Data sheet 12/10-757-6 We reserve the right to make technical changes without prior notice.
Emergency lighting modules with DALI interfaceT5, T8, TC-DD, TC-F, TC-L linear and compact lamps
EM PRO EZ 220–240 V 50/60 Hz
21304
280270
Description:Low profile emergency lighting modules with DALI interface and automatic testing facility to cover 1 hour and 3 hour duration operating from NiCd and NiMh batteries. All modules incorporate five pole technology for use with HF ballasts and have preheat starting and permanent cathode heating during the emergency operation. Boost starting for 55 seconds at higher power levels is provided for all lamps to ensure rapid warm up, optimised lamp life and improved initial visibility during an emergency operation. Power control technology ensures maxi-mum emergency ballast lumen factors for all lamps on a given module.
DALI interface terminals are provided to allow control and monitoring via a seperate controller.
When the EM PRO EZ operates in Selftest mode testing is being conducted on a default weekly func-tional and 13 weeks duration basis with adaptive duration testing feature to minimise risk.
Fitted with the unique EZ easy addressing feature which uses the LED to indicate the DALI address during commissioning.
EM PRO EZ 3 h duration – NiCd 4.0 Ah D cells or NiMh 4.0 Ah Cs cellstype article number number of cellsEM 34 PRO EZ 89899827 4EM 35 PRO EZ 89899828 5EM 36 PRO EZ 89899829 6
EM PRO EZ 1 h duration standard BLF – NiCd 1.5 Ah or NiMh 2.0 Ah Cs cellstype article number number of cellsEM 14 PRO EZ 89899830 4EM 15 PRO EZ 89899831 5EM 16 PRO EZ 89899832 6
EM PRO HO EZ 1 h duration “high output” – NiCd 4.0 Ah D cells or NiMh 4.0 Ah Cs cellstype article number number of cellsEM 14 HO PRO EZ 89899833 4EM 15 HO PRO EZ 89899834 5EM 16 HO PRO EZ 89899835 6
NiCd 4.0 AhD cells
type numberof cells
articlenumber
Accu-NiCd 4A stick 4 89895961Accu-NiCd 4B side by side 4 89895977Accu-NiCd 4C stick + stick 2 + 2 89895978Accu-NiCd 5A stick 5 89895973Accu-NiCd 5B stick + stick 3 + 2 89895962Accu-NiCd 6A stick + stick 3 + 3 89895963
NiCd 1.5 AhCs cells
type numberof cells
articlenumber
Accu-NiCd C 4A stick 4 89899692Accu-NiCd C 4B * side by side 4 89899693Accu-NiCd C 4C * stick + stick 2 + 2 89899694Accu-NiCd C 5A stick 5 89899695Accu-NiCd C 5B * side by side 5 89899696Accu-NiCd C 5C * stick + stick 3 + 2 89899697Accu-Nicd C 6A stick 6 89899698Accu-NiCd C 6C stick + stick 3 + 3 89899699
* on request
NiMh 4.0 AhCs cells
type numberof cells
articlenumber
Accu-NiMh C 4A stick 4 89899850Accu-NiMh C 5A stick 5 89899851Accu-NiMh C 6A stick 6 89899852Accu-NiMh C 6C stick + stick 3 + 3 89899853
NiMh 2.0 AhCs cells
type numberof cells
articlenumber
Accu-NiMh C 4A stick 4 89899700Accu-NiMh C 5A stick 5 89899703Accu-NiMh C 5B * side by side 5 89899704Accu-NiMh C 6A stick 6 89899706Accu-NiMh C 6C stick + stick 3 + 3 89899707
Features:Module• DALIinterfaceforcontrolandreporting• Lowprofilecrosssection(21mmx30mm)• 5poletechnology• ForusewithHFballasts• NiCdorNiMhbatteyoptions• 10–15houraccurechargetime• 3hourand1houroperation• HighandstandardBLFfor1hourversions• Bi-colourLEDtoindicatestatus• ACoperationoflamps• Pre-heatingofcathodesduring emergency operation• Permanentcathodeheatingduring emergency operation• Booststartingfacilityforalllamps• Restmodefunction• Electronicmultilevelchargingsystem• Deepdischargeprotection• Testing –Batterycondition –Lampcondition –Chargecondition• PatentedEZeasyaddressingfeatureusingLED
Batteries• NiCdorNiMhoptions• DorCscells• Hightemperaturecells• Spadeterminalsforeasyconnection
Standards• EN55015• EN601347-2-7• EN60925• IEC62034• AllowscompliancewithEN60598-2-22• DALIstandardEN62386-102 EN 62386-202• EN61000-3-2• EN61547• IEC60068-2-64• IEC60068-2-29• IEC60068-2-30
