dawsonela.files.wordpress.com … · Web view1811 Poplar Avenue, Apt. # 311. Memphis, TN 38104 ...
ELEVATOR MODERNIZATIONS (REBID)SHEET TITLE SEAL PROJECT NAME Architecture Planning Interior Design...
Transcript of ELEVATOR MODERNIZATIONS (REBID)SHEET TITLE SEAL PROJECT NAME Architecture Planning Interior Design...
EXISTING ELEVATOR LOCATIONS TO BE MODERNIZED
ELEV. #15(4 LEVELS)
ELEV. #7(3 LEVELS)
ELEV. #14(4 LEVELS)
ELEV. #25 (2 LEVELS) ELEVATOR SCHEDULE
Provide/Replace Elev. 14Elev. 07 Elev. 25Elev. 15
Infra-Red Door ProtectionDoor Restrictor DeviceTop of Car Inspection StationTop of Car HandrailNew Car Fixtures and Buttons w/ LED IndicatorsHall Station Replacement w/ LED IndicatorsHoistway Braille SignsClosed-Loop Door OperatorSolid-State StarterHydraulic Oil ReplacementJack Replacement
FREIGHT
DRAWING LIST
G000 COVER SHEET
A201 FLOOR PLANSA501 MACHINE ROOM ENLARGED PLANS
E001 ELECTRICAL NOTES, LEGEND, & DETAILSE101 OVERALL FLOOR PLANSE201 ENLARGED MACHINE ROOMS - ELECTRICALGrand total: 6
ARCHITECT ANF ARCHITECTS, INC.
2491 WINCHESTER ROAD #113 MEMPHIS, TN 38116
ELEVATOR MODERNIZATIONS (REBID)MEMPHIS - SHELBY COUNTY AIRPORT AUTHORITY
INNOVATIVE ENGINEERING SERVICES, LLCENGINEER
CODE ANALYSIS - INTERNATIONAL...
CODE COMMENTS
Memphis and Shelby County Construction Code Enforcement
2009 International Building Code with Local Amendments2012 International Existing Building Code or Chapter 34 IBC2009 American National Standard ICC A 117.1 2009 inconjunction with Chapter 11 of 2009 IBC2008 National Electrical Code2012 Joint Electrical Code2009 International Mechanical Code2009 International Gas Code with Local Amendments2009 International Plumbing Code with Local Amendments2010 ANSI/ASME Elevator Code - A17.12009 International Energy Conservation CodeCSA B44 Elevator Code
DRAWN BY:
CHECKED BY:
PROJECT NUMBER
DATE DWG NO.
SHEET TITLE
SEAL
PROJECT NAME
ArchitecturePlanningInterior Design
1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com
PROJECT STATUS
This information is released solely for its use in the interest of the Memphis-Shelby County Airport Authority (MSCAA) or its Tenants.
All drawings received from MSCAA or produced for MSCAA as a work product shall be regarded as priveleged information, not to be released to others without the express written permission of MSCAA.
Your acceptance of the released materials establishes your understanding of, and commitment to, providing adequate control of the materials issued and produced.
MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113
MEMPHIS, TENNESSEE38116-3856
APPROVED BY:
SCALE
14-1379-22-01MSCAA NO.
As indicatedG000
COVER SHEET
EKM
SD
ELEVATORMODERNIZATIONS
(REBID)
14053.022
02/27/2018
ISSUE FOR REBID /CONSTRUCTION
SD
1" = 200'-0"1 KEY PLAN
MSCAA PROJECT #: 14-1379-22-01
NOTES: 1. ALL NOISE PRODUCING, LOUD OR DISRUPTIVE WORK EFFORTS AND ALL JACK REPLACEMENT AND OIL ACTIVITIES SHOULD BE SCHEDULED AT NIGHT (8PM-5AM). CONTRACTOR RESPONSIBLE FOR
COORDINATING WORK HOURS WITH OWNER.2. ALL NORMAL WORK THAT DOES NOT PRODUCE NOISE CAN BE
COMPLETED DURING NORMAL DAYTIME HOURS. 3. BADGES WILL BE REQUIRED ON THIS PROJECT. REFERENCE SPECIFICATIONS SECTION 00802 FOR FURTHER INSTRUCTIONS. 4. CONTRACTOR SHALL KEEP CONSTRUCTION OPERATIONS WITHIN
BOUNDARIES OF PROJECT LIMITS AND KEEP CONSTRUCTION MATERIAL LIMITED TO SAME SPECIFIC AREA.5. CONTRACTOR SHALL CLEAN UP AS THE WORK PROGRESSES AND NOT ALLOW QUANTITIES OF DEBRIS TO ACCUMULATE.6. CONTRACTOR SHALL COORDINATE STAGING AREA AND PARKING
WITH OWNER.7. AN ALLOWANCE FOR SHAFT HOLE STABILIZATION AND EXCAVATION
WILL BE PROVIDED. THIS IS NOT PART OF THE BASE BID. 8. ONLY ONE ELEVATOR MAY BE MODERNIZED AT A TIME.
9. CONTRACTOR SHALL HAUL OFF ALL MATERIALS/DEBRIS DAILY. DUMPSTERS WILL NOT BE ALLOWED AT TERMINAL DRIVES.
BASE BID: ELEVATOR #7
ALTERNATE #1: ELEVATOR #15
ALTERNATE #2: ELEVATOR #14
ALTERNATE #3: ELEVATOR #25
ALLOWANCE #1: ALLOWANCE COST OF $4,000 FOR ALL WORK RELATED TO ADDING A NEW DOOR AT ELEVATOR #7, IF REQUIRED. ALL WORK WILL BE ON TIME & MATERIAL BASIS.
ALLOWANCE #2: ALLOWANCE COST OF $60,000 FOR ALL WORK RELATED TO RE-DRILLING SHAFT HOLES THAT MAY BE REQUIRED IF ANY SHAFTS COLLAPSE DURING PROJECT. ALL WORK WILL BE ON TIME & MATERIAL BASIS.
