Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat...

16
1 Electric Actuator Suitable for valve stroke≤20mm. Rating force 500N/1000N TC500-X.../ TC1000-X... : proportional control type, 0(2)~10VDC,0(4)~20mA many kinds of control signals TC500-D.../ TC1000-D... : 3-position control type Max. force can reach 700N/1200N 24VAC/ 220VAC can be selected Alternating current magnet synchronous motor,fixed torque output force. Input/valve position feedback signals: 0(2)~10VDC and 0(4)~20mA(only proportional) Valve position feedback signals: 0-10K resistance, SPDT feedback or active signal feedback available (only 3-position) PCB is made of 32bit signalchip + embedded operating system, adopt SMT paster welding technology,precision of the electronic pieces using first-class brand home and aboard is 1%. PCB has a function with defend wrong connection. Proportional control type has self-adaption function which can automatic testing the max stroke of valve. Datasheet No.: TC500-02 TC500-X...Proportional TC1000-X...Proportional TC500-D...3-Position TC1000-D...3-Position These actuators are used in 2-port, 3-port valve (TL/TF/TFR/TTF...series), whose stroke is 22 mm. Environment temperature: -10~60Permissible medium temperature: -25~+150(water valve) / 2~+180(steam valve) 2~+220(high temperature steam valve) /2~+450(super-high temperature steam valve) Application Functions Proportional type TC500-X... / TC1000-X... Control singnal: 0(2)~10VDC , 0(4)~20mA Tiger Controls Equipment Co., Ltd Http:// www.tiger-control.com Note: when temperature of medium is below 0℃,e.g.refrigerant(R12,R22,R134a,R202),glycol, stem heater(THOT-1/ THOT-2) can be used to avoid connection part frosting or freezing. TC500-X.../TC1000-X... realize controlling by terminal O,E signal Control singal at terminal O,E increasing: the actuator shaft extends, and valve stem retracts Control singal at terminal O,E decreasing: the actuator shaft retracts, and valve stem extends Control singal at terminal has no changing: the actuator shaft and valve stem stays in present position Notes: 1.This DA mode was made before leaving factory, if RA mode needed(control signal increases, actuator shaft retracts), just put the 5th switch of S2 from ON to OFF. 2. Pay attention to relationship between valve stem and valve opening,closing. Tiger Controls globe valve is: valve stem retracts, valve opens. PICV is: valve stem retracts,valve closes

Transcript of Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat...

Page 1: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

1

Electric ActuatorSuitable for valve stroke≤20mm. Rating force 500N/1000N

TC500-X.../ TC1000-X... : proportional control type, 0(2)~10VDC,0(4)~20mA many kinds of control

signals

TC500-D.../ TC1000-D... : 3-position control type

Max. force can reach 700N/1200N

24VAC/ 220VAC can be selected

Alternating current magnet synchronous motor,fixed torque output force.

Input/valve position feedback signals: 0(2)~10VDC and 0(4)~20mA(only proportional)

Valve position feedback signals: 0-10K resistance, SPDT feedback or active signal feedback

available (only 3-position)

PCB is made of 32bit signalchip + embedded operating system, adopt SMT paster welding

technology,precision of the electronic pieces using first-class brand home and aboard is 1%.

PCB has a function with defend wrong connection.

Proportional control type has self-adaption function which can automatic testing the max stroke of

valve.

Datasheet No.:

TC500-02

TC500-X...ProportionalTC1000-X...ProportionalTC500-D...3-PositionTC1000-D...3-Position

These actuators are used in 2-port, 3-port valve (TL/TF/TFR/TTF...series), whose stroke is 22 mm.

Environment temperature: -10~60℃

Permissible medium temperature: -25~+150℃(water valve) / 2~+180℃(steam valve)

2~+220℃(high temperature steam valve) /2~+450℃(super-high temperature steam valve)

Application

Functions

Proportional typeTC500-X.../ TC1000-X...

Control singnal:0(2)~10VDC , 0(4)~20mA

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Note: when temperature of medium is below 0℃,e.g.refrigerant(R12,R22,R134a,R202),glycol, stem heater(THOT-1/

THOT-2) can be used to avoid connection part frosting or freezing.

