En PBM User-Manual R009
Transcript of En PBM User-Manual R009
-
8/14/2019 En PBM User-Manual R009
1/128
MANUAL DE USUARIO
PBMMotor management system
-
8/14/2019 En PBM User-Manual R009
2/128
www.fanox.com 2/128
1. RECEPTION, HANDLING, INSTALLATION ...................................................... 61.1. Unpacking .............................................................................................................................. 61.2. Reception of relays ............................................................................................................... 61.3. Handling electronic equipment ............................................................................................ 61.4. Installation, commissioning and service ............................................................................ 61.5. Storage ................................................................................................................................... 71.6. Recycling ................................................................................................................................ 7
2. DIMENSIONS AND CONNECTION DIAGRAMS ............................................... 82.1. Equipment frontal view ......................................................................................................... 82.2. Equipment dimensions ......................................................................................................... 9
2.2.1. PBM B base module dimensions..................................................................................... 92.2.2. PBM-H module dimensions mm .................................................................................... 10
2.3. Connection diagrams .......................................................................................................... 112.3.1. Direct pass PBM protection connection ........................................................................ 112.3.2. Multiple pass PBM protection connection ..................................................................... 112.3.3. External CT pass PBM protection connection ............................................................... 122.3.4. PTC and differential PBM protection connection ........................................................... 122.3.5. Direct start-up PBM protecction and control connection ............................................... 13
2.4. PBM-B base module terminals ........................................................................................... 143. DESCRIPTION .................................................................................................. 15
3.1. Introduction .......................................................................................................................... 153.2. Description ........................................................................................................................... 193.3. PBM-B base module functional diagram .......................................................................... 233.4. List of Models....................................................................................................................... 24
3.4.1. PBM B model l ist ........................................................................................................... 243.4.2. PBM H model list ........................................................................................................... 24
4. PBM-B PROTECTION FUNCTIONS AND FEATURES ................................... 254.1. General settings .................................................................................................................. 254.2. Overload ............................................................................................................................... 264.3. Phase imbalance ................................................................................................................. 274.4. Phase failure ........................................................................................................................ 284.5. Phase sequence .................................................................................................................. 294.6. PTC Function ....................................................................................................................... 304.7. Jam function ........................................................................................................................ 314.8. Locked rotor ......................................................................................................................... 314.9. Instantaneous neutral overcurrent. ................................................................................... 324.10. Neutral inverse time overcurrent ................................................................................... 324.11. Instantaneous earth leakage overcurrent. .................................................................... 334.12. Earth leakage inverse time overcurrent. ....................................................................... 33
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
3/128
www.fanox.com 3/128
4.13. Undercurrent .................................................................................................................... 344.14. Motor start up monitoring ............................................................................................... 354.15. Overload curves............................................................................................................... 364.16.
IEC60255-151 Curves ...................................................................................................... 46
5. MONITORING AND CONTROL ........................................................................ 50
5.1. Measurements ..................................................................................................................... 505.2. States .................................................................................................................................... 515.3. Statistics ............................................................................................................................... 555.4. Fault reports ......................................................................................................................... 565.5. Date-time synchronisation ................................................................................................. 575.6. Inputs .................................................................................................................................... 575.7. Outputs ................................................................................................................................. 575.8. Leds ...................................................................................................................................... 58
5.8.1. PBM-B equipment leds .................................................................................................. 585.8.2. PBM-H hmi leds ............................................................................................................. 58
5.9. Self-diagnosis ...................................................................................................................... 615.10. Commands ....................................................................................................................... 625.11. Test programm................................................................................................................. 63
5.11.1. Base module PBM-B test programm ............................................................................. 635.11.2. Module PBM-H test programm ...................................................................................... 64
5.12. Power suppply ................................................................................................................. 655.13. Earth toroidal transformer monitoring .......................................................................... 655.14. Time delayed equipment start ........................................................................................ 655.15. Equipment reset............................................................................................................... 655.16. Thermal image reset ........................................................................................................ 665.17. Reset/Test Button ............................................................................................................ 66
6. TECHNICAL SPECIFICATIONS AND STANDARDS ...................................... 676.1. Technical specifications ..................................................................................................... 676.2. Standards ............................................................................................................................. 72
7. COMMUNICATION AND HMI ........................................................................... 747.1. RS485 Communication ....................................................................................................... 74
7.1.1. Modbus RTU Protocol ................................................................................................... 757.2. LCD and keypad .................................................................................................................. 75
7.2.1. PBM-H LCD contrast ..................................................................................................... 757.3. PBCom communications programm ................................................................................. 767.4. User password ..................................................................................................................... 76
8. ACCESSORIES ................................................................................................ 778.1. Toroidal transformer ........................................................................................................... 778.2. Current transformer ............................................................................................................ 79
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
4/128
www.fanox.com 4/128
8.3. 8.3. PTC sensors .................................................................................................................. 808.4. Cables section ..................................................................................................................... 818.5. PBM-B to PBM-H connection cable ................................................................................... 818.6.
PBM-B to PC connection cable .......................................................................................... 82
8.7. Menus ................................................................................................................................... 83
8.7.1. Standby mode screen .................................................................................................... 838.7.2. Date-time menu ............................................................................................................. 838.7.3. Versions ......................................................................................................................... 848.7.4. Communication parameters: ......................................................................................... 848.7.5. Test menu ...................................................................................................................... 858.7.6. Functions menu ............................................................................................................. 868.7.7. Measurements menu ..................................................................................................... 878.7.8. States menu ................................................................................................................... 878.7.9. Settings menu ................................................................................................................ 898.7.10. Configuration Menu ....................................................................................................... 918.7.11. Reports menu ................................................................................................................ 918.7.12. Command menu ............................................................................................................ 938.7.13. Password menu ............................................................................................................. 93
9. COMMISSIONING............................................................................................. 949.1. Checklist for commissioning ............................................................................................. 949.2. Inspection ............................................................................................................................. 94
9.2.1. 11.2.1. Visual inspection ................................................................................................ 949.2.2. Current transformers ..................................................................................................... 94
9.3. Commissioning .................................................................................................................... 9410. MODBUS RTU PROTOCOL ............................................................................. 95
10.1. ModBus package format ................................................................................................. 9610.2. Function codes ................................................................................................................ 9610.3. Error responses and exceptions .................................................................................... 9710.4. Types of data .................................................................................................................... 9710.5. Data reading ..................................................................................................................... 9910.6. Adjustments writing ........................................................................................................ 9910.7. Command ......................................................................................................................... 9910.8. PBM memory map ......................................................................................................... 101
10.8.1. Mapa de medidas ........................................................................................................ 10110.8.2. Mapa de estados ......................................................................................................... 10110.8.3. Data reading ................................................................................................................ 10610.8.4. Settings reading ........................................................................................................... 10610.8.5. Date writing .................................................................................................................. 11010.8.6. Settings writing ............................................................................................................ 11010.8.7. Reports ........................................................................................................................ 114
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
5/128
www.fanox.com 5/128
10.8.8. Estadsticos ................................................................................................................. 12211. APPENDIX ...................................................................................................... 123
11.1. Identification .................................................................................................................. 12311.1.1. Model: .......................................................................................................................... 123
11.2. Checks ............................................................................................................................ 12411.3. Register of commissioning settings ........................................................................... 124
11.3.1. General ........................................................................................................................ 12411.3.2. Overload ...................................................................................................................... 12411.3.3. Imbalance .................................................................................................................... 12411.3.4. Phase failure ................................................................................................................ 12511.3.5. Sequence ..................................................................................................................... 12511.3.6. PTC .............................................................................................................................. 12511.3.7. Jam .............................................................................................................................. 12511.3.8. Locked rotor ................................................................................................................. 12511.3.9. I0>> .............................................................................................................................. 12511.3.10. I0> ............................................................................................................................ 12511.3.11. IG>> ......................................................................................................................... 12611.3.12. IG> ........................................................................................................................... 12611.3.13. Communications ...................................................................................................... 12611.3.14. Reset ....................................................................................................................... 126
11.4. Comments ...................................................................................................................... 126
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
6/128
www.fanox.com 6/128
1. RECEPTION, HANDLING, INSTALLATION
1.1. UnpackingRelays must only be handled by qualified personnel and special care must be taken to protect allof their parts from any damage while they are being unpacked and installed. The use of goodillumination is recommended to facilitate the equipment visual inspection. The facility must beclean and dry and relays should not be stored in places that are exposed to dust or humidity.Special care must be taken if construction work is taking place.
