Electric ActuatorSuitable for valve stroke≤20mm. Rating force 500N/1000N
TC500-X.../ TC1000-X... : proportional control type, 0(2)~10VDC,0(4)~20mA many kinds of control
signals
TC500-D.../ TC1000-D... : 3-position control type
Max. force can reach 700N/1200N
24VAC/ 220VAC can be selected
Alternating current magnet synchronous motor,fixed torque output force.
Input/valve position feedback signals: 0(2)~10VDC and 0(4)~20mA(only proportional)
Valve position feedback signals: 0-10K resistance, SPDT feedback or active signal feedback
available (only 3-position)
PCB is made of 32bit signalchip + embedded operating system, adopt SMT paster welding
technology,precision of the electronic pieces using first-class brand home and aboard is 1%.
PCB has a function with defend wrong connection.
Proportional control type has self-adaption function which can automatic testing the max stroke of
valve.
Datasheet No.:
TC500-02
TC500-X...ProportionalTC1000-X...ProportionalTC500-D...3-PositionTC1000-D...3-Position
These actuators are used in 2-port, 3-port valve (TL/TF/TFR/TTF...series), whose stroke is 22 mm.
Environment temperature: -10~60℃
Permissible medium temperature: -25~+150℃(water valve) / 2~+180℃(steam valve)
2~+220℃(high temperature steam valve) /2~+450℃(super-high temperature steam valve)
Application
Functions
Proportional typeTC500-X.../ TC1000-X...
Control singnal:0(2)~10VDC , 0(4)~20mA
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
Note: when temperature of medium is below 0℃,e.g.refrigerant(R12,R22,R134a,R202),glycol, stem heater(THOT-1/
THOT-2) can be used to avoid connection part frosting or freezing.
TC500-X.../TC1000-X... realize controlling by terminal O,E signalControl singal at terminal O,E increasing: the actuator shaft extends, and valve stem retracts
Control singal at terminal O,E decreasing: the actuator shaft retracts, and valve stem extends
Control singal at terminal has no changing: the actuator shaft and valve stem stays in present position
Notes:1.This DA mode was made before leaving factory, if RA mode needed(control signal increases, actuator
shaft retracts), just put the 5th switch of S2 from ON to OFF.
2. Pay attention to relationship between valve stem and valve opening,closing. Tiger Controls globe
valve is: valve stem retracts, valve opens. PICV is: valve stem retracts,valve closes
3-position control type
TC500-D.../ TC1000-D..
3-position control signal
Ordering andTransportation
Combination device
Mechanical Design
Flow character
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
2
When ordering, please give clear indication on products type reference and any accessories required,
such as: TC500-X24-S.12.
Actuator, valve body and accessories are supplied in seperated packages.
TC500/TC1000...electric actuator can be fitted with 2-port, 3-port TL...,TF... series valve body whose
stroke is less than 20mm.
Actuator have long service time without repairing
TC500/TC1000...actuator with AC magnet synchronous motor
Limit force mechanical part was designed in order to protect the other part from overloading
TC500-X/D.../ TC1000-X/D… actuator has function of outage at limit position
Manual device is standard configuration
Type DN (mm) PN(Mpa) Datasheet No.
2-portTL…series 15...65 1.6/ 2.5 optional TL-02
TF…series 15...50 1.6/ 2.5 optional TF-02
TFR...series 15...50 1.6/ 2.5 optional TFR-02
TTF...series 15...50 1.6/ 2.5 optional TTF-02
Equal-linear flow characteristic.
The relationship between control signal0(2)~10VDC, 0(4)~20mA and flow is shown in the belowing
figure:
medium flow100%
control signal 100%
equal-linear curve
medium flow100%
control signal 100%
equal-percentage curve
Voltage on terminal 1 and 2: the actuator shaft extends, and valve stem retracts
Voltage on terminal 1 and 3: the actuator shaft retracts, and valve stem extends
No voltage on terminal 1,2 and1,3: the actuator shaft and valve stem stays in present position
Debugging Description
Type Summary
500N actuator
1000N actuator
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
3
A. Connect actuator and valve body.B. Turn off power of actuator.C. Wiring power and control signal wires.D. Set dip switch to needed position. After the setting,turn on power of actuator,setted function will come into effect.(dip switch can be setted with power)E. Turn on the power of actuator.F. Actuator self-stroking: this step is for matching stroke of actuator and valve.(1) Running light on PCB will keep flickering( frequency is 1Hz),actuator shaft extends to down limited positon firstly, and then retracts to up limited position.(actuator will not be controlled by signal now)(2) Running light stops flickering after 3 minutes of self-stroking. Self-stroking stops. By then, actuator running direction can be controlled by control signal.Remarks: If self-stroking is needed when power on, press down the red button on PCB over 3 seconds until the running light flickering. Self-stroking phenomenon are the same as step (2), (3) above.G.Kvs adjustment. By aperture potentiometer, max. aperture can be setted from 100% to 30%. Ralationship between relative flow and opening can be adjusted flexibly.100%-40% opening has high and low sensitivity. 40%~30% opening only has low sensitivity.
