ELECTRICAL NOTES PV SYSTEM NOTES AGNES ......GROUND LUG LOCATED IN HOLE OF BALLAST TRAY SPECIFICALLY...

8
Site Location Map - NTS AGNES SCOTT OBSERVATORY - SOLAR 220 E Hancock St, Decatur, GA 30030 Roof-Mounted Installation 6kW N S E W ELECTRICAL NOTES PV SYSTEM NOTES ELECTRICAL REQUIREMENTS MATERIALS AND METHODS AS BUILT DRAWINGS VC MJ 10/24/14 220 E Hancock St, Decatur, GA 30030 PV01 NOTES, SCHEDULE & CALCULATIONS NTS A 02/02/2015 NUMBER PV01 PV02 PV03a PV04a SHEET NAME NOTES, SCHEDULE AND CALCULATIONS LAYOUT LAYOUT WITH WIRING - DC SINGLE-LINE DIAGRAM AND ELECTRICAL PLAN PV05 PRODUCT SPECIFICATION PV06 BLANK PV04b SIGNAGE DETAILS DRAWING LIST REVISION HISTORY REVISION NUMBER DESCRIPTION PV03b LAYOUT WITH WIRING - AC PV07 BLANK PV08 DETAILS NUMBER SHEET NAME DRAWING LIST (CONT) - FOR CONSTRUCTION A AS BUILT

Transcript of ELECTRICAL NOTES PV SYSTEM NOTES AGNES ......GROUND LUG LOCATED IN HOLE OF BALLAST TRAY SPECIFICALLY...

  • Site

    Location Map - NTS

    AGNES SCOTT OBSERVATORY - SOLAR

    220 E Hancock St, Decatur, GA 30030

    Roof-Mounted Installation

    6kW

    N

    S

    E

    W

    ELECTRICAL NOTESPV SYSTEM NOTES

    ELECTRICAL REQUIREMENTS

    MATERIALS AND METHODS

    AS BUILT

    DRAWINGS

    VC

    MJ

    10/24/14

    22

    0 E

    H

    an

    co

    ck S

    t, D

    eca

    tu

    r, G

    A 3

    00

    30

    PV01

    NOTES,

    SCHEDULE

    &

    CALCULATIONS

    NTS

    A 02/02/2015

    NUMBER

    PV01

    PV02

    PV03a

    PV04a

    SHEET NAME

    NOTES, SCHEDULE AND CALCULATIONS

    LAYOUT

    LAYOUT WITH WIRING - DC

    SINGLE-LINE DIAGRAM AND ELECTRICAL PLAN

    PV05 PRODUCT SPECIFICATION

    PV06 BLANK

    PV04b SIGNAGE DETAILS

    DRAWING LIST

    REVISION HISTORY

    REVISION

    NUMBER

    DESCRIPTION

    PV03b LAYOUT WITH WIRING - AC

    PV07 BLANK

    PV08 DETAILS

    NUMBER SHEET NAME

    DRAWING LIST (CONT)

    - FOR CONSTRUCTION

    A AS BUILT

  • 32'-5"

    OVERALL

    22'-0 5/8"

    PV ARRAY:

    24 RENESOLA

    250W MODULES

    ROOF ACCESS

    INVERTER AREA

    TELESCOPE

    EXISTING

    PANELBOARD

    EAST ROOF

    WEST ROOF

    60.09" TYP

    AS BUILT

    DRAWINGS

    VC

    MJ

    10/24/14

    22

    0 E

    H

    an

    co

    ck S

    t, D

    eca

    tu

    r, G

    A 3

    00

    30

    PV02

    LAYOUT

    NTS

    A 02/02/2015

    SYSTEM LAYOUT

    PLAN VIEW

    A

    NOTES:

    1. LOCATIONS OF DISCONNECTS AND EQUIPMENT ARE APPROXIMATE;

    THEY ARE SUBJECT TO ON-SITE REQUIREMENTS AND SHOWN HERE FOR

    VISUAL CLARITY.