TC500-X.../TC1000-X... realize controlling by terminal O,E signalControl singal at terminal O,E increasing: the actuator shaft extends, and valve stem retracts

Control singal at terminal O,E decreasing: the actuator shaft retracts, and valve stem extends

Control singal at terminal has no changing: the actuator shaft and valve stem stays in present position

Notes:1.This DA mode was made before leaving factory, if RA mode needed(control signal increases, actuator

shaft retracts), just put the 5th switch of S2 from ON to OFF.

2. Pay attention to relationship between valve stem and valve opening,closing. Tiger Controls globe

valve is: valve stem retracts, valve opens. PICV is: valve stem retracts,valve closes

Page 2: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

3-position control type

TC500-D.../ TC1000-D..

3-position control signal

Ordering andTransportation

Combination device

Mechanical Design

Flow character

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

2

When ordering, please give clear indication on products type reference and any accessories required,

such as: TC500-X24-S.12.

Actuator, valve body and accessories are supplied in seperated packages.

TC500/TC1000...electric actuator can be fitted with 2-port, 3-port TL...,TF... series valve body whose

stroke is less than 20mm.

Actuator have long service time without repairing

TC500/TC1000...actuator with AC magnet synchronous motor

Limit force mechanical part was designed in order to protect the other part from overloading

TC500-X/D.../ TC1000-X/D… actuator has function of outage at limit position

Manual device is standard configuration

Type DN (mm) PN(Mpa) Datasheet No.

2-portTL…series 15...65 1.6/ 2.5 optional TL-02

TF…series 15...50 1.6/ 2.5 optional TF-02

TFR...series 15...50 1.6/ 2.5 optional TFR-02

TTF...series 15...50 1.6/ 2.5 optional TTF-02

Equal-linear flow characteristic.

The relationship between control signal0(2)~10VDC, 0(4)~20mA and flow is shown in the belowing

figure:

medium flow100%

control signal 100%

equal-linear curve

medium flow100%

control signal 100%

equal-percentage curve

Voltage on terminal 1 and 2: the actuator shaft extends, and valve stem retracts

Voltage on terminal 1 and 3: the actuator shaft retracts, and valve stem extends

No voltage on terminal 1,2 and1,3: the actuator shaft and valve stem stays in present position

Page 3: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

Debugging Description

Type Summary

500N actuator

1000N actuator

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

3

A. Connect actuator and valve body.B. Turn off power of actuator.C. Wiring power and control signal wires.D. Set dip switch to needed position. After the setting,turn on power of actuator,setted function will come into effect.(dip switch can be setted with power)E. Turn on the power of actuator.F. Actuator self-stroking: this step is for matching stroke of actuator and valve.(1) Running light on PCB will keep flickering( frequency is 1Hz),actuator shaft extends to down limited positon firstly, and then retracts to up limited position.(actuator will not be controlled by signal now)(2) Running light stops flickering after 3 minutes of self-stroking. Self-stroking stops. By then, actuator running direction can be controlled by control signal.Remarks: If self-stroking is needed when power on, press down the red button on PCB over 3 seconds until the running light flickering. Self-stroking phenomenon are the same as step (2), (3) above.G.Kvs adjustment. By aperture potentiometer, max. aperture can be setted from 100% to 30%. Ralationship between relative flow and opening can be adjusted flexibly.100%-40% opening has high and low sensitivity. 40%~30% opening only has low sensitivity.

Note:

1. The factory default setting is automatic self-stroking,it means that actuator will repeat automatic self-stroking when power on each time.

2.If you don't need automatic self-stroking function,you can set the 7th switch to OFF. It will change into manual self-stroking(Phenomenon as

same with (1),(2).