Note:
1. The factory default setting is automatic self-stroking,it means that actuator will repeat automatic self-stroking when power on each time.
2.If you don't need automatic self-stroking function,you can set the 7th switch to OFF. It will change into manual self-stroking(Phenomenon as
same with (1),(2).
Type Type Description Rating Force
ActualOutput Force
OperatingVoltage
Control Signal
Feedback Signal
Running Time
(50Hz)Wiring
Diagram
TC500-X24-S.12 Proportional 500N 500N~700N 24VAC 0(2)~10VDC 0(4)~20mA
0(2)~10VDC0(4)~20mA 3.85s/mm Wiring
Diagram 1
TC500-X220-S.12 Proportional 500N 500N~700N 220VAC 0(2)~10VDC 0(4)~20mA
0(2)~10VDC0(4)~20mA 3.85s/mm Wiring
Diagram 2
TC500-D24-S.12 3-position 500N 500N~700N 24VAC 3-position No 3.85s/mm WiringDiagram 3
TC500-D220-S.12 3-position 500N 500N~700N 220VAC 3-position No 3.85s/mm WiringDiagram 3
TC500-D24-SF10K.12 3-position with 0-10K resistance feedback 500N 500N~700N 24VAC 3-position 0-10K resistance
feedback 3.85s/mm WiringDiagram 4
TC500-D220-SF10K.12 3-position with 0-10K resistance feedback 500N 500N~700N 220VAC 3-position 0-10K resistance
feedback 3.85s/mm WiringDiagram 4
TC500-D24-SF2.12 3-position with 2 SPDT feedback 500N 500N~700N 24VAC 3-position 2 SPDT
feedback 3.85s/mm WiringDiagram 5
TC500-D220-SF2.12 3-position with 2 SPDT feedback 500N 500N~700N 220VAC 3-position 2 SPDT
feedback 3.85s/mm WiringDiagram 5
TC500-D24-SF3.12 3-position with active signal feedback 500N 500N~700N 24VAC 3-position active signal 3.85s/mm Wiring
Diagram 6
TC500-D220-SF3.12 3-position with active signal feedback 500N 500N~700N 220VAC 3-position active signal 3.85s/mm Wiring
Diagram 6
Type Type Discription Rating Force
ActualOutput Force
OperatingVoltage
Control Signal
Feedback Signal
Running Time
(50Hz)Wiring
Diagram
TC1000-X24-S.12 Proportional 1000N 1000N~1200N 24VAC 0(2)~10VDC 0(4)~20mA
0(2)~10VDC0(4)~20mA 3.85s/mm Wiring
Diagram 1
TC1000-X220-S.12 Proportional 1000N 1000N~1200N 220VAC 0(2)~10VDC 0(4)~20mA
0(2)~10VDC0(4)~20mA 3.85s/mm Wiring
Diagram 2
TC1000-D24-S.12 3-position 1000N 1000N~1200N 24VAC 3-position No 3.85s/mm WiringDiagram 3
TC1000-D220-S.12 3-position 1000N 1000N~1200N 220VAC 3-position No 3.85s/mm WiringDiagram 3
TC1000-D24-SF10K.12 3-position with 0-10K resistance feedback 1000N 1000N~1200N 24VAC 3-position 0-10K resistance
feedback 3.85s/mm WiringDiagram 4
TC1000-D220-SF10K.12 3-position with 0-10K resistance feedback 1000N 1000N~1200N 220VAC 3-position 0-10K resistance
feedback 3.85s/mm WiringDiagram 4
TC1000-D24-SF2.12 3-position with 2 SPDT feedback 1000N 1000N~1200N 24VAC 3-position 2 SPDT
feedback 3.85s/mm WiringDiagram 5
TC1000-D220-SF2.12 3-position with 2 SPDT feedback 1000N 1000N~1200N 220VAC 3-position 2 SPDT
feedback 3.85s/mm WiringDiagram 5
TC1000-D24-SF3.12 3-position with active signal feedback 1000N 1000N~1200N 24VAC 3-position active signal 3.85s/mm Wiring
Diagram 6
TC1000-D220-SF3.12 3-position with active signal feedback 1000N 1000N~1200N 220VAC 3-position active signal 3.85s/mm Wiring
Diagram 6
Wiring Diagram
Feedback resistence Terminal Actuator axes
4-5 5-6 1-2-2 extend
restract
2 4 5 631
1-3
10K 0
0 10K 10K 00 10K
Wiring diagram1: proportional (24VAC) Wiring diagram 2: proportional (220VAC)