1.2. Reception of relays
It is necessary to inspect the equipment at the time it is delivered to ensure that the relays have
not been damaged during transport.If any defect is found, the transport company and FANOX should be informed immediately.
If the relays are not for immediate use, they should be returned to their original packaging.
1.3. Handling electronic equipment
Relays contain an electronic component that is sensitive to electrostatic discharges.
Just by moving, a person can build up an electrostatic potential of several thousand volts.Discharging this energy into electronic components can cause serious damage to electronic
circuits. It is possible that this damage may not be detected straight away, but the electroniccircuit reliability and life will be reduced. This electronic component in the equipment is wellprotected by the plastic housing, which should not be removed as the equipment cannot beadjusted internally.
1.4. Installation, commissioning and service
The personnel in charge of installing, commissioning and maintaining this equipment must bequalified and must be aware of the procedures for handling it. The product documentation shouldbe read before installing, commissioning or carrying out maintenance work on the equipment.
In order to guarantee safety, the crimp terminal and a suitable tool must be used to meetisolation requirements on the terminal strip. Crimped terminations must be used for the voltageand current connections.
Before supplying the equipment the value of the rated voltage and its polarity must be checked.
The equipment must be used within the stipulated electrical and environmental limits.
NOTE:Current transformer circuits: Do not open a live CT secondary circuit. The high voltageproduced as a result could damage the isolation and threaten lives.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
7/128
www.fanox.com 7/128
1.5. Storage
If the relays are not going to be installed immediately, they must be stored in a dust- and
humidity free environment after the visual inspection has been performed.
1.6. Recycling
All electrical power sources should be removed before performing this operation to avoid the riskof electrical discharge.
This product must be disposed of in a safe way. It should not be incinerated or brought intocontact with water sources like rivers, lakes, etc
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
8/128
www.fanox.com 8/128
2. DIMENSIONS AND CONNECTION DIAGRAMS
2.1. Equipment frontal view
PBM BPBM H
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
9/128
www.fanox.com 9/128
2.2. Equipment dimensions
2.2.1. PBM B base module dimensions
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
10/128
www.fanox.com 10/128
2.2.2. PBM-H module dimensions mm
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
11/128
www.fanox.com 11/128
2.3. Connection diagrams
2.3.1. Direct pass PBM protection connection
CONTACTOR (K1 Conexion alimentacion)
A1
A2
K1
L1 L2 L3
L (230 V)
N (0 V)
PBM-B 11-12-14 (disparo por falta)
K1
STOP (parada externa m otor)
M
PBM-B
I1
141211242221A1A2
E1C1 C2 I2E2T1 T2
START (arranque externo motor)
STOP
START
2.3.2. Multiple pass PBM protection connection
CONTACTOR (K1 Conexion alimentacion)
L1 L2 L3
PBM-B 11-12-14 (disparo por falta)
K1
STOP (parada externa motor)
M
PBM-B
I1
141211242221A1A2
E1C1 C2 I2E2T1 T2
START (arranque externo motor)A1
A2
K1
L (230 V)
N (0 V)
STOP
START
For motor wiht nominal current below the minimum relay setting value, pass cables through therelay hole several time. Set the value IBand CT relation as explained in paragraph 6.2.1.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
12/128
www.fanox.com 12/128
2.3.3. External CT pass PBM protection connection
CONTACTOR (K1 Conexion alimentacion)
L1 L2 L3
PBM-B 11-12-14 (disparo por falta)
K1
STOP (parada externa motor)
M
PBM-B
I1
141211242221A1A2
E1C1 C2 I2E2T1 T2
START (arranque externo motor)
Transformador de corriente
A1
A2
K1
L (230 V)
N (0 V)
STOP
START
For motors with nominal current over the maximum relay current setting value, combine the relaywith current transformers. Set the value IBand CT relation as explained in paragraph 6.2.1.
2.3.4. PTC and differential PBM protection connection
CONTACTOR (K1 Conexion alimentacion)
L1 L2 L3
PBM-B 11-12-14 (disparo por falta)
K1
STOP (parada externa motor)
PBM-B
I1
141211242221A1A2
E1C1 C2 I2E2T1 T2
START (arranque externo motor)
N
Transformador toroidal
Sondas PTC
A1
A2
K1
L (230 V)
N (0 V)
STOP
START
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
13/128
www.fanox.com 13/128
2.3.5. Direct start-up PBM protecction and control connection
CONTACTOR (K1 Conexion alimentacion)
L1 L2 L3
PBM-B 11-12-14 (disparo por falta)
K1
STOP (parada externa motor)
M
PBM-B
I1
141211242221A1A2
E1C1 C2 I2E2T1 T2
START (arranque externo motor)A1
A2
K1
L (230 V)
N (0 V)
STOP
START
PBM-B relay allows to perform start/stop actions by means of relay own commands, withoutnecessity for external actuators. It can be done in two ways:
By means of [O] and RESET keys of PBM-H:o Key [O]: By means of a short press we can generate de stop of the motor in a
voluntarie way, without existing previous fault.
o Key RESET: By means of a long press we can start the motor again.
By means of ModBus communication commands:
Description Commandnumber
Leds and outputs reset 47
Motor stop 57
NOTE: PBM H [I] key is not activated in actual version and has no functionality.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
14/128
www.fanox.com 14/128
2.4. PBM-B base module terminals
Input 24Vac/dc
24Vac/dc digital input
earth fault Toroidal earth connection
+t PTC sensor connection
A RS485 connection A
B RS485 connection B
14 Output 1 contact normally closed
12 Output 1 contact normally open
11 Common output 1
24 Output 2 contact normally closed
22 Output 2 contact normally open
21 Common output 2
A1 Supply voltage (+ with direct current)
A2 Supply voltage (- with direct current)
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
15/128
www.fanox.com 15/128
3. DESCRIPTION
3.1. Introduction
Industrial company management is gradually increasing its use of information technology andcommunication as the basis for predictive maintenance and monitoring of their facilities.
This ever increasing technology implies a technological leap for industries, as it requires thehandling of a larger amount of data, and in many occasions in real time.
To implement these new technologies the industries require simple, flexible systems which adaptto the specific requirements of the same.
These requirements include:
Simple controls.
Simple installation.
Large volume of data Real time.
Reasonable cost.
System profitability, understood as maintenance and monitoring.
The PBM is a motor control and protection system equipped with ModBus RTU communicationin real time RS485. This makes up a platform which is specifically designed to cover all themaintenance and monitoring requirements of industrial plants with motors.
The PBM devices structure is based on a base module which, according to the requirements,can be connected to various modules with specific functions.
The PBM B base module (DIN rail EN50022-35), with the following functions:
Motor related current protections.
Temperature protection.
Earth protections.
Trip and signalling.
Communications with the scada.
Fault reports.
Statistics.
The PBM H module, is an HMI module (panelable) to access the PBM B information.
