    HOT TAP WATER EXCHANGERS

    ENSOL/2

    200l 250l300l 400l500l 750l

    1000l

    INSTALLATION AND OPERATIONMANUAL

    WARRANTY CARD

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    2/18

    Version 01/13 ENSOL/22

    Before you install and activate the exchanger, please read this "Installation andOperation Manual" and Terms and Conditions of the Warranty

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    3/18

    Version 01/13 ENSOL/23

    1. Structure and Intended Use

    ENSOL/2 exchangers are pressure storage water heaters that aredesigned to heat and store hot tap water, in systems with solar collectors,for needs of flats, detached houses and multi-family buildings, public utilitybuildings, industrial facilities and others.

    ENSOL/2 200-350 exchangers have been adapted for installation in roomswith doors that are up to 70 cm wide. They are equipped with twoindependent helical coils, allowing the connection of two power sourceswith different heating media, such as solar collectors with a glycol-basedheating medium or e.g. low-temperature central heating water boiler.Pressure tanks in these heat exchangers are made of steel sheet coveredinside with a layer of a special high-temperature vitreous enamel, formingglass coating that protects them from corrosion and ensures clean healthywater. Additional corrosion protection of the tanks is the magnesium anode

    that owing to the difference of electrochemical potentials of steel andmagnesium in water, generates protective current for the tank.The outer casing of exchangers is made of plastic or artificial leather likefabric.

    ENSOL/2 exchangers are designed for installation of an electric heatingelement on the 1" plug, especially EJK type heating element produced byZUG ELEKTROMET with insulated heating units (Tab. 3), which do notconsume protective current generated by the magnesium anode for thecorrosion protection of the tank. This increases the durability of the tankand the life of the magnesium anode.The structure and dimensions of exchangers are shown in Fig. 1, whereastheir connection dimensions and technical parameters in Tab. 1, 2 and 3.

    ENSOL/2 200 ENSOL/2 250 - 500

    Fig. 1.Structure and dimensions of ENSOL/2 200- 500 exchangers

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    4/18

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    5/18

    Version 01/13 ENSOL/25

    Tab. 2Technical parameters of ENSOL/2 200-500 exchangers

    * 80C, 70C, 60C - temperature of heating water in the coil supply10C - temperature of cold tap water on sup ply45C - temperature of hot tap water

    ENSOL/2Type200 250 300

    Tank capacity

    dm207 247 302

    bottom upper bottom upper bottom upperExchanger surface m

    2

    1.1 0.8 1.1 0.8 1.4 1.0

    Coil capacity dm 6,4 4.3 6,4 4.3 8.0 5.7Hot tap water capacity

    80/10/450C

    70/10/450C

    60/10/450C

    dm/h 629526378

    442368270

    629526378

    442368270

    826727506

    595504361

    Heating power80/10/45

    0C

    70/10/450C

    60/10/450C

    kW 25,621,415,4

    181511

    25,621,415,4

    181511

    33,629,620,6

    24,220,514,7

    Hot tap water capacity80/10/60

    0C

    70/10/600C

    dm/h 354227

    264198

    354227

    264198

    450279

    326206

    Heating power80/10/60

    0C

    70/10/600C

    kW 20,613,2

    15,411,5

    20,613,2

    15,411,5

    26,216,2

    1912

    Heating water flow inthe coil

    m/h 1.8 1.4 1,8 1.4 2.2 1.7

    Pressure loss mbar 40 25 40 25 70 35Daily readiness loss kWh/24h 3.1 3.2 3.4Tank operationparameters

    Maximum pressure and operating temperaturepr = 0,6 MPa ot = 80C

    Heating mediumparameters

    Maximum pressure and operating temperaturepr = 0.6 MPa ot = 100C

    Type of tank steel tank coated inside with vitreous enamel

    Type of outer casing plate-like coating made of plastic or artificial leather

    Thermal insulation 60 mm foam polyurethane

    Heater weight in thecasing

    kg 85 105 130

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    6/18

    Version 01/13 ENSOL/26

    * 80C, 70C, 60C - temperature of heating water in the coil supply10C - temperature of cold tap water on sup ply45C - temperature of hot tap water