Type Type Description Rating Force

ActualOutput Force

OperatingVoltage

Control Signal

Feedback Signal

Running Time

(50Hz)Wiring

Diagram

TC500-X24-S.12 Proportional 500N 500N~700N 24VAC 0(2)~10VDC 0(4)~20mA

0(2)~10VDC0(4)~20mA 3.85s/mm Wiring

Diagram 1

TC500-X220-S.12 Proportional 500N 500N~700N 220VAC 0(2)~10VDC 0(4)~20mA

0(2)~10VDC0(4)~20mA 3.85s/mm Wiring

Diagram 2

TC500-D24-S.12 3-position 500N 500N~700N 24VAC 3-position No 3.85s/mm WiringDiagram 3

TC500-D220-S.12 3-position 500N 500N~700N 220VAC 3-position No 3.85s/mm WiringDiagram 3

TC500-D24-SF10K.12 3-position with 0-10K resistance feedback 500N 500N~700N 24VAC 3-position 0-10K resistance

feedback 3.85s/mm WiringDiagram 4

TC500-D220-SF10K.12 3-position with 0-10K resistance feedback 500N 500N~700N 220VAC 3-position 0-10K resistance

feedback 3.85s/mm WiringDiagram 4

TC500-D24-SF2.12 3-position with 2 SPDT feedback 500N 500N~700N 24VAC 3-position 2 SPDT

feedback 3.85s/mm WiringDiagram 5

TC500-D220-SF2.12 3-position with 2 SPDT feedback 500N 500N~700N 220VAC 3-position 2 SPDT

feedback 3.85s/mm WiringDiagram 5

TC500-D24-SF3.12 3-position with active signal feedback 500N 500N~700N 24VAC 3-position active signal 3.85s/mm Wiring

Diagram 6

TC500-D220-SF3.12 3-position with active signal feedback 500N 500N~700N 220VAC 3-position active signal 3.85s/mm Wiring

Diagram 6

Type Type Discription Rating Force

ActualOutput Force

OperatingVoltage

Control Signal

Feedback Signal

Running Time

(50Hz)Wiring

Diagram

TC1000-X24-S.12 Proportional 1000N 1000N~1200N 24VAC 0(2)~10VDC 0(4)~20mA

0(2)~10VDC0(4)~20mA 3.85s/mm Wiring

Diagram 1

TC1000-X220-S.12 Proportional 1000N 1000N~1200N 220VAC 0(2)~10VDC 0(4)~20mA

0(2)~10VDC0(4)~20mA 3.85s/mm Wiring

Diagram 2

TC1000-D24-S.12 3-position 1000N 1000N~1200N 24VAC 3-position No 3.85s/mm WiringDiagram 3

TC1000-D220-S.12 3-position 1000N 1000N~1200N 220VAC 3-position No 3.85s/mm WiringDiagram 3

TC1000-D24-SF10K.12 3-position with 0-10K resistance feedback 1000N 1000N~1200N 24VAC 3-position 0-10K resistance

feedback 3.85s/mm WiringDiagram 4

TC1000-D220-SF10K.12 3-position with 0-10K resistance feedback 1000N 1000N~1200N 220VAC 3-position 0-10K resistance

feedback 3.85s/mm WiringDiagram 4

TC1000-D24-SF2.12 3-position with 2 SPDT feedback 1000N 1000N~1200N 24VAC 3-position 2 SPDT

feedback 3.85s/mm WiringDiagram 5

TC1000-D220-SF2.12 3-position with 2 SPDT feedback 1000N 1000N~1200N 220VAC 3-position 2 SPDT

feedback 3.85s/mm WiringDiagram 5

TC1000-D24-SF3.12 3-position with active signal feedback 1000N 1000N~1200N 24VAC 3-position active signal 3.85s/mm Wiring

Diagram 6

TC1000-D220-SF3.12 3-position with active signal feedback 1000N 1000N~1200N 220VAC 3-position active signal 3.85s/mm Wiring

Diagram 6

Page 4: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

Wiring Diagram

Feedback resistence Terminal Actuator axes

4-5 5-6 1-2-2 extend

restract

2 4 5 631

1-3

10K 0

0 10K 10K 00 10K

Wiring diagram1: proportional (24VAC) Wiring diagram 2: proportional (220VAC)

Wiring diagram3: 3-position Wiring diagram4: 3-position with 0~10K feedback

2 31COM DOWN UP

Power

Power

7 8 9DL

UL

4

2 3 1 COM DOWN UP

Power

4 5 6 7

UP DOWN

COM NO COM NO

Power

M

power Control signal

Feedback signal

B O O E Y

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Wiring diagram 6: 3-position with active signal feedback

Wiring diagram 5: 3-position with SPDT feedback

M

Controls signal

Feedback signal

L N O E Y AC220V

M

1 2 3

Power

Power

Terminal Shaft

1-2

1-3

extent

retract

Page 5: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

The PCB of Proportional typeActuator

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

5

The S2,S3 switch setting of Proportional type Actuator

PCB diagram 1: Proportional type (24VAC) TC500-X24../ TC1000-X24..