The system functions can be increased in the future with additional modules.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
16/128
www.fanox.com 16/128
Description PBM-B PBM-H
PROTECTION FUNCTIONS
Overload (trip classes 5-10-15-20-25-30-35-40-45)
Phase imbalance
Phase failure
Phase sequence
PTC
PT100
Jam
Locked rotor
Instantaneous neutral overcurrent
Neutral inverse time overcurrent
Instantaneous earth leakage overcurrent
Earth leakage inverse time overcurrent
Undercurrent
Excessive start up time
MEASUREMENTS
Phase A current (IA)
Phase B current (IB)
Phase C current (IC)
Neutral current (I0)
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
17/128
www.fanox.com 17/128
Earth leakage current (IG)
Thermal image
Frequency measurement
Positive sequence current (I1)
Negative sequence current (I2)
Average phase current
STATISTICS
Number of start-ups
Maximum start-up current
Maximum current in last start-up
Medium start-up current
Overload faults
PTC faults
Jam faults
Locked rotor faults
Neutral faults
Operating hours
SIGNALLING AND CONTROL
Time delayed equipment start
Digital Inputs 1
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
18/128
www.fanox.com 18/128
Digital outputs 2
Reset/Test Button
Led 1:
Led 2:
Led 3:
Led 4:
Led 5:
Led 1 configurable
Led 2 configurable
Led 3 configurable
Led 4 configurable
Led 5 configurable
Led 6 configurable
MECHANICAL
DIN rail EN50022-35
Panelable
Width 78 mm.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
19/128
www.fanox.com 19/128
ACCESSORIES
Toroidal transformer
Current transformer
PTC sensors
Cables section
PBM-B to PBM-H connection cable
3.2. Description
The PBM is a three phase motor control and protection system. It includes the motor current andthermal protections, as well as the monitoring and diagnosis functions to perform predictivemaintenance and to prevent system down times.
The base module is the essential components of the PBM system. This must always be includedand provide basic system protection on its own. The base module is a 78 mm item to bemounted on a DIN rail.
The available protection functions are as follows:
Overload protection and availability of a PTC sensor.
Protection against imbalance, phase failure and phase reversal
Protection against jam, locked rotor and undercurrent.
Earth protection: Instantaneous neutral overcurrent, neutral inverse time overcurrent,instantaneous earth leakage overcurrent, earth leakage inverse timeovercurrent.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
20/128
www.fanox.com 20/128
To facilitate predictive maintenance there are surveillance algorithms of the status of theequipment, both regarding external connections and the internal operation of the equipment andof test functions to check the correct operation of the outputs and leds:
Monitoring of the neutral toroidal transformer in open circuit.
PTC sensor short circuit
Self-diagnosis
PBM-B base module leds and outputs test
PBM-H module leds test
This allows the installation motors to be started up in a staggered way, by means of anadjustable timer from 0 to 3600 s.
The alarm and trip output relays are activated with positive safety.
The following measurements are provided: Phase currents, neutral current (calculated as adigital sum of the phase currents), earth leakage current (measured by an external toroidaltransformer), average phase current, negative sequence current, positive sequence current,thermal image and frequency.
The algorithm used to measure the currents is the real RMS (real Root Mean Square realefficient value). 16 samples cycles sampling is performed. The sampling type is determinedwhen the system frequency is adjusted. This is performed at a set time if the adjusted frequencyis 50 or 60 Hz, and at variable time is it is adjusted at a variable frequency (45Hz to 65 Hz). Theaccuracy of the measurement is 2% over the whole range. The variable frequency sampling isonly valid for models with alternating supply, as the alternating supply signal is taken asreference to calculate the line frequency.
Up to four fault reports are stored in the non volatile memory. The fault reports contain
information regarding the date, measurements and a subassembly of the statusof the equipmentwhich are sufficient to determine the cause of the incident (all the phase discriminated functionstrips, the inputs and outputs).
All the equipment information can be accessed from the PBM-H and from an RS485communications port on terminals, which allows for the equipment to be included as part of aSCADA system. The RTU Modbus protocol is used. A communication session is established witha key that can be set by the user.
The PBM-B is fitted with five signal leds and a reset button to reset the output and led latchs.
The PBM-H module is equipped with an LCD with two rows and twenty columns and a six keymembrane keyboard which can be used to access all the system information. It is also equippedwith six adjustable signal leds. Each led can be assigned a 16 bit status OR and can be set aslatched or not latched and/or as flashing or not flashing. It is also equipped with a start buttonand a stop button and a test/reset button which has the double function of testing the equipmentleds (PBM-B and PBM-H) and resets the output and led interlocks.
The PBM-B can operate normally without the PBM-H module. Once programmed, either by themobile PBM-H or the communication, the PBM-B operates on its own, providing information viaits leds or communication.
Thanks to the available protection and monitoring functions, its easy to use HMI and its simpleintegration, the PBM provides a precise and practical solution for motor control central unitprotection.
The main features of the equipment are listed below, and these features will be explained in therest of the manual.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
21/128
www.fanox.com 21/128
Function Description PBM-B
Protection
Overload Overload (trip classes 5-10-15-20-25-30-35-40-45) 1
Imbalance Phase imbalance 1
Phase failure Phase failure 1
Sequence Phase sequence 1
PTC PTC function (Positive Temperature Coefficient) 1
Jam Jam 1
Locked rotor Locked rotor 1
I0>> Instantaneous neutral overcurrent. 1
I0> Neutral inverse time overcurrent 1
IG>> Instantaneous earth leakage overcurrent (with external toroidal transformer) 1
IG> Earth leakage inverse time overcurrent (with external toroidal transformer) 1
I< Phase undercurrent 1
Excessive start up time 1
Measurements
IA, IB, IC Phase current rms measurement with 2% accuracy
I0 Neutral current rms measurement with 2% accuracy
IG Earth current rms measurement with 2% accuracy
Thermal image
f Frequency
Iavg Average current of the three phases
I1 Positive sequence current
I2 Negative sequence current
Inputs and Outputs
Digital input 24 Vac/dc 1
Button 1
Digital outputs: Trip and alarm 2
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
22/128
www.fanox.com 22/128
Communication
RS485 Communication (ModBus, RTU 19200)
Control and signalling
Time delayed equipment start
Led indicators on the PBM-B base module 5
Thermal image reset command
Led and output latch reset command
Power
110/230 Vac/dc
24/48 Vdc
Selected bymodel
Monitoring and Recording
Real-Time Clock (RTC)
Neutral toroidal transformer monitoring
PTC sensor open circuit and short circuit detection
Fault reports 4
Self-diagnosis
Number of start ups
Maximum start up current:
Maximum last start-up current
Average start-up current
Overload faults
PTC faults
Jam faults
Locked rotor faults
Neutral faults
Operating hours
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
23/128
www.fanox.com 23/128
Control and signalling
LCD, 20x2 and 6 keys
Reset/Test Button
Start and stop buttons
Adjustable LED indicators 6
Session establishment with adjustable key
Monitoring
Base module PBM-B test menu
Module PBM-H test menu
3.3. PBM-B base module functional diagram
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
24/128
www.fanox.com 24/128
3.4. List of Models
3.4.1. PBM B model list
MODULE
PHASE
MEASUREMENT
POWERSUPPLY
ADAPTATION
PBM B BASE module
1
5
IB= 0,8 - 6 A
IB= 425 A
1
2
110/230 Vca/cc
24/48 Vcc
0
3.4.2. PBM H model list
MODULE
HMI
LANGUAGE
ADAPTATION
PBM H HMI module
1 HMI with 6 leds
E
S
F
X
English
Spanish
French
Polish
0
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
25/128
www.fanox.com 25/128
4. PBM-B PROTECTION FUNCTIONS AND FEATURES
4.1. General settingsThe equipment's general adjustments are as follows:
General settings
Description Mnimum Maximum Step Unit Defect
IB Rated motor current
Model PBMB1* 0,8 6 0,01 A 0,8
Model PBMB5* 4 25 0,01 A 4
Phase transformation ratio 1 2000 1 - 1
Frequency - - 50Hz/60Hz/var Hz 50
Motor start up threshold 1 8 0,01 xIB 1,5
Motor start up time 1 200 1 s 60
Motor phases sequence - - ABC/ACB - ABC
Time delayed equipment start up 0 3600 1 s 0
The first group adjustment is the motor rated current, which is referred to as IBin this manual.For model PBMB1*, the rated current range is 0.8 to 6 A. For model PBMB5*, the rated currentrange is 4 to 25 A. To protect the motor, the motor rated current (IB), must be adjusted with thesame value as the rated current that appears on the motor characteristics badge.