    ENSOL/2Type

    400 500Usable capacity of thetank dm 400 500

    bottom upper bottom upperExchanger surface m

    2

    1.6 1.1 1,9 1.4Coil capacity dm 9.5 6.3 10,7 8,0Hot tap water capacity

    80/10/450C

    70/10/450C

    60/10/450C

    dm/h 948826600

    629526378

    1143980700

    826727506

    Heating power80/10/45

    0C

    70/10/450C

    60/10/450C

    kW 38,633,624,4

    25,621,415,4

    46,539,928,5

    33,629,620,6

    Hot tap water capacity80/10/60

    0C

    70/10/600C

    dm/h 523330

    354227

    621392

    450279

    Heating power80/10/60

    0C

    70/10/600C

    kW 30,419,2

    20,613,2

    36,122,8

    26,216,2

    Heating water flow inthe coil

    m/h 2.9 2.2 3.1 2.2

    Pressure loss mbar 110 40 130 70Daily readiness loss kWh/24h 4.0 4.5Tank operationparameters

    Maximum pressure and operating temperaturepr = 0,6 MPa ot = 80C

    Heating mediumparameters

    Maximum pressure and operating temperaturepr = 0.6 MPa ot = 100C

    Type of tank steel tank coated inside with vitreous enamel

    Type of outer casing plate-like coating made of plastic or artificialleather

    Thermal insulation 100 mm expanded polystyrene

    Heater weight in thecasing

    kg ca. 210 ca. 235

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    7/18

    Version 01/13 ENSOL/27

    Structure of exchangersENSOL/2 750 and ENSOL/2 1000

    Fig. 2 Structure of exchangers750 l.

    Fig. 3 Structure of exchangers1000 l

    1 tank2 thermal insulation (10 cm foam

    polyurethane)

    3 outer casing4 sling

    5 cleaning hatch 1306 magnesium anode 1 1/47 cold utility water - inlet 1 1/48 hot utility water - outlet 1 1/49 circulation 3/410 drain 111 heating element - sleeve

    1 1/212 coil pipe 113 Temperature sensor sleeve -

    closed 1/2 x 20014 feeding with heating water

    -inlet 115 return heating water -outlet 1

    1 tank2 thermal insulation (8 cm foam

    polyurethane)

    3 outer casing4 sling5 cleaning hatch 1306 magnesium anode 1 1/47 cold utility water - inlet 1 1/48 hot utility water - outlet 1 1/49 circulation 110 drain 111 heating element - sleeve

    1 1/212 coil pipe 113 Temperature sensor sleeve -

    open 1/214 Temperature sensor sleeve -

    closed 1/2 x 200

    15 feeding with heating water-inlet 1

    16 return heating water -outlet 1

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    8/18

    Version 01/13 ENSOL/28

    Dimensions of exchangersENSOL/2 750 and 1000 l

    Fig. 4 Dimensions of exchangers750 l.

    Fig. 5 Dimensions of exchangers1000 l.

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    9/18

    Version 01/13 ENSOL/29

    Tab. 3Technical parameters of ENSOL/2 750 and 1000 exchangers

    * 80C, 70C, 60C - temperature of heating water in the coil supply10C - temperature of cold tap water on sup ply45C - temperature of hot tap water

    Accessories:- safety valve with the opening pressure: 0.6 MPa

    ENSOL/2Type

    750 1000Usable capacity of thetank dm 750 1000

    bottom upper bottom upperExchanger surface m

    2

    2,5 1,6 2,8 1,8Coil capacity dm 14,5 8,7 16,0 10,5Hot tap water capacity

    80/10/450C

    70/10/450C

    60/10/450C

    dm/h 14901285860

    948826600

    17201400983

    1081934688

    Heating power80/10/45

    0C

    70/10/450C

    60/10/450C

    kW 60,750,435

    38,633,624,4

    70,057,040,0

    44,038,028,0

    Hot tap water capacity80/10/60

    0C

    70/10/600C

    dm/h 882646

    523330

    911585

    585378

    Heating power80/10/60

    0C

    70/10/600C

    kW 51,337,6

    30,419,2

    53,034,0

    34,022,0

    Heating water flow in thecoil

    m/h 3,5 2,7 5,0 3,0

    Tank operationparameters

    Maximum pressure and operating temperaturepr = 0,6 MPa ot = 80C

    Heating mediumparameters

    Maximum pressure and operating temperaturepr = 0.6 MPa ot = 100C

    Type of tank steel tank coated inside with vitreous enamel

    Type of outer casing plate-like coating made of plastic or artificial leather

    Thermal insulation 100 mm foam polyurethane 80 mm foampolyurethaneDiameter w/o thermalinsulation