PCB diagram 2: Proportional type (220VAC) TC500-X220../ TC1000-X220..

self-stroking button

connecting terminalrunning light

power light

ON

S2 S3 switch

OFF

aperture potentiometer

B O O E Y

self-stroking button

connecting terminal

running light

power light

20%

0

II

UI

IO

UO

1 2 3 4

DA

RA

DW

UP

DF

RF

HS

LS

5 6 7 8

ON

S2

S2、S3 Switch

OFF

S3 S1

S2 S3 UI

II

aperture potentiometer

Switch Function Description

S2

1 Starting of control/ feedback signal

ON 20%:the starting control / feedback signal is 20% (namely 4~20mA or 2~10V)

OFF 0:the starting control / feedback signal is 0 (namely 0~20mA or 0~10V)

2 Type of control signal

ON II: current signal

OFF UI: voltage signal

3 Impedence match of control signal

ON UI: voltage signal

OFF II: current signal

4 Type of feedback signal

ON IO: current signal

OFF UO: voltage signal

S3

1 Operating mode ON DA:DA mode (when control signal increases, the actuator shaft extends )

OFF RA: RA mode (when control signal increases, the actuator shaft retracts)

2 Losing control signal mode

ON DW: When lose control signal (voltage type), actuator will provide a min. control signal internally When lose control signal (current type), actuator will provide a min. control signal internally

OFF UP: When lose control signal (voltage type), actuator will provide a max. control signal internally When lose control signal (current type), actuator will provide a min. control signal internally

3 Self-stroking modeON DF: Power on each time, self-stroking starts automatically (factory setting)

OFF RF: self-stroking starts only when press the red self-stroking button manually

4 SensitivityON HS: the high sensitivity of control signal ≤1%(100%~40%); ≤1.5%(40%~30%)

OFF LS: the low sensitivity of control signal ≤1.5%(100%~30%)

The setting of S2,S3 switch

Page 6: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

Nominal setting of S2,S3 switch

Proportional actuatorOpening adjustment potentiometer

Dimensions

Mounting Orientation

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

6

Medium is chilled/hot water Medium is steam

Installation downwards is forbidden Random direction is OK

Control signal: 4~20mA; Feedback signal: 4~20mA; DA mode; When lose control signal (current type), means input a minimum control signal, the actuator shaft retracts.

2 3 41

2 3 41

ON

OFF

S2

S3

ON

OFF 2 3 41

S2

2 3 41

S3

2 3 41

2 3 41

ON

OFF

S2

S3

ON

OFF 2 3 41

S2

2 3 41

S3

1.Dip switch sample when matched with electric control valve.

2.When matched with pressure independent control valve,the fifth dip switch is OFF, other dip switch is the same with electric control valve.

Control signal: 0~10VDC; Feedback signal: 0~10VDC; DA mode(factory setting); When lose control signal (voltage type), means input a minimum control signal, the actuator shaft retracts.

maximum opening

30

40

50

60 70

80

90

100

By aperture potentiometer, max. aperture can be setted from 100% to 30%. Flexibly adjust the relationship between the relative flow and opening of valve body, the factory default value is 100%.

Page 7: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

Installation Sheet

Technology Data

Eelectric parameter

Function Parameter

Electric Motor

Operating VoltageTC500-X24.../ TC1000-X24...TC500-X220.../ TC1000-X220...

Frequency

Power consumptionTC500/1000-D.../F10K/F3...TC500/1000-D...F2...TC500/1000-X...

Impedance(only for proportional type)voltage input impedancecurrent input impedance

Load requirements(only for proportional type)voltage output load requirementcurrent output load requirement

Up and down dead band Sensitivity

Control Signal typeTC500-D.../ TC1000-D...TC500-X.../ TC1000-X...