REVISIONSNO. DESCRIPTION DATE BY
PODIUM
PODIUM
POD IU MPOD IU M
POD IU MPOD IU M POD IU MPOD IU MPOD IU MPOD IU M
LANE 1
LANE 2
LANE 3
LANE 4
LANE 5
TCOP
L3AIT
E N T E R
E X I T
R oo f
F R O N TTCOP
L3AIT
E N T E R
E X I T
R oo f
F R O N T
LANE 5
LANE 1
LANE 2
LANE 3
LANE 4
LANE 5
TCOP
L3AIT
E N T E R
E X I T
R oo f
F R O N TTCOP
L3AIT
E N T E R
E X I T
R oo f
F R O N T
LANE 5
PODIUM
PODIU
M
LANE 2
LANE 1
TCOP
L 3A IT
ENTER
EXIT
RoofFRONT
8'-0"
8'-6
3 __ 16"
6'-1 1_8"
101'-2"
20'-1 7__16"
15'-7"
38'-2 1_4"
11'-511 __ 16"
14'-0 1_2"12'-10"
42'-6 1__16"
10'-215 __ 16"
12'-11 1_2"
VITREOUS CHINA
C_TOILETS
KINGSTON
K-4329
VITREOUS CHINA
C_TOILETS
KINGSTON
K-4329
xx
xxx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
2
X-RAY6 0 4 0 a T i XH E I M A N N
TABLE630 S.S.
TABLE630 S.S.
TABLE630 S.S.
TABLE630 S.S.
TABLE630 S.S.
BINS
EMPTY
BINS
EMPTY
TABLE630 S.S.
BINS
EMPTY
BINS
EMPTY
TABLE430 SS
TABLE630 S.S.
TABLE630 S.S.
TABLE430 SS
TABLE630 S.S.
TABLE630 S.S.
TABLE430 SS
TABLE630 S.S.
WTMD CEIA
3'-9"
3'
L
ADA GATE
ETD
FRONT
ETD
FRONT
T A B L E 5 3 0 S . S T A B L E 5 3 0 S . S T A B L E 6 3 0 S . S .
3
3
TABLE630 S.S.
4
RA D A G A T E
4
RA D A G A T E
ETDFR
ONT
BENCH
BENCH
X-RAY6 0 4 0 a T i XH E I M A N N
X-RAY6 0 4 0 a T i XH E I M A N N
X-RAY6 0 4 0 a T i XH E I M A N N
X-RAY6 0 4 0 a T i XH E I M A N N
2
RA D A G A T E
3
3
4
3'-9"
3'
L
ADA GATE
4
3'-9"
3'
L
ADA GATE
4
3'-9"
3'
L
ADA GATE
TABLE630 S.S.
TABLE630 S.S.
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
2
X-RAY6 0 4 0 a T i XH E I M A N N
TABLE630 S.S.
TABLE630 S.S.
TABLE630 S.S.
TABLE630 S.S.
TABLE630 S.S.
BINS
EMPTY
BINS
EMPTY
TABLE630 S.S.
BINS
EMPTY
BINS
EMPTY
TABLE430 SS
TABLE630 S.S.
TABLE630 S.S.
TABLE430 SS
TABLE630 S.S.
TABLE630 S.S.
TABLE430 SS
TABLE630 S.S.
WTMD CEIA
3'-9"
3'
L
ADA GATE
ETD
FRONT
ETD
FRONT
T A B L E 5 3 0 S . S T A B L E 5 3 0 S . S T A B L E 6 3 0 S . S .
3
3
TABLE630 S.S.
4
RA D A G A T E
4
RA D A G A T E
ETDFR
ONT
BENCH
BENCH
X-RAY6 0 4 0 a T i XH E I M A N N
X-RAY6 0 4 0 a T i XH E I M A N N
X-RAY6 0 4 0 a T i XH E I M A N N
X-RAY6 0 4 0 a T i XH E I M A N N
2
RA D A G A T E
3
3
4
3'-9"
3'
L
ADA GATE
4
3'-9"
3'
L
ADA GATE
4
3'-9"
3'
L
ADA GATE
TABLE630 S.S.
TABLE630 S.S.
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
TABLE430 SS
BI N SEM P T Y
BI N SEM P T Y
2
L
B I N SE M P T Y
B I N SE M P T Y
B I N SE M P T Y
B I N SE M P T Y
3'-9"
3'
R4
WTMD
CEIA
TSA.S3
D6R
TSA.S3
D6R
3'-9"
3'
L
ADA GATE
3
AVS
I.T.
RACK
3
T A B L E 5 3 0 S . S
T A B L E 6 3 0 S . S . T A B L E 6 3 0 S . S .
ET D
T A B L E 6 3 0 S . S . T A B L E 6 3 0 S . S .
ET D
T A B L E 6 3 0 S . S .
ET D
X-RAY
6040 aTiX
HEIMANN
X-RAY
6040 aTiXHEIMAN
N
3
BI N SEM P T Y
BI N SEM P T Y
TABLE430 SS
44444444 4
ETD
FRONT
ETD
FRONT
ETD
FRONT
ETD
FRONT
I.T.
RACK
POD IU M
PODIU
MPO
DIU
M
LANE 3
LANE 2
LANE 1
B I N SE M P T Y
B I N SE M P T Y
WTMD
CEIA
3'-9"
3'
LADA GATE
L
2
X-RAY
6040 aTiX
HEIMANN
ETDFRON
T
TABLE630 S.S.
T A B L E 6 3 0 S . S .
X-RAY
6040 aTiX
HEIMANN
X-RAY
6040 aTiX
HEIMANN
B I N SE M P T Y
B I N SE M P T Y
B I N SE M P T Y
B I N SE M P T Y
T A B L E 6 3 0 S . S . T A B L E 6 3 0 S . S .
T A B L E 6 3 0 S . S . T A B L E 6 3 0 S . S .
T A B L E 6 3 0 S . S . T A B L E 6 3 0 S . S .
B I N SE M P T Y
B I N SE M P T Y
B I N SE M P T Y
B I N SE M P T Y
B I N SE M P T Y
B I N SE M P T Y
L
21
2
ETDFRONT
AVS
1
L 3A IT
ENTER
EXIT
Roof
TCOP
FRONT
WTMD
CEIA 2
1
R
A D A G A T E
ETDFRON
T
CENTER LINE BAGGAGE BELT:231'
CENTER LINE BAGGAGE BELT:112'
CENTER LINE BAGGAGE BELT:
83'
CENTER LINE BAGGAGE BELT:112'
APPROX. LENGTH CENTER LINE BAGGAGE BELT : 194'
APPROX. LENGTH CENTER LINE BAGGAGE BELT : 166'
APPROX. LENGTH CENTER LINE BAGGAGE BELT : 166'
STAIR NO. 3
RAMP UP
RAMP DOWN RAMP UP
NEW WINDOW
NEW WINDOW
NEW 1-1/2"
DIA. RAILING
OFFICE AREA TOOL ROOM LOCKER ROOM LOCKERSTOOLS
CARTS
SHOP AREA SHOP AREA
OFFICESUPERVISOR
WORK BENCH
LOCKER ROOM LOCK SHOP
REPORT ROOM
COMPUTERMAINTENANCE
SAFETY/COM/ETC
MAINTENANCE
OFFICEROOMSTORAGE
LUNCH ROOM
LUNCH ROOMEXPANSION
MAINT. KITCHEN
FILEROOM
SHOP AREA
ELEV.EQ. RM.