    N

    S

    E

    W

    Project:

    AGNES SCOTT OBSERVATORY -

    SOLAR

    Address: 220 E Hancock St, Decatur, GA 30030

    System Size:

    6kW

    MODULE: Renesola 250W

    MODULE Qty:

    24

    Tilt:

    Azimuth:

    Mounting:

    Roof-Mounted

  • ROOF ACCESS

    TELESCOPE

    A1-1 A2-12

    A1-12

    A2-1

    AREA FOR INVERTERS

    SEE PV-03b/B

    EAST ROOF

    WEST ROOF

    SEE NOTE 1

    AS BUILT

    DRAWINGS

    VC

    MJ

    10/24/14

    22

    0 E

    H

    an

    co

    ck S

    t, D

    eca

    tu

    r, G

    A 3

    00

    30

    PV03a

    LAYOUT WITH

    WIRING - DC

    NTS

    A 02/02/2015

    LAYOUT WIRING - DCA

    N

    S

    E

    W

    NOTES:

    1. EMT CONDUIT SUPPORTED BY SLEEPERS

    LEGEND:

    DC HOME RUNS: STRINGS TO

    COMBINER BOXES

    DC STRINGS

  • ROOF ACCESS

    TELESCOPE

    EXISTING

    PANELBOARD

    SEE DETAIL C

    AREA FOR INVERTERS

    SEE PV-03b/B

    EAST ROOF

    WEST ROOF

    EXISTING PANELBOARD

    FROM INVERTER THROUGH

    BUILDING'S PENETRATION INTO

    EXISTING PANELBOARD WITH

    1" NM LIQUIDTIGHT

    A

    FROM MODULES' HOME RUNS

    TO INVERTERS IN ONE 1" EMT

    INVERTER

    FROM INVERTER TO EXISTING

    PANELBOARD IN 1" NM LIQUIDTIGHT

    THROUGH PENETRATION

    AS BUILT

    DRAWINGS

    VC

    MJ

    10/24/14

    22

    0 E

    H

    an

    co

    ck S

    t, D

    eca

    tu

    r, G

    A 3

    00

    30

    PV03b

    LAYOUT WITH

    WIRING - AC

    NTS

    A 02/02/2015

    EQUIPMENT MOUNTING - AC

    EXISTING PANELBOARD

    C

    LEGEND:

    RUN FROM INVERTER TO EXISTING

    PANELBOARD

    LAYOUT WIRING - ACA

    EQUIPMENT MOUNTING - AC

    INVERTER

    B

  • "TYPE A" ARRAY

    INVERTER A

    1 CONDUIT SCHEDULE

    MODULE WATTAGE 250W

    TOTAL NUMBER OF STRINGS IN PARALLEL 2

    NUMBER OF MODULES IN SERIES 12

    TOTAL NUMBER OF INVERTERS 1

    TOTAL NUMBER OF MODULES 24

    TOTAL SYSTEM POWER @ STC (DC)

    6kW

    SYSTEM SUMMARY

    TO UTILITY

    3 - TYP

    LEGEND:

    COMPONENT

    CONDUCTOR/ CONDUIT

    SIGN - SEE PV 04b

    #

    #

    #

    PV MODULE ARRAY "TYPE A" - 1 INVERTER TOTAL

    12 MODULES PER STRING

    2 STRINGS PER INVERTER

    250W MODULES

    1 2 12

    1 2 12

    STRING #1

    STRING #2

    TYP- 1

    EGC FROM RACKING AND MODULES

    TO INVERTER GROUNDING STUD

    ARRAY ON

    EAST ROOF

    WALL ON WEST ROOF

    FACING NORTH - OUTSIDE

    2b

    2a2 - TYP

    1 - TYP

    TO

    A

    C C

    OM

    BIN

    ER

    L1

    L2

    N

    G

    TYP - 3

    INVERTER A

    1 & 3

    2 2a

    NO. ITEM PART NO. DESCRIPTION QTY

    1 SOLAR MODULE JC250M-24/Bb RENESOLA 250W 24

    2a DC DISCONNECT

    SMA INTEGRAL

    DC DISCONNECT

    DC DISCONNECT; PART OF SMA INVERTER1

    2b INVERTER

    SMA SUNNYBOY

    SB 6000TL-US-12

    SMA 6KW - 1-PHASE INVERTER, 208V, NEMA 3R.1

    3

    EXISTING

    PANELBOARD

    AQF3301MBX

    NAME: "L2A", FED BY SWBD "SL"

    1

    4 BREAKERS TBD ONE 2-POLE 40A BREAKER 1

    COMPONENT SCHEDULE

    ID

    CONDUCTOR

    TYPE AND SIZE

    NUMBER OF

    CONDUCTORS

    NEUTRAL

    SIZE

    GROUND

    SIZE

    CONDUIT SIZE FROM TO

    MAX

    DISTANCE

    (FT)

    1

    #10 AWG

    PV WIRE CU

    4 - #6 CU

    FREE AIR , THEN ONE

    1" EMT CONDUIT

    MODULES

    SMA

    DISCONNECT

    52

    2*

    #8 AWG

    PV WIRE CU

    L1,L2,N &GND#8 CU #8 CU

    N/A INSIDE OF

    INVERTER

    SMA

    DISCONNECT

    INVERTER 2

    3 #8 THWN-2 CU

    3-WIRE

    (2+N+GND)

    #8 CU #8 CU

    (1) 1" NM LIQUIDTIGHT

    INVERTER

    EXISTING

    PANELBOARD

    15

    4

    WALL ON WEST ROOF

    INSIDE BUILDING

    WALL ON WEST ROOF

    FACING NORTH - OUTSIDE

    EXISTING

    PANELBOARD

    3 4

    *PROVIDED BY OTHERS

    5 6

    AS BUILT

    DRAWINGS

    VC

    MJ

    10/24/14

    22

    0 E

    H

    an

    co

    ck S

    t, D

    eca

    tu

    r, G

    A 3

    00

    30

    PV04a

    SINGLE LINE

    NTS

    A 02/02/2015

  • EQUIPMENT NOTES:

    1. RED LABELS WITH WHITE LETTERS. "WARNING" SHALL BE 3/8" TALL.

    ALL OTHER LETTERS SHALL BE 1/4" TALL.

    INTERACTIVE POWER FLOWING

    THROUGH THIS PANEL

    4. LOAD CENTER (AC COMBINERS #1) PER NEC 690.17 AND 690.54

    QUANTITY: 1

    INVERTER A

    WARNING!

    BREAKER 26 & 28:

    INVERTER OUTPUT CONNECTION

    DO NOT RELOCATE THIS OVERCURRENT

    DEVICE

    5. AT EXISTING PANELBOARD PER SECTION 690.54, AND 705.12(D)(7)

    WARNING!

    DISCONNECT IS ENERGIZED FROM TWO

    SOURCES: SOLAR SYSTEM AND UTILITY GRID

    THE DISCONNECTING MEANS FOR THIS PHOTOVOLTAIC

    SYSTEM IS AT THE SOLAR BREAKER LOCATED AT

    PANELBOARD "L2A" ON THE OTHER SIDE OF THE WALL OF

    THIS INVERTER

    3 AT INVERTER PER SECTION 690.56(B) AND 690.54

    QUANTITY: 1

    BREAKERS 26 & 28 DISCONNECT THE PHOTOVOLTAIC

    SYSTEM LOCATED ON THE ROOF OF THIS OBSERVATORY

    ROOF; THE DC SOLAR POWER DISCONNECT IS LOCATED

    AT INVERTER "A" ON THE OTHER SIDE OF THIS WALL -

    OUTSIDE.