In case to use a motor with nominal current below the minimum relay current setting value,pass through the hole of the relay n time. IB setting value will be INxn, being IN nominalcurrent shown on the motor plate.
To protect a motor with nominal current greater than the maximum relaycurrent setting value,current transformer will be used. IB setting value be nominal current shown on the motor platedivided by CTR which is phase transformation ratio.
The motor start up threshold and "motor start up time" adjustments are used for the functionwhich monitors the motor start up, to establish that the start up is excessively long.
NOTE:It is necessary to select a value between 1 and 200 second for motor Start Up itemin order to get a correct monitoring of the motor start. In case of wanting to deactivate thismonitoring, it is possible to do it, under user responsibility, selecting 0 value. Nevertheless, it is
recommende to maintain the monitoring of motor start activated to avoid unexpected damages inthe motor.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
26/128
www.fanox.com 26/128
The frequency can be adjusted to 50 HZ, 60 Hz and variable frequency (with the equipmentmaintaining measurement accuracy and time within the range of 45 Hz to 65 Hz). The variablefrequency can only be applied to models with alternating supply voltage.
The motor phasesequence adjustment is used for the reverse function to determine whether or
not the wiring consistent with the adjustments.The time delayed equipment start up " adjustment is used for staggered installation motor startup.
4.2. Overload
The overload function meets international standard IEC 947-4-1 and IEC 255-8.
A physical model based mathematic model is used to simulate the motor's thermal condition. Themathematic model used combines two thermal images: A heating image and a cooling image.The heating image represents the thermal condition of the windings of the stator and rotor, and
the cooling image represents the thermal condition of the casing.
The fact that PBM-B is fitted with a heating and cooling thermal memory, it can define themargins at all times so that the motor operates in a safe mode.
The thermal image is a measurement of the motor heating condition. Unlike the overcurrentrelay, time is not counted as of when a fault is detected but rather this is continuouslydetermining the thermal condition of the motor. The trip time depends on the trip class selected,the circulating current and the previous motor thermal condition.
The thermal image is calculated based on the following equation:
= 100 x (I/It)2x (1e
-t/) + 0x e
-t/
Where:
I,maximum current of the three phases
It, trip threshold current
, thermal constant.
0, initial thermal condition
The trip time comes from the equation:
t = x ln { [(I/It)
2
(0/ 100)] / [(I/It)
2
- 1] }
The trip time accuracy is 5% above the theoretical time.
The algorithm uses the maximum current of the three phase currents. If the maximum current isgreater than 15% of the adjusted current IB, the heating thermal constant is applied. If themaximum current is less than 15% of the adjusted current IB, the cooling thermal constant isapplied.
The overload function trips when the thermal image reaches a value of 100%. This value isreached in the time when the circulating current is equal to the adjusted input in the thermalfunction (It).
A thermal image adjustable level is established to generate an alarm. Should a trip occur, the
overload function is reset when the thermal image drops below the set alarm level.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
27/128
www.fanox.com 27/128
The thermal constant has the following values:
heating = 37 x trip class
cooling = 90 x trip class
If there is independent mechanical ventilation,
cooling = (90 x trip class) / 4
This function settings are as follows:
Overload
Description Minimum Maximum Step Unit Defect
Enable function - - Yes/No - Yes
Tap 1 2 0,01 IB 1,15
Trip class - - 5,10,15,20,25,30,35,40,45 - 5
Independent mechanical ventilation - - Yes/No - No
Alarm 20 95 1 % 80
We allow the overload function tap adjustment in a range of between 1 and 2 times I B, so that theuser can make the most of the motor capacity. However, it must be pointed out that standardIEC-947-4-1 recommends the tap setting to be between 1.05 and 1.20 times IB.
Trip classes 5, 10, 20, 30 and 40 are standard. The other class settings 15, 25, 35 and 45 permitadaptation to the various motor types.
4.3. Phase imbalance
The imbalance function is applied on the three phase system made up of the three phasecurrents (IA, IB, IC). The average current of the three values is taken as reference. The function
is operative if the average current is greater than 10% of the motor set current I Band becomesinoperative if the average current is less than 8%.
A correct operation band is established based on the average current. Its upper and lower limitsresult from the % adjusted imbalance and 5% hysteresis is considered in resetting.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
28/128
www.fanox.com 28/128
The imbalance resetting and activation limits are determined as follows, based on the % adjustedimbalance (value d1%):
Upper limit activation Iaverage* (100 + d1)%
Upper limit resetting Iaverage* (100 + d15)%
Lower limit activation Iaverage* (100 - d1)%
Lower limit resetting Iaverage* (100 - d1+ 5)%
The criteria is applied to the three phases. If a phase current is greater than the upper limit orless than the lower limit the function start up is activated. Once the function has been activated, if
the phase current drops below the upper reset limit or rises above the lower reset limit, thefunction is instantly reset.
The function trip can be time delayed and two different times have been established: one applieswhen the motor is starting up, and the other when the motor is in operation. As a result, apossible phase failure can be detected in the motor start up and a fast trip can be executed.
This function settings are as follows:
Imbalance
Description Minimum Maximum Step Unit Defect
Enable function - - Yes/No - Si
% Imbalance 5 30 1 % 30
Motor start up time 0,02 20 0,001 s 0,6
Motor operation time 0,02 20 0,001 s 5
This function is similar to the phase failure function. In principle, this function must be used to
detect small current imbalances. The use of the phase failure function is recommended toprovide protection against large imbalances of the lower limit.
4.4. Phase failure
The phase failure function is applied on the three phase system made up of the three phasecurrents (IA, IB, IC). The average current of the three values is taken as reference. The functionis operative if the average current is greater than 10% of the adjusted current IBand becomesinoperative if the average current is less than 8%.
Based on the average current, a lower limit is established resulting from the % adjusted
imbalance and 5% resetting hysteresis. The phase failure resetting and activation limits aredetermined as follows, based on the % adjusted imbalance (value d2%):
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
29/128
www.fanox.com 29/128
Lower limit activation Iaverage* (100d2)%
Lower limit resetting Iaverage* (100d2+ 5)%
The criteria is applied to the three phases. If a phase current is less than the lower limit thefunction start up is activated. Once the function has been activated, if the phase current risesabove the lower reset limit, the function is instantly reset.
There is only on operating time, regardless of whether the motor is starting up or in operation.
This function settings are as follows:
Phase failure
Description Minimum Maximum Step Unit Defect
Enable function - - Yes/No - Yes
% Imbalance 10 100 1 % 30
Time 0,02 20 0,001 s 5
4.5. Phase sequence
The sequence function is activated when the phase sequence is detected to not be inaccordance with the general phase sequence adjustment (ABC/ACB).
The phase sequence function detection algorithm is based on the determination of the positiveand negative sequence of the essential currents component.
The function is operative if the positive sequence current or the negative sequence current isgreater than 10% of the adjusted current IBand stops operating if the positive sequence currentand the negative sequence current is less than 8%.
This function settings are as follows:
Phase sequence
Description Minimum Maximum Step Unit Defect
Enable function - - Yes/No - No
Time 0,02 2 0,001 s 0,02
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
30/128
www.fanox.com 30/128
4.6. PTC Function
The PTC sensors provide accurate control of the temperature the motor is subjected to at
various points of its structure. The sensor operation is based on an extremely fast increase in itsresistance once its own temperature limit has been reached.
PTC sensor protection is used in cases such as the following:
Motors with high start up/stoppage frequencies
Motor operating at speeds which are lower than the range it is designed for.