12
5
6
7
10
12a
13
9
11
14
14a
8
4
13
12
10
9
8
6
5
4
7
11
14
12
5
6
7
10
12a
13
9
11
14
14a
8
4
13
12
10
9
8
6
5
4
7
11
14
13
14a
12a
14
12
9
10
11
7
6
5
4
8
13
12
9
10
8
6
5
4
7
11
14
13
14a
12a
14
12
9
10
11
7
6
5
4
8
13
12
9
10
8
6
5
4
7
11
14
ELEV. #15(4 LEVELS)
ELEV. #7(3 LEVELS)
ELEV. #14(4 LEVELS)
ELEV. #15(4 LEVELS)
ELEV. #7(3 LEVELS)
ELEV. #14(4 LEVELS)
ELEV. #25 (2 LEVELS)
A5011
6
ELEV. #15(4 LEVELS)
ELEV. #14(4 LEVELS)
ELEV. #25 (2 LEVELS)
A5012
A5015
A5013
6
ELEV. #15(4 LEVELS)
ELEV. #7(3 LEVELS)
ELEV. #14(4 LEVELS)
1" = 50'-0"2 CONCOURSE FLOOR PLAN
DRAWN BY:
CHECKED BY:
PROJECT NUMBER
DATE DWG NO.
SHEET TITLE
SEAL
PROJECT NAME
ArchitecturePlanningInterior Design
1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com
PROJECT STATUS
This information is released solely for its use in the interest of the Memphis-Shelby County Airport Authority (MSCAA) or its Tenants.
All drawings received from MSCAA or produced for MSCAA as a work product shall be regarded as priveleged information, not to be released to others without the express written permission of MSCAA.
Your acceptance of the released materials establishes your understanding of, and commitment to, providing adequate control of the materials issued and produced.
MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113
MEMPHIS, TENNESSEE38116-3856
APPROVED BY:
SCALE
14-1379-22-01MSCAA NO.
1" = 50'-0"A201
FLOOR PLANS
JD
SD
ELEVATORMODERNIZATIONS
(REBID)
14053.022
02/27/2018
ISSUE FOR REBID /CONSTRUCTION
SD
1" = 50'-0"3 APRON FLOOR PLAN
1" = 50'-0"4 TUNNEL FLOOR PLAN
1" = 50'-0"1 MEZZANINE FLOOR PLAN
REVISIONSNO. DESCRIPTION DATE BY
REPLACE MACHINE ROOM EQUIP. REFERENCE SPECIFICATIONS
REPLACE / MODERNIZE ELEVATOR. REFERENCE SPECIFICATIONS
ELEVATOR 15 MACHINE ROOM 154 1/2"
A501 6
PROVIDE PIT LADDER. ENSURE A CLEAR DISTANCE OF NOT LESS THAN 4.5" FROM CENTERLINE OF RUNGS, CLEATS, OR STEPS TO NEAREST PERMANENT OBJECT IN BACK OF LADDER.
NOTE: PROVIDE SLOPED METAL 'BEVEL' AT ALL FLAT CONCRETE LEDGES TO MEET CODE REQUIREMENT TO PREVENT STANDING.
EQEQ
UP
AHU ROOMMACHINEROOM 7
REPLACE MACHINE ROOM EQUIP. REFERENCE SPECIFICATIONS
REPLACE / MODERNIZE ELEVATOR. REFERENCE SPECIFICATIONS
PROVIDE NEW 6'-0" H CHAIN LINK FENCE AND GATE, BOLT TO SLAB
PROVIDE 2HR RATED METAL DOOR AND FRAME WITH CLOSER AND LOCKING HARDWARE. SEE SPECIFICATIONS. CUT AND PATCH EXISTING BRICK & CMU WALL AS REQUIRED FOR NEW FRAME. (ALLOWANCE #1)
STAIR
ELEVATOR 7
PROVIDE PIT LADDER. ENSURE CLEAR DISTANCE OF NOT LESS THAN 4.5" FROM CENTERLINE OF RUNGS, CLEATS, OR STEPS TO NEAREST PERMANENT OBJECT IN BACK OF LADDER.
NOTE: THIS SHAFT DOES NOT HAVE A HOIST BEAM
A5014
A5016
4 1/2"
NOTE: PROVIDE SLOPED METAL 'BEVEL' AT ALL FLAT CONCRETE LEDGES TO MEET CODE REQUIREMENT TO PREVENT STANDING.
REPLACE ELEVATOR JACK ONLY. REFERENCE SPECIFICATIONS
ELEVATOR 25
MACHINE ROOM 25
4 1/
2"
A501
6
PROVIDE PIT LADDER. ENSURE A CLEAR DISTANCE OF NOT LESS THAN 4.5" FROM CENTERLINE OF RUNGS, CLEATS, OR STEPS TO NEAREST PERMANENT OBJECT IN BACK OF LADDER.
REPLACE MACHINE ROOM EQUIP. REFERENCE SPECIFICATIONS
REPLACE / MODERNIZE ELEVATOR. REFERENCE SPECIFICATIONS
ELEVATOR 14MACHINE ROOM 14
PROVIDE SLOPED METAL 'BEVEL' AT FLAT CONCRETE LEDGE TO MEET CODE REQUIREMENT TO PREVENT STANDING
4 1/2"
A5016
PROVIDE PIT LADDER. ENSURE CLEAR DISTANCE OF NOT LESS THAN 4.5" FROM CENTERLINE OF RUNGS, CLEATS, OR STEPS TO NEAREST PERMANENT OBJECT IN BACK OF LADDER.NOTE: PROVIDE SLOPED METAL 'BEVEL' AT
ALL FLAT CONCRETE LEDGES TO MEET CODE REQUIREMENT TO PREVENT STANDING.
