Troubleshooting Flow Chart Page A - D
Wiring Diagram Page E
Gas Ignition Control Module Page F
Component Location Identification Page G
AC Voltage Testing Page H
Continuity Testing Page I
Low Level Water Switch Testing Page 1
High Temperature Water Snap Switch Testing Page 2
Safety Relay Testing (Early Models Only) Page 3
Master Control Module Testing (Input Side Only) Page 4
Remote Switch Testing Page 5
Master Control Module Testing (Output Side) Page 6
Lighting Testing Page 7
Water Pump Testing Page 8
Purging Air Page 9Gas Control (Pilot Side/Burner Side)
Incoming Voltage Testing Page 10Gas Control Pilot Operator and Burner
Operation Continuity Testing Page 11
Incoming Gas Pressure Testing Page 12
Outgoing Gas Pressure Testing Page 13
Flame Rectification Page 14 -15
RING OF FIRE
ACopyright ' 10/27/04 Travis Industries, Inc.
ROF TROUBLESHOOTING FLOW CHART
Simultaneouslydepress light and
water button.
Hold forapproximately
5 seconds,then release.
Switchpad lights
up
YES
NO
¥ Check for low water (fill if needed)
¥ Check for 110 AC incoming voltage
¥ Check low water switch (see page 1)
¥ Test high water temperature snap disk (see page 2)
¥ Continuity test relay (see page 3)
¥ Check for over heated water snap disk
¥ Disconnect power from master control module and ¥ ¥ ¥ ¥ continuity test transformer - Black and White wires (see page 4)¥ Disconnect Blue wires output side of Master Control and conduct test #4 on page 6)
Continuity - GoodNo Continuity - Replace Module
¥ Disconnect switch pad wires from master control module¥ and conduct Tests 1, 2, 3. (see page 5)
Ropelights come on NO
¥ Check control module output side - (Red & White wires) for 110 v AC (See Test #1 page 6)
¥ Test lighting components (see page 7)
YES
WaterComes
onNO
NEXT PAGE
¥ Check control module output side (Yellow and ¥White wires) (See test #2 on Page 6)
¥ Check water pump (See page 8)
ROF TROUBLESHOOTING FLOW CHART
PushFlameButton
Switchpad lights
up
YES
NO ¥ Conduct test # 3 on Test Page #3
Ignitionstarts to
clickNO
¥ Verify AC voltage on output of master control module¥ - Grey wires (See test #3 on Test Page #6)
¥ If all of above check out good - replace the gas ¥ ignition control module
NEXT PAGE
B
RING OF FIRE
Copyright ' 10/27/04 Travis Industries, Inc.
ROF TROUBLESHOOTING FLOW CHART
Pilot flamecomes on
NO
YES
¥ Check gas shut offs- main shut off- gas control valve
¥ Check fuel supply (LP)
¥ Check wiring to make sure ignition control module is¥ properly wired (see Wiring Diagram pages E & F)
¥ Check orifice for blockage
¥ Purge air (see Test Page #9 for procedure)
¥ Check that 30 VAC is present at the P & C terminals¥ of the wiring harness that connects to the valve
(see Test Page #10) see pilot side test
¥ NO VOLTAGE - Replace the ignition control module
¥ Continuity check the pilot side of the gas control valve¥ (see Test Page #11)
¥ CONTINUITY - Good¥ NO CONTINUITY - Replace gas control valve
¥ Test incoming gas valve pressure (See Test Page #12)
¥ Check pilot tube for blockage
¥ Replace the gas control valve
Ignition sparkturns off
NO
NEXT PAGE
No Flame Rectification
¥ Check pilot flame for proper contact with spark electrode(see Page #14)
¥ Check all ground connections (valve & ignition control)(see Page #15)
¥ If all of the above are good - replace the ignition control¥ module
C
RING OF FIRE
Copyright ' 10/27/04 Travis Industries, Inc.
ROF TROUBLESHOOTING FLOW CHART
Burnercomes
on
NO
YES
¥ Check burner orifice for blockage
¥ Check that 30 VAC is present at the M & C terminals of the wiring harness that connects to the valve
(see Test Page #10)
NO VOLTAGE - Replace the ignition control module
¥ Continuity check the burn side of the gas control valve(see Test Page #11)
¥ CONTINUITY - Good¥ NO CONTINUITY - Replace gas control valve
¥ Test incoming gas valve pressure (see Test Page #12)
¥ Check outgoing pressure (see Test Page #13)
¥ IF NO PRESSURE - Replace gas control valve¥ IF PRESSURE IS PRESENT - Blockage is in burner supply tube, burner orifice or burner
Burner stays onfor desired time
NO
YES
¥ Did you exceed automatic 2 hour shut down?
¥ Wind interruption - ROF will lose flame rectification and automatically relight
¥ Lack of primary air see service bulletin
¥ Condensation effecting electronic ignition control see service bulletin
END
D
RING OF FIRE
Copyright ' 10/27/04 Travis Industries, Inc.