Control SignalTC500-D.../ TC1000-D...TC500-X.../ TC1000-X...

synchronous motor with permanent magnetic

24VAC ± 15%220VAC ± 15%

50Hz or 60Hz available

5.5VA7.5VA7.5VA

>100K<0.167K

>1K<0.5K

≤2%≤1%; ≤1.5%

3-positionproportional

24VAC/ 220VAC 0(2)~10VDC, 0(4)~20mA

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

7

1 2

3 4

Prepare for assembling the actuator, take down the sliding block firstly, and then disentangle the clip.

Keep the actuator’s axes and the valve’s stem concentric.Make these two connectiong faces coinciding. Then lock the two screws on the clip.

Pull the sliding block to the groove and lock it by two screws.

The status after assembled.

Observation hole

Page 8: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

EnvironmentCondition

Material

Dimension and Weight

Lifetime

Certificate

Feedback SignalTC500-X.../ TC1000-D...TC5000-D.../TC1000-D...TC500/1000-D..-F10KTC500/1000-D..-F2TC500/1000-D..-F3

IP degree

Permissible medium temperature

Running Enviroment tempreture: Enviroment humidity:

Transportation Enviroment tempreture: Enviroment humidity:

Storage Enviroment tempreture: Enviroment humidity:

CoverBracket

Product DimensionsWeight

Lifetime

Certificate

0(2)~10VDC,0(4)~20mAno0-10K resistance feedbackSPDT feedbackactive signal feedback

IP54

-25~+130℃(water) /2~+180℃(steam)

2~+220℃(high tempreature steam valve)/

2~+450℃(super-high tempreature steam valve) Notes: 1. When medium temperature below 0℃ (R12, R22, R134a, R202, glycol), the stem of the valve should be protected by electric heating cover(THOT-1/THOT-2) to avoid frosting and icing.

-10~+60℃ (3-position type)≤95% RH

-30~+65℃≤95% RH

-15~+50℃≤95% RH

PCdie casting aluminum(surface anti-rust process)

refer to the dimension figure

1.7Kg

100 thousand times

CE,RoHS,REACH

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

8

Page 9: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

9

Electric ActuatorStroke≤ 40mm. Rating force 1800N/ 3000N/5000N

TR1800-X.../ TR3000-X... /TR5000-X...: proportional control type, many kinds of control signal:

0(2)~10VDC,0(4)~20mA

TR1800-D.../ TR3000-D./TR5000-D...: 3-position control type

Max. actual force: 2000N/3500N/5500N

24VAC/220VAC can be selected

Visible window, PCB status can be seen clearly

LED display module can display the percentage of control signal and valve position feedback signal

and relative alarm information.

0-1K resistance feedback,0-10K resistance feedback, SPDT are optional(only 3-position)

Control signals: 0(2)~10VDC and 0(4)~20mA(only proportional control type)

PCB is made of 32bit signalchip + embedded operating system, adopt SMT paster welding

technology,precision of the electronic pieces using first-class brand home and aboard is 1%.

PCB has a function with defend wrong connection.

Selfstroke for proportional control type can automatic testing the max stroke of valve.

TR1800/3000-D...SeriesTR1800/3000-X...SeriesTR5000-D...SeriesTR5000-X...Series

These actuators used in 2-port, 3-port valve (TL/TF/TFR/TTF...series), whose stroke is less than 44mm.

Environment temperature: -10~60℃

Permissible medium temperature: -25~+150℃(water valve) / 2~+180℃(steam valve)

/2~+220℃(high temperature steam valve) / 2~+450℃(super-high temperature steam valve)

Notes:

When medium temperature below 0℃ (R12, R22, R134a, R202, glycol), the stem of the valve should be protected by stem heater (THOT-1/THOT-2) to avoid frosting and icing.

Application

Functions

Proportional typeTR1800-X.../TR3000-X.../TR5000-X...

Control singnal/vale feedback signal:0(2)~10VDC,0(4)~20mA

Datasheet No.:

TR1800/3000-02

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

TR1800-X.../TR3000-X.../TR5000-X... realize controlling by terminal O,E signal

Control singal at terminal O,E increasing: the actuator shaft extends, and valve stem retracts

Control singal at terminal O,E decreasing: the actuator shaft retracts, and valve stem extends

Control singal at terminal has no changing: the actuator shaft and valve stem stays in present position

Notes:

1.This DA mode was made before leaving factory, if RA mode needed(control signal increases, actuator

shaft retracts), just put the 5th switch of S2 from ON to OFF.