7' -
0"2"
6' -
11"
10' - 4" +/-
2"
3' - 0"
2"
5' - 1"
10' - 3" +/- 8' - 7"
9' -
9"
EXISTING PIPE
EXISTING STAIR & LANDING
PROVIDE 2HR RATED METAL DOOR AND FRAME WITH CLOSER AND LOCKING HARDWARE. SEE SPECIFICATIONS. CUT AND PATCH EXISTING BRICK & CMU WALL AS REQUIRED FOR NEW FRAME.
TYP.
1' -
0"
PIT FLOOR
NO LESS THAN 9"
5/8" DIAM. RUNGS
NOTE: PROVIDE PIT LADDER TO MEET CURRENT CODE REQUIREMENTS. SECURE TO EXISTING PIT WALL & MEET INDUSTRY STANDARDS.
LANDING
MIN
. PE R
CO
DE
4' -
0"
2"
3/8"
X 2
" FLA
T BA
R (2
SID
ES)
300 LBS. CAPACITYA. LADDER SHALL EXTEND NOT LESS THAN
48" ABOVE SILL OF ACCESS DOOR OR HANDGRIPS SHALL BE PROVIDED TO SAME HEIGHT.
B. LADDER RUNGS, CLEATS, OR STEPS SHALL BE A MINIMUM OF 16" WIDE. WHEN OBSTRUCTIONS ARE ENCOUNTERED, WIDTH SHALL BE PERMITTED TO BE DECREASED TO LESS THAN 16". REDUCED WIDTH SHALL BE AS WIDE AS AVAILABLE SPACE PERMITS, BUT NOT LESS THAN 9".
C. LADDER RUNGS, CLEATS, OR STEPS SHALL BE SPACED 12" (+/- 5") ON CENTER, SHALL BE PROVIDED TO NOT LESS THAN THE HEIGHT OF ACCESS DOOR SILL, AND SHALL BE DESIGNED TO MINIMIZE SLIPPING (E.G. KNURLING, DIMPLING, COATING WITH SKID-RESISTANT MATERIAL, ETC).
D. SIDE RAILS, IF PROVIDED, SHALL HAVE A CLEAR DISTANCE OF NOT LESS THAN 4.5" FROM THEIR CENTERLINE TO NEAREST PERMANENT OBJECT.
E. LADDER AND ITS ATTACHMENTS SHALL BE CAPABLE OF SUSTAINING A LOAD OF 300 LBS.
A
B
C
D
E
DRAWN BY:
CHECKED BY:
PROJECT NUMBER
DATE DWG NO.
SHEET TITLE
SEAL
PROJECT NAME
ArchitecturePlanningInterior Design
1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com
PROJECT STATUS
This information is released solely for its use in the interest of the Memphis-Shelby County Airport Authority (MSCAA) or its Tenants.
All drawings received from MSCAA or produced for MSCAA as a work product shall be regarded as priveleged information, not to be released to others without the express written permission of MSCAA.
Your acceptance of the released materials establishes your understanding of, and commitment to, providing adequate control of the materials issued and produced.
MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113
MEMPHIS, TENNESSEE38116-3856
APPROVED BY:
SCALE
14-1379-22-01MSCAA NO.
As indicatedA501
MACHINE ROOMENLARGED PLANS
JD
SD
ELEVATORMODERNIZATIONS
(REBID)
14053.022
02/27/2018
ISSUE FOR REBID /CONSTRUCTION
SD
1/4" = 1'-0"2 ELEVATOR #15
1/4" = 1'-0"1 ELEVATOR #7
1/4" = 1'-0"5 ELEVATOR #25
1/4" = 1'-0"3 ELEVATOR #14
1/4" = 1'-0"4 STAIR ELEVATION (ALLOWANCE #1)
1/2" = 1'-0"6 PIT LADDER ELEVATION
REVISIONSNO. DESCRIPTION DATE BY
ELECTRICAL ABBREVIATIONSSYMBOL DESCRIPTION
AAFFAFGAICANNAUXAWGCCBCKTCLPCTCUDISCEDFFAAPFACPFLAGGFIHPHZKCMILKVAKWLEDMCCMLONNECPFSOWBUGWVVAVFDWPXFMR3P3PH4W30/3
AMPEREABOVE FINISHED FLOORABOVE FINISHED GRADEAMPERES INTERRUPTING CURRENTANNUNCIATORAUXILIARYAMERICAN WIRE GAUGECONDUITCIRCUIT BREAKERCIRCUITCURRENT LIMITING PANELCURRENT TRANSFORMERCOPPERDISCONNECTELECTRIC DRINKING FOUNTAINFIRE ALARM ANNUMNICATOR PANELFIRE ALARM CONTROL PANELFULL LOAD AMPSGROUNDGROUND FAULT CURRENT INTERRUPTHORSEPOWERHERTZTHOUSAND CIRCULAR MILSKILOVOLT-AMPEREKILOWATTLIGHT EMITTING DIODEMOTOR CONTROL CENTERMAIN LUGS ONLYNEUTRALNATIONAL ELECTRIC CODEPOWER FACTORSPACE ONLY WITH BUSUNDERGROUND ELECTRICALVOLTVOLT-AMPEREVARIABLE FREQUENCY DRIVEWEATHER PROOFTRNASFORMERTHREE POLETHREE PHASEFOUR WIRE30 AMPERE, 3-POLE
ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH DIVISION 26 SPECIFICATIONS, NATIONAL ELECTRICAL CODE, AND ALL OTHER APPLICABLE STANDARDS AND REGULATIONS ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
ALL ABOVE GROUND EXTERIOR CONDUIT SHALL BE GALVANIZED RIGID STEEL CONDUIT WITH CORROSION RESISTANT FITTINGS, CLAMPS AND SUPPORT, INTERIOR EXPOSED CONDUIT ABOVE GROUND SHALL BE EMT WITH COMPRESSION FITTINGS.
IN THE EVENT OF CONFLICTS BETWEEN THE DRAWINGS, SPECIFICATIONS, CODES AND REGULATIONS, NOTIFY THE ARCHITECT IN WRITING FOR ENGINEER OF RECORD'S OPINION PRIOR TO INSTALLATION.
SHOP DRAWINGS SHALL BE SUBMITTED TO ARCHITECT FOR APPROVAL AND TO THE ENGINEER FOR REVIEW.