E
Wir
ing
Dia
gra
m
Gas V
alv
e
Ro
bert
Sh
aw
20001P
ER
C
Bro
wn (
Hot)
Blu
e (
Com
mon)
Bro
wn (
Gro
und)
Flo
at
Sw
itch
Wate
r T
em
p
Sw
itch
Gro
undW
hite
Bla
ck
Red
White
Yello
w
Ora
nge
Bro
wn
Gre
en
Bla
ck
Red
White
Yello
w
Ora
nge
Bro
wn
Gre
en
Rem
ote
Cable
Rin
g o
f F
ire
Co
ntr
ol M
od
ule
Ora
nge
Bla
ck
Red
White
Yello
w
Bro
wn
Gre
en
Light Water FlameRem
ote
Co
ntr
ol P
an
el
Blu
e
Blu
e
Ign
itio
n C
on
tro
l U
nit
Ro
bert
Sh
aw
780-7
15 U
TH
24V
GN
D
P
C (
M/P
) M
Gra
yP C
(M
/P)
MG
ND
Gra
y
Pow
er
Sourc
e
Red
White
Fle
xib
le R
op
e L
igh
t
30F
T, 110V
AC
, 1/2
” D
IA, 5.5
2W
/FT
Yello
w
White
Bla
ck
White
Wate
r
Pu
mp
Bla
ck
RING OF FIRE
Igni
tion
Con
trol
Uni
tR
ober
tSha
w 7
80-7
15 U
Gas
Val
veR
ober
tSha
w 2
0001
PE
RC
Copyright ' 10/27/04 Travis Industries, Inc.
Gas Ignition Control ModuleI.P.I.
F
RING OF FIRE
TH
PV
OPT Sensor
MVMV PV
TR
Ground
Igniter
Accessory Term.
Grey-Power Wire
Blue-Pilot Valve
Not Used
Common SharedBetween Pilot & Burner
Not Used
Green-Ground
Orange-Igniter
Not Used
Red-Main Valve (Burner)White
Copyright ' 10/27/04 Travis Industries, Inc.
Total ComponentsMasterControlModule
WaterConnection
Gas IgnitionControl Module
SafetyRelay
Newer ModelsHave This BuiltInto the Circuitry ofMaster Control Module
Remote SwitchTerminal
Low LevelWater Switch
Electronic GasControl Valve
N. C. HighTemperatureSnap Disk140ß
G
RING OF FIRE
Copyright ' 10/27/04 Travis Industries, Inc.
When Testing ROF Componentsfor AC Voltage
AVCAVC
¥ The ROF contains 110 VAC circuits (caution-shock potential)
¥ The ROF contains low voltage circuits 24-30 volts AC
H
RING OF FIRE
Copyright ' 10/27/04 Travis Industries, Inc.
When Testing ROF Componentsfor Continuity
A. Disconnect all power - No live voltage
B. Isolate the component being tested by disconnecting it from the electrical circuit
Use this scale setting
Do not use audiblebeep scale
I
RING OF FIRE
Copyright ' 10/27/04 Travis Industries, Inc.
RING OF FIRETEST Page #1
TESTING ROF COMPONENTS
TESTING LOW WATERLEVEL SWITCH - N.O. Switch
No ContinuityHas Continuity - GoodNo Continuity - Replace
Disconnect Wires Disconnect Wires
1Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
TESTING THE WATERTEMPERATURE SNAP DISK
CHECK
Continuity Test
COLD = ContinuityWARM = No ContinuityCOOLED = Continuity
If the snap disk does not perform as described• in the above box, it is defective and should be• replaced.
Disconnect all wiresto snap disk
N.C. 140ß F Snap Disk
2
RING OF FIRETEST Page #2
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
2
¥ Reconnect Blue & White¥ (#7 & #8)
¥ Disconnect Brown & Black wires
¥ Turn on 110 VAC (power)
¥ Continuity test switch (#3-#5)
¥ Continuity - Good No Continuity - Defective Replace Relay
1
¥ Disconnect relay wires (#7 & #8) Blue & White
Continuity TestRelay Coil (#7 & #8)
Continuity - Coil Good
No Continuity - Defective ¥Coil-Replace Relay
1 23 45 6
7 8BROWN WIRE
WHITE W
IRE
BLUE WIRE
BLACK WIRE
1 23 45 6
7 8BROWN WIRE
WHITE W
IRE
BLUE WIRE
BLACK WIRE
3
RING OF FIRETEST Page #3
Note: Found on older units.Newer models have thisbuilt into the circuitry ofmaster control module. Ifthis relay is not seen onthe outside of the mastercontrol, skip this page.
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
Continuity Test
CONTINUITY -Transformer isgood
NO CONTINUITY- Transformer isdefective. Replacethe Master ControlModule
Disconnect the BLACK and WHITE wires from the•incoming power.
