shown in Table 4.

Alarm output connector (EXT): Reserved for future use.

Figure 18 PDP300DFT Alarm Input/output Connector

Table 4 PDP300DFT Alarm Input/output Connector Pins Description

Pin Index M S1 S2 S3

1

2 CR1 (Input) CR2 (Input) CR3 (Input) CR4 (Input)

3 MJ1 (Input) MJ2 (Input) MJ3 (Input) MJ4 (Input)

4 GND GND GND GND

5 MN1 (Input) MN2 (Input) MN3 (Input) MN4 (Input)

6 BUZZER1 (Input) BUZZER2 (Input) BUZZER3 (Input) BUZZER4 (Input)

7 GND GND GND GND

8 ACO (Output) ACO (Output) ACO (Output) ACO (Output)

DIP Switch SW2 Settings

The DIP switch SW2 is located on the replaceable alarm/control module, as shown in Figure 19. To set SW2, the alarm/control module must be removed.

Figure 19 PDP300DFT SW2

SW2 is used to set the monitoring point of over-voltage and under-voltage alarm. The settings are described in Table 5.

Page 29: En Rack PDP300DFT Installation V1.3

Chapter 2 PDP300DFT Description and Installation 19

Rack and PDP300DFT Installation Guide

Table 5 PDP300DFT SW2 Settings

Switch Bit Status Function

ON The over-voltage monitoring point of input A is 70 1VDC 1

OFF The over-voltage monitoring point of input A is 55 1VDC

ON The under-voltage monitoring point of input A is 52 1VDC 2

OFF The under-voltage monitoring point of input A is 42 1VDC

ON The over-voltage monitoring point of input B is 70 1VDC 3

OFF The over-voltage monitoring point of input B is 55 1VDC

ON The under-voltage monitoring point of input B is 52 1VDC 4

OFF The under-voltage monitoring point of input B is 42 1VDC

PDP300DFT Specification

The technical specification of PDP300DFT is listed in Table 6.

Table 6 PDP300DFT Technical Specifications

Physical Specifications

Dimensions Including the hangers: 88.9 mm x 483.5 mm x 222 mm (H x W x D)

Environmental Specifications

Operational temperature -5 oC to 55 oC

Altitude -60 m to 3962 m

Storage temperature -40 oC to 70 oC

Relative humidity 5% to 95%, non-condensing

Acoustical noise < 55 dBA

Functional Specifications

Circuit breakers 2 x 4

Output current range 2 A to 80A

Input power Dual-input

Standards

EMC and Safety CE Marking

FCC Part 15 Class A

Page 30: En Rack PDP300DFT Installation V1.3

20 Chapter 2 PDP300DFT Description and Installation

Installation Guide Rack and PDP300DFT

Installing PDP300DFT

The distance between the bottom of the PDP300DFT and the top of the mounting bar is 3U.

The installation procedure is as follows:

1 Take the air breaker out of the accessory package and install it on the PDP300DFT, as shown in Figure 20.

Figure 20 Installing Air Breaker

2 The device bracket has been installed in the rack, and usually does not require adjustment.

3 Install the mounting nuts for the PDP300DFT inside the rack, as shown in Figure 21. For the typical application, install the mounting nuts in the 4th and 9th holes on both sides of the mounting bar.

Page 31: En Rack PDP300DFT Installation V1.3

Chapter 2 PDP300DFT Description and Installation 21

Rack and PDP300DFT Installation Guide

Figure 21 Installing Mounting Nuts

4 Slide the PDP300DFT into the rack from the front side and place it on the bracket (Figure 22), with the flange holes aligned with the corresponding square holes on the mounting bar.

5 Install four M6 screws, as shown in Figure 22.

Figure 22 Mounting PDP300DFT in Rack

6 Turn off all the air breakers of the PDP300DFT.

Page 32: En Rack PDP300DFT Installation V1.3
Page 33: En Rack PDP300DFT Installation V1.3

Rack and PDP300DFT Installation Guide

3 Power Supply and Grounding

This chapter contains the following topics:

Rack Grounding

PDP300DFT Power Supply

PDP300DFT Grounding

Rack Grounding

Use a 16 mm2 ground cable to connect the equipment room ground bar to the rack grounding point, one of the M10 screw on the top of the rack.