type article numberLED bi-colour 89899720LED bi-colour high brightness 89899753
type article numberTest switch EM 2 89805277
RoHS
PHASED
OUT
2 Data sheet 12/10-757-6 We reserve the right to make technical changes without prior notice.
Mechanical detailsChannel manufactured from galvanised steel. Cover manufactured from white pre-coated steel.
LED bi-colour status indicator •Green/red•Mountinghole6.5mmdia•Leadlength1000mm•Insulationrating:90°C
Testswitch•Mountinghole7.0mmdia•Leadlength550mm
Battery leads•Quantity:1redand1black•Length:1300mm•Wiretype:0.5mm²solidconductor•Insulationrating:90°C
Battery end terminationPush on 4.8 mm receptacle to suit battery spade fitted with insulating cover
Module end termination8.0 mm stripped insulation
Two-piecebatteriesaresuppliedwitha200mmleadwith4.8mmreceptacles at each end and insulating covers to connect the separate sticks together.
Technical data:EM PRO EZ 3 hour 1 hourRatedmainssupplyvoltage 220–240V 220–240VMains frequency 50 / 60 Hz 50 / 60 HzMains supply current 60 mA max 60 mA maxMains supply power < 10.0 W < 10.0 WOvervoltageprotection 320Vfor1hour 320Vfor1hourMax.workingvoltageU-OUT 460V 460VOutputfrequencyrange 20–72kHz 20–72kHzRecharge period 15 hours 10 hoursDischarge current 1.1 A 1.1 AChargecurrent: Initial 330mA 130mA Fast 330 mA 210 mA Trickle 130mA 50mAEarth leakage current < 0.5 mA < 0.5 mAAmbienttemperaturerange -5°Cto+60°C -5°Cto+60°CMaximumcasetemperaturetc 70°C 70°CMains change over voltage in accordance with in accordance with EN 60598-2-22 EN 60598-2-22Min.lampstartingtemperature(emergencymode) -5°C -5°CIngress protection IP20 IP20Protection class class I class IFunction test 30 seconds 30 seconds via DALI command via DALI commandDuration test 3 hr via 1 hr via DALI command DALI commandTimer crystalcontrolled crystalcontrolledBoost starting time 55 seconds 55 seconds
Accu-NiCdcasetemperaturerange 0°Cto+55°Cto ensure 4 years design lifestorage life in temperate conditions 4 yearsbatteryvoltage/cell 1.2Vcapacity D 4.0 Ahcapacity Cs 1.5 Ah
Accu-NiMhcase temperature range (toensure4yearsdesignlife)2.0AhCs 0°Cto+55°C4.0AhCs 0°Cto+50°Cstorage life in temperate conditions 4 yearsbatteryvoltage 1.2Vcapacity Cs 2.0 Ah 4.0 Ah
DALI ControllerDALI controllers and hardware/software solutions are available from Tridonic.PleaserefertotheLightingcontrolssection.
Service lifeAverage service life 50,000 hours under rated conditions with a fail-ure rate of less than 10 %. Average failure rate of 0.2 % per 1000 operating hours.
Testing:
DALI ControlA DALI command from a suitable control unit can be used to initiate function and duration tests at individually selected times. Status flags are set for report back and data logging of results.