Continuity test the incoming side of the step down transformer. (black and white wires)
Master ControlModule
Incoming 110vPower Wires
Testing Master Control Module - Incoming Side
4
RING OF FIRETEST Page #4
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
NOReplace Remote
Switch
NOReplace Remote
Switch
NOReplace Remote
Switch
TESTING REMOTE SWITCH
LIGHT
WATER
FLAME
RemoteSwitch
GREENYELLOW
REDBROWN
1
2
3
4
Test# Test Circuit Continuity No Continuity
1 2
1 3
1 4
Continuity
Continuity
Flame
Push in LIGHT
button
Push inWATERbutton
Push in FLAME
button
1
2
3
TestPoints
YESGOOD
YESGOOD
YESGOOD
Disconnect Green wire from the terminal block
before testing
Testpoints
5
RING OF FIRETEST Page #5
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
ACV
TESTING CONTROL MODULE - Output Side
Testing AC voltage output of control module Disconnect each set of wires as you test them With power ON and the light, water and flame buttons pushed ON,
• conduct the following test
Test# Test Circuit Reading Low or No
Voltage
AC Volts
AC Volts
Lighting
Water Pump
1
2
3
TestPoints
110 - 125VAC Replace Module1 2
3 4 110 - 125VAC Replace Module
7 8
AC Volts
Gas ControlUnit
30 VAC Replace Module
RED
BLUE
WHITE
WHITE
YELLOW
BLUE
GREY
GREY
1
2
3
4
Ground
MasterControlModule
Test Points
6
RING OF FIRETEST Page #6
5
6
7
8
Replace Module 30 VAC WaterSafety4
AC Volts
5
6
BLACK
WHITE
INPUTSIDE Output Side
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
TESTING LIGHTING CONNECTOR
TESTING ROPE LIGHTING
Continuity: Good
No Continuity: Defective - Replace
7
RING OF FIRETEST Page #7
JumperWire
Continuity: Good
No Continuity: Defective - Replace
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
TESTING WATER PUMP
Continuity: Pump is Good
No Continuity: Defective - Replace Pump
Continuity Test
8
RING OF FIRETEST Page #8
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
PURGING AIR
¥ To purge air, loosen the inlet gas pressure port.• When gas is present, re-tighten.
Purge AirThrough InletGas PressureTap (3/16 Hex)
ON/OFFGas Cock
IncomingGas Port
9
RING OF FIRETEST Page #9
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
TESTING THEROBERTSHAW GAS VALVE
Electrical Connections
GroundConnections
Main Burner &Pilot Burner
Operator
Top of Operator
ContinuityTest of Pilot
Operator
ContinuityTest of Burner
Operator
NOTE: DO NOTCONDUCTCONTINUITYTEST USINGTHE AUDIBLETONE SCALE
M C P
11
RING OF FIRETEST Page #11
Note: Disconnectall wires fromgas valve
Pilot or Burner Coil Side Continuity TestContinuity - Component GoodNo Continuity - Component Defective
Replace Valve
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
TESTING GAS PRESSURE
INCOMING PRESSURE TESTING1. Turn off gas to Ring of Fire2. Remove inward pressure plug (3/16” Hex)3. Screw barbed adapter into pressure port4. Zero out pressure gauge5. Slip hose over barbed connector6. Turn on gas, turn on fountain and flame7. Read pressure8. Turn fountain off, turn gas off9. Disconnect hose10. Remove barbed connector and replace hex plug
Inlet GasPressure Tap(3/16 Hex)
ON/OFF Gas Cock Incoming Gas Port
ROF IncomingGas Pressur e
NG = 7 W.C.
LP = 13 W.C. If incoming gas pressure is incorrect,•check for adequate pipe sizing and/or
•call your gas supplier.
11. Test for gas leak at replaced plug
12
RING OF FIRETEST Page #12
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
TESTING GAS PRESSURE
OUTGOING PRESSURE TESTING1. Turn off gas to Ring of Fire2. Remove outward pressure plug (3/16” Hex)3. Screw barbed adapter into pressure port4. Zero out pressure gauge5. Slip hose over barbed connector6. Turn on gas, turn on fountain flame7. Read pressure8. Turn fountain off, turn gas off9. Disconnect hose10. Remove barbed connector and replace hex plug
ROF OutgoingGas Pressur e
NG = 3.5 W.C.
LP = 11 W.C.Gas Outlet ToMain Burner
Reversible (NG & LPGas) Regulator Body
Burner Outgoing GasPressure Tap (3/16 Hex)
Pilot Outlet toPilot Burner
•
11. Test for gas leak at replaced plug
13
RING OF FIRETEST Page #13
Copyright ' 10/27/04 Travis Industries, Inc.
TESTING ROF COMPONENTS
Flame Rectification
Proper FlameElectrode ContactFlame completelyimmerses electrode tip
Results in good flamerectification keeping the ROF
Improper FlameElectrode ContactFlame lifts up and is too faraway from electrode tip
Results in no flame rectificationshutting down the ROF
Improper FlameElectrode ContactFlame is too small to reachelectrode tip
Results in no flame rectificationshutting down the ROF
14
RING OF FIRETEST Page #14