SCHEDULE OF LOADS AND COMPUTATION
CKT NAME KVA KW HP VOLTSLINE CURRENT
WIRE SIZEAB BC CA 3Ø
12345678
TOTAL 0 0 0 0
CKT NO.
CIRCUIT BREAKER
STANDARD 3 PHASE, 60HZ MOTOR DATA, 230VAC
HP KW Volts
1/4 0.2 1.1 2.0 14 15AT 3A 230VAC1/3 0.3 1.5 2.0 14 15AT 3A 230VAC1/2 0.4 2 2.0 14 15AT 6A 230VAC3/4 0.60 2.8 2.0 14 15AT 10A 230VAC1 0.75 3.6 2.0 14 15AT 10A 230VAC
1.5 1.1 5.2 2.0 14 15AT 15A 230VAC2 1.5 6.8 2.0 14 15AT 20A 230VAC3 2.5 9.6 2.0 14 20AT 25A 230VAC5 4 15.2 3.5 12 30AT 40A 230VAC
7.5 5.5 22 5.5 10 50AT 60A 230VAC10 7.5 28 8.0 8 50AT 70A 230VAC15 11 42 14 6 70AT 100A 230VAC20 15 54 14 6 100AT 150A 230VAC25 19 68 22 4 125AT 175A 230VAC30 22 80 30 2 125AT 200A 230VAC40 30 104 50 0 175AT 300A 230VAC50 37 130 60 00 200AT 350A 230VAC60 45 154 80 000 225AT 400A 230VAC75 55 192 125 250MCM 300AT 500A 230VAC100 75 249 200 400MCM 400AT 600A 230VAC
SIMPLIFIED MOTOR CIRCUIT CALCULATIONNOTES :
respectively
General Formula :
Full Load = HP ( 746 watts )K ( volts ) ( P.F. ) ( Eff. )
K = √3 for 3 phase , 1 for single phase P.F. = 0.80 to 0.85 Eff. = 0.80 to 0.90
CB Amp trip and fuse sizes are approximate selections for general installations
Full load current
WIRE SIZE in sq.mm
WIRE SIZE in AWG
CB, thermal - magnetic trip, amps
Safety switch, single
element
Motors 200 and 208 Volts increase, indicated full load current value by 15 and 10 %
Use FULL-VOLTAGE starters for motors up to 7.5 HP, reduced - voltage types for higherratings, that is, WYE - DELTA up to 150 HP and Auto - Transformer for bigger units
STANDARD 3 PHASE, 60HZ MOTOR DATA, 460VAC
HP KW Volts
1/4 0.2 0.6 2.0 14 15AT 3A 460VAC1/3 0.3 0.8 2.0 14 15AT 3A 460VAC1/2 0.4 1 2.0 14 15AT 3A 460VAC3/4 0.60 1.4 2.0 14 15AT 3A 460VAC1 0.75 1.8 2.0 14 15AT 6A 460VAC
1.5 1.1 2.6 2.0 14 15AT 10A 460VAC2 1.5 3.4 2.0 14 15AT 10A 460VAC3 2.5 4.8 2.0 14 15AT 15A 460VAC5 4 7.6 2.0 14 15AT 20A 460VAC
7.5 5.5 11 2.0 14 20AT 30A 460VAC10 7.5 14 3.5 12 30AT 35A 460VAC15 11 21 5.5 10 40AT 50A 460VAC20 15 27 8.0 8 50AT 70A 460VAC25 19 34 8.0 8 50AT 80A 460VAC30 22 40 14 6 70AT 100A 460VAC40 30 52 14 6 100AT 150A 460VAC50 37 65 22 4 125AT 175A 460VAC60 45 77 30 2 125AT 200A 460VAC75 55 96 38 1 150AT 250A 460VAC100 75 124 60 00 200AT 350A 460VAC
SIMPLIFIED MOTOR CIRCUIT CALCULATIONNOTES :
respectively
General Formula :
Full Load = HP ( 746 watts )K ( volts ) ( P.F. ) ( Eff. )
K = √3 for 3 phase , 1 for single phase P.F. = 0.80 to 0.85 Eff. = 0.80 to 0.90
CB Amp trip and fuse sizes are approximate selections for general installations
Full laod current
WIRE SIZE in sq.mm
WIRE SIZE in AWG
CB, thermal - magnetic trip, amps
Safety switch, single
element
Motors 200 and 208 Volts increase, indicated full load current value by 15 and 10 %
Use FULL-VOLTAGE starters for motors up to 7.5 HP, reduced - voltage types for higherratings, that is, WYE - DELTA up to 150 HP and Auto - Transformer for bigger units
STANDARD SINGLE PHASE, 60HZ MOTOR DATA, 230VAC
HP KW Volts
1/6 0.1 2.2 2.0 14 15AT 6A 230VAC1/4 0.2 2.9 2.0 14 15AT 6A 230VAC1/3 0.3 3.6 2.0 14 15AT 10A 230VAC1/2 0.4 4.9 2.0 14 15AT 15A 230VAC3/4 0.60 6.9 2.0 14 15AT 20A 230VAC1 0.75 8 2.0 14 15AT 20A 230VAC
