Electrical Installation Practice 2. LSEGG304A 9080D. Protection Devices Fuses. Content. Operating principles of fuses Inverse time/current characteristic of fuses Fuses used as fault current limiters Fuses and fault loop impedance Fuse selection. Circuit Protection. What is it’s Job?. - PowerPoint PPT Presentation

Transcript of Electrical Installation Practice 2

Page 1: Electrical Installation Practice 2
Page 2: Electrical Installation Practice 2
Page 3: Electrical Installation Practice 2

ContentContent• Operating principles of fuses• Inverse time/current characteristic of

fuses• Fuses used as fault current limiters• Fuses and fault loop impedance• Fuse selection

Page 4: Electrical Installation Practice 2

Circuit ProtectionCircuit ProtectionWhat is it’s Job?

• Protect circuit wiring against overheating & deterioration due to overloads

• Quickly interrupt a short circuit so:• Limit the energy let through

• Reduce the touch potentials rising too high

Page 5: Electrical Installation Practice 2

Circuit ProtectionCircuit Protection

• Fuses• Circuit breakers

Next lesson

Page 6: Electrical Installation Practice 2

FusesFuses•Two Basic types

• Rewireable

Page 7: Electrical Installation Practice 2

FusesFuses•Two Basic types

• Rewireable

• Sealed • Gas filled

• Silica filled

Glass automotive fuses

HRC

Page 8: Electrical Installation Practice 2

HRC FusesHRC Fuses(High Rupture Capacity)(High Rupture Capacity)

Page 9: Electrical Installation Practice 2

FusesFuses•Two Basic types

•Still provides the greatest fault handling capacity for the size

• Rewireable

• Sealed • Gas filled

• Silica filled

Glass automotive fuses

HRC

Page 10: Electrical Installation Practice 2

How Does A Fuse How Does A Fuse Work?Work?•As current increases, fuse element heats up

•Becomes liquid, and falls away.•An arc forms between the ends.•The ends melt away, the arc becomes

longer.•Eventually the gap is so great that it is too

long for the arc. Current stops flowing

H = I2t

Page 11: Electrical Installation Practice 2

DefinitionsDefinitions•Current Rating•Voltage Rating•Time-Current characteristics

The maximum current that a fuse can carry continuously without deterioration

The maximum voltage that the fuse can safely operate.

Page 12: Electrical Installation Practice 2

Time-Current Time-Current characteristicscharacteristics

Logarithmic Scale

10 Amp Fuse

Current

Tri

p t

ime

20A

100 Sec

0.6 Sec

0.1 Sec

30A 40A

Page 13: Electrical Installation Practice 2

Time-Current Time-Current characteristicscharacteristics

CABLEInsulation

Damage toCABLE

Insulation

Page 14: Electrical Installation Practice 2
Page 15: Electrical Installation Practice 2

DefinitionsDefinitions•Current Rating•Voltage Rating•Time-Current characteristics•Pre-arcing time

Page 16: Electrical Installation Practice 2

Peak Prospective Current

RMS Prospective Current

Current that fuse blows

Page 17: Electrical Installation Practice 2

Pre-arcing time

Current that fuse blows

Page 18: Electrical Installation Practice 2

DefinitionsDefinitions•Current Rating•Voltage Rating•Time-Current characteristics•Pre-arcing time•Arcing time

Page 19: Electrical Installation Practice 2

Arcing time

Current that fuse blows

Page 20: Electrical Installation Practice 2

DefinitionsDefinitions•Current Rating•Voltage Rating•Time-Current characteristics•Pre-arcing time•Arcing time•Minimum fusing current

Page 21: Electrical Installation Practice 2

Minimum fusing current

The minimum current that the fuse element will start to melt

Page 22: Electrical Installation Practice 2

DefinitionsDefinitions•Current Rating•Voltage Rating•Time-Current characteristics•Pre-arcing time•Arcing time•Minimum fusing current•Fusing Factor Min fusing current=

Current rating

Typical values are in the order of 1.5 to 2

Page 23: Electrical Installation Practice 2

DefinitionsDefinitions•Current Rating•Voltage Rating•Time-Current characteristics•Pre-arcing time•Arcing time•Minimum fusing current•Fusing Factor•Total operating time

Page 24: Electrical Installation Practice 2

Total operating time

Current that fuse blows

Page 25: Electrical Installation Practice 2

DefinitionsDefinitions•Current Rating•Voltage Rating•Time-Current characteristics•Pre-arcing time•Arcing time•Minimum fusing current•Fusing Factor•Total operating time•Cut-off current

Page 26: Electrical Installation Practice 2

Current that fuse blows

Cut off current

Shaded area = I2 t OR Energy let through

Page 27: Electrical Installation Practice 2

ConstructiConstructiononCopper Tangs

Tangs Riveted & Soldered to end-caps

End-capsSealing Disk

Ceramic Tube

Graded Sand

Fuse elements

Page 28: Electrical Installation Practice 2

With multiple arc points the time to blow is faster

Standard HRC Fuse Element

Page 29: Electrical Installation Practice 2

Fusible Elements

Silverbond Rolled Element Standard Element

Copper sections that blow in short circuit conditions

Silver/Tin section blows in overload conditions

Page 30: Electrical Installation Practice 2

Tin

Silver

With overload currents the tin & silver combine to produce an alloy that melts at 230oC not at Silver’s melting point of 9600C

Also known as the “M” effect

Eutechnic Alloy

When heated changes from solid to liquid without going though the plastic region

Page 31: Electrical Installation Practice 2

HRC HV Fuse Types

•Distribution/Transformer Transformer inrush currents

(high current for short period of time) Overload protection Operate in reasonable period of time with regard to

secondary short circuit

Motor circuit Fast operation for short circuits High inrush for long period of time

Page 32: Electrical Installation Practice 2

HRC Low Voltage

•High breaking capacity & energy limitation.