2. Pay attention to relationship between valve stem and valve opening,closing. Tiger Controls globe

valve is: valve stem retracts, valve opens. PICV is: valve stem retracts,valve closes.

Page 10: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

3-position control typeTR1800-D.../ TR3000-D... / TR5000-D... 3-position control signal

Ordering andTransportation

Combination device

Mechanical Design

Flow character

10

When ordering, please give clear indication on products type and accessories required, such as:

TR1800-X24-S.12.

Actuator and valve body are supplied in separated packages.

TR1800/TR3000/TR5000...electric actuator can be fitted with 2-port, 3-port TL...,TF... series valve body

whose stroke is less than 40mm.

Actuator have long service time without repair

TR1800/TR3000/TR5000...actuator with synchronous motor

TR1800-D.../ TR3000-D.../TR5000-D… actuator have limit switch

Manual device is standard configuration

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Type DN (mm) PN(Mpa) Datasheet No.TL…series 15...80 1.6/ 2.5 optional TL-02

TF... series 15...250 1.6/ 2.5 optional TF-02

TFR... series 15...250 1.6/ 2.5 optional TFR-02TTF...series 15...250 1.6/ 2.5 optional TTF-02

medium flow100%

control signal 100%

equal-linear curve

medium flow100%

control signal 100%

equal-percentage curve

Linear flow characteristic.

The relationship between control signal and flow is shown in the belowing figure:

Voltage on terminal 1 and 2: the actuator shaft extends, and valve stem retracts

Voltage on terminal 1 and 3: the actuator shaft retracts, and valve stem extends

No voltage on interminal 1,2 and1,3: the actuator shaft and valve stem stays in present position

Page 11: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

Debugging

Type Summary

1800N actuator

3000N actuator

11Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Type Type Discription Rating Force

ActualOutput Force

OperatingVoltage

Control Signal

Feedback Signal

Running Time

(50Hz)Wiring

Diagram

TR1800-X24-S.12 Proportional 1800N 1800N~2000N 24VAC 0(2)~10VDC 0(4)~20mA

0(2)~10VDC0(4)~20mA 3.13s/mm Wiring

Diagram 1

TR1800-X220-S.12 Proportional 1800N 1800N~2000N 220VAC 0(2)~10VDC 0(4)~20mA

0(2)~10VDC0(4)~20mA 3.13s/mm Wiring

Diagram 2

TR1800-D24-S.12 3-position 1800N 1800N~2000N 24VAC 3-position No 3.13s/mm WiringDiagram 3

TR1800-D220-S.12 3-position 1800N 1800N~2000N 220VAC 3-position No 3.13s/mm WiringDiagram 3

TR1800-D24-SF1K.12 3-position with 0-1K resistance feedback 1800N 1800N~2000N 24VAC 3-position 0-1K resistance

feedback 3.13s/mm WiringDiagram 4

TR1800-D220-SF1K.12 3-position with 0-1K resistance feedback 1800N 1800N~2000N 220VAC 3-position 0-1K resistance

feedback 3.13s/mm WiringDiagram 4

TR1800-D24-SF10K.12 3-position with 0-10K resistance feedback 1800N 1800N~2000N 24VAC 3-position 0-10K resistance

feedback 3.13s/mm WiringDiagram 5

TR1800-D220-SF10K.12 3-position with 0-10K resistance feedback 1800N 1800N~2000N 220VAC 3-position 0-10K resistance

feedback 3.13s/mm WiringDiagram 5

TR1800-D24-SF2.12 3-position with 2 SPDT feedback 1800N 1800N~2000N 24VAC 3-position 2 SPDT

feedback 3.13s/mm WiringDiagram 6

A. Connect actuator and valve body.

B. Turn off power of actuator.

C. Wiring power and control signal wires.

D. Set dip switch to needed position. After the setting,turn on power of actuator,setted function will come

into effect.(dip switch can be setted with power)

E. Turn on the power of actuator.

F. Actuator self-stroking: this step is for matching stroke of actuator and valve.

(1) Running light on PCB will keep flickering( frequency is 1Hz),actuator shaft extends to down limited

positon firstly, and then retracts to up limited position.(actuator will not be controlled by signal now)

(2) Running light stops flickering after 5 minutes of self-stroking. Self-stroking stops. By then, actuator

running direction can be controlled by control signal.