SMACNA SEISMIC RESTRAINT MANUAL, THIRD EDITION, OR LATEST REVISION MAY BE USED AS A GUIDE FOR GENERAL SEISMIC SUPPORT DETAIL AND SUPPORT SPACING RECOMMENDATIONS.
COORDINATE LOCATION OF ALL LIGHTING FIXTURES, MECHANICAL EQUIPMENT AND ACCESS PANELS WITH OTHER DISCIPLINES PRIOR TO ROUGH-IN.
WHILE GREAT EFFORT HAS BEEN MADE TO IDENTIFY EXISTING CIRCUITS , THE INFORMATION MAY NOT BE ACCURATE. ELECTRICAL CONTRACTOR SHALL VERIFY VOLTAGE AND AMP DRAW FOR ALL NEW EQUIPMENT.
FOR ALL LIGHTING FIXTURES, CONDUCTORS SHALL BE STRANDED THHN #12 INSTALLED IN EMT.
WORK SHALL OCCUR AT NIGHT (8PM-5AM) FOR ANY "NOISE PRODUCING ACTIVITY." ALL OTHER WORK MAY OCCUR DURING THE DAY/EVENING SHIFT. ONLY ONE ELEVATOR MAY BE UNDER CONSTRUCTION AT A TIME.
1.
2.
3.
4.
5.
6.
7.
8.
9.
GENERAL PROJECT NOTES:
BASIC MATERIALS
SERVICE AND DISTRIBUTION
LIGHTING
A
A
LV
J
G
T
3S
KS
S
MS
T
A
M
R
CB
LC
PC
1
UE
SD
ELECTRICAL LEGENDSYMBOL DESCRIPTION
FIRE ALARM
F
F
F
L
FS
FS
F
L
F
S
H
S
SR
D
R
V
SD
FS
SYMBOL DESCRIPTION
COMMUNICATIONS
S
GFCI
WP
ANNP
FLUORESCENT LIGHTING FIXTURE
(LETTER REFERENCES FIXTURE SCHEDULE)
FLUORESCENT LIGHTING FIXTURE - DUAL SWITCHED
FLUORESCENT EMERGENCY LIGHTING FIXTURE
INCANDESCENT, FLUORESCENT OR H.I.D. LIGHTING FIXTURE
(LETTER REFERENCES FIXTURE SCHEDULE)
INCANDESCENT OR FLUORESCENT EMERGENCY LIGHTING FIXTURE
WALL MOUNTED LIGHTING FIXTURE
POLE MOUNTED LIGHTING FIXTURE
EXIT SIGN (FURNISH WITH DUAL FACES AND DIRECTIONAL ARROWS WHERE INDICATED)
EMERGENCY LIGHTING UNIT
REMOTE EMERGENCY TWIN LIGHTING HEAD
SWITCHBOARD
DISTRIBUTION PANEL
BRANCH CIRCUIT PANEL
TRANSFORMER
MOTOR CONNECTION
GENERATOR CONNECTION
DISCONNECT SWITCH (FUSED AS REQUIRED)
MOTOR CONTROLLER (SPECIFIED IN OTHER THAN DIV. 16)
COMBINATION MOTOR CONTROLLER & DISCONNECT SWITCH (SPECIFIED IN OTHER THAN DIV. 16)
EQUIPMENT NOT FURNISHED UNDER DIV. 16 (SPECIFIED IN OTHER THAN DIV. 16)
EQUIPMENT ELECTRICAL CONNECTION
AMMETER
ELECTRIC METER
RELAY
CIRCUIT BREAKER
LIGHTING CONTACTOR
PHOTOCELL
THERMOSTAT
BRANCH CIRCUIT WIRE & CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING,HOME RUN TO PANELBOARD. A NUMERAL, IF PRESENT AT ARROW HEAD, INDICATESCIRCUIT NUMBER. ANY BRANCH CIRCUIT SHOWN WITHOUT SLASH MARKSINDICATES A CONDUIT CONTAINING (3) #12 AWG CONDUCTORS (HOT, NEUTRAL &GROUND). SLASH MARKS, IF PRESENT, INDICATE THE FOLLOWING:
HOT (ENERGIZED) CONDUCTOR
NEUTRAL CONDUCTOR
GROUND CONDUCTOR
WIRE & CONDUIT RUN EXPOSED
WIRE & CONDUIT RUN IN OR UNDER FLOOR
UNDERGROUND ELECTRICAL DUCTBANK OR CONDUIT
WIRE & CONDUIT TURNED UP
WIRE & CONDUIT TURNED DOWN
LOW VOLTAGE WIRING RUN IN CONDUIT
ELECTRICAL CONNECTION REQUIRED
EXISTING LIGHT FIXTURE OR ELECTRICAL DEVICE BE REMOVED AND/OR RELOCATEDAND CIRCUITRY MADE CONTINUOUS WHERE REQUIRED. UNO, LINE TYPE TYPICALFOR ALL DEVICES TO BE REMOVED AND/OR RELOCATED.
DISCONNECT SWITCH
JUNCTION BOX
PUSHBUTTONMANUAL MOTOR STARTER SWITCHSINGLE-POLE, SINGLE-THROW (S.P.S.T.) WALL SWITCHKEYED WALL SWITCHWALL BOX DIMMER CONTROLSINGLE-POLE, DOUBLE-THROW (S.P.D.T.) WALL SWITCHSINGLE RECEPTACLE IN WALL (NEMA 5-20R)DUPLEX RECEPTACLE IN WALL (NEMA 5-20R)G.F.I. TYPE DUPLEX RECEPTACLE IN WALL 44" A.F.F. (NEMA 5-20R)DUPLEX RECEPTACLE IN WALL, EMERGENCY CIRCUIT (NEMA 5-20R)DUPLEX RECEPTACLE IN FLOOR (NEMA 5-20R)DOUBLE DUPLEX RECEPTACLE IN WALL (NEMA 5-20R)G.F.I. TYPE DUPLEX RECEPTACLE OUTDOORS (WEATHER PROOF)
FIRE ALARM SPEAKER & ADA SIGNAL LIGHT (80" MH)
FIRE ALARM HORN & ADA SIGNAL LIGHT (80" MH)
FIRE ALARM CHIME & ADA SIGNAL LIGHT (80" MH)
FIRE ALARM ADA VISUAL SIGNAL LIGHT (80" MH)
CEILING MOUNTED FIRE ALARM SPEAKER & SIGNAL LIGHT
CEILING MOUNTED FIRE ALARM HORN & SIGNAL LIGHT
CEILING MOUNTED FIRE ALARM SPEAKER
CEILING MOUNTED FIRE ALARM ADA VISUAL SIGNALING LIGHT
FIRE ALARM SIGNAL PULL STATION (46" MH)
CEILING MOUNTED SMOKE DETECTOR
CEILING MOUNTED HEAT DETECTOR
DUCT MOUNTED SMOKE DETECTOR
DUCT MOUNTED DETECTOR REMOTE TEST STATION AND ALARM INDICATOR LIGHT,
WALL MOUNTED AT 80" MH, UNLESS NOTED OTHERWISE.