    mm 790 912

    Height w/o thermalinsulation

    mm ok. 1910 ok. 1980

    Max. height at tiltedposition

    mm ok. 2220 ok. 2300

    Magnesium anode ( 2 pc) mm 33 x 680 33 x 680

    Heater weight in thecasing

    kg ca. 330 ca. 460

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    10/18

    Version 01/13 ENSOL/210

    2. Safety devices and conditions for safeuse of exchangers.

    Heaters may only be used with a functional safety valve with the openingpressure of 0.6 MPa (water pressure in the water supply network up to 0.6

    MPa) installed on the cold tap water inlet. This valve protects theexchanger from excessive pressure in the water supply network orexcessive pressure increase as a result of heating the water in the tank.Even in case of regular operation of the exchanger during heating, watermay leak from the safety valve for a short time, which shows that the valveoperates in a correct manner. Neverobstruct the outlet hole in such cases.All types of exchangers should be used with an installed thermometer ofthe measuring range between 0 and 120C, whereas on exchangers withthe capacity exceeding 250 l, also install pressure gauges with the

    measuring range between 0 and 1 MPa.

    3. Installation

    3.1 Exchanger connection to the water supply network,central heating system and solar collector.Connect the exchanger vertically to the water supply network in which thepressure does not exceed 0.6 MPa and not lower than 0.1 MPa. If thepressure in the network often exceeds 0.4 MPa, it is recommended toinstall a pressure reducing valve or a diaphragm reservoir before theexchanger in order to limit the inconvenient outflow of water from the safety

    valve. When the pressure in the water supply network exceeds 0.6 MPa, itis necessary to install the pressure reducing valve in order to avoid thecontinuous outflow of water from the safety valve.

    ATTENTION!1. A safety valve has to be installed on the cold water inlet to theexchanger; the valve is supplied with the exchanger. Install it so that thearrowhead on the valve body is in line with the direction of the waterflow.2. Do not install any shut-off valves between the safety valve and theexchanger.

    3. It is not permitted to use the tank without a safety valve or with amalfunctioning safety valve becausethe situation may result in failure and poses a threat to human life andhealth.

    Installation and any repairs of the exchanger in terms of electricityand water system should be entrusted only to skilled processionals

    with relevant permissions.

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    11/18

    Version 01/13 ENSOL/211

    The exchanger is fed by the heating medium from the solar collector ande.g. from a low-temperature water boiler that operates in an open system orin a closed system, i.e. with a diaphragm vessel.

    3.2Installation of EJK type heating elementDuring the warranty period of the tank, only heating elements tanks

    suitable for enamelled tanks may be used, i.e. those with insulated heating

    units (insulated heating units do not "steal" protective current generated bythe magnesium anode). This is one of the warranty conditions for theENSOL/2 exchanger. EJK type heating elements by ZUG ELEKTROMETcomply with this condition.Among EJK heating elements manufactured by ZUG ELEKTROMET forENSOL/2 exchangers, you can install single phase 230 V 1.5 kW and 2.0kW heating elements as well as three phase 400 V 3.0, 4.5, 6.0 and 9.0 kWheating elements.Install in accordance with the Installation and Operation Manual of the

    heaters.It is particularly important that the free end of the yellow-green protectiveconductor drawn from the marked connection on the casing of the heatingelement is connected using the M4 screw to the earth plate located on theMG connector of the tank, see Fig. 4.

    1 tank casing2 electric EJK type heatingelement

    3 earth wire4 MG 1 '' connector5 earth plate6 M4 screw7 spring washer

    Fig. 4 Earth of the heating element

    ATTENTION!During the warranty period of the tank, use only heatingelements with an insulated heating unit e.g. EJKmanufactured by ZUG ELEKTROMET

    ATTENTION!Do not insert the plug of the connection into theelectrical socket without making sure that the tank is filledwith water.