Wiring diagram3: 3-position Wiring diagram4: 3-position with 0~10K feedback
2 31COM DOWN UP
Power
Power
7 8 9DL
UL
4
2 3 1 COM DOWN UP
Power
4 5 6 7
UP DOWN
COM NO COM NO
Power
M
power Control signal
Feedback signal
B O O E Y
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
Wiring diagram 6: 3-position with active signal feedback
Wiring diagram 5: 3-position with SPDT feedback
M
Controls signal
Feedback signal
L N O E Y AC220V
M
1 2 3
Power
Power
Terminal Shaft
1-2
1-3
extent
retract
The PCB of Proportional typeActuator
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
5
The S2,S3 switch setting of Proportional type Actuator
PCB diagram 1: Proportional type (24VAC) TC500-X24../ TC1000-X24..
PCB diagram 2: Proportional type (220VAC) TC500-X220../ TC1000-X220..
self-stroking button
connecting terminalrunning light
power light
ON
S2 S3 switch
OFF
aperture potentiometer
B O O E Y
self-stroking button
connecting terminal
running light
power light
20%
0
II
UI
IO
UO
1 2 3 4
DA
RA
DW
UP
DF
RF
HS
LS
5 6 7 8
ON
S2
S2、S3 Switch
OFF
S3 S1
S2 S3 UI
II
aperture potentiometer
Switch Function Description
S2
1 Starting of control/ feedback signal
ON 20%:the starting control / feedback signal is 20% (namely 4~20mA or 2~10V)
OFF 0:the starting control / feedback signal is 0 (namely 0~20mA or 0~10V)
2 Type of control signal
ON II: current signal
OFF UI: voltage signal
3 Impedence match of control signal
ON UI: voltage signal
OFF II: current signal
4 Type of feedback signal
ON IO: current signal
OFF UO: voltage signal
S3
1 Operating mode ON DA:DA mode (when control signal increases, the actuator shaft extends )
OFF RA: RA mode (when control signal increases, the actuator shaft retracts)
2 Losing control signal mode
ON DW: When lose control signal (voltage type), actuator will provide a min. control signal internally When lose control signal (current type), actuator will provide a min. control signal internally
OFF UP: When lose control signal (voltage type), actuator will provide a max. control signal internally When lose control signal (current type), actuator will provide a min. control signal internally
3 Self-stroking modeON DF: Power on each time, self-stroking starts automatically (factory setting)
OFF RF: self-stroking starts only when press the red self-stroking button manually
4 SensitivityON HS: the high sensitivity of control signal ≤1%(100%~40%); ≤1.5%(40%~30%)
OFF LS: the low sensitivity of control signal ≤1.5%(100%~30%)
The setting of S2,S3 switch
Nominal setting of S2,S3 switch
Proportional actuatorOpening adjustment potentiometer
Dimensions
Mounting Orientation
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
6
Medium is chilled/hot water Medium is steam
Installation downwards is forbidden Random direction is OK
Control signal: 4~20mA; Feedback signal: 4~20mA; DA mode; When lose control signal (current type), means input a minimum control signal, the actuator shaft retracts.
2 3 41
2 3 41
ON
OFF
S2
S3
ON
OFF 2 3 41
S2
2 3 41
S3
2 3 41
2 3 41
ON
OFF
S2
S3
ON
OFF 2 3 41
S2
2 3 41
S3
1.Dip switch sample when matched with electric control valve.
2.When matched with pressure independent control valve,the fifth dip switch is OFF, other dip switch is the same with electric control valve.