Remarks: If self-stroking is needed when power on, press down the red button on PCB over 3 seconds

until the running light flickering. Self-stroking phenomenon are the same as step (2), (3) above.

G.Kvs adjustment. By aperture potentiometer, max. aperture can be setted from 100% to 30%.

Ralationship between relative flow and opening can be adjusted flexibly.100%-40% opening has high and

low sensitivity. 40%~30% opening only has low sensitivity.

Note:

1. The factory default setting is automatic self-stroking,it means that actuator will repeat automatic self-

stroking when power on each time.

2.If you don't need automatic self-stroking function,you can set the 7th switch to OFF. It will change into

manual self-stroking(Phenomenon as same with (1),(2).

Type Type Discription Rating Force

ActualOutput Force

OperatingVoltage

Control Signal

Feedback Signal

Running Time

(50Hz)Wiring

Diagram

TR3000-X24-S.12 Proportional 3000N 3000N~3500N 24VAC 0(2)~10VDC 0(4)~20mA

0(2)~10VDC0(4)~20mA 3.13s/mm Wiring

Diagram 1

TR3000-X220-S.12 Proportional 3000N 3000N~3500N 220VAC 0(2)~10VDC 0(4)~20mA

0(2)~10VDC0(4)~20mA 3.13s/mm Wiring

Diagram 2

TR3000-D24-S.12 3-position 3000N 3000N~3500N 24VAC 3-position No 3.13s/mm WiringDiagram 3

TR3000-D220-S.12 3-position 3000N 3000N~3500N 220VAC 3-position No 3.13s/mm WiringDiagram 3

TR3000-D24-SF1K.12 3-position with 0-1K resistance feedback 3000N 3000N~3500N 24VAC 3-position 0-1K resistance

feedback 3.13s/mm WiringDiagram 4

TR3000-D220-SF1K.12 3-position with 0-1K resistance feedback 3000N 3000N~3500N 220VAC 3-position 0-1K resistance

feedback 3.13s/mm WiringDiagram 4

TR3000-D24-SF10K.12 3-position with 0-10K resistance feedback 3000N 3000N~3500N 24VAC 3-position 0-10K resistance

feedback 3.13s/mm WiringDiagram 5

TR3000-D220-SF10K.12 3-position with 0-10K resistance feedback 3000N 3000N~3500N 220VAC 3-position 0-10K resistance

feedback 3.13s/mm WiringDiagram 5

TR3000-D24-SF2.12 3-position with 2 SPDT feedback 3000N 3000N~3500N 24VAC 3-position 2 SPDT

feedback 3.13s/mm WiringDiagram 6

Page 12: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

5000N actuator

Wiring Diagram

8 - 9 9 - 10 1 - 2 extend 1 - 3 retract

1K 0 0 1K

0 1K1K 0

Electricityterminals shaft

feedback resistance

Wiring diagram1: proportional (24VAC ) Wiring diagram 2: proportional (220VAC)

Wiring diagram3: 3-position Wiring diagram4: 3-position with 1K feedback

12

M

power Control signal

Feedback signal

B O O E Y

M

Controls signal

Feedback signal

L N O E Y AC220V

Wiring diagram 6: 3-position with SPDT feedback

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Type Type Discription Rating Force

ActualOutput Force

OperatingVoltage

Control Signal

Feedback Signal

Running Time

(50Hz)Wiring

Diagram

TR5000-X24-S.12 Proportional 5000N 4500N~5500N 24VAC 0(2)~10VDC 0(4)~20mA

0(2)~10VDC0(4)~20mA 3.13s/mm Wiring

Diagram 1

TR5000-X220-S.12 Proportional 5000N 4500N~5500N 220VAC 0(2)~10VDC 0(4)~20mA

0(2)~10VDC0(4)~20mA 3.13s/mm Wiring

Diagram 2

TR5000-D24-S.12 3-position 5000N 4500N~5500N 24VAC 3-position No 3.13s/mm WiringDiagram 3