1.5 1.1 10 2.0 14 20AT 35A 230VAC2 1.5 12 2.0 14 30AT 40A 230VAC3 2.5 17 5.5 10 40AT 45A 230VAC5 4 28 8.0 8 50AT 70A 230VAC
7.5 5.5 40 8.0 8 70AT 100A 230VAC
STANDARD SINGLE PHASE, 60HZ MOTOR DATA, 115VAC
HP KW Volts
1/6 0.1 4.4 2.0 14 15AT 15A 115VAC1/4 0.2 5.8 2.0 14 15AT 15A 115VAC1/3 0.3 7.2 2.0 14 15AT 20A 115VAC1/2 0.4 9.8 2.0 14 15AT 25A 115VAC3/4 0.60 13.8 3.5 12 20AT 35A 115VAC1 0.75 16 3.5 12 30AT 40A 115VAC
1.5 1.1 20 3.5 12 40AT 50A 115VAC2 1.5 24 5.5 10 50AT 60A 115VAC3 2.5 34 8.0 8 70AT 95A 115VAC5 4 56 22 4 100AT 150A 115VAC
7.5 5.5 80 30 2 125AT 200A 115VAC
Full laod current
WIRE SIZE in sq.mm
WIRE SIZE in AWG
CB, thermal - magnetic trip, amps
Safety switch, single
eleement
Full laod current
WIRE SIZE in sq.mm
WIRE SIZE in AWG
CB, thermal - magnetic trip, amps
Safety switch, single
eleement
TABLE OF AMPACITY
PEC Table 3.10.1.16
TABLE 1Size of wire Ampacity
AWG mm² MCM THW @ 75°C14 2.0 4 1512 3.5 7 2010 5.5 11 308 8.0 16 456 14.0 28 654 22.0 44 852 30.0 60 1101 38.0 76 1250 50.0 100 14500 60.0 120 160
000 80.0 160 1950000 100.0 200 220
125 250 255150 300 280175 350200 400 330250 500 375300 600325 650 435380 750400 800 485500 1,000 540
AWG American Wire Gaugemm² Square millimeterMCM Area in circular mills
NOTE:Square millimeter to MCM multiply by 2MCM to Square millimeter divided by 2
TABLE II TABLE IIIFull Load Current in Amperes Full Load Current, Three Phase AC Motors ,
Single Phase AC Motors Induction Type, Squirrel Cage , Wound RotorHP 115V 230V HP 115V 230V 460V
0.167 4.4 2.2 0.5 4 2 10.25 5.8 2.9 0.75 5.6 2.8 1.4
0.333 7.2 3.6 1 7.2 3.6 1.80.5 9.8 4.9 1.5 10.4 5.2 2.6
0.75 13.8 6.9 2 13.6 6.8 3.41 16 8 3 9.6 4.8
1.5 20 10 5 15.2 7.62 24 12 7.5 22 113 34 17 10 28 145 56 28 15 42 21
7.5 80 40 20 54 2710 100 50 25 68 34
30 80 4040 104 5250 130 6560 154 7775 192 96100 248 124125 312 156150 360 180
CB Standard Ampere Ratings
15 50 125 35020 60 150 40025 70 175 45030 80 200 50035 90 225 60040 100 250 70045 110 300 800
OHMS LAW where:
E = I x R R = E E = volts ( V )I I = ampere ( A )
I = ER
COVERSIONS : 1 TON = 12,000 BTU 1HP = 746 watts1 TON = 4.7 HP 1 KW = 1,000 watts1 HP = 2,545 BTU/hr 1 KW = 1.34HP1 KW = 3,412 BTU/hr KVA to KW ( x 0.8 )
KW to KVA ( / 0.8 )
STANDARD MAGNETIC STARTERS DATA, NON-REVERSING, 3P, 60Hz
220VAC 440VACHP KW HP KW0.5 0.4 1.5 1.1 2.5A 1.7-2.5A Stop-Start1 0.75 2 1.5 3.6A 2.8-4.4A Stop-Start2 1.5 3 2.2 6.6A 5.2-8A Stop-Start3 2.5 5 4 9.0A 7-11A Stop-Start4 2.7 7.5 5.5 12.5A 9-16A Stop-Start5 4 10 7.5 15A 12-18A Stop-Start
7.5 5.5 15 11 22A 18-26A Stop-Start10 7.5 20 15 29A 24-34A Stop-Start15 11 30 22 42A 34-50A Stop-Start20 15 40 30 54A 43-65A Stop-Start25 19 50 37 67A 54-80A Stop-Start30 22 60 45 82A 65-93A Stop-Start40 30 75 55 105A 85-125A Stop-Start50 37 100 75 125A 100-150A Stop-Start75 55 120 90 125A 100-150A Stop-Start
150 110 180A 140-220A Stop-Start100 75 200 150 250A 200-300A (3E) Stop-Start150 110 300 200 330A 260-400A (3E) Stop-Start200 150 400 300 500A 400-600A (3E) Stop-Start
