    Building Services - I Electrical Service Appraisal

    Table of Contents About the project:.................. ............. ............ .............. ............. ............. ............. ............. .. 2

    S.L NO . ............................................................................................................................. 3

    Expected maximum demand ............................................................................................. 7

    Transformer selection ........................................................................................................ 8

    Generator selection ........................................................................................................... 9

    Material specifications ....................................................................................................... 9

    Observation and Recommendations ............ ............. ............. .............. ............ ............. ... 10

    Annexures ............ ............. ............. ............. ............. ............. ............. ............. .............. ...... 11

  • 8/12/2019 Electrical Services Appraisal -Group 6

    3/14

    Building Services - I Electrical Service Appraisal

    About the project:

    This housing project, Spire Woods is being developed by Spire World at Sector 103,

    Gurgaon. It is located on the upcoming Dwarka - Gurgaon Expressway connecting WestDelhi to Gurgaon. 620 dwelling units are accommodated within 12 Towers (T1-T12) in theComplex,having 3 BHK and 2 BHK units as well as penthouses. The sizes of theapartments vary between 1460 sq.ft. to 2208 sq.ft. In addition to this, there is a ClubBuilding and E.W.S. Accommodation consisting of 110 dwelling units. There is a commondouble basement for car parking (in addition to surface parking) and services.

    The Complex also has amenities such as a swimming pool, a gym, a sports complex, a

    sports club, a media room, meditation centers, restaurants, etc.

  • 8/12/2019 Electrical Services Appraisal -Group 6

    4/14

    Building Services - I Electrical Service Appraisal

    S.L NO . Particulars Area (in m 2)

    1. Total Plot Area

    46,538.775

    (11.5 acres)

    2. Built-Up Area 1,43,664.68

    3. Permissible F.A.R. (@ 1.75) 81,442.856

    4. Proposed F.A.R. (@ 1.732) 80,629.365

    5. Permissible Commercial Area (@ 0.5%) 232.693

    6. Proposed Commercial Area 214.875

    7. Permissible Ground coverage (@ 35%) 16,288.571

    8. Proposed Ground Coverage (@ 17.52%) 8,152.853

    9. Basement Area 45,976

    10. Stilt Area 803

    11. Landscape Area (@ 34.5%) 16,050

    12 H i h f ll b ildi 44 975

  • 8/12/2019 Electrical Services Appraisal -Group 6

    5/14

    Building Services - I Electrical Service Appraisal

  • 8/12/2019 Electrical Services Appraisal -Group 6

    6/14

    Building Services - I Electrical Service Appraisal

    Fig 3: Electrical Layout at site level

  • 8/12/2019 Electrical Services Appraisal -Group 6

    7/14

    Building Services - I Electrical Service Appraisal

    Fig 5: Typical Location of Electrical and LV Shafts

  • 8/12/2019 Electrical Services Appraisal -Group 6

    8/14

    Building Services - I Electrical Service Appraisal

    Expected maximum demand

    Load perUnit(kW)

    TotalNo. ofUnits

    TotalLoad

    (kW)

    DiversityFactor

    Expected Max.Demand

    Reference

    A) APARTMENTS

    Tower - T1, T8, T9, T11

    T& T12

    PENTHOUSE

    Tower T2 & T3

    PENTHOUSE

    Tower T4

    PENTHOUSE

    Tower T5, T6 & T7

    PENTHOUSE

    T T10

    7

    9

    9

    11

    10

    12

    10

    12

    260

    20

    104

    8

    36

    4

    156

    12

    1820

    180

    936

    88

    360

    48

    1560

    144

    0.6

    0.6

    0.6

    0.6

    0.6

    0.6

    0.6

    0.6

    1092

    108

    562

    53

    216

    29

    936

    86

    Table : A

    Table : B

    Table : C

    Table : D

    Table : E

    Table : F

    Table : E

    Table : F

  • 8/12/2019 Electrical Services Appraisal -Group 6

    9/14

    Building Services - I Electrical Service Appraisal

    C) BASEMENT

    Lighting

    Ventilation

    Drainage pumps

    52

    235

    20

    0.7

    -

    -

    36

    235

    20

    Table : J

    Table : J

    Table : J

    D) CLUB BUILDING

    750 Sq.m

    95 0.7 67 Table : K

    E) UTILITIES &EXTERNAL SERVICES

    150 0.6 90 Table : L

    F) COMMERCIAL 232Sq.Meter

    @100W/Sq.m

    23 0.7 16

    TOTAL 3874

    Applying and overall diversity factor of 0.70

    The expected max. Demand of the Complex = 3874 x 0.70

    = 2712 kW

  • 8/12/2019 Electrical Services Appraisal -Group 6

    10/14

    Building Services - I Electrical Service Appraisal

    Generator selection

    Being a prestigious project it is proposed to provide 100% power back up.

    Expected maximum demand = 2712 kW

    Load requirement in kVA at 0.8 p. f. = 2712 / 0.8 = 3390 kVA

    Considering up to 90% loading of rated D.G. set capacity, the required installed capacity ofD.G. sets required = 3390 / 0.90 = 3766O kVA

    6 nos. of 600 kVA D.G. sets with weather and sound proof canopies may be selected.These gensets will be radiator cooled and will be installed outdoor with their exhaust pipesgoing above the top the nearest tower.

    However, as it is seen normally the standby power demand is less than the grid powerdemand in the residential colonies because of substantial tariff difference. Hence, it isproposed that only 4 nos. 600 KVA gensets shall be provided initially. However, provisionshall be made to add two more sets in future if the need arises.

    Material specifications

    ) f l k l d d l l d d

  • 8/12/2019 Electrical Services Appraisal -Group 6

    11/14

    Building Services - I Electrical Service Appraisal

    Observation and Recommendations

    Oil type transformers can be replaced by dry type transformers and placed in the firstbasement so that cabling work is reduced.

    HSD tank shall be located near the DG Room instead of the gate so that distance ofpiping work for the same may be provided .

    Restricted Access should be provided to the HSD Tank.

    The Electrical and LV Shafts may be provided separately instead of single asprovided in case of Tower 10

    Acoustic Cover shall be provided to the DG Sets.

    Power Back up should be provided to sewerage treatment plant and water treatmentPlant.