Panel layout
Power supply board
Tamper switch
Controller board
Access board
Input board
Input board
Ribbon cable
Empty expansion slot
Wire hold-down
Power cable
Power requirements
IEI eMerge systems must be AC powered using the grounded plug-in transformer provided. Power should come from a circuit with an isolated ground and must be wired to the power supply mounted inside the eMerge cabinet.
Transformer Input: 120 V AC 60 Hz 48W.
Transformer Output: 16.5V AC 2400mA.
The IEI eMerge includes a DC power supply. The eMerge power supply provides 12V DC at 3.3 amps.
The recommended battery which is not included 12V DC, 7 AH, SLA (sealed lead acid).
CAUTION!!! MAKE SURE ALL POWER IS OFF BEFORE CONNECTING OR DISCONNECTING MODULES IN THE IEI eMerge.
Network Controller board layout
Compact flash
socket
I-buttonsocket
Battery
Ribbon cable connector
NetworkController
Reset
Processor
PanelLED
2-portNetworkswitch
Ribbon cable connector
Node Reset
CabinetTamperSwitch input
Network port(reserved for future use)
Power supplyInput2-pin
BatteryInput/
Charger3-pin
Top side of board
Bottom side of board
The network controller board must be located in the top
position
Expansion Node Card
Battery
Ribbon cable connector
Ribbon cable connector
Node Reset
CabinetTamperSwitch Input
Network port
Power supplyInput2-pin
BatteryInput/
Charger3-pin
Panel LED
The Expansion Node board must be located in
the top position
I-button and tamper switch
Processor
Cabinet tamper switch connector
Compact flash
socket
Controler I-buttonsocket
Battery
Ribbon cable connector
MODEL
XXXSerial Number
Revision
xxxxxxxxREV.X
The label
is here
This side goes down into socket
Tamper switch mounts
Mounting holes
The tamper switch is installed on the tamper switch mounts and wired to the provided cord which is then plugged into the tamper switch connector on the control board
The controller I-button comes pre installed
The I-button contains system licensing.
Installing board in panel
standoff tube
lock washer
Boardgoes down
into slot
Standoff comesflush to flange
1. Power down the eMerge.
2. Thread the standoff tube provided down onto the threaded post on the chassis next to the slot where you will insert the additional module.
3. Be sure that you are grounded and insert the additional module into the slot on the chassis with the ribbon cable connector toward the left of the eMerge cabinet. See diagram below.
4. Place the lock washer provided over the top of the standoff and thread the screw provided through the flange and down into the top of the standoff and snugly down onto the lock washer. See diagram below.
5. Connect the ribbon cable from the Controller/Node module in the topmost slot to the newly installed module. The connector is polarized. Make sure that the center bump fits into the opening for it on the connector on the module. Press the connector firmly into place until you hear the click of the extraction levers snapping into vertical position. You may have to press the extraction levers into full vertical position before you will hear the click.
Ribbon cable
Slot numbers are determined by the connector on the ribbon cable that is plugged into the module. The ribbon cable (see diagram below) is a bus and a module’s place on the bus determines the slot number. You will see that it is possible to place a module in physical slot 5 and yet attach ribbon cable connector 6 to the module. If this occurs the module will be in slot 6 on the bus.
Controller/Nodeconnector
Connectors for slots 1 2 3 4 5 6 7
Note: When connecting the modules to the ribbon cable be sure the connector is fully seated in the board
(push on cable do not rely on the tabs on the boards)
Access Control module (ACM)
Ribbon cable connector
Form C relay outputs
2-pin supervised inputs
Position 4 3 2 1 4 3 2 1
#2
#1
Weigand reader connections
The access control module can be used for 2 doors with both in reader or 1 door for
in and out readers.
The ACM board can be located in slot positions
2-7
Input Board layout
2-pin supervised inputs
Position 8 7 6 5 4 3 2 1
Ribbon cableconnector
The input board is used for monitoring alarm points, or when multi supervised inputs are
needed.
The Input board can be located in slot positions
2-7
Output Board layout
Form C relay outputs
Position 8 7 6 5 4 3 2 1
Ribbon cableconnector
The Output board is Used for elevator control or
when additional form C relays are required.
The Output board can be located in slot
positions 2-7
Wiring battery and power to controller.
Batteryinput3-pin
Power supplyinput2-pin
Processor
pin 2ground
pin 1+12V DC
pin 1+12V DC
pin 3ground
AC GND AC
AC IN +V NEG +BATT-
The power supply is pre wired to the
network controller.
Note: Do Not connect Battery to power supply board connect to the controller
board
Wiring Weigand readers
Bpr
Grn LED control
Red LED controlD1(white)
D0(green)
Gnd(black)
Pwr(red)
CAUTION!!! Each eMerge Access module can supply a total of 400 milliamps of power for readers. If the reader(s) connected to the Access module draw more than 400 milliamps then external power must be supplied to these readers.
The maximum distance for wiring weigand devices to the access board is 500 Ft.
For distances longer then 500 ft. you need to use an additional expansion node with acm or there are 3rd party devises made
to extend the distance.
Access Control module (ACM)
Supervised Inputs wiring
2-pin input connector
Input deviceNormally Open (NO)
1K Resistors - Install at or near input device
2-pin input connector
Input deviceNormally Closed (NC)
1K Resistors - Install at or near input device
Input state Resistance Value
Normal 1k Ohms ±5%
Alarm 0.5k Ohms ±5%
Short 0 Ohms
Open No current (∞ Ohms)
Input State Resistance Value
Normal 1k Ohms ±5%
Alarm 2k Ohms ±5%
Short 0 Ohms
Open No current (∞ Ohms)
2-pin inputs
Position 8 7 6 5 4 3 2 1
Ribbon cableconnector
Ribbon cable connector
2-pin inputs
4 3 2 1 positions
ACM
Supervised input board
The inputs on the eMerge panel are supervised that allows the panel to monitor the status including if the input is in a normal state, alarmed or triggered, and if
the wires before the devise is shorted or the same is opened.
Wiring Outputs
3-pin outputconnector
DCpowersupply
-+
Pin 2common
Pin 3normally open
DC outputdevice
Diode - 1N4933 or equivalent
+
-
3-pin outputconnector
DCpowersupply
-+
Pin 2common
DC outputdevice
Diode - 1N4933 or equivalent
Pin 1normally closed
+
-
Ribbon cable connector
3-pin outputs 1 2 3 4
Ribbon cable connector
3-pin outputs
positions 8 7 6 5 4 3 2 1
ACM
Output board
The dry contact relay is wired up as shown we show using a DC power supply for the lock. A diode is used for dc this is so the relay does not fail prematurely from a voltage spike from the lockset. When using AC voltage use a mov SNR- D56k2 or equivalent. Diodes and movs are supplyed with the access boards and output boards.
Connecting to the network
When connecting to the controller board use a patch cord. A router or DHCP server needs to be connected so the node will get an IP address issued through DHCP.
Panel Led operation
Green steady The network communication is functioning and external power is on.
Green flashing The network communication is functioning and the eMerge is using battery power.
Yellow steady The network communication is not functioning and external power is on.
Yellow flashing The network communication is not functioning and the eMerge is using battery power.