STANDARD MAGNETIC STARTERS DATA, REVERSE-FORWARD, DUAL SPEED (LOW AND HIGH), 3P, 60Hz
220VAC 440VACHP KW HP KW0.5 0.4 1 0.75 2.1A 1.7-2.5A S / R / F1 0.75 2 1.5 3.6A 2.8-4.4A S / R / F2 1.5 3 2.2 6.6A 5.2-8A S / R / F3 2.5 5 4 9.0A 7-11A S / R / F4 2.7 7.5 5.5 12.5A 9-16A S / R / F5 4 10 7.5 15A 12-18A S / R / F
R = ohm ( Ω )
RATED AMPERE
ADJ.OVERLOAD / HEATER RATING
PUSH BUTTON
RATED AMPERE
ADJ.OVERLOAD / HEATER RATING
PUSH BUTTON
7.5 5.5 15 11 22A 18-26A S / R / F10 7.5 20 15 29A 24-34A S / R / F15 11 30 22 42A 34-50A S / R / F20 15 40 30 54A 43-65A S / R / F25 19 50 37 67A 54-80A S / R / F30 22 60 45 82A 65-93A S / R / F40 30 75 55 105A 85-125A S / R / F50 37 100 75 125A 100-150A S / R / F75 55 120 90 125A 100-150A S / R / F
150 110 180A 140-220A S / R / F100 75 200 150 250A 200-300A (3E) S / R / F150 110 300 200 330A 260-400A (3E) S / R / F200 150 400 300 500A 400-600A (3E) S / R / F
WYE-DELTA REDUCE VOLTAGE MAGNETIC STARTERS , 3P, 60HzWITH ADJ. OVERLOAD RELAY AND ADJ. TIMER AND AUTO-
TRANSFORMER
220VAC 440VACHP KW HP KW
7.5 5.5 12.5A 9-16A Stop-Start10 7.5 15A 12-18A Stop-Start
7.5 5.5 15 11 22A 18-26A Stop-Start10 7.5 20 15 29A 24-34A Stop-Start15 11 30 22 42A 34-50A Stop-Start20 15 40 30 54A 43-65A Stop-Start25 19 50 37 67A 54-80A Stop-Start30 22 60 45 82A 65-93A Stop-Start40 30 75 55 105A 85-125A Stop-Start50 37 100 75 125A 100-150A Stop-Start75 55 120 90 125A 100-150A Stop-Start
150 110 180A 140-220A Stop-Start100 75 200 150 250A 200-300A (3E) Stop-Start150 110 300 200 330A 260-400A (3E) Stop-Start200 150 400 300 500A 400-600A (3E) Stop-Start
SIMPLIFIED MOTOR CIRCUIT CALCULATIONNOTES :
respectively
RATED AMPERE
ADJ.OVERLOAD / HEATER RATING
PUSH BUTTON
Motors 200 and 208 Volts increase, indicated full load current value by 15 and 10 %
Use FULL-VOLTAGE starters for motors up to 7.5 HP, reduced - voltage types for higherratings, that is, WYE - DELTA up to 150 HP and Auto - Transformer for bigger units
AIR COMPRESSOR MOTOR DATA @ 240VAC
Electrical power cable, AWG # 10 - 3 conductorMolded case circuit breaker, 240VAC,50AT, 3 Pole, 60Hz
Electrical power cable, AWG # 8 - 3 conductorMolded case circuit breaker, 240VAC,50AT, 3 Pole, 60Hz
Electrical power cable, AWG # 6 - 3 conductorMolded case circuit breaker, 240VAC,70AT, 3 Pole, 60Hz
AIR COMPRESSOR MOTOR DATA @ 440VAC
Electrical power cable, AWG # 14 - 3 conductorMolded case circuit breaker, 440VAC,20AT, 3 Pole, 60Hz
Magnetic contactor, wye - start, delta-run,7.5HP,220VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (18-26A), pilot lamps ( red and green) stop - start push
button with enclosure
Magnetic contactor, wye - start, delta-run, 10HP,220VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (24-34A), pilot lamps ( red and green) stop - start push
button with enclosure
Magnetic contactor, wye - start, delta-run, 15HP,220VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (34-50A), pilot lamps ( red and green) stop - start push
button with enclosure