ELECTROMAGNETIC DOOR HOLDER (WALL MOUNTED)
FIRE ALARM CONTROLLED PROGRAMMABLE RELAY
VALVE TAMPER SWITCH
SMOKE DAMPER
FIRE SHUTTER
ANNUNCIATOR PANEL
DATA OUTLET WITH 3/4" CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE
TELEPHONE OUTLET WITH 3/4" CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE
COMBINATION TELEPHONE/DATA OUTLET IN FLOOR WITH 3/4" CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE
CEILING MOUNTED SPEAKER
TO SHUNT TRIP CIRCUIT BREAKER OF ELEVATION POWER CKT.
WARNING LIGHT ACTIVATION BY MACHINE ROOM SMOKE DETECTOR (TYPICAL)
ELEVATOR MACHINE ROOM
ELEVATOR PIT
WARNING LIGHT "DO NOT USE ELEVATOR"
1ST. FLOOR
FIRE ALARM FLOOR ZONE
2ND. FLOOR
TOP FLOOR (TYP)
FIRE ALARM FLOOR ZONE
FIRE ALARM FLOOR ZONE
NOTES:1. DERIVE POWER FOR FLASHING WARNING LIGHT FROM VISUAL ALARM CIRCUIT IN FIRE ALARM CONTROL
PANEL.
2. INITIATION OF ELEVATOR LOBBY, TOP OF SHAFT, OR MACHINE ROOM SMOKE DETECTOR LOOP SHALL PLACE ELEVATION CONTROL INTO PHASE 1 RECALL MODE & RETURN ELEVATOR TO DESIGNATED SAFE PLACE.
3. EXISTING FIRE ALARM IS SIMPLEX GRINNELL.
A
H
B
H BE
E D
C
DE
C
C
E
LEGEND
SMOKE DETECTOR(S) AND 135 DEG F FIXED TEMPERATURE HEAT DETECTORS(S) LOCATED IN ELEVATOR MACHINE ROOM. ALSO, NEED RELAYS 4090-9002 OR 4909-9008 IN MACHINE ROOM.
SHUNT TRIP CONTACT LOCATED IN HEAT DETECTOR TO SHUNT TRIP POWER TO ELEVATOR UPON ACTIVATION OF HEAT DETECTOR.
SMOKE DETECTOR LOCATED IN ELEVATOR LOBBY.
FLASHING WARNING LIGHTS LOCATED ADJACENT TO ELEVATOR CALL BUTTON AT PRIMARY & ALTERNATE ACCESS LEVELS.
SMOKE DETECTOR LOCATED AT TOP OF SHAFT.
A
B
C
D
E
DRAWN BY:
CHECKED BY:
PROJECT NUMBER
DATE DWG NO.
SHEET TITLE
SEAL
PROJECT NAME
ArchitecturePlanningInterior Design
1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com
PROJECT STATUS
This information is released solely for its use in the interest of the Memphis-Shelby County Airport Authority (MSCAA) or its Tenants.
All drawings received from MSCAA or produced for MSCAA as a work product shall be regarded as priveleged information, not to be released to others without the express written permission of MSCAA.
Your acceptance of the released materials establishes your understanding of, and commitment to, providing adequate control of the materials issued and produced.
MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113
MEMPHIS, TENNESSEE38116-3856
APPROVED BY:
SCALE
MSCAA NO.
2787 STAGE CENTER DR. SUITE 101
BARTLETT, TENNESSEE 38134901-379-0500
www.innovativees-llc.com
14-1379-22-01
As indicatedE001
ELECTRIAL NOTES,LEGEND, &
DETAILS
PTH
RJH
ELEVATORMODERNIZATIONS
(REBID)
14053.022
2/27/18
ISSUED FORREBID/CONSTRUCTION
RJH
N.T.S.4FIRE ALARM FOR HYDRAULICELEVATOR DETAIL
REVISIONSNO. DESCRIPTION DATE BY
12
5
6
7
10
12a
13
9
11
14
14a
8
4
13
12
10
9
8
6
5
4
7
11
14
12
5
6
7
10
12a
13
9
11
14
14a
8
4
13
12
10
9
8
6
5
4
7
11
14
15
12
5
6
7
10
12a
13
9
14b
15
11
14
14a
8
4
13
12
10
9
8
6
5
4
7
11
14
PODIUM
PODIUM
PO DI U MPO DI U M
PO DI U MPO DI U M PO DI U MPO DI U MPO DI U MPO DI U M
LANE 1
LANE 2
LANE 3
LANE 4
LANE 5
TCOP
L3AIT
EN TE R
EXIT
Ro of
FR ON TTCOP
L3AIT
EN TE R
EXIT
Ro of
FR ON T
LANE 5
LANE 1
LANE 2
LANE 3
LANE 4
LANE 5
TCOP
L3AIT
EN TE R
EXIT
Ro of
FR ON TTCOP
L3AIT
EN TE R
EXIT
Ro of
FR ON T
LANE 5
PODIUM
PODIUM
LANE 2
LANE 1
TCOP
L3AIT
ENTER
EXIT
RoofFRONT
8'-0"
8'-63 __ 16"
6'-11_8"
101'-2"
20'-1 7__16"
15'-7"
38'-21_4"
11'-511 __ 16"
14'-01_2"12'-10"
42'-6 1__16 "10
'-215 __ 16"
12'-111_2"
VITREOUSCHINA C_TOILETSKINGSTONK-4329
VITREOUSCHINA C_TOILETSKINGSTONK-4329
xx
xxx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
2
X-RAY604 0 aT iXHEI MA NN
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE63
0 S.S.
BINS
EMPTY
BINS
EMPTY
TABLE63
0 S.S.
BINS
EMPTY
BINS
EMPTY
TABLE430
SS
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE430
SS
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE430
SS
TABLE63
0 S.S.
WTMD CEIA
3'-9"
3'
L
ADA GATE
ETD
FRONT
ETD
FRONT
TAB LE 53 0 S. S TAB LE 53 0 S. S TAB LE 63 0 S. S.