Control signal: 0~10VDC; Feedback signal: 0~10VDC; DA mode(factory setting); When lose control signal (voltage type), means input a minimum control signal, the actuator shaft retracts.
maximum opening
30
40
50
60 70
80
90
100
By aperture potentiometer, max. aperture can be setted from 100% to 30%. Flexibly adjust the relationship between the relative flow and opening of valve body, the factory default value is 100%.
Installation Sheet
Technology Data
Eelectric parameter
Function Parameter
Electric Motor
Operating VoltageTC500-X24.../ TC1000-X24...TC500-X220.../ TC1000-X220...
Frequency
Power consumptionTC500/1000-D.../F10K/F3...TC500/1000-D...F2...TC500/1000-X...
Impedance(only for proportional type)voltage input impedancecurrent input impedance
Load requirements(only for proportional type)voltage output load requirementcurrent output load requirement
Up and down dead band Sensitivity
Control Signal typeTC500-D.../ TC1000-D...TC500-X.../ TC1000-X...
Control SignalTC500-D.../ TC1000-D...TC500-X.../ TC1000-X...
synchronous motor with permanent magnetic
24VAC ± 15%220VAC ± 15%
50Hz or 60Hz available
5.5VA7.5VA7.5VA
>100K<0.167K
>1K<0.5K
≤2%≤1%; ≤1.5%
3-positionproportional
24VAC/ 220VAC 0(2)~10VDC, 0(4)~20mA
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
7
1 2
3 4
Prepare for assembling the actuator, take down the sliding block firstly, and then disentangle the clip.
Keep the actuator’s axes and the valve’s stem concentric.Make these two connectiong faces coinciding. Then lock the two screws on the clip.
Pull the sliding block to the groove and lock it by two screws.
The status after assembled.
Observation hole
EnvironmentCondition
Material
Dimension and Weight
Lifetime
Certificate
Feedback SignalTC500-X.../ TC1000-D...TC5000-D.../TC1000-D...TC500/1000-D..-F10KTC500/1000-D..-F2TC500/1000-D..-F3
IP degree
Permissible medium temperature
Running Enviroment tempreture: Enviroment humidity:
Transportation Enviroment tempreture: Enviroment humidity:
Storage Enviroment tempreture: Enviroment humidity:
CoverBracket
Product DimensionsWeight
Lifetime
Certificate
0(2)~10VDC,0(4)~20mAno0-10K resistance feedbackSPDT feedbackactive signal feedback
IP54
-25~+130℃(water) /2~+180℃(steam)
2~+220℃(high tempreature steam valve)/
2~+450℃(super-high tempreature steam valve) Notes: 1. When medium temperature below 0℃ (R12, R22, R134a, R202, glycol), the stem of the valve should be protected by electric heating cover(THOT-1/THOT-2) to avoid frosting and icing.
-10~+60℃ (3-position type)≤95% RH
-30~+65℃≤95% RH
-15~+50℃≤95% RH
PCdie casting aluminum(surface anti-rust process)
refer to the dimension figure
1.7Kg
100 thousand times
CE,RoHS,REACH
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
8
9
Electric ActuatorStroke≤ 40mm. Rating force 1800N/ 3000N/5000N
TR1800-X.../ TR3000-X... /TR5000-X...: proportional control type, many kinds of control signal:
0(2)~10VDC,0(4)~20mA
TR1800-D.../ TR3000-D./TR5000-D...: 3-position control type
Max. actual force: 2000N/3500N/5500N
24VAC/220VAC can be selected
Visible window, PCB status can be seen clearly
LED display module can display the percentage of control signal and valve position feedback signal
and relative alarm information.
0-1K resistance feedback,0-10K resistance feedback, SPDT are optional(only 3-position)
Control signals: 0(2)~10VDC and 0(4)~20mA(only proportional control type)
PCB is made of 32bit signalchip + embedded operating system, adopt SMT paster welding
technology,precision of the electronic pieces using first-class brand home and aboard is 1%.
PCB has a function with defend wrong connection.
Selfstroke for proportional control type can automatic testing the max stroke of valve.
TR1800/3000-D...SeriesTR1800/3000-X...SeriesTR5000-D...SeriesTR5000-X...Series
These actuators used in 2-port, 3-port valve (TL/TF/TFR/TTF...series), whose stroke is less than 44mm.