When there is a restricted air supply.
In intermittent operations and/or constant braking.
High air temperatures.
PTC sensor short circtui or open circuit and overtemperature are detected. Overtemperatureactivates the trip contact whilst sensor open circuit and short circuit activate the alarm contact.The PTC sensor protection thresholds cannot be set. They are predefined as follows:
Activationresistance
Resetresistance
Overtemperature > 3600 < 1800
Short-circuit < 20 > 30
Open circuit > 4000 < 3900
The PTC function has the enable function adjustment:
PTC
Description Minimum Maximum Step Unit Defect
Enable function - - Yes/No - No
The trip time is 500 ms.
The PTC sensors used shall have a maximum current of 1mA and a maximum voltage of 2.3 V.
Maximum cold resistance 1500
Minimum cold resistance 50
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
31/128
www.fanox.com 31/128
4.7. Jam function
The motor is considered to be operating in jam conditions when the resistant torque of the motoris very close to the maximum torque the motor can provide, whereby motor rotation is slowingdown.
This function shall be disabled during motor start up. Following start up, the function shall beenabled whenever permitted by the user.
This function settings are as follows:
JAM
Description Minimum Maximum Step Unit Defect
Enable function - - Yes/No - No
Tap 1 3,5 0,01 IB 2,5
Operating time 0,02 50 0,001 s 10
Operation time is independent of the operating current which flows through the equipment,whereby, should the phase current exceed the adjusted value during the preestablished time, theprotection function is activated (trips). It is deactivated when the average phase current valuefalls below 95% of the adjusted tap.
4.8. Locked rotorThis function detects a locked rotor. This function shall be disabled during motor start up.Following start up, the function shall be enabled whenever permitted by the user.
This function settings are as follows:
Locked rotor
Description Minimum Maximum Step Unit Defect
Enable function - - Yes/No - No
Tap 3,5 6 0,01 IB 3,5
Operating time 1 30 0,001 s 5
Operation time is independent of the operating current which flows through the equipment,whereby, should the phase current exceed the adjusted value during the preestablished time, theprotection function is activated (trips). It is deactivated when the average phase current valuefalls below 95% of the adjusted tap.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
32/128
www.fanox.com 32/128
4.9. Instantaneous neutral overcurrent.
This protection function can be set by using three parameters:
Instantaneous neutral overcurrent
Group Description Minimum Maximum Step Unit Defect
I0>> Enable function - - Yes/No - No
Tap 0,1 1 0,01 IB 0,1
Operating time 0,02 5 0,001 s 1
Operation time is independent of the operating current which flows through the equipment,whereby, should the neutral current (I0) exceed the adjusted value during the preestablishedtime, the protection function is activated (trips). It is deactivated when the average neutral currentvalue falls below 95% of the adjusted tap.
4.10. Neutral inverse time overcurrent
This protection function can be set by using five parameters:
Neutral inverse time overcurrent
Group Description Minimum Maximum Step Unit Defect
I0> Enable function - - Yes/No - No
Curve - - (1*) - Inverse
Dial 0,05 1,25 0,01 - 1,25
Tap 0,1 1 0,01 IB 1,00
Operating time 0,02 5 0,001 s 0,2
(1*) Inverse, Very inverse, Extremely inverse, Defined time
If the option "Defined time" is selected for the curve setting, the unit behaves like aninstantaneous overcurrent unit. In this case, the unit operating time is adjusted by using theparameter "Operating time".
If a curve (inverse, very inverse or extremely inverse) is selected for the curve setting, theoperating time depends on the curve, dial and tap settings.
If the unit operates as defined time, the function is activated at 100% of the set tap value, and it
deactivates at 95%.
If the unit operates with a curve, the function is activated at 110% of the set tap value, and itdeactivates at 100%.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
33/128
www.fanox.com 33/128
The reset is instantaneous in both cases.
The activation time is accurate to 5% or 30ms, whichever is higher, of the theoretical activationtime.
The curves used are IEC60255-151, which are described in the "Curves" section.
4.11. Instantaneous earth leakage overcurrent.
With external toroidal transformer.
This protection function can be set by using three parameters:
Instantaneous earth leakage overcurrent.
Group Description Minimum Maximum Step Unit Defect
IG>> Enable function - - Yes/No - No
Tap 100 15000 1 mA 100
Operating time 0,02 5 0,001 S 0,2
Operation time is totally independent of the operating current which flows through the equipment,whereby, should the earth leakage current (IG) exceed the adjusted value during thepreestablished time, the protection function is activated (trips). It is deactivated when the average
earth leakage current value falls below 95% of the adjusted tap.
4.12. Earth leakage inverse time overcurrent.
With external toroidal transformer.
This protection function can be set by using the following parameters:
Earth leakage inverse time overcurrent.
Group Description Minimum Maximum Step Unit Defect
IG> Enable function - - Yes/No - No
Curve - - (1*) - Inverse
Dial 0,05 1,25 0,01 - 1,25
Tap 100 450 1 mA 100
Operating time 0,02 5 0,001 s 0,2
(1*) Inverse, Very inverse, Extremely inverse, Defined time
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
34/128
www.fanox.com 34/128
If the option "Defined time" is selected for the curve setting, the unit behaves like aninstantaneous overcurrent unit. In this case, the unit operating time is adjusted by using theparameter "Operating time".
If a curve (inverse, very inverse or extremely inverse) is selected for the curve setting, the
operating time depends on the curve, dial and tap settings.If the unit operates as defined time, the function is activated at 100% of the set tap value, and itdeactivates at 95%.
If the unit operates with a curve, the function is activated at 110% of the set tap value, and itdeactivates at 100%. The reset is instantaneous in both cases.
The activation time is accurate to 5% or 30ms, whichever is higher, of the theoretical activationtime.
The curves used are IEC60255-151, which are described in the "Curves" section.
4.13. Undercurrent
The undercurrent function is used to detect whether the motor operation current is less than thedesired level, due to the operation of the motor in no load due to transmission breakage,transformer belt underload, no load pump,
The undercurrent function is not enabled during motor start-up.
This function settings are as follows:
Undercurrent
Group Description Minimum Maximum Step Unit Defect
I
-
8/14/2019 En PBM User-Manual R009
35/128
www.fanox.com 35/128
4.14. Motor start up monitoring
The adjustments relating to motor start up monitoring are as follows, which as in the general
settings group:
Motor start up monitoring
Description Minimum Maximum Step Unit Defect
Motor start up threshold 1 8 0,01 IB 1,5
Motor start up time 1 200 0,001 s 60
The following automaton describes the operation of this function:
MotorStand by Motor
first stepMotorsecond step
Motorin operation
Iaverage > 10% IB
Iaverage < 8% IBIav erage> Treshold Iav erage < 95% Treshold
tstart up ++ tstart up ++
Iaverage < 8% IB
Extendedstart up
t real start up > t real adjusted
Iaverage < 8% IB
The motor is considered to be on standby when the average current is less than 8% of theadjusted current IB. When the average current is greater than 10% of the adjusted current westart monitoring start up and switch to Motor first step status. From Motor first step, when theaverage current is greater than the adjusted motor start up threshold, we switch to Motor secondstep". From Motor second step, when the average current is less than 95% of the adjusted startup threshold, we switch to Motor in operation".
In Motor first step" and "Motor second step" we monitor the start up time. If the measured startup time is greater than the adjusted start up time, we switch to Extended start up.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
36/128
www.fanox.com 36/128
Iaverage
10% IB
Treshold
Stand by
firststep
second step in operation
95% Treshold
t < Adjusted start up time
There are two status bits in the miscellanous group, related to motor monitoring: Motor in
operation and excessive start up time.
