Electromagnetic Lock Installation Instruction (Indoor Series) · the electromagnetic lock...

2
Electromagnetic Lock (Indoor Series) Installation Instruction Optional Bracket Regular Installation L-bracket for narrow frame (optional) U-bracket for frameless glass door (optional) LZ-bracket for inswing door (optional) Bracket installation is according to door swing direction and door frame type ,e. g. narrow frame door , frameless glass door, inswing door , etc. Regular Installation 1 2 3 4 Tem pl ate Fold the mounting template 90° Place the template to the proper position of the door and frame. Mark the hole positions of the template on the door and frame. Drill the holes according to the marks. Please install the armature plate as illustrated herr. (Dimensions of the holes are depending on the door types as illustrated below) Armature Plate Fix the mounting plate on the door with mounting screws Use the Allen wrench and fixing bolts to tighten the electromagnetic lock to mounting plate. Allen wrench 9 Connect the power and test the unit. Outswing Power Drill a Ø8mm hole through door, on closing side, enlarge to Ø12.7mm by a sexnut bolt on the opening side. 12.7mm 8mm Hollow Metal Door 6.8mm for M8-1.25 thread Reinforced Door 12.7mm 8mm Solid Door 36mm 5 Rubber Washer (outswing door) Copyright © Gianni Industries, Inc. All rights reserved. P-MU-AM-EM-GEM Ver. B Published on: 2011.04.07 6 7 7 8 Outdoor Outdoor Outdoor Recommendation: For Micro EM-locks (300 LBS), maximum thickness of door is 44 mm. For Mini EM-locks (600 LBS), maximum thickness of door is 50 mm. For Midi EM-locks (800 LBS), maximum thickness of door is 48 mm. For Maxi EM-locks (1200 LBS), maximum thickness of door is 46 mm. Drill a Ø8mm hole thrugh door on closing side enlarge to Ø 12.7mm, by a sexnut blot on the opening side. The depth is 36mm. Drill a and tap on closing side a M8x12.5 thread. Ø6.8mm hole The rubber washer makes the surface of the armature plate adjustable in order to completely fit the surface of magnetic lock. Fasten the mounting plate with the mounting screws. The position of the mounting plate should be adjustable.

Transcript of Electromagnetic Lock Installation Instruction (Indoor Series) · the electromagnetic lock...

Electromagnetic Lock (Indoor Series)

Installation Instruction

Optional Bracket

Regular Installation L-bracket for narrow frame (optional)

U-bracket for frameless glass door (optional)

LZ-bracket for inswingdoor (optional)

Bracket installation is according to door swing direction and door frame type ,e. g. narrow frame door , frameless glass door, inswing door , etc.

Regular Installation

1

2

3

4

Template

Fold the mounting template 90°

Place the template to the proper position of the door and frame. Mark the hole positions of the template on the door and frame.

Drill the holes according to the marks.

Please install the armature plate as illustrated herr. (Dimensions of the holes are depending on the door types as illustrated below)

Armature Plate

Fix the mounting plate on the door with mounting screws

Use the Allen wrench and fixing bolts to tighten the electromagnetic lock to mounting plate.

Allen wrench

9

Connect the power and test the unit.

Outswing

Power

D r i l l a Ø 8 m m h o l e through door, on closing s i d e , e n l a r g e t o Ø12.7mm by a sexnut bolt on the opening side.

12.7mm 8mm

Hollow Metal Door

6.8mm for M8-1.25 thread

Reinforced Door

12.7mm 8mm

Solid Door

36mm

5

Rubber Washer

(outswing door)

Copyright © Gianni Industries, Inc. All rights reserved. P-MU-AM-EM-GEM Ver. B Published on: 2011.04.07

6

77

8

OutdoorOutdoorOutdoor

Recommendation:

For Micro EM-locks (300 LBS), maximum thickness of door is 44 mm.

For Mini EM-locks (600 LBS), maximum thickness of door is 50 mm.

For Midi EM-locks (800 LBS), maximum thickness of door is 48 mm.

For Maxi EM-locks (1200 LBS), maximum thickness of door is 46 mm.

Drill a Ø8mm hole thrugh d o o r o n c l o s i n g s i d e enlarge to Ø 12.7mm, by a sexnut blot on the opening side. The depth is 36mm.

Drill a and tap on closing side a M8x12.5 thread.

Ø6.8mm hole

The rubber washer makes the su r face o f the a rmatu re p la te adjustable in order to completely fit the surface of magnetic lock.

Fasten the mounting plate with the mounting screws. The position of the mounting plate should be adjustable.