The installation procedure is as follows:

1 Terminate the ends of the 16 mm2 ground cable with M10 copper lugs, as shown in Figure 23.

Figure 23 Rack Ground Cable

2 Connect the ground cable from the equipment room ground bar to the rack top, as shown in Figure 24.

3

Page 34: En Rack PDP300DFT Installation V1.3

24 Chapter 3 Power Supply and Grounding

Installation Guide Rack and PDP300DFT

Figure 24 Rack Grounding

Power Supply to PDP300DFT

Use four 16 mm2 cables to supply power to the PDP300DFT.

The installation procedure is as follows:

1 Remove the front panel of the PDP300DFT, as shown in Figure 25.

Page 35: En Rack PDP300DFT Installation V1.3

Chapter 3 Power Supply and Grounding 25

Rack and PDP300DFT Installation Guide

Figure 25 Removing PDP300DFT Front Panel

2 Measure the resistance between the PDP300DFT RETURN and FGND, which must be less than 1 ohm.

3 Measure the resistance between the PDP300DFT -48 V input terminals and the RETURN/FGND terminals.

- With the circuit breaker open, the resistance must be infinite.

- With the circuit breaker closed, the resistance must be greater than 1000 ohm.

4 Open all the PDP300DFT circuit breakers.

5 Run the power cable from the PDP300DFT to the power supply equipment and cut the length. It is recommended that the user connect two power cables to both power input A and B terminals to achieve 1+1 power input protection.

6 Terminate the cables with double-M6 copper lugs in one end, as shown in Figure 26.

Page 36: En Rack PDP300DFT Installation V1.3

26 Chapter 3 Power Supply and Grounding

Installation Guide Rack and PDP300DFT

Figure 26 Connecting Copper Lugs to Power Cable

7 Label the four power cables. For example, label two cables with ’-48V-A’, ’-48V-B’, and the other two cables both with ’return’. The descriptions of the labels are shown in Table 7.

Table 7 PDP300DFT Power Cable Label Descriptions

Label Description Connect To The PDP300DFT Position

-48V-A One of the -48 V power input. IN A / 150 A

-48V-B The other -48 V power input IN B / 150 A

Return The return of the power input Return

8 Insert the power cables to the PDP300DFT input terminals and tighten the screws on the terminals. Ensure that the connections are proper, as shown in Figure 27.

Figure 27 PDP300DFT Power Supply

9 Lead the power cable upward along the back side of the mounting bar and then out of the rack from the top, as shown in Figure 28.

Page 37: En Rack PDP300DFT Installation V1.3

Chapter 3 Power Supply and Grounding 27

Rack and PDP300DFT Installation Guide

Figure 28 PDP300DFT Power Cabling

10 Lay the power cables along the cable trough to the power supply equipment. Use cable straps to bundle them in the cable trough.

11 Measure the power supply equipment output voltage at the terminals to which the PDP300DFT will be attached. When the PDP300DFT works in -48 V mode, the voltage should be between -39.5 V and -60 V.

12 Remove the fuses or open the breakers in the power supply equipment and connect the power cable to the power supply equipment.

13 Inspect the installation to ensure each cable is properly connected.

14 Insert the fuses or close the circuit breakers on the power supply equipment.

15 Close all the PDP300DFT input and output circuit breakers, measure the voltage on each of the PDP300DFT output terminals. When the PDP300DFT works in -48 V mode, the voltage should be between -39.5 V and -60 V.

16 Ensure the LED status is normal referring to Table 2.

17 Open all the PDP300DFT input and output circuit breakers. Remove the fuses or open the circuit breakers on the power supply equipment.

Page 38: En Rack PDP300DFT Installation V1.3

28 Chapter 3 Power Supply and Grounding

Installation Guide Rack and PDP300DFT

PDP300DFT Grounding

Use two 16 mm2 ground cables (yellow/green) to

Connect the rack grounding point to the PDP300DFT FGND terminal

Connect the rack grounding point to the mounting bar in the rack.

The installation procedure is as follows:

1 Terminate two 16 mm2 ground cables (yellow/green) with M10 and double-M6 copper lugs for each, as shown in Figure 29.

Figure 29 PDP300DFT Ground Cable

2 Take the grounding copper plates out of the accessory package, and connect the two ground cables (yellow/green) to the copper plates, as shown in Figure 30.