The following statistics are related to motor start up:
Number of start ups
Maximum start up current:
Maximum last start up current:
Medium last start up current:
Measured start up time (second step time)
Number of operating hours (motor in operation)
NOTE: To ensure proper working of undercurrent function (I
-
8/14/2019 En PBM User-Manual R009
37/128
www.fanox.com 37/128
1.15 IB
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
38/128
www.fanox.com 38/128
1,15 IB
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
39/128
www.fanox.com 39/128
1,15 IB
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
40/128
www.fanox.com 40/128
1,15 IB
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
41/128
www.fanox.com 41/128
1,15 IB
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
42/128
www.fanox.com 42/128
1,15 IB
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
43/128
www.fanox.com 43/128
1,15 IB
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
44/128
www.fanox.com 44/128
1,15 IB
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
45/128
www.fanox.com 45/128
1,15 IB
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
46/128
www.fanox.com 46/128
4.16. IEC60255-151 Curves
The PBM-B relay complies with the curves shown in standard IEC60255-151:
Inverse Curve
Very Inverse Curve
Extremely Inverse Curve
There is a general mathematical equation which defines the time, in seconds, as a function of thecurrent:
KDBQV
DAt
P
adjustedI
IV
Parmetros: A P Q B K
Ext. Inverse 80 2 1 0 0
Very Inverse 13,5 1 1 0 0
Inverse 0,14 0,02 1 0 0
The curve can move from its axis using the D time selection device, which the user can adjust. Vis the tap.
Iadjustedis the initial operating current, set by the user.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
47/128
-
8/14/2019 En PBM User-Manual R009
48/128
www.fanox.com 48/128
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
49/128
www.fanox.com 49/128
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
50/128
www.fanox.com 50/128
5. MONITORING AND CONTROL
5.1. Measurements
The three phase currents are provided (IA,IB,IC), as well as the neutral current (I0) calculated asa digital sum of the phase currents, the earth leakage current (IG) measured by mediums of anexternal toroidal transformer, the positive sequence current, the negative sequence current, theaverage current of the three phases, the thermal image measurement (%) and the linefrequency.
The earth current value is obtained in two ways:
By mediums of an external toroidal transformer which covers the three phases (IG).Additionally, the PBM-B will check that the toroidal transformer is not in an open circuit.
If the three phase motor is directly connected to earth of via a sufficiently low impedance,
the earth current value can be obtained by adding the currents measured via the threetransformers fitted on the PBM-B itself (I0).
The currents measurement (IA,IB,IC,I0,IG) are R.M.S. values (real efficient value). Themeasurement accuracy is 2% in the whole measurement range. 16 samples cycles sampling isperformed. Sampling can be taken at line frequency (50 or 60Hz) or at a variable frequency,adjusting the equipment sampling to the real frequency. Using the sampling at a variablefrequency, a measurement accuracy of 2% is guaranteed in the 45HJz to 65 Hz range. Thevariable frequency sampling will be valid in the models which are supplied alternating voltage, asthe supply voltage is taken as a reference to calculate the frequency.
The frequency is measured using the zero cross algorithm. The supply voltage shall be taken asreference, whereby the frequency measurement shall be valid for models supplied with gridalternating voltage.
Below are the residual neutral and phase measurement ranges of the PBM-B models:
Model PBM1X PBM5X
Range IB 0,8 - 6 A 425 A
Residual neutral and phase measurement range with no external currenttransformers.
Transformer Ratio = 1
0,2 - 30 A 1- 150 A
Residual neutral and phase measurement range with external currenttransformers.
Transformer Ratio = R
0,2R30RA R150RA
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
51/128
www.fanox.com 51/128
5.2. States
The states are real time information regarding the changes in the equipment. The equipmentstates can be consulted from the PBM-H and communications.
All the equipment states are listed below:
Group States
Overload
Alarm overload
Trip overload
Imbalance
Phase A pick up imbalance
Phase B pick up imbalance
Phase C pick up imbalance
Function pick up imbalance
Phase A trip imbalance
Phase B trip imbalance
Phase C trip imbalance
Function trip imbalance
Phase failure
Phase A pick up phase failure
Phase B pick up phase failure
Phase C pick up phase failure
Function pick up phase failure
Phase A trip phase failure
Phase B trip phase failure
Phase C trip phase failure
Function trip phase failure
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
52/128
www.fanox.com 52/128
Phase sequence
Phase sequence
Phase sequence
PTC
Overtemperature PTC
Open circuit PTC
Short circuit PTC
JAM
Phase A pick up jam
Phase B pick up jam
Phase C pick up jam
Function pick up jam
Phase A trip jam
Phase B trip jam
Phase C trip jam
Function trip jam
Locked rotor
Phase A pick up locked rotor
Phase B pick up locked rotor
Phase C pick up locked rotor
Function pick up locked rotor
Phase A trip locked rotor
Phase B trip locked rotor
Phase C trip locked rotor
Function trip locked rotor
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
53/128
www.fanox.com 53/128
Instantaneous neutral overcurrent
I0>> I0>> pick up
I0>> trip
Neutral inverse time overcurrent
I0> I0> pick up
I0> trip
Instantaneous earth leakage overcurrent
IG>> IG>> pick up
IG>> trip
Earth leakage inverse time overcurrent
IG> IG> pick up
IG> trip
Phase undercurrent
I < I< Phase A pick up
I< Phase B pick up
I< Phase C pick up
I< Phases pick up
I< Phase A trip
I< Phase B trip
I< Phase C trip
I< Phases trip
Outputs
Output 1
Output 2
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
54/128
www.fanox.com 54/128
Inputs
Input 1
Trip locking
Miscellaneous
Motor : In operation
Motor : Excessive start up time
G toroidal transformer open
Settings error
Configuration error
Reports error
Statistics error
Equipment alarm
Protection trip
Enable outputs
Trip disenabling
The Equipment alarm bit consists of the following bits:
Overload: Alarm
PTC: Short-circuit
PTC: Open circuit
Miscellaneous: G toroidal transformer open
Miscellaneous: Adjustment error
Miscellaneous: Settings error
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
55/128
www.fanox.com 55/128
The Protection trip bit consists of the following bits:
Overload: Function trip
Imbalance: Function trip
Phase failure: Function trip
Sequence: Function trip
PTC: Overtemperature
Jam: Function trip
Locked rotor: Function trip
I0>>: Function trip
I0>: Function trip
IG>>: Function trip
IG>: Function trip
I operations) earth current operations (sum of I0>>, I0>, IG>>,IG>>)
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
56/128
www.fanox.com 56/128
5.4. Fault reports
Up to four fault reports are stored in the non volatile memory. The fault report is generated whenoutput 1 is activated (trip). They can be displayed via the PBM-H or communications.
The information related to each fault report is as follows:
1. Date
2. IA
3. IB
4. IC
5. I0
6. IG
7. Thermal imaging
8. Frequency9. Medium current
10. Overload: trip
11. Imbalance: Phase A trip
12. Imbalance: Phase B trip
13. Imbalance: Phase C trip
14. Phase failure: Phase A trip
15. Phase failure: Phase B trip
16. Phase failure: Phase C trip
17. Sequence: Trip
18. PTC: Overtemperature
19. PTC: Short-circuit
20. PTC: Open circuit
21. Jam: Phase A trip
22. Jam: Phase B trip
23. Jam: Phase C trip
24. Locked rotor: Phase A trip
25. Locked rotor: Phase B trip
26. Locked rotor: Phase C trip
27. I0>>: Trip
28. I0>: Trip
29. IG>>: Trip
30. IG>: Trip
31. I
-
8/14/2019 En PBM User-Manual R009
57/128
www.fanox.com 57/128
36. Output 1
37. Output 2
38. Motor : In operation
39. Motor : Excessive start up time
40. G toroidal transformer open
41. Enable outputs
To obtain more detailed information, the method for navigating the menus is explainedgraphically in the LCD and keyboard section.
5.5. Date-time synchronisation
The equipment can be synchronised from the PBM-H or by using communications. The PBM-Bequipment is fitted with a Real Time Clock. Without power supply, RTC maintains date and time
during 72 hours with 65C (worst situation).