LZ bracket for Inswing doors

Connecting Diagram

Problem Possible Cause Solution

Door does not lock No power

Poor contact between electromagnet and armature plate

Low voltage or incorrect voltage setting

A secondary diode was installed across the electromagnetic lock

Misalignment between the armature plateand electromagnetic lock

Make sure the wires are connected properly

Check that the power supply is connected and works properly

Make sure the lock switch is wired correctly (N.C.)

Make sure if the armature plate is deformed

Make sure the contact surfaces of the electromagnet and armature plate are clean and free from dust

Make sure the armature plate and electromagnetic lock are aligned correctly

Make sure if the rubber washer was used between magnet lock and armature plate

Ensure the electromagnet lock is set for the correct voltage.

Check for proper voltage at the electromagnetic locks input. If low, determine if the correct wire gauge is being used to prevent excessive voltage drop.

Remove any diode installed across the magnet for "spike" suppression. (The magnet is fitted with a metal oxide varistor to prevent back EMF)

Low holding force

Sensor output is not functioning

Trouble Shooting

2

Use the fixing bolt to tighten the electromagnetic lock on L bracket.

1

Find a mounting location on the door frame for the L bracket. Make sure that the door is still closeable.

Close the door and connect thepower.

4

Insert the guide pins into the armature plate.

3

Models:

GEM-300, GEM-600 , GEM-800 , GEM-1200

GEM-D600 , GEM-D800 , GEM-D1200

+-

N.O.COM.N.C.

Mag Power Input

Sensor Input

+-

+

-

N.O.

COM.

N.C.Mag Power Input

Sensor Input

+

-

Po

we

rIn

pu

t

SP

DT

re

lay

0.5

A/1

25

VA

C1

A/2

4V

DC

Model:GEM-300M

Relay rating output: 0.2A/12VDC

N.C. contact output: open statusN.O. contact output: locked statusRelay rating output needs to meet the instruction of PCB 0.5A/125VAC,1A/24VDC

12VDC

24VDC

上鎖時間延遲:利用「時間調整鈕」調整電磁鎖可以開門時間(1~80秒),運用讀卡機觸發接點後電磁鎖內部自行斷電,有此功能的型號為

GEM-600MTD , GEM-800MTD,GEM-1200MTD

GEM-D600MTD , GEM-D800MTD , GEM-D1200MTD

+-

+-

N.O.COM.N.C. Mag Power Input

Sensor Input

N.O.Com.N.C.

Door Status Sensor (Optional) Door Status Sensor indicates the door is in an open or closed status.GEM-600MDS , GEM-800MDS , GEM-1200MDSGEM-D600MDS , GEM-D800MDS , GEM-D1200MDS

Ensures the automatic lock mode after the door is closed properly and it can be adjusted from 1 to 80 seconds. (Timer Adjustment)

GEM-600MTD , GEM-800MTD,GEM-1200MTD

GEM-D600MTD , GEM-D800MTD , GEM-D1200MTD

N.C. contact output: open statusN.O. contact output: locked statusRelay rating output needs to meet the instruction of PCBGEM-600M , GEM-800M ,GEM-1200M

GEM-D600M , GEM-D800M , GEM-D1200M

Orange:White:Brown:

Buzzer Alarm

Door Held Open Alarm is an auditory feedback for users. Alarm sounds when the door is not closed for over a specif ied t ime l imit . VR t imer (Timer Adjustment) is adjustable from 1 to 20 seconds.

Timer Adjustment

Shorten

LED indicatorGREEN: OpenRED : LockedNO LED: No power

Powersupply

Control Device N.C. contact or Access Relay

Bond sensor output (optional)

Relock time delay (Optional)

Powersupply

Control Device N.C. contact or Access Relay

Bond sensor output (optional)N.C. contact output: open statusN.O. contact output: locked statusRelay rating output 0.1A/30VDC, need to meet the instruction of PCB

Powersupply

Control Device N.C. contact or Access Relay

LED indicatorGREEN: OpenRED : LockedNO LED: No power

Bond sensor output (optional)Voltage Selection jumpersCheck jumper settings before connecting the lock to 24 VDC input power. Damage to the lock may result from incorrect jumper settings.

5 6 7 Power

Outdoor

Finish

Outdoor

Power

Fasten the armature plate to the Z bracket (Rubber washer must be added)

After the maglock attracts the armature plate, adjust the position between Z bracket and the door. Then fix the Z bracket.

Fasten the cover to the bracket. Connect the power, close the door and test the unit.

Copyright © Gianni Industries, Inc. All rights reserved. P-MU-AM-EM-GEM Ver. B Published on: 2011.04.07

Assemble the Z bracket , and makesure that the position of the Z bracket is adjustable.