When a DALI bus has not been connected or when a DALI bus is connected but the DALI defaultDELAYandINTERVALtimeshavenotbeenre-setbysendingappropriateDALIcom-mands, then the EM PRO EZ will conduct self-tests in accordance with the default times setwithintheEEPROM.Thesedefaulttimesarefactorypre-set,inaccordancewiththeDALI standard EN 62386-202, to conduct an automatic function test every 7 days and a duration test every 13 weeks. Since the DELAY time is factory pre-set to Zero, all units are testedatthesametime.TesttimescanbechangedwithacommandovertheDALIbus.
TheDELAYandINTERVALtimevaluesmustbere-setwhentheemergencysystemtesttimes are to be scheduled by a DALI control and monitoring system.Note that once the default values have been set to Zero, tests will only be conducted fol-lowing a command from the control system. If the DALI bus is disconnected the EM PRO EZ does not revert to self-testing mode.
AddressingTheEMPROEZincludesthenewEZeasyaddressingsystemwhichallowsaddressingandidentification by using the bi-colour LED in conjunction with the EZ PRO ADDRESS tool. Binary address codes given by the LED can be simply converted to the DALI addresses 0 to 63. For single handed addressing using this method it is necessary to send a broadcast ident command every 3 to 9 seconds. During this command the main fluorescent lamp will be switched off and the LED will flash the 6 bit binary address preceded by a 3 second start indication period.
Functional testThetimeofdayandfrequencyofthe30secondsfunctiontestcanbesetbytheDALIcontroller.Thedefaultsettingisa30secondstestonaweeklybasis.
Duration testThetimeofdayandfrequencyofthedurationtestcanbesetbytheDALIcontroller.Thedefault setting is a duration test conducted every 13 weeks.
Prolong timeProlongtimecanbesetbytheDALIcontroller.Thisisthedelaytimebetweenreturn ofthemainssupplyandtheendoftheemergencyoperation.Thedefaultprolongtime is set as 2 minutes as specified within the DALI standard.
Emergency lighting modules with DALI interfaceT5, T8, TC-DD, TC-F, TC-L linear and compact lamps
Rest ModeRestmodecanbeinitiatedbytheDALIcontroller.Theappropriatecommand should be sent after the mains supply has been discon-nected and whilst the module is in emergency operation. A mains reset is required to exit the rest mode. EM PRO EZ does not support the re-light command via the DALI bus.
Test switchAnoptionaltestswitchcanbewiredtoeachEM...PROEZ.Thiscanbe used to initiate a 30 seconds function test by a short press < 1 second.
PHASED
OUT
3Data sheet 12/10-757-6 We reserve the right to make technical changes without prior notice.
LED StatusPermanent green System OKFast flashing green Function test underwaySlow flashing green Duration test underwayPermanent red Lamp faultFast flashing red Charging faultSlow flashing red Battery faultDouble pulsing green Inhibit mode
101621283855
579
111013182618263242571824361824364055142128352439495480224055
468
1315183036385870
37251914
40393934312621142114
18
18
24
13
14
3843402720161210
11
1211
12115
16
108
104
75
6
1412
8665
77
6
37251914
40393934312621142114
18
18
24
13
14
3843402720161210
11
1211
12115
16
108
104
75
6
1412
8665
77
TC-DD
TC-SEL
TC-DEL
TC-TEL
TC-F
TC-L
T5 FH
T5 FQ
T5 C
T5
T8
EM 34PRO EZ
EM 35PRO EZ
EM 36PRO EZ
EM 14PRO EZ
EM 15PRO EZ
EM 16PRO EZ
Type3 hours 1 hour
53535353514734273625
1932
32
47
30
30
7073685236332723
2824
3326
332624
44
18
19
21
4236
31222315
2723
EM 14 HOPRO EZ
EM 15 HOPRO EZ
EM 16 HOPRO EZ
1 hour “high output”
Emergency light output factors (BLF) in %:
Emergency lighting modules with DALI interfaceT5, T8, TC-DD, TC-F, TC-L linear and compact lamps
Status indicationSystem status is indicated by a bi-colour LED and by a DALI status flag.
BatteriesConnectionmethod:4.8x0.5mmspadetagweldedtoendofcellFor stick packs this connection is accessible after the battery caps have been fitted.