Figure 30 Connecting Ground Cable to Copper Plate

3 Install copper plates on the rack top, the copper plates that connect the ground cables with M10 copper lug must be installed close to the rack edge, as shown in Figure 31.

Page 39: En Rack PDP300DFT Installation V1.3

Chapter 3 Power Supply and Grounding 29

Rack and PDP300DFT Installation Guide

Figure 31 Connecting Ground Cable to Rack Inner Grounding Point

4 Connect the ground cable with M10 copper lug to the rack mounting bar, as shown in Figure 32.

Figure 32 Connecting Rack Inner Grounding Point to Mounting Bar

Page 40: En Rack PDP300DFT Installation V1.3

30 Chapter 3 Power Supply and Grounding

Installation Guide Rack and PDP300DFT

5 Connect the other ground cable to the dual-M6 FGND terminal of the PDP300DFT, as shown in Figure 33.

Figure 33 Connecting Rack Inner Grounding Point to PDP300DFT

Page 41: En Rack PDP300DFT Installation V1.3

Rack and PDP300DFT Installation Guide

4 Cabling in the Rack

This chapter describes the cabling in the Rack, including the following topics:

Installing the cable blocks

Cabling in the Rack

Sending Alarm to SAICEXT

Sending Alarm to PDP300DFT

Installing the Cable Blocks

The cable blocks are already installed in the Rack. Usually, it is not necessary to adjust the positions. If you want to adjust the position of the cable blocks, follow the steps below. Ignore this section if the rack does not use cable blocks.

1 Remove the cable block, as shown in Figure 34.

Figure 34 Removing Cable Block

2 Determine the locations of the cable blocks.

3 Mount the cable block in the rack with the M6 screws as shown in Figure 35.

4

Page 42: En Rack PDP300DFT Installation V1.3

32 Chapter 4 Cabling in the Rack

Installation Guide Rack and PDP300DFT

Figure 35 Positioning Cable Block

Cabling in the Rack

As required in practice, the engineers must bundle the cables according to their types (power cables, optical fibers, and service cables, etc.) inside the rack to keep the cabling tidy. All cables must be laid and bundled through the cable blocks.

Figure 36 is an example of SpectralWave MN5200 cabling in the rack.

Figure 36 SpectralWave MN5200 Cabling in the Rack

Page 43: En Rack PDP300DFT Installation V1.3

Chapter 4 Cabling in the Rack 33

Rack and PDP300DFT Installation Guide

Figure 37 is an example of SpectralWave MN3100 E1 cabling in the rack.

Figure 37 SpectralWave MN3100 E1 cabling in Rack

Page 44: En Rack PDP300DFT Installation V1.3

34 Chapter 4 Cabling in the Rack

Installation Guide Rack and PDP300DFT

Figure 38 is an example of SpectralWave MN3100 and MN4100 cabling in the ETSI-compliant rack.

Figure 38 SpectralWave MN3100 and MN4100 cabling in ETSI rack

Page 45: En Rack PDP300DFT Installation V1.3

Chapter 4 Cabling in the Rack 35

Rack and PDP300DFT Installation Guide

Sending Alarm to SAICEXT

The external alarm from the NE can be sent to the SAICEXT module, thus the LEDs in the rack will be lit when an alarm occurs.

If several pieces of NEs need to send alarms to SAICEXT, the alarm cable can be connected to the A, B, C and D connectors. One interface is for one NE, so up to four NEs can send alarms to SAICEXT.

The alarm cable is an Ethernet cable. The installation procedure is as follows:

1 Label an Ethernet cable for sending the alarms.

2 Connect the cable from external alarm interface of the NE to the A port on SAICEXT along the cable blocks, as shown in Figure 39.

Figure 39 Sending Alarm to SAICEXT

3 If more NEs need to send alarms to SAICEXT, the alarm cables can be connected to the B, C or D port on SAICEXT. Up to four NEs can send alarms to SAICEXT.

Page 46: En Rack PDP300DFT Installation V1.3

36 Chapter 4 Cabling in the Rack

Installation Guide Rack and PDP300DFT

Sending Alarm to PDP300DFT

The external alarm from the NE can be sent to the PDP300DFT instead of the SAICEXT module, thus the LEDs in the PDP300DFT will be lit when an alarm occurs.