Environment temperature: -10~60℃
Permissible medium temperature: -25~+150℃(water valve) / 2~+180℃(steam valve)
/2~+220℃(high temperature steam valve) / 2~+450℃(super-high temperature steam valve)
Notes:
When medium temperature below 0℃ (R12, R22, R134a, R202, glycol), the stem of the valve should be protected by stem heater (THOT-1/THOT-2) to avoid frosting and icing.
Application
Functions
Proportional typeTR1800-X.../TR3000-X.../TR5000-X...
Control singnal/vale feedback signal:0(2)~10VDC,0(4)~20mA
Datasheet No.:
TR1800/3000-02
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
TR1800-X.../TR3000-X.../TR5000-X... realize controlling by terminal O,E signal
Control singal at terminal O,E increasing: the actuator shaft extends, and valve stem retracts
Control singal at terminal O,E decreasing: the actuator shaft retracts, and valve stem extends
Control singal at terminal has no changing: the actuator shaft and valve stem stays in present position
Notes:
1.This DA mode was made before leaving factory, if RA mode needed(control signal increases, actuator
shaft retracts), just put the 5th switch of S2 from ON to OFF.
2. Pay attention to relationship between valve stem and valve opening,closing. Tiger Controls globe
valve is: valve stem retracts, valve opens. PICV is: valve stem retracts,valve closes.
3-position control typeTR1800-D.../ TR3000-D... / TR5000-D... 3-position control signal
Ordering andTransportation
Combination device
Mechanical Design
Flow character
10
When ordering, please give clear indication on products type and accessories required, such as:
TR1800-X24-S.12.
Actuator and valve body are supplied in separated packages.
TR1800/TR3000/TR5000...electric actuator can be fitted with 2-port, 3-port TL...,TF... series valve body
whose stroke is less than 40mm.
Actuator have long service time without repair
TR1800/TR3000/TR5000...actuator with synchronous motor
TR1800-D.../ TR3000-D.../TR5000-D… actuator have limit switch
Manual device is standard configuration
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
Type DN (mm) PN(Mpa) Datasheet No.TL…series 15...80 1.6/ 2.5 optional TL-02
TF... series 15...250 1.6/ 2.5 optional TF-02
TFR... series 15...250 1.6/ 2.5 optional TFR-02TTF...series 15...250 1.6/ 2.5 optional TTF-02
medium flow100%
control signal 100%
equal-linear curve
medium flow100%
control signal 100%
equal-percentage curve
Linear flow characteristic.
The relationship between control signal and flow is shown in the belowing figure:
Voltage on terminal 1 and 2: the actuator shaft extends, and valve stem retracts
Voltage on terminal 1 and 3: the actuator shaft retracts, and valve stem extends
No voltage on interminal 1,2 and1,3: the actuator shaft and valve stem stays in present position
Debugging
Type Summary
1800N actuator
3000N actuator
11Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
Type Type Discription Rating Force
ActualOutput Force
OperatingVoltage
Control Signal
Feedback Signal
Running Time
(50Hz)Wiring
Diagram
TR1800-X24-S.12 Proportional 1800N 1800N~2000N 24VAC 0(2)~10VDC 0(4)~20mA
0(2)~10VDC0(4)~20mA 3.13s/mm Wiring
Diagram 1
TR1800-X220-S.12 Proportional 1800N 1800N~2000N 220VAC 0(2)~10VDC 0(4)~20mA
0(2)~10VDC0(4)~20mA 3.13s/mm Wiring
Diagram 2
TR1800-D24-S.12 3-position 1800N 1800N~2000N 24VAC 3-position No 3.13s/mm WiringDiagram 3
TR1800-D220-S.12 3-position 1800N 1800N~2000N 220VAC 3-position No 3.13s/mm WiringDiagram 3
TR1800-D24-SF1K.12 3-position with 0-1K resistance feedback 1800N 1800N~2000N 24VAC 3-position 0-1K resistance
feedback 3.13s/mm WiringDiagram 4
TR1800-D220-SF1K.12 3-position with 0-1K resistance feedback 1800N 1800N~2000N 220VAC 3-position 0-1K resistance
feedback 3.13s/mm WiringDiagram 4
TR1800-D24-SF10K.12 3-position with 0-10K resistance feedback 1800N 1800N~2000N 24VAC 3-position 0-10K resistance
feedback 3.13s/mm WiringDiagram 5
TR1800-D220-SF10K.12 3-position with 0-10K resistance feedback 1800N 1800N~2000N 220VAC 3-position 0-10K resistance
feedback 3.13s/mm WiringDiagram 5
TR1800-D24-SF2.12 3-position with 2 SPDT feedback 1800N 1800N~2000N 24VAC 3-position 2 SPDT