5.6. Inputs
A digital input of 24 Vac/dc is fitted, with a reset function.
5.7. Outputs
There are two digital outputs. Ouput 1 is assigned the protection trip bit and output 2 is assigned
the equipment alarm bit. The outputs operate with positive safety.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
58/128
www.fanox.com 58/128
5.8. Leds
5.8.1. PBM-B equipment leds
The PBM-B equipment leds cannot be set and they have the following meanings:
LED ON Constant Equipment OK
Flashing -
LED I>
Constant Overload trip
Jam trip
Locked rotor trip
Extended start up trip
Flashing Undercurrent trip
Led I0
Constant Instantaneous neutral overcurrent trip.
Neutral inverse time overcurrent trip.
Instantaneous earth leakage overcurrent trip.
Earth leakage inverse time overcurrent trip.
Flashing CT connection alarm
LED
+t
Constant PTC sensor overtemperature trip
Flashing PTC sensor short circuit
PTC sensor open circuit
LED Constant Phase imbalance trip
Phase loss trip
Flashing Phase sequence trip
Once activated, the leds are latched and maintain signalling. Holding down the Test/Reset key(3 seconds) resets the leds and the latched outputs.
If the equipment supply is cut off led signalling is lost.
5.8.2. PBM-H hmi leds
The user can set the six hmi leds. The leds can be set as latched or not latched, and as flashingor constant, with the possibility of all the combinations:
Not latched Constant
Not latched Flashing
Latched Constant
Latched Flashing
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
59/128
www.fanox.com 59/128
If the leds have been set as latched, once activated they maintain signalling. Holding down theTest/Reset key (3 seconds) resets the leds and the latched outputs.
If the equipment supply is cut off led signalling is lost.
The following status bits can be assigned to the leds:
1. Not configured
2. Overload: alarm
3. Overload: trip
4. Imbalance: Phase A pick up
5. Imbalance: Phase B pick up
6. Imbalance: Phase C pick up
7. Imbalance: Pick up
8. Imbalance: Phase A trip
9. Imbalance: Phase B trip
10. Imbalance: Phase C trip
11. Imbalance: trip
12. Phase failure: Phase A pick up
13. Phase failure: Phase B pick up
14. Phase failure: Phase C pick up
15. Phase failure: Pick up
16. Phase failure: Phase A trip
17. Phase failure: Phase B trip
18. Phase failure: Phase C trip
19. Phase failure: trip
20. Sequence: Pick up
21. Sequence: trip
22. PTC: overtemperature
23. PTC: Short circuit
24. PTC: Open circuit
25. Jam: Phase A pick up
26. Jam: Phase B pick up
27. Jam: Phase C pick up
28. Jam: Pick up
29. Jam: Phase A trip
30. Jam: Phase B trip
31. Jam: Phase C trip
32. Jam: trip
33. Locked rotor: Phase A pick up
34. Locked rotor: Phase B pick up
35. Locked rotor: Phase C pick up
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
60/128
www.fanox.com 60/128
36. Locked rotor: Pick up
37. Locked rotor: Phase A trip
38. Locked rotor: Phase B trip
39. Locked rotor: Phase C trip
40. Locked rotor: trip
41. I0>>: Pick up
42. I0>>: trip
43. I0>: Pick up
44. I0>: trip
45. IG>>: Pick up
46. IG>>: trip
47. IG>: Pick up
48. IG>: trip49. I
-
8/14/2019 En PBM User-Manual R009
61/128
www.fanox.com 61/128
The default leds configuration is shown below:
Led 1 Equipment OK
Led 2 Overload / jam / locked rotor / extended start up trip
Led 3 Neutral / earth leakage trip
Led 4 PTC sensor trip
Led 5 Phase imbalance / phase loss trip / Phase sequence trip
Led 6 % Thermal image alarm / G toroidal transformer open alarm / Shortcircuit PTCsensor / open circuit PTC sensor alarm / Undercurrent trip /
LED indicator operation can be checked from the module test menu, to check each led'soperation individually. Also, all the leds flash at the same time when the "Test" key is pressed.
Each led has an identification label where the corresponding legend is written.
5.9. Self-diagnosis
Diagnostic algorithms are run while the PBM-B is being started up and continuously when the
relay is operating. This diagnostic is a preventative process to guarantee that the equipment is ingood operational condition.
The following status bits are associated with this process:
Adjustment errorProblem in the adjustments saved in e2prom.
The active adjustments are the default adjustments.
Settings errorProblem in the setting saved in e2prom.
The settings block is not executed.
Reports error Problem in the reports saved in e2prom.
The reports are not displayed.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
62/128
www.fanox.com 62/128
5.10. Commands
The following table lists the available commands and how to execute the:
Test leds
PBM-B: Short press test/reset button
PBM-H: Short press test/reset button
Communication: Control 44
Outputs and leds reset
PBM-B: Test/reset button held down
PBM-H: Test/reset button held down
Communication: Control 47
Statistics reset
PBM-H: Control menu
Communication: Control 51
Operation hours reset
PBM-H: Control menu
Communication: Control 53
Thermal image reset to 75%
PBM-H: Control menu
Communication: Control 54
Motor stop command
PBM-H: Stop key
Communication: Control 57
To facilitate the overload function tests, the following commands are included which are onlyavailable from communication:
Thermal image reset to 75% Communication: Control 54
Thermal image reset to 0% Communication: Control 55
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
63/128
www.fanox.com 63/128
5.11. Test programm
5.11.1. Base module PBM-B test programm
The PBM-B equipment is equipped with a test menu from where the led and outputs operationcan be checked via the PBM-H.
The following table shows the components that can be tested, along with their status dependingon whether they are activated or deactivated:
Led 1
Deactivated Led 1 off
Activated Led 1 on
Led 2
Deactivated Led 2 off
Activated Led 2 on
Led 3
Deactivated Led 3 off
Activated Led 3 on
Led 4
Deactivated Led 4 off
Activated Led 4 on
Led 5
Deactivated Led 5 off
Activated Led 5 on
Output 1
Deactivated Output 1 deactivated
Activated Output 1 activated
Output 2
Deactivated Output 2 deactivated
Activated Output 2 activated
The following key sequence is used to access to the test menu: from the main menu, press thekeys , , and in sequence and then press and hold the "OK" key until the "TEST -DISPLAY" appears on the display. Pressing the key we access the TEST-PBM menu, andpressing OK, we access the test menu for the PBM-B base module. We navigate the variousmenu items using the and keys. Each item can be activated or deactivated by pressing"OK" on it (if the item is deactivated, it is activated by pressing OK; if the item is activated, it isdeactivated by pressing OK). Press the C key to exit the test menu.
To obtain more detailed information, the method for navigating the menus is explainedgraphically in the LCD and keyboard section.
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
64/128
www.fanox.com 64/128
5.11.2. Module PBM-H test programm
The PBM-H equipment is equipped with a test menu from where the led and keys operation canbe checked.
The following table shows the components that can be tested, along with their status:
Led 1
Deactivated Led 1 Switched off
Activated Led 1 Switched on
Led 2
Deactivated Led 2 Switched off
Activated Led 2 Switched on
Led 3Deactivated Led 3 Switched off
Activated Led 3 Switched on
Led 4
Deactivated Led 4 Switched off
Activated Led 4 Switched on
Led 5
Deactivated Led 5 Switched off
Activated Led 5 Switched on
Led 6
Deactivated Led 5 Switched off
Activated Led 5 Switched on
Tecla
Deactivated No key pressed
Up key pressed
Down key pressed
Left key pressed
Right key pressed
OK OK key pressed
C C key pressed
Operation I key pressed
Stop O key pressed
Reset RESET key pressed
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
65/128
www.fanox.com 65/128
The following key sequence is used to access to the test menu: from the main menu, press thekeys , , and in sequence and then press and hold the "OK" key until the "TEST -DISPLAY" appears on the display. Pressing the OK key gives access to the hmi module testmenu. Use the and keys to browse through the different menu items. Each item can beactivated or deactivated by pressing "OK" on it (if the item is deactivated, it is activated by
pressing OK; if the item is activated, it is deactivated by pressing OK). To exit the hmi testmenu from any status, except the Key status, press the C key. To exit the hmi test menu fromthe Key status, hold the C key down.