Magnetic contactor, wye - start, delta-run,7.5HP,440VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (9-16A), pilot lamps ( red and green) stop - start push
button with enclosure
Electrical power cable, AWG # 12 - 3 conductorMolded case circuit breaker, 440VAC,30AT, 3 Pole, 60Hz
Electrical power cable, AWG # 10 - 3 conductorMolded case circuit breaker, 440VAC,40AT, 3 Pole, 60Hz
Magnetic contactor, wye - start, delta-run, 10HP,440VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (12-18A), pilot lamps ( red and green) stop - start push
button with enclosure
Magnetic contactor, wye - start, delta-run, 15HP,220VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (18-26A), pilot lamps ( red and green) stop - start push
button with enclosure
ELECTRICAL FORMULAS FOR DETERMINING AMPERES, HORSEPOWER, KILOWATTS AND KILOVOLTS-AMPERES
ALTERNATING CURRENT ( AC ) SINGLE PHASE THREE PHASE, 4 WIRES THREE PHASE
KILOWATTS
KVA
HP OUTPUT
I - Ampere HP - Horsepower % Eff - Percent EfficiencyE - Volts KVA - Kilovolt-ampereKW - Kilowatts PF - Power Factor
DESIRE DATA
DIRECT CURRENT
I x E x PF 1,000
I x E x 2 x PF 1,000
I x E x 1.73 x PF 1,000
I x E 1,000
I x E 1,000
I x E x 2 1,000
I x E x 1.73 1,000
I x E x % Eff x PF 746
I x E x % Eff x PF 746
I x E x 1.73 x % Eff x PF 746
I x E x % Eff 746
AMP WHEN HP KNOWN
HP x 746 E x % Eff x PF
KW x 1,000 2 x E x PF
KW x 1,000 1.73 x E x PF
HP x 746 E x % Eff
AMP WHEN KW KNOWN
KW x 1,000 E x PF
KW x 1,000 2 x E x PF
KW x 1,000 1.73 x E x PF
KW x 1,000 E
AMP WHEN KVA KNOWN
KVA x 1,000 E
KVA x 1,000 2 x E
KVA x 1,000 1.73 x E
GENERATOR DATA @ 440VAC
KILOWATTS KILOVOLT-AMPERES AMPERES WIRE SIZE
30 37.5 49
35 44 57
40 50 66
44 55 72
45 56.2 74
50 62.5 82
60 75 99
RATED VOLTAGE
440VAC / 3Phase / 60Hz
AWG #6 / 14mm² - 3C
440VAC / 3Phase / 60Hz
AWG #6 / 14mm² - 3C
440VAC / 3Phase / 60Hz
AWG #6 / 14mm² - 3C
440VAC / 3Phase / 60Hz
AWG #4 / 22mm² - 3C
440VAC / 3Phase / 60Hz
AWG #4 / 22mm² - 3C
440VAC / 3Phase / 60Hz
AWG #4 / 22mm² - 3C
440VAC / 3Phase / 60Hz
AWG #2 / 30mm² - 3C
67 84 110
76 95 125
85 106 140
99 124 162
100 125 164
105 131 172
125 156 205
150 187.5 246
165 206 271
440VAC / 3Phase / 60Hz
AWG #2 / 30mm² - 3C
440VAC / 3Phase / 60Hz
AWG #1 / 38mm² - 3C
440VAC / 3Phase / 60Hz
AWG #1/0 / 50mm² - 3C
440VAC / 3Phase / 60Hz
AWG #2/0 / 60mm² - 3C
440VAC / 3Phase / 60Hz
AWG #2/0 / 60mm² - 3C
440VAC / 3Phase / 60Hz
AWG #3/0 / 80mm² - 3C
440VAC / 3Phase / 60Hz
AWG #4/0 / 100mm² - 3C
440VAC / 3Phase / 60Hz
125mm² / 250MCM - 3C
440VAC / 3Phase / 60Hz
150mm² / 300MCM - 3C
175 219 287
200 250 328
225 281 369
230 287.5 377
250 312.5 410
260 325 427
275 344 452
350 437.5 575
400 500 657
440VAC / 3Phase / 60Hz
175mm² / 350MCM - 3C
440VAC / 3Phase / 60Hz
200mm² / 400MCM - 3C
440VAC / 3Phase / 60Hz
250mm² / 500MCM - 3C
440VAC / 3Phase / 60Hz
250mm² / 500MCM - 3C
440VAC / 3Phase / 60Hz
300mm² / 600MCM - 3C
440VAC / 3Phase / 60Hz
300mm² / 600MCM - 3C
440VAC / 3Phase / 60Hz
380mm² / 750MCM - 3C
440VAC / 3Phase / 60Hz
500mm² / 1,000MCM - 3C
440VAC / 3Phase / 60Hz
200mm² / 400MCM - 6C
550 687.5 903
GENERATOR DATA @ 240VAC
KILOWATTS KILOVOLT-AMPERES AMPERES WIRE SIZE
15 19 49