feedback 3.13s/mm WiringDiagram 6
A. Connect actuator and valve body.
B. Turn off power of actuator.
C. Wiring power and control signal wires.
D. Set dip switch to needed position. After the setting,turn on power of actuator,setted function will come
into effect.(dip switch can be setted with power)
E. Turn on the power of actuator.
F. Actuator self-stroking: this step is for matching stroke of actuator and valve.
(1) Running light on PCB will keep flickering( frequency is 1Hz),actuator shaft extends to down limited
positon firstly, and then retracts to up limited position.(actuator will not be controlled by signal now)
(2) Running light stops flickering after 5 minutes of self-stroking. Self-stroking stops. By then, actuator
running direction can be controlled by control signal.
Remarks: If self-stroking is needed when power on, press down the red button on PCB over 3 seconds
until the running light flickering. Self-stroking phenomenon are the same as step (2), (3) above.
G.Kvs adjustment. By aperture potentiometer, max. aperture can be setted from 100% to 30%.
Ralationship between relative flow and opening can be adjusted flexibly.100%-40% opening has high and
low sensitivity. 40%~30% opening only has low sensitivity.
Note:
1. The factory default setting is automatic self-stroking,it means that actuator will repeat automatic self-
stroking when power on each time.
2.If you don't need automatic self-stroking function,you can set the 7th switch to OFF. It will change into
manual self-stroking(Phenomenon as same with (1),(2).
Type Type Discription Rating Force
ActualOutput Force
OperatingVoltage
Control Signal
Feedback Signal
Running Time
(50Hz)Wiring
Diagram
TR3000-X24-S.12 Proportional 3000N 3000N~3500N 24VAC 0(2)~10VDC 0(4)~20mA
0(2)~10VDC0(4)~20mA 3.13s/mm Wiring
Diagram 1
TR3000-X220-S.12 Proportional 3000N 3000N~3500N 220VAC 0(2)~10VDC 0(4)~20mA
0(2)~10VDC0(4)~20mA 3.13s/mm Wiring
Diagram 2
TR3000-D24-S.12 3-position 3000N 3000N~3500N 24VAC 3-position No 3.13s/mm WiringDiagram 3
TR3000-D220-S.12 3-position 3000N 3000N~3500N 220VAC 3-position No 3.13s/mm WiringDiagram 3
TR3000-D24-SF1K.12 3-position with 0-1K resistance feedback 3000N 3000N~3500N 24VAC 3-position 0-1K resistance
feedback 3.13s/mm WiringDiagram 4
TR3000-D220-SF1K.12 3-position with 0-1K resistance feedback 3000N 3000N~3500N 220VAC 3-position 0-1K resistance
feedback 3.13s/mm WiringDiagram 4
TR3000-D24-SF10K.12 3-position with 0-10K resistance feedback 3000N 3000N~3500N 24VAC 3-position 0-10K resistance
feedback 3.13s/mm WiringDiagram 5
TR3000-D220-SF10K.12 3-position with 0-10K resistance feedback 3000N 3000N~3500N 220VAC 3-position 0-10K resistance
feedback 3.13s/mm WiringDiagram 5
TR3000-D24-SF2.12 3-position with 2 SPDT feedback 3000N 3000N~3500N 24VAC 3-position 2 SPDT
feedback 3.13s/mm WiringDiagram 6
5000N actuator
Wiring Diagram
8 - 9 9 - 10 1 - 2 extend 1 - 3 retract
1K 0 0 1K
0 1K1K 0
Electricityterminals shaft
feedback resistance
Wiring diagram1: proportional (24VAC ) Wiring diagram 2: proportional (220VAC)
Wiring diagram3: 3-position Wiring diagram4: 3-position with 1K feedback
12
M
power Control signal
Feedback signal
B O O E Y
M
Controls signal
Feedback signal
L N O E Y AC220V
Wiring diagram 6: 3-position with SPDT feedback
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
Type Type Discription Rating Force
ActualOutput Force
OperatingVoltage
Control Signal
Feedback Signal
Running Time
(50Hz)Wiring
Diagram
TR5000-X24-S.12 Proportional 5000N 4500N~5500N 24VAC 0(2)~10VDC 0(4)~20mA
0(2)~10VDC0(4)~20mA 3.13s/mm Wiring
Diagram 1
TR5000-X220-S.12 Proportional 5000N 4500N~5500N 220VAC 0(2)~10VDC 0(4)~20mA
0(2)~10VDC0(4)~20mA 3.13s/mm Wiring