Toinhibitinverteroperationdisconnectthebatteriesbyremovingtheconnectorfrom the battery spade tag.
For battery data see separate data sheet.
PHASED
OUT
4 Data sheet 12/10-757-6 We reserve the right to make technical changes without prior notice.
Electrical connections:Anearthedstartingaidisrecommended.The module should be earthed by the fixings used to attach it to the luminaire.
Wiring:Lamp/ballast/supply
Loosen wire through twisting and pulling
8 – 9 mm
wire preparation:0.5 – 0.75 mm²
IDC interface•solidwirewithacrosssectionof0.5mm² accordingtothespecificationfromWAGO
•alternativelyaflexibleleadwithacrosssection of0.75mm²
Horizontal interface•solidwirewithacrosssectionof0.5–0.75mm²accordingtothespecificationfromWAGO
•solidwirewithacrosssectionof1.0mm²with an insulation diameter up to 2.5 mm
•strip9mmofinsulationfromthecables•Loosenwirethroughtwistingandpulling
Batteries/LED/Test switchpushterminalwithbuttonrelease: 0.5mm² 6.5 mm strip
Maximum lamp lead capacitanceterminals5and6(*hotleads) 100pF1)
terminals 3 and 4 200 pF 1)
1)Note:careshouldbetakennottoexceedthetotalmaximumlamp lead capacitance for HF ballast. Leads should always be kept as short as possible.
Wiring guidelinesToensurethataluminairecontaininghighfrequencyemergency units complies with EN 55015 for radio frequency conducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout.
Within the luminaire the switched and unswitched 50 Hz supply wiring must be routed as short as possible and be kept as far away as possible from the lamp leads.Thismeans,forexample,inalinearT8orT5luminairethe mains wiring should be routed along one side of the luminaire body, while the wires to the emergency lamp from the emergency module are routed along the other side.
Thehighfrequencyemergencylampwiringcontains“hot” leads at pins 1 and 6, which have high voltage toearth.Theseshouldbekeptasshortaspossibleand separated from other wiring to minimize coupling. Theyalsohavearestrictiononcapacitancetootherwiring and earth of 100 pF, which must be observed to ensure good lamp starting.
With an earth connection of the metal case of the emergency module the noise suppression can be furtherimproved.Thewiringoftheearthshouldbekept as short as possible.
Throughwiringmayaffecttheemcperformanceof the luminaire.
With the use of the fifth pole possible compatibility problems between the products can be prevented. Depending on the luminaire wiring the radio suppres-sion in the emergency mode of operation can be further improved.
Capacitive loading limits of lamp leads must not be exceeded. Note the capacitance of the emergency lamp leads adds to the capacitance of the leads from the ballast to the EM BASIC module when considering ballast loading.
TheLEDandtestswitchwiringshouldberoutedseparately and kept as far away as possible from the high frequency lamp leads to avoid coupling.
Emergency lighting modules with DALI interfaceT5, T8, TC-DD, TC-F, TC-L linear and compact lamps
Isolation and electric strength testing of lumi-nairesElectronic devices can be damaged by high voltage. Thishastobeconsideredduringtheroutinetestingofthe luminaires in production.
AccordingtoIEC60598-1AnnexQ(informativeonly!)or ENEC 303-Annex A, each luminaire should be sub-mittedtoanisolationtestwith500VDC for 1 second. Thistestvoltageshouldbeconnectedbetweentheinterconnected phase and neutral terminals and the earthterminal.Theisolationresistancemustbeatleast 2 MΩ.
Asanalternative,IEC60598-1AnnexQdescribesatestoftheelectricalstrengthwith1,500VAC(or1,414x1,500VDC).Toavoiddamagetotheelectronicdevices this test must not be conducted.
EM FLT1 filterWhen the EM PRO EZ is used in a remote appli-cation, where the lamp leads and LED indicator leads are routed together in close proximity, it is possible to have electrical interference picked up in the indicator leads.
Under certain conditions this interference can cause a lock-up of the EM PRO EZ micro-controller.