18 23 56
20 25 66
30 37.5 99
35 44 115
440VAC / 3Phase / 60Hz
380mm² / 750MCM - 6C
RATED VOLTAGE
240VAC / 3Phase / 60Hz
AWG #6 / 14mm² - 3C
240VAC / 3Phase / 60Hz
AWG #6 / 14mm² - 3C
240VAC / 3Phase / 60Hz
AWG #6 / 14mm² - 3C
240VAC / 3Phase / 60Hz
AWG #2 / 30mm² - 3C
240VAC / 3Phase / 60Hz
AWG #1 / 38mm² - 3C
40 50 131
44 55 145
50 62.5 164
60 75 197
67 84 220
76 95 250
85 106 279
99 124 325
100 125 328
240VAC / 3Phase / 60Hz
AWG #1/0 / 50mm² - 3C
240VAC / 3Phase / 60Hz
AWG #1/0 / 50mm² - 3C
240VAC / 3Phase / 60Hz
AWG #2/0 / 60mm² - 3C
240VAC / 3Phase / 60Hz
AWG #3/0 / 80mm² - 3C
240VAC / 3Phase / 60Hz
AWG #4/0 / 100mm² - 3C
240VAC / 3Phase / 60Hz
125mm² / 250MCM - 3C
240VAC / 3Phase / 60Hz
150mm² / 300MCM - 3C
240VAC / 3Phase / 60Hz
200mm² / 400MCM - 3C
240VAC / 3Phase / 60Hz
200mm² / 400MCM - 3C
105 131 345
125 156 411
150 187.5 493
165 206 541
AIR COMPRESSOR MOTOR DATA @ 240VAC
Electrical power cable, AWG # 10 - 3 conductorMolded case circuit breaker, 240VAC,50AT, 3 Pole, 60Hz
240VAC / 3Phase / 60Hz
250mm² / 500MCM - 3C
240VAC / 3Phase / 60Hz
300mm² / 600MCM - 3C
240VAC / 3Phase / 60Hz
400mm² / 800MCM - 3C
240VAC / 3Phase / 60Hz
500mm² / 1,00MCM - 3C
Magnetic contactor, wye - start, delta-run,7.5HP,220VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (18-26A), pilot lamps ( red and green) stop - start push button with enclosure
Electrical power cable, AWG # 8 - 3 conductorMolded case circuit breaker, 240VAC,50AT, 3 Pole, 60Hz
Electrical power cable, AWG # 6 - 3 conductorMolded case circuit breaker, 240VAC,70AT, 3 Pole, 60Hz
AIR COMPRESSOR MOTOR DATA @ 440VAC
Electrical power cable, AWG # 14 - 3 conductor
Magnetic contactor, wye - start, delta-run, 10HP,220VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (24-34A), pilot lamps ( red and green) stop - start push button with enclosure
Magnetic contactor, wye - start, delta-run, 15HP,220VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (34-50A), pilot lamps ( red and green) stop - start push button with enclosure
Magnetic contactor, wye - start, delta-run,7.5HP,440VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (9-16A), pilot lamps ( red and green) stop - start push button with enclosure
Molded case circuit breaker, 440VAC,20AT, 3 Pole, 60Hz
Electrical power cable, AWG # 12 - 3 conductorMolded case circuit breaker, 440VAC,30AT, 3 Pole, 60Hz
Electrical power cable, AWG # 10 - 3 conductorMolded case circuit breaker, 440VAC,40AT, 3 Pole, 60Hz
Magnetic contactor, wye - start, delta-run, 10HP,440VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (12-18A), pilot lamps ( red and green) stop - start push button with enclosure
Magnetic contactor, wye - start, delta-run, 15HP,220VAC, 3 Pole, 60 HZ with adjustable timer ,adjustable thermal overload relay (18-26A), pilot lamps ( red and green) stop - start push button with enclosure
KEY OPERATION OF JOB ORDER
KEY OP SHOP SPECIFICATION
041 P/E
042 DES Provide sketches and technical assistance.045 S/S Do coordinating and monitoring work.046 SFTY Implement industrial safety and regulation.