Diagram 2
TR5000-D24-S.12 3-position 5000N 4500N~5500N 24VAC 3-position No 3.13s/mm WiringDiagram 3
TR5000-D220-S.12 3-position 5000N 4500N~5500N 220VAC 3-position No 3.13s/mm WiringDiagram 3
TR5000-D24-SF1K.12 3-position with 0-1K resistance feedback 5000N 4500N~5500N 24VAC 3-position 0-1K resistance
feedback 3.13s/mm WiringDiagram 4
TR5000-D220-SF1K.12 3-position with 0-1K resistance feedback 5000N 4500N~5500N 220VAC 3-position 0-1K resistance
feedback 3.13s/mm WiringDiagram 4
TR5000-D24-SF10K.12 3-position with 0-10K resistance feedback 5000N 4500N~5500N 24VAC 3-position 0-10K resistance
feedback 3.13s/mm WiringDiagram 5
TR5000-D220-SF10K.12 3-position with 0-10K resistance feedback 5000N 4500N~5500N 220VAC 3-position 0-10K resistance
feedback 3.13s/mm WiringDiagram 5
TR5000-D24-SF2.12 3-position with 2 SPDT feedback 5000N 4500N~5500N 24VAC 3-position 2 SPDT
feedback 3.13s/mm WiringDiagram 6
8 - 9 9 - 10 1 - 2 extend 1 - 3 retract
10K 0 0 10K
0 10K 10K 0
Electricityterminals shaft
feedback resistance
Wiring diagram 5: 3-position with 10K feedback
The PCB Figure of Proportional typeActuator
PCB diagram 2: Proportional type (220VAC) TR1800-X220../ TR3000-X220../ TR5000-X220..
PCB diagram 1: Proportional type (24VAC) TR1800-X24../ TR3000-X24.. / TR5000-X24..
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
S1
self-stroking button
function digit
number digit
ERR
RUN
B O O E Y
connecting terminal1 2
3
4
5 6
UL DL AL
auxiliary terminal
error light
running light
CPU
maximumopening
aperture potentiometerr
2 3 41
ON
OFF
S22 3 41
S3
1 2 3 4
20%
0
II
UI
UI
II
IO
UO
5 6 7 8
DA
RA
DW
UP
DF
RF
HS
LSS2 S3
30
40
50
60 70
80
90
100
24VAC
S1
self-stroking button
function digit
number digit
ERR
RUN
L N O E Y
connecting terminal1 2
3
4
5 6
UL DL AL
auxiliary terminal
error light
running light
CPU
maximumopening
aperturepotentiometer
2 3 41
ON
OFF
S22 3 41
S3
1 2 3 4
20%
0
II
UI
UI
II
IO
UO
5 6 7 8
DA
RA
DW
UP
DF
RF
HS
LSS2 S3
30
40
50
60 70
80
90
100
220VAC
13
The S2,S3 switch setting of Proportional type Actuator
Switch Function Description
S2
1 Starting of control/ feedback signal
ON 20%:the starting control / feedback signal is 20% (namely 4~20mA or 2~10V)
OFF 0:the starting control / feedback signal is 0 (namely 0~20mA or 0~10V)
2 Type of control signal
ON II: current signal
OFF UI: voltage signal
3 Impedence match of control signal
ON UI: voltage signal
OFF II: current signal
4 Type of feedback signal
ON IO: current signal
OFF UO: voltage signal
S3
1 Operating mode ON DA:DA mode (when control signal is increasing, the actuator axes extends )
OFF RA: RA mode (when control signal is increasing, the actuator axes retracts)
2 Losing control signal mode
ON DW: When lose control signal (voltage type), actuator will provide a min. control signal internally When lose control signal (current type), actuator will provide a min. control signal internally
OFF UP: When lose control signal (voltage type), actuator will provide a max. control signal internally When lose control signal (current type), actuator will provide a min. control signal internally
3 Self-stroking modeON DF: Power up each time, self-stroking starts automatically (factory setting)
OFF RF: self-stroking starts only when press the red self-stroking button manually
4 SensitivityON HS: the high sensitivity of control signal ≤1%(100%~40%); ≤1.5%(40%~30%)
OFF LS: the low sensitivity of control signal ≤1.5%(100%~30%)
14Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
Nominal setting of S2,S3 switch
Control signal: 0~10VDC; Feedback signal: 0~10VDC; ( factory setting)DA mode; When lose control signal (voltage type), means input a minimum control signal, the actuator shaft retracts.