3
3
TABLE63
0 S.S.
4
RADA GA TE 4
RADA GA TE
ETDF
RONT
BENCH
BENCH
X-RAY604 0 aT iXHEI MA NN
X-RAY604 0 aT iXHEI MA NN
X-RAY604 0 aT iXHEI MA NN
X-RAY604 0 aT iXHEI MA NN
2
RADA GA TE
3
3
4
3'-9"
3'
L
ADA GATE
4
3'-9"
3'
L
ADA GATE
4
3'-9"
3'
L
ADA GATE
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
BINS
EMPTY
2
X-RAY604 0 aT iXHEI MA NN
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE63
0 S.S.
BINS
EMPTY
BINS
EMPTY
TABLE63
0 S.S.
BINS
EMPTY
BINS
EMPTY
TABLE430
SS
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE430
SS
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE430
SS
TABLE63
0 S.S.
WTMD CEIA
3'-9"
3'
L
ADA GATE
ETD
FRONT
ETD
FRONT
TAB LE 53 0 S. S TAB LE 53 0 S. S TAB LE 63 0 S. S.
3
3
TABLE63
0 S.S.
4
RADA GA TE 4
RADA GA TE
ETDF
RONT
BENCH
BENCH
X-RAY604 0 aT iXHEI MA NN
X-RAY604 0 aT iXHEI MA NN
X-RAY604 0 aT iXHEI MA NN
X-RAY604 0 aT iXHEI MA NN
2
RADA GA TE
3
3
4
3'-9"
3'
L
ADA GATE
4
3'-9"
3'
L
ADA GATE
4
3'-9"
3'
L
ADA GATE
TABLE63
0 S.S.
TABLE63
0 S.S.
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
TABLE430
SS
BINSEMPTY
BINSEMPTY
2
L
BIN SEMP TY
BIN SEMP TY
BIN SEMP TY
BIN SEMP TY
3'-9" 3'
R4
WTMD
CEIA
TSA.S3
D6R
TSA.S3
D6R
3'-9" 3'
L
ADA GATE
3
AVS
I.T.
RACK
3
TAB LE 53 0 S. S
TAB LE 63 0 S. S. TAB LE 63 0 S. S.
ET D
TAB LE 63 0 S. S. TAB LE 63 0 S. S.
ET D
TAB LE 63 0 S. S.
ET D
X-RAY
6040 aTiX
HEIMANN
X-RAY
6040 aTiXHEIM
ANN
3
BINSEMPTY
BINSEMPTY
TABLE430 SS
44444444 4
ETD
FRONT
ETD
FRONT
ETD
FRONT
ETD
FRONT
I.T.
RACK
PO DI U M
PODIUM
PODIUM
LANE 3
LANE 2
LANE 1
BIN SEMP TY
BIN SEMP TY
WTMD
CEIA
3'-9"
3'
LADA GATE
L
2
X-RAY
6040 aTiX
HEIMANN
ETDFRONT
TABLE63
0 S.S.
TAB LE 63 0 S. S.
X-RAY
6040 aTiX
HEIMANN
X-RAY
6040 aTiX
HEIMANN
B IN SEMP TY
BIN SEMP TY
BIN SEMP TY
BIN SEMP TY
TAB LE 63 0 S. S. TAB LE 63 0 S. S.
TAB LE 63 0 S. S. TAB LE 63 0 S. S.
TAB LE 63 0 S. S. TAB LE 63 0 S. S.
BIN SEMP TY
BIN SEMP TY
BIN SEMP TY
BIN SEMP TY
BIN SEMP TY
BIN SEMP TY
L
21
2
ETDFRONT
AVS
1
L3AIT
ENTER
EXIT
Roof
TCOP
FRON
T
WTMD
CEIA 2
1
R
ADA GA TE
ETDFRONT
FECFE
FEC
ADMINBEHAVIORALTSSE
SCREENINGMANAGERS
205 AFSDSBREAK ROOM
202TRAINING
201
LOCKERS203
MANAGERS205
CORRIDOR211
SERVER213
STORAGE212
CENTER LINE BAGGAGE BELT:231'
CENTER LINE BAGGAGE BELT:112'
CENTER LINE BAGGAGE BELT:
83'
CENTER LINE BAGGAGE BELT:112'
APPROX. LENGTH CENTER LINE BAGGAGE BELT : 194'
APPROX. LENGTH CENTER LINE BAGGAGE BELT : 166'
APPROX. LENGTH CENTER LINE BAGGAGE BELT : 166'
12
5
6
7
10
12a
13
9
11
14
14a
8
4
13
12
10
9
8
6
5
ER EB ED EF EH EJ EL EN EO EQ ER ES ETEPEMEIEE
4
7
11
14
12
5
6
7
10
12a
13
9
11
14
14a
8
4
13
12
10
9
8
6
5
ER EB ED EF EH EJ EL EN EO EQ ER ES ETEPEMEIEE
4
7
11
1414A
14
14A
1414
14A
14
14A
STAIR NO. 3
OFFICEAREA
TOOLROOM
LOCKERROOM LOCKERS
TOOLS
CARTS
SHOPAREA
SHOPAREA
OFFICESUPERVISOR
WORKBENCH
SHOP AREASHOP AREA
SUPERVISOROFFICE
OFFICE AREA TOOL ROOM LOCKER ROOMTOOLSLOCKERSCARTS
DOCK
RAMP UP
RAMP DOWN RAMP UP
NEW WINDOW
NEW WINDOW
NEW 1-1/2"
DIA. RAILING
OFFICE AREA TOOL ROOM LOCKER ROOM LOCKERSTOOLS
CARTS
SHOP AREA SHOP AREA
OFFICESUPERVISOR
WORK BENCH
LOCKER ROOM LOCK SHOP
REPORT ROOM
COMPUTERMAINTENANCE
SAFETY/COM/ETC
MAINTENANCE
OFFICEROOMSTORAGE
LUNCH ROOM
LUNCH ROOMEXPANSION
MAINT. KITCHEN
FILEROOM
SHOP AREA
ELEV.EQ. RM.