•Restriction of electro-mechanical stress on cables and busbars

•Reliable short circuit and back-up protection.

•Accurate discrimination.•Low over-current protection.•Non-deterioration due to no moving parts

Page 33: Electrical Installation Practice 2

HRC Semiconductor Fuses

•Electronics are more sensitive than motors or cables

•Energy let through has to be a lot less.•Must be very fast & accurate in operation•Fusing elements are made of all silver, &

thinner than standard

Page 34: Electrical Installation Practice 2

Matching Protection to a Matching Protection to a CableCableA cable’s current carrying capacity must be equal or larger than the load

current

Load Current

Circuit protection must be equal to or smaller than the cable’s current carrying capacity

IB ≤ IN ≤ IZ

≤ Protection ≤ Cable Current carrying capacity

AS/NZS 3000:2007Clause 2.5.3.1

Page 76

Page 35: Electrical Installation Practice 2

Load Current

10 Amps

Maximum Current

Cable can supply

CurrentRating of

Protection

15 Amps

20 Amps

XCable will be

damaged

IB IN IZ

Page 36: Electrical Installation Practice 2

Load Current

10 Amps

Maximum Current

Cable can supply

CurrentRating of

Protection

15 Amps

20 Amps

XCable will be

damaged

IB IN IZ

Protection will nuisance trip

Page 37: Electrical Installation Practice 2

Matching Protection to a Matching Protection to a CableCable

But the protection must match the cable

I2 ≤ 1.45 ≤ IZ

Tripping current for protective device

AS/NZS 3000:2007Clause 2.5.3.1

Page 76

Constant for circuit breakers

Cable current carrying capacity

For circuit breakers

Page 38: Electrical Installation Practice 2

Matching Protection to a Matching Protection to a CableCable

But the protection must match the cable

I2 ≤ 1.45 ≤ IZ

Tripping current for protective device

AS/NZS 3000:2007Clause 2.5.3.1

Page 76

Constant for fuses

Cable current carrying capacity

I2 ≤ 1.60 ≤ IZ

For Fuses

Page 39: Electrical Installation Practice 2

HoweverHoweverA cable can withstand a overload current of 1.45 x it’s rating before the

insulation is damaged

10 Amps

Maximum Current

Cable can supply

IZ

A1045.114.5 Amps

14.5 Amps

Page 40: Electrical Installation Practice 2

A Circuit breaker’s trip curve is matched to a cable’s curve

10 Amps

Maximum Current

Cable can supply

IZ A1045.1 14.5 Amps

14.5 Amps

Tripping current is 1.45 x rated current

CurrentRating of

Protection

IN

Circuit BreakersCircuit Breakers

Page 41: Electrical Installation Practice 2

A Fuse’s trip curve is different to a cable’s curve

10 Amps

Maximum Current

Cable can supply

IZ

A106.116 Amps

14.5 Amps

CurrentRating of

Protection

IN

FusesFusesTripping current is 1.6 x rated current

16 Amps

Cable will be damaged

X

Page 42: Electrical Installation Practice 2

10 Amps

Maximum Current

Cable can supply

IZ

6.1

5.149 Amps

14.5 Amps

CurrentRating of

Protection

IN

FusesFuses16 Amps

1.6

Page 43: Electrical Installation Practice 2

10 Amps

Maximum Current

Cable can supply

IZ 9.010 9 Amps

14.5 Amps

CurrentRating of

Protection

IN

FusesFuses16 Amps

0.9

Page 44: Electrical Installation Practice 2

DiscriminationDiscriminationA fault in one circuit should not affect other circuits

AS/NZS 3000:2007Clause 2.5.6

Page 90

PoorPoor

Page 45: Electrical Installation Practice 2

DiscriminationDiscriminationA fault in one circuit should not affect other circuits

Page 46: Electrical Installation Practice 2

DiscriminationDiscriminationA fault in one circuit should not affect other circuits

F1

F2

For times greater than 0.01 seconds

F1 = F2 x 1.6

AS/NZS 3000:2007Clause 2.5.7.2.3(b)

Page 92

40A

64A

Page 47: Electrical Installation Practice 2

DiscriminationDiscriminationA fault in one circuit should not affect other circuits

F1

F2

For times greater than 0.01 seconds

F1 = F2 x 1.6

AS/NZS 3000:2007Clause 2.5.7.2.3(b)

Page 92

For times less than 0.01 seconds

F1 = F2 x 2

40A

80A

(I2t) F1 = (I2t) F2 x 2

Page 48: Electrical Installation Practice 2

F1F2

F1 = 2 x F2

Page 49: Electrical Installation Practice 2

Figure 13.15(b) Time–current characteristic curves for 2 A to 800 A general fuse links