120 REMOVAL OF UNIT400 INSPECTION OF UNIT420 SHOP WORK421 SHOP REPAIR OF CONTROLLER490 SHOP TEST520 REPAIR WORK ABOARDSHIP620 REINSTALLATION OF UNIT690 OPERATIONAL TEST
Conduct inspection, prepare workspec and material requisition.
KEY OPERATION OF JOB ORDER
SPECIFICATION
WIRE TABLEGauge No.
mm²Diameter Area in CIR MILS (D²)
AWG in inch IMIL 0.001 inch 0000 107.2195533 0.460000 211,600.00 000 85.02821169 0.409640 167,805.00 00 67.43230256 0.364800 133,179.00 0 53.47500208 0.324860 105,538.00 1 42.40872321 0.289300 83,694.20 2 33.63188406 0.257630 66,373.00 3 26.66986891 0.229420 52,634.00 4 21.15132497 0.204310 41,742.00 5 16.77315309 0.181940 33,102.00 6 13.30134585 0.162020 26,250.50 7 10.53631754 0.144200 20,818.00 8 8.365597947 0.128490 16,509.00 9 6.634957205 0.114430 13,094.00
10 5.260432529 0.101890 10,381.00 11 4.172295163 0.090742 8,234.00 12 3.308773558 0.080808 6,529.00 13 2.623932809 0.071961 5,178.41 14 2.078593073 0.064048 4,106.70 15 1.650226798 0.057068 3,256.70 16 1.308662481 0.050820 2,582.90 17 1.037838684 0.045257 2,048.20 18 0.823063001 0.040303 1,624.30 19 0.65185115 0.035867 1,287.10 20 0.517605698 0.031961 1,021.50 21 0.410477313 0.028462 810.10 22 0.325545323 0.025347 642.70 23 0.25814275 0.022571 509.54 24 0.204715367 0.020100 404.01 25 0.162354523 0.017900 320.40 26 0.128746362 0.015940 254.01 27 0.102100795 0.014195 201.26 28 0.080969451 0.012641 159.79 29 0.064210147 0.011257 126.78 30 0.050924537 0.010025 100.50 31 0.040389334 0.008928 79.71 32 0.032025254 0.007950 63.20 33 0.025399481 0.007080 50.13 34 0.020136813 0.006304 39.74 35 0.015969935 0.005614 31.52
36 0.012667717 0.005000 25.00 37 0.010047632 0.004453 19.83 38 0.006806225 0.003665 15.72 39 0.006314046 0.003530 12.47 40 0.005008681 0.003144 9.89
CONDUIT SIZE WIRE SIZE NO. OF CONDUCTORSAWG mm²
1 / 2 '' 6 14 112 3.5 212 3.5 3
3 / 4'' 1 38 18 8.'0 2
10 5.5 3
1 '' 000 80 16 14 28 8.'0 3
1 1 / 4 '' 400MCM 200 12 30 24 22 3
1 1 / 2'' 550MCM 275 10 50 21 38 3
2 '' 1,000MCM 500 1200MCM 100 2
000 80 3
2 1 / 2 '' 1,700MCM 850 1350MCM 175 2250MCM 125 3
3 '' 2,000MCM 1,000 1600MCM 300 2500MCM 225 3
3 1 / 2 '' NO ESTABLISHED STANDARD 1900MCM 450 2750MCM 325 3
4 '' NO ESTABLISHED STANDARD 11,100MCM 550 21,000MCM 500 3