Control signal: 4~20mA; Feedback signal: 4~20mA; DA mode; When lose control signal (current type), means input a minimum control signal, the actuator shaft retracts.
2 3 41
2 3 41
ON
OFF
S2
S3
ON
OFF 2 3 41
S2
2 3 41
S3
2 3 41
2 3 41
ON
OFF
S2
S3
ON
OFF 2 3 41
S2
2 3 41
S3
1.Dip switch sample when used with electric control valve.
2.When used with Pressure independent control valve,the fifth dial code is OFF,other dip switch are the same with electric control valve.
By aperture potentiometer, max. aperture can be setted from 100% to 30%.Flexibility adjust the relationship between the relative flow and opening of valve body,the factory default value is 100%.
Proportional actuatorOpening adjustment potentiometer
maximum opening
30
40
50
60 70
80
90
100
Mounting Orientation
Dimensions
Medium is chilled/hot water Medium is steam
Installation downwards is forbidden random direction is OK
44
Electric Parameter
Function Parameter
Electric Motor
Operating VoltageTR1800-X24.../ TR3000-X24.../TR5000-X24..TR1800-X220.../ TR3000-X220.../TR5000-X220
Frequency
Power consumptionTR1800/3000/5000-D...TR1800/3000/5000-D...F1K/F10K/F2...TR1800/3000/5000-X...
Impedance (only for proportional type)voltage input impedancecurrent input impedance
Load requirements(only for proportional type)voltage output load requirementcurrent output load requirementUp and down dead band
Sensitivity
Control Signal typeTR1800-X.../TR3000-X.../TR5000-X...TR1800-D.../TR3000-D.../TR5000-D...
Synchronous motor with permanent magnetic
24VAC± 15%220VAC± 15%
50Hz or 60Hz available
13VA13VA15VA
>100K<0.167K
>1K<0.5K≤2%
≤1% ≤1.5%
proportional3-position
15
Technology Data
Installation Sheet
Tiger Controls Equipment Co., Ltd
Http:// www.tiger-control.com
1.Prepare for assembling the actuator, take down the fixed litting stly,and then disentangle the clip.
2.Keep the actuators’s axis and valve’s stem concentric. Make these two connecting faces keep coinciding and Observe by observation hole.Put the actuator on the convex platform of valve body.Then lock the two screws on the clip.
3.Full the fixed litting to the grooved and lock by two screws.
4.The status after assembled.
Observation hole
EnvironmentCondition
Material
Control SignalTR1800-X.../TR3000-X.../TR5000-X...TR1800-D.../TR3000-D.../TR5000-D...
Feedback SignalTR1800-X.../TR3000-X.../TR5000-X... TR1800-D.../TR3000-D.../TR5000-D..TR1800/3000/5000-D...-SF0K.12TR1800/3000/5000-D..-SF10K.12TR1800/3000/5000-D..-SF2.12
IP degree
Permissible medium temperature
Running Enviroment tempreture: Enviroment humidity:
Transportation Enviroment tempreture: Enviroment humidity:
Storage Enviroment tempreture: Enviroment humidity:
CoverBracketGear
Product DimensionsWeight
Lifetime
certificate
0(2)~10VDC, 0(4)~20mA24VAC/220VAC
0(2)~10VDC, 0(4)~20mAno0-1K resistance feedback0-10K resistance feedbackSPDT feedback
IP54
-25~+150℃(water)/2~+180℃(steam)2~+220℃(high tempreature steam valve) /2~+450℃(super-high tempreature steam valve)Notes: 1. When medium temperature is below 0℃ (R12, R22, R134a, R202, glycol), the stem of the valve should be protected by electric heating cover(THOT-1/THOT-2) to avoid frosting and icing.
-10~+60℃ ≤95% RH
-30~+65℃≤95% RH
-15~+50℃≤95% RH
aluminum die castingaluminum die casting(surface anti-rust process)metal gear
refer to the dimension figure 5.2Kg
100 thousand times
CE, RoHS, REACH
16Tiger Controls Equipment Co., Ltd