    6. AT BREAKER PER SECTION 690.56(B)

    MAX AC OUTPUT CURRENT = 25 A

    NOMINAL AC VOLTAGE = 208 V

    THIS PHOTOVOLTAIC SYSTEM INTERCONNECTS TO THE

    ELECTRICAL GRID AT THE "L2A" EXISTING PANELBOARD.

    WARNING!

    ELECTRICAL SHOCK HAZARD

    SOLAR PHOTOVOLTAIC COMBINING PANELBOARD

    PANELBOARD CONTAINS BACKFED CIRCUIT BREAKERS

    THAT MAY BE ENERGIZED IN THE OPEN POSITION

    DO NOT CONNECT ADDITIONAL LOADS !

    WARNING!

    DC VOLTAGE IS ALWAYS PRESENT WHEN

    MODULES ARE EXPOSED TO SUNLIGHT

    MAXIMUM POWER-POINT CURRENT (Imp): 16.62A

    MAXIMUM POWER-POINT VOLTAGE (Vmp): 361.2V

    MAXIMUM SYSTEM VOLTAGE (Voc @Tmin): 497.3V

    NEC MAXIMUM CURRENT (Isc x 1.25): 22.08A

    WARNING

    ELECTRIC SHOCK HAZARD

    DO NOT TOUCH TERMINALS. TERMINALS ON

    BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED

    IN THE OPEN POSITION

    2a LABEL PER SECTION 690.17(4), 690.53.

    DC COMBINER A

    TOTAL QUANTITY: 1

    1 FOR INVERTER "A" .

    1 TOTAL

    MAX AC OUTPUT CURRENT = 25 A

    NOMINAL AC VOLTAGE = 208 V

    DC COMBINER A

    2 FOR DC COMBINER "A".

    1 TOTAL

    AS BUILT

    DRAWINGS

    VC

    MJ

    10/24/14

    22

    0 E

    H

    an

    co

    ck S

    t, D

    eca

    tu

    r, G

    A 3

    00

    30

    PV04b

    SIGNAGE

    DETAILS

    NTS

    A 02/02/2015

  • AS BUILT

    DRAWINGS

    VC

    MJ

    10/24/14

    22

    0 E

    H

    an

    co

    ck S

    t, D

    eca

    tu

    r, G

    A 3

    00

    30

    PV05

    PRODUCT

    SPECIFICATIONS

    NTS

    A 02/02/2015

  • NEGATIVE

    CONDUCTOR

    TOCOMBINER BOX

    POSITIVE

    CONDUCTOR

    TOCOMBINER BOX

    MODULES CONNECTED IN SERIES:

    MALE TO FEMALE

    SEE NOTE 3

    AS BUILT

    DRAWINGS

    VC

    MJ

    10/24/14

    22

    0 E

    H

    an

    co

    ck S

    t, D

    eca

    tu

    r, G

    A 3

    00

    30

    PV08

    DETAILS

    NTS

    A 02/02/2015

    NOTES:

    1. READ PANEL CLAW'S POLAR BEAR III SYSTEM ASSEMBLY INSTRUCTIONS

    AND PANEL CLAW'S DRAWINGS FOR THE MANUFACTURER'S

    INSTRUCTIONS ON RACKING AND GROUNDING. SEE RACKING

    EQUIPMENT GROUNDING LAYOUT ON PV03a.

    2. GROUND LUG LOCATED IN HOLE OF BALLAST TRAY SPECIFICALLY

    DESIGNATED FOR GROUNDING AND MARKED "GND".

    3. MODULES SHALL BE WIRED FROM POSITIVE TO NEGATIVE IN SERIES, IN

    THE ORDER DEPICTED ON PV03a, AND WITH THE APPROPRIATE WIRING

    METHODS AS STATED ON NEC 690 SECTION IV.

    GROUNDING

    RACKING - SEE NOTE 1

    A MODULE WIRING

    SERIES WIRING METHOD

    B

    SEE NOTE 2