ELEV. #15(4 LEVELS)
ELEV. #7(3 LEVELS)
ELEV. #14(4 LEVELS)
ELEV. #15(4 LEVELS)
ELEV. #7(3 LEVELS)
ELEV. #14(4 LEVELS)
ELEV. #15(4 LEVELS)
ELEV. #7(3 LEVELS)
ELEV. #14(4 LEVELS)
ELEV. #25(2 LEVELS)
E2012
ELEV. #15(4 LEVELS)
ELEV. #25(2 LEVELS)
ELEV. #14(4 LEVELS)
E2011
E2013
DRAWN BY:
CHECKED BY:
PROJECT NUMBER
DATE DWG NO.
SHEET TITLE
SEAL
PROJECT NAME
ArchitecturePlanningInterior Design
1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com
PROJECT STATUS
This information is released solely for its use in the interest of the Memphis-Shelby County Airport Authority (MSCAA) or its Tenants.
All drawings received from MSCAA or produced for MSCAA as a work product shall be regarded as priveleged information, not to be released to others without the express written permission of MSCAA.
Your acceptance of the released materials establishes your understanding of, and commitment to, providing adequate control of the materials issued and produced.
MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113
MEMPHIS, TENNESSEE38116-3856
APPROVED BY:
SCALE
MSCAA NO.
2787 STAGE CENTER DR. SUITE 101
BARTLETT, TENNESSEE 38134901-379-0500
www.innovativees-llc.com
14-1379-22-01
1" = 50'-0"E101
OVERALL FLOORPLANS
PTH
RJH
ELEVATORMODERNIZATIONS
(REBID)
14053.022
2/27/18
ISSUED FORREBID/CONSTRUCTION
RJH
1" = 50'-0"1 4 - Power - Mezz
1" = 50'-0"2 3 - Power - Concourse
1" = 50'-0"3 2 - Power - Apron
1" = 50'-0"4 1 - Power - Tunnel
GENERAL NOTES:
1. REFER TO BID REQUIREMENTS FOR BASE BID, ALTERNATES, AND ALLOWANCE INFOMRATION.
REVISIONSNO. DESCRIPTION DATE BY
S
S
GFC
I
H
S
CR
S
S
GFC
I
H
S
CR
S
S
GFC
I
H
S
CR
ELEV. MACHINE ROOM
ELEV. 15
NEW GFCI OUTLET IN PIT
NEW LED LIGHT IN PIT
PROVISIONS FOR NEW CARD READER IN CAB
NEW SMOKE DETECTOR WITH ELEVATOR RECALL
NEW LED FIXTURE IN MACHINE ROOM
NEW SMOKE DETECTOR IN MACHINE ROOM
NEW SMOKE DETECTOR IN TOP OF SHAFT AND HEAT DETECTOR IN PIT OF ELEVATOR SHAFT
REPLACE CAB LIGHTS WITH LED
PROVIDE FUSED DISCONNECT WITH SHUNT TRIP FOR ELEVATORS AND 110V DISCONNECT FOR FAN AND LIGHTS
ELEV. MACHINE ROOM
ELEV. 14
NEW GFCI OUTLET IN PIT
NEW LED LIGHT IN PIT
PROVISIONS FOR NEW CARD READER IN CAB NEW SMOKE DETECTOR
WITH ELEVATOR RECALL
NEW SMOKE DETECTOR IN TOP OF SHAFT AND HEAT DETECTOR IN PIT OF ELEVATOR SHAFT
REPLACE CAB LIGHTS WITH LED
NEW LED FIXTURE IN MACHINE ROOM
NEW SMOKE DETECTOR IN MACHINE ROOM
PROVIDE FUSED DISCONNECT WITH SHUNT TRIP FOR ELEVATORS AND 110V DISCONNECT FOR FAN
AND LIGHTS
MOVE EXISTING VFD TO ALLOW FOR NEW ACCESS
ELEV. MACHINE ROOM
ELEV. 14
NEW GFCI OUTLET IN PIT
NEW LED LIGHT IN PIT
PROVISIONS FOR NEW CARD READER IN CAB NEW SMOKE DETECTOR
WITH ELEVATOR RECALL
NEW SMOKE DETECTOR IN TOP OF SHAFT AND HEAT DETECTOR IN PIT OF ELEVATOR SHAFT
REPLACE CAB LIGHTS WITH LED
NEW LED FIXTURE IN MACHINE ROOM
NEW SMOKE DETECTOR IN MACHINE ROOM
PROVIDE FUSED DISCONNECT WITH SHUNT TRIP FOR ELEVATORS AND 110V DISCONNECT FOR FAN
AND LIGHTS
DRAWN BY:
CHECKED BY:
PROJECT NUMBER
DATE DWG NO.
SHEET TITLE
SEAL
PROJECT NAME
ArchitecturePlanningInterior Design
1500 Union AvenueMemphis, TN 38104Tel. 901-278-6868www.anfa.com
PROJECT STATUS
This information is released solely for its use in the interest of the Memphis-Shelby County Airport Authority (MSCAA) or its Tenants.
All drawings received from MSCAA or produced for MSCAA as a work product shall be regarded as priveleged information, not to be released to others without the express written permission of MSCAA.
Your acceptance of the released materials establishes your understanding of, and commitment to, providing adequate control of the materials issued and produced.
MEMPHIS INTERNATIONAL AIRPORT2491 WINCHESTER RD. SUITE 113
MEMPHIS, TENNESSEE38116-3856
APPROVED BY:
SCALE
MSCAA NO.
2787 STAGE CENTER DR. SUITE 101
BARTLETT, TENNESSEE 38134901-379-0500
www.innovativees-llc.com
14-1379-22-01
1/4" = 1'-0"E201
ENLARGEDMACHINE ROOMS -
ELECTRICAL
PTH
RJH
ELEVATORMODERNIZATIONS
(REBID)
14053.022
2/27/18
ISSUED FORREBID/CONSTRUCTION
RJH
1/4" = 1'-0"1 ELEVATOR #15 - ELECTRICAL 1/4" = 1'-0"2 ELEVATOR #7 - ELECTRICAL
1/4" = 1'-0"3 ELEVATOR #14 - ELECTRICAL
GENERAL NOTES:
A. REFER TO SHEET E001 FOR GENERAL PROJECT NOTES AND LEGEND.
B. ALL LIGHTING CONDUCTORS SHALL BE THHN #12 STRANDED INSTALLED IN EMT.
C. RE-USE EXISTING LIGHTING AND POWER CIRCUITS.
REVISIONSNO. DESCRIPTION DATE BY