To obtain more detailed information, the method for navigating the menus is explainedgraphically in the LCD and keyboard section.
5.12. Power suppply
The PBM.B equipment permits two different power supplies to be selected per model:
110-230 Vac/dc
24/48 Vdc
The equipments maximum consumption is 5W. It generates 24 Vdc, which are available via RJ -45 to supply the other modules.
To protect the power supply against unstable power situations, the microproccessor of theequipments power supply inhibits the possibility of successive and repetitive starts, beingnecessary to wait a minimum of 1 minute after each relay switch off, so that it may consider thefollowing switch on as correct and stable powering.
5.13. Earth toroidal transformer monitoringThe earth toroidal transformer connection is checked if the IG> function or the IG>> function, orboth, are permitted. If it is detected that the transformer connection has opened during a periodof 1 second, the "G toroidal transformer open" status bit is activated. This bit is reset instantly.
5.14. Time delayed equipment start
An adjustable timer is fitted which delays output activation in the PBM power supply for theamount of time set in the Time delayed equipment start up parameter in the set of generalsettings. In this way all the installation's motors can be started up in a staggered way. The time
delay can be adjusted within a range of 0 to 3600 seconds (1 hour).The "Miscellaneous" states group includes the Enable outputs " bit. During the equipment startup time delay this bit is at 0, thus preventing the physical outputs from being activated. Once theequipment start up time delay is complete, the bit switches to 1 and the physical outputs areenabled.
5.15. Equipment reset
The three reset types considered on the PBM equipment are as follows:
Automatic reset
Time delayed automatic reset
Manual reset
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
66/128
www.fanox.com 66/128
If automatic reset has been set, the equipment is reset when the trip condition has disappeared.
If automatic time delayed reset has been set, the equipment is reset when the trip condition hasdisappeared and the set reset time has passed.
If manual reset has been set, the equipment is reset when the reset order is received. This
manual reset command can be recevied via three different routes: PBM-H, communicationcommand or digital input. Each route may or may not be permitted by the settings.
5.16. Thermal image reset
There are two thermal image reset commands.
Reset of the thermal image to 75%, which can be accessed from the hmi andcommunication.
Reset of the thermal image to 0%, which can be accessed from communication.
5.17. Reset/Test Button
The Test/Reset button has two functions.
A short press of the Test/Reset button tests the PBM-H and PBM-B leds simultaneously, withthe following sequence: Lit for one second, off for one second, lit for one second and offpermanently.
Holding down the Test/Reset key (3 seconds) resets the leds and the latched outputs. Thisway, it is possible to restart the motor after a trip or after a manual stop generated by the user
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
67/128
www.fanox.com 67/128
6. TECHNICAL SPECIFICATIONS AND STANDARDS6.1. Technical specifications
General
PBMB1*, Motor rated current: 0.8 to 6 A (step 0.01)
PBMB5*, Motor rated current: 4 to 25 A (step 0.01)
Phase transformation ratio: 1 to 2000
Frequency: 50Hz/60Hz/variable frequency (45Hz65Hz)
Phase sequence ABC/ACB
Time delayed equipment start up: 0 to 3600 s (step 1 s)
Overload
Enable function: Yes/no
Tap: 1 to 2 IB(step 0.01)
Trip class: 5, 10, 15, 20, 25, 30, 35, 40 and 45
Independent mechanical ventilation: yes/no (yes, cooling thermal constant /4)
Alarm: 20 to 100% (step 1)
Maximum current of the three phases
Heating thermal constant: 37
Cooling thermal constant: 90
Heating I > 15% IB
Cooling I < 15% IB
Activation level: 100% thermal image
Reset level: Adjusted alarm level
Instant function reset
Imbalance
Enable function: Yes/no
%Imbalance: 1 to 30% (step 1)
Motor starting up time: 0.02 to 20 s (step 0.001 s)
Motor operation time: 0.02 to 20 s (step 0.001 s)
Reference: Average current of phases IA, IB, IC
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
68/128
www.fanox.com 68/128
Upper limit, activation level: (100 + d)%
Upper limit, reset level: (100 + d5)%
Lower limit, activation level: (100d)%
Lower limit, reset level: (100d + 5)%
Instant function reset
Phase failure
Enable function: Yes/no
%Imbalance: 10 to 100% (step 1)
Operating time: 0.02 to 20s (step 0.001)
Reference: Average current of phases IA, IB, IC
Activation level: (100d)%
Reset level: (100d + 5)%
Instant function reset
Sequence
Enable function: Yes/no
Operating time: 0.02 to 2 s (step 0.001)
Instant function reset
PTC
Enable function: Yes/no
Overtemperature, activation level: > 3600
Overtemperature, reset level: < 1800
Short circuit, activation level: < 20
Short circuit, reset level: > 30
Open circuit, activation level: > 4000
Open circuit, reset level: < 3900
Operating time: 500 ms
Instant function reset
Jam
Enable function: Yes/no
Tap: 1 to 3.5 times IB(Step 0,01)
Operating time: 0.02 to 50 s (Step 0.001)
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
69/128
www.fanox.com 69/128
Activation level: 100%
Reset level: 95%
Instant function reset
Locked rotor
Enable function: Yes/no
Tap: 3.5 to 6 times IB(Step 0,01)
Motor starting up time: 0.02 to 200 s (Step 0.001)
Motor operation time: 0.02 to 30 s (Step 0.001)
Activation level: 100%
Reset level: 95%
Instant function reset
I0>>
Enable function: Yes/no
Tap: 0.1 to 1 times IB(Step 0,01)
Operating time: 0.02 to 5 s (Step 0.001)
Activation level: 100%
Reset level: 95%
Instant function reset
I0>
Enable function: Yes/no
Tap: 0.1 to 1 times IB(Step 0,01)
IEC 255-4/BS-142 Curves
Operating time: Inverse curve, very inverse curve, extremely inverse curve. Definedtime : 0.02 to 300 s (Step 0.01 s)
Dial: 0.05 to 1.25
Curve activation level 110%
Curve reset level 100%
Defined time activation level 100%
Defined time reset level 95%
Instant function reset
Timer precision: 5% or 30 ms (whichever is greater)
http://www.fanox.com/http://www.fanox.com/http://www.fanox.com/ -
8/14/2019 En PBM User-Manual R009
70/128
-
8/14/2019 En PBM User-Manual R009
71/128
www.fanox.com 71/128
RTC Memory It maintains the date during 72 (65C) hours without power supply
Inputs 24Vac/dc
Outputs
Ith: 5A8A, 250 Vac, General Use (AC15)
8A, 30 Vdc, Resistance (DC13)
In case of using 630 or 780 A contactors, PBM-B outputs wont be able ofmanipulating the coil of the contactors. It will be necessary to introduce an auxiliarcontactor.
Current measurement
Real RMS
Sampling: 16 samples/cycle
2% Accuracy in the whole range
Frequencymeasurement
Thermal imagemeasurement
Communications RS485 port: ModBus RTU
Power110/230 Vac/dc
24/48Vdc
Short Circuit WithstandRating
5,000A rms Sym, 230Vac(performed on PBM-B Model, were applied 3 cycles usingRK5 fuses)
Max. Nominal voltage ofthe motor
1000 Vac
Power consumption Maximum consumption: 5 W.
Electrical life 5x105OP
Mechanical life 106OP
Environmentalconditions
Operating temperature : -10 to 65C
Storage temperature: -20 to 70C
Relative humidity: 95%
Height: 3000 m