    ATTENTION! The heating element and the metal tank have to be

    connected with an earth cable drawn from a marked connectionon the heater casing.

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    12/18

    Version 01/13 ENSOL/212

    4. Operation and service

    1. Periodically, at least once a month and before every start-up, afterputting out of service, check the correct operation of the safety valve(according to instructions of valve manufacturer).2. A temporary small outflow of water from the safety valve during heatingof water in the exchanger is normal and indicates the proper operation of

    the safety valve.

    3. If the exchanger is put out of service in the winter and there is a concernthat the water in the exchanger may freeze, drain the water by unscrewingthe safety valve.

    4. The magnesium anode wears down during operation, so its conditionshould be checked periodically, at least once a year. The anode should bereplaced if it loses 2/3 of its volume, and always at the latest after 18months. A relevant magnesium anode can be purchased at a point of saleor from the manufacturer of exchangers.The anode is located at the top end cap of the exchanger tank; todetermine its condition or replace it with a new one:- cut off the cold water supply, open the hot tap water tap for a moment,then close the outlet of hot water from the exchanger,

    - remove the top cover of the exchanger casing,- remove the insulation element covering the cap with the affixed anode,- unscrew the cap with the anode,- install a new anode in the reverse order, paying particular attention totightness of connections.5. Periodically, depending on water hardness, remove the accumulatedsediment and loose scale.

    ATTENTION!Continuous leaking of water from the safety valve outletdemonstrates a malfunction of the valve or overly high pressure inthe water supply system. Never obstruct the outlet hole.

    ATTENTION!The magnesium anode plays an important role in the corrosionprotection of the enamelled tank, and its regular checking andreplacement with a new one is necessary to maintain the warranty of thetank.Replaced used anodes and certification of their exchange (anodepurchase) should be kept in order to make them available for themanufacturer's service personnel in case of failure of the tank.

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    13/18

    Version 01/13 ENSOL/213

    5. Warranty conditions

    1. The warranty is granted for a period of 60 months for the enamelled tank.2. The warranty for other parts of the exchanger is 24 months.3. The warranty period starts on the date of sale of the product to the user,

    as entered in the warranty card and confirmed by a proof of purchase(bill) issued by the vendor.

    4. The guarantor ensures the efficient operation of the exchanger providedthat it is installed and used in accordance with its manual.

    5. During the warranty period, the user is entitled to free repair of anydamage occurring through the fault of the manufacturer of theexchanger. Any damage shall be removed in 14 days after the date ofnotification.

    6. The user loses the right to warranty repairs in case of:- installation of the tank in a system without solar collectors,- improper use of the device,

    - repairs and modifications of the device by unauthorised persons,- improper installation and operation of the device that is not in conformity

    with this manual,- use of the exchanger without the safety valve or with malfunctioning

    safety valve,- lack of the magnesium anode and lack of documents confirming its

    replacement,- use of a heating element with non-insulated electrical units.

    7. The guarantor may refuse to repair if:

    - it is not granted service access to the device,- it is necessary to dismantle other devices, partition walls, etc. in orderto replace the tank,

    - the tank is connected to the water supply network permanently, bymeans of inseparable connections.

    8. In case of unjustified calls for service, costs of arrival shall be borne bythe customer.

    9. In case of irregularities in the operation of the exchanger, notifymanufacturer's service, tel. 32/ 415 01 81 from 6 to 14,or by e-mail:

    [email protected] or point of sale. DO NOT DISMANTLE THEDEVICE.10. The manner of repair of the equipment is determined by themanufacturer.11. The basis for repairs under the granted warranty is a correctly filled out,

    complete Warranty Card that contains no amendments.12. In all matters not regulated by these conditions, relevant regulations of

    the Civil Code apply.13. We recommend that you keep the Warranty Card throughout the life of

    the exchanger.

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    14/18

    Version 01/13 ENSOL/214

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    15/18

    Version 01/13 ENSOL/215

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    16/18

    Version 01/13 ENSOL/216

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    17/18

    Version 01/13 ENSOL/217

  • 8/11/2019 En Ensol - Installation Manual Water Heater 2 Heat Exchanger

    18/18

    Energetyka Solarna Ensol Sp. z o.o. 47-400 Racibrz, ul. Piaskowa 11 Tel./fax: 0048 32 415 96 65