If several NEs need to send alarms to the PDP300DFT, the alarm cable can be connected to the M, S1, S2 and S3 connectors. Each interface is for one NE, so up to four NEs can send alarms to the PDP300DFT.

The alarm cable is an Ethernet cable. The installation procedure is as follows:

1 Label an Ethernet cable for sending the alarms.

2 Connect the Ethernet cable to the external alarm interface of the NE.

3 Lead in the cable from the bottom of the PDP300DFT and connect it to the M connector, and then bundle it along the top of the PDP300DFT as shown in Figure 40.

Figure 40 Sending Alarms to PDP300DFT

4 If more NEs need to send alarms to the PDP300DFT, the alarm cables can be connected to the S1, S2 or S3 port on the PDP300DFT. Up to four NEs can send alarms to the PDP300DFT.

Page 47: En Rack PDP300DFT Installation V1.3

Rack and PDP300DFT Installation Guide

A Appendix

Installation Accessories

Table 8 IEC 19-inch Rack Installation Accessories

No. Description Quantities

1 Expansion bolts, M12 x 90, for rack fixing 4

2 Nut, M12, hex head, for fixing the rack to the rack base 4

3 Blot, hex head with Spring and Flat, M12 x 60, for fixing the rack to the rack base

4

4 Washer, hole 12, Spring, for fixing the rack to the rack base 4

5 Bolt, hex head, M12 x 45, for fixing the rack to the floor 4

6 Insulated mat for insulation between the rack and the floor 8

7 Rack grounding copper plates (Ground sheet) 1

8 Screw, Pan Head, Phillips with Spring and Flat, M6 x 12, for fixing the ground cable to the ground copper plates

6

9 Ground cable, 16 mm2, 0.7 m, yellow/green, from the ground copper plates to the PDP300DFT FGND terminal

1

10 Ground cable, 16 mm2, 0.6 m, yellow/green, from the ground copper plates to the mounting bar

1

11 Bolt, hex head, M10 x 25, for fixing the ground cable to the mounting bar 1

12 Washer, hole 10, Flat, for fixing the ground cable to the mounting bar 1

13 Washer, hole 10, Spring, for fixing the ground cable to the mounting bar 1

14 Screw, pan head, Phillips with Spring and Flat, M6 x 16, for fixing the ground cable

16

15 Floating nut, M6, for equipment mounting 10

16 Panel screw, Phillips, M6 x 16 with Nylon washer, for equipment mounting 10

A

Page 48: En Rack PDP300DFT Installation V1.3

38 Chapter 4 Cabling in the Rack

Installation Guide Rack and PDP300DFT

Table 9 ETSI 600 Rack Installation Accessories

No. Description Quantities

1 Expansion bolts, M12 x 90, for rack fixing 4

2 Nut, M12, hex head, for fixing the rack to the rack base 4

3 Blot, hex head with Spring and Flat, M12 x 60, for fixing the rack to the rack base

4

4 Washer, hole 12, Spring, for fixing the rack to the rack base 4

5 Bolt, hex head, M12 x 45, for fixing the rack to the floor 4

6 Insulated mat for insulation between the rack and the floor 8

7 Rack grounding copper plates (Ground sheet) 1

8 Screw, Pan Head, Phillips with Spring and Flat, M6 x 12, for fixing the ground cable to the ground copper plates

6

9 Ground cable, 16 mm2, 0.7 m, yellow/green, from the ground copper plates to the PDP300DFT FGND terminal

1

10 Ground cable, 16 mm2, 0.6 m, yellow/green, from the ground copper plates to the mounting bar

1

11 Bolt, hex head, M10 x 25, for fixing the ground cable to the mounting bar 1

12 Washer, hole 10, Flat, for fixing the ground cable to the mounting bar 1

13 Washer, hole 10, Spring, for fixing the ground cable to the mounting bar 1

14 Screw, pan head, Phillips with Spring and Flat, M6 x 16, for fixing the ground cable

16

15 Floating nut, M6, for equipment mounting 10

16 Panel screw, Phillips, M6 x 16 with Nylon washer, for equipment mounting 10

17 Flat cable tie holder, NYLON 6/6, adhesive mount, for fixing fibers and cables

20