ToovercomethisprobleminsuchapplicationsitisnecessarytofitthefilterEMFLT1betweentheindicatorLEDandtheEMPROEZunit.Tobeeffectivethefilter must be connected close to the EM PRO EZ module.
ForfurtherinformationpleasecontactTridonic.
1
114,5
14,5
67,5
67,75
61,75
3,230
,4
14
7
30,4
EM FLT1 filter
Technicaldata:Pushwireterminals0.5–1.5mm²solidconductor
Product article numberEMFLT1 89899942
Circuit diagram with EM FLT1 filter
EM FLT1 87654321
Lout
Lin
ND1D2L
+LEDLED–
Switch
EM PRO EZEMERGENCY MODULE
Emergency lamp
BatteriesOptional
TestSwitch
* Hot leads
PHASED
OUT
Data sheet 12/10-757-6 We reserve the right to make technical changes without prior notice.
Wiring diagram for non-maintained operation
87654321
Lout
Lin
ND1D2L
+LEDLED–
Switch
DALI control
Permanent line
Neutral
DALI control
No connection to be made
EM ... PRO EZEMERGENCY MODULE
Emergency lamp
LEDBattery
orange (+)
OptionalTest
Switch
pink (–)
* Hot leads
EM ... PRO EZ emergency module wiring diagramsNot for use with magnetic ballasts and switch start circuits
Wiring diagram for single lamp high frequency ballasts
87654321
Lout
Lin
ND1D2L
+LEDLED–
Switch
LED
DALI control
Permanent line
Neutral
DALI control
Line in from switchSwitched line out to ballast
Battery
orange (+)
EM ... PRO EZEMERGENCY MODULE
OptionalTest
Switch
Neutral to ballast
HF BALLASTU-OUT max. 460 V
* Hot leads
Emergency lamp
L
N
pink (–)
Wiring diagram for twin lamp high frequency ballasts with 7 terminals
87654321
Lout
Lin
ND1D2L
+LEDLED–
Switch
DALI control
Permanent line
Neutral
DALI control
Line in from switchSwitched line out to ballast
EM ... PRO EZEMERGENCY MODULE
Neutral to ballast
Lamp
HF BALLASTU-OUT max. 460 V
* Hot leads
L
N
Emergency lamp
LEDBattery
orange (+)
OptionalTest
Switch
pink (–)
Wiring diagram for twin lamp high frequency ballasts with 6 terminals
87654321
Lout
Lin
ND1D2L
+LEDLED–
Switch
DALI control
Permanent line
Neutral
DALI control
Line in from switchSwitched line out to ballast
EM ... PRO EZEMERGENCY MODULE
Neutral to ballast
Lamp
HF BALLASTU-OUT max. 460 V
* Hot leads
L
N
Emergency lamp
LEDBattery
orange (+)
OptionalTest
Switch
pink (–)
Wiring diagram for twin lamp high frequency ballasts with 8 terminals
87654321
Lout
Lin
ND1D2L
+LEDLED–
Switch
DALI control
Permanent line
Neutral
DALI control
Line in from switchSwitched line out to ballast
EM ... PRO EZEMERGENCY MODULE
Neutral to ballast
Lamp
HF BALLASTU-OUT max. 460 V
* Hot leads
L
N
Emergency lamp
LEDBattery
orange (+)
OptionalTest
Switch
pink (–)
Note: All hot leads normally marked with an * should be kept as short as possible. ForcomprehensivewiringdiagramsandinstructionsconsulttheTridonicAtcowebsite www.tridonicatco.com
Packing quantities: EM...PROEZ:25 units per carton
Bi-colourLED:25 pieces per bag
AccuNiCd:25 pieces per box
AccuNiMh:25 pieces per box
Addressing ToolAn addressing tool is available to convert the LED binary identification signal toaDALIaddressofbetween0to63.Thissimpletoolispoweredfroma9Vbattery(notsupplied).
EZ PRO ADDRESS: 89899836
Emergency lighting modules with DALI interfaceT5, T8, TC-DD, TC-F, TC-L linear and compact lamps
EMFLT1:25 pieces per box
PHASED