TR5000-D220-S.12 3-position 5000N 4500N~5500N 220VAC 3-position No 3.13s/mm WiringDiagram 3

TR5000-D24-SF1K.12 3-position with 0-1K resistance feedback 5000N 4500N~5500N 24VAC 3-position 0-1K resistance

feedback 3.13s/mm WiringDiagram 4

TR5000-D220-SF1K.12 3-position with 0-1K resistance feedback 5000N 4500N~5500N 220VAC 3-position 0-1K resistance

feedback 3.13s/mm WiringDiagram 4

TR5000-D24-SF10K.12 3-position with 0-10K resistance feedback 5000N 4500N~5500N 24VAC 3-position 0-10K resistance

feedback 3.13s/mm WiringDiagram 5

TR5000-D220-SF10K.12 3-position with 0-10K resistance feedback 5000N 4500N~5500N 220VAC 3-position 0-10K resistance

feedback 3.13s/mm WiringDiagram 5

TR5000-D24-SF2.12 3-position with 2 SPDT feedback 5000N 4500N~5500N 24VAC 3-position 2 SPDT

feedback 3.13s/mm WiringDiagram 6

8 - 9 9 - 10 1 - 2 extend 1 - 3 retract

10K 0 0 10K

0 10K 10K 0

Electricityterminals shaft

feedback resistance

Wiring diagram 5: 3-position with 10K feedback

Page 13: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

The PCB Figure of Proportional typeActuator

PCB diagram 2: Proportional type (220VAC) TR1800-X220../ TR3000-X220../ TR5000-X220..

PCB diagram 1: Proportional type (24VAC) TR1800-X24../ TR3000-X24.. / TR5000-X24..

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

S1

self-stroking button

function digit

number digit

ERR

RUN

B O O E Y

connecting terminal1 2

3

4

5 6

UL DL AL

auxiliary terminal

error light

running light

CPU

maximumopening

aperture potentiometerr

2 3 41

ON

OFF

S22 3 41

S3

1 2 3 4

20%

0

II

UI

UI

II

IO

UO

5 6 7 8

DA

RA

DW

UP

DF

RF

HS

LSS2 S3

30

40

50

60 70

80

90

100

24VAC

S1

self-stroking button

function digit

number digit

ERR

RUN

L N O E Y

connecting terminal1 2

3

4

5 6

UL DL AL

auxiliary terminal

error light

running light

CPU

maximumopening

aperturepotentiometer

2 3 41

ON

OFF

S22 3 41

S3

1 2 3 4

20%

0

II

UI

UI

II

IO

UO

5 6 7 8

DA

RA

DW

UP

DF

RF

HS

LSS2 S3

30

40

50

60 70

80

90

100

220VAC

13

The S2,S3 switch setting of Proportional type Actuator

Switch Function Description

S2

1 Starting of control/ feedback signal

ON 20%:the starting control / feedback signal is 20% (namely 4~20mA or 2~10V)

OFF 0:the starting control / feedback signal is 0 (namely 0~20mA or 0~10V)

2 Type of control signal

ON II: current signal

OFF UI: voltage signal

3 Impedence match of control signal

ON UI: voltage signal

OFF II: current signal

4 Type of feedback signal

ON IO: current signal

OFF UO: voltage signal

S3

1 Operating mode ON DA:DA mode (when control signal is increasing, the actuator axes extends )

OFF RA: RA mode (when control signal is increasing, the actuator axes retracts)

2 Losing control signal mode

ON DW: When lose control signal (voltage type), actuator will provide a min. control signal internally When lose control signal (current type), actuator will provide a min. control signal internally

OFF UP: When lose control signal (voltage type), actuator will provide a max. control signal internally When lose control signal (current type), actuator will provide a min. control signal internally

3 Self-stroking modeON DF: Power up each time, self-stroking starts automatically (factory setting)

OFF RF: self-stroking starts only when press the red self-stroking button manually

4 SensitivityON HS: the high sensitivity of control signal ≤1%(100%~40%); ≤1.5%(40%~30%)

OFF LS: the low sensitivity of control signal ≤1.5%(100%~30%)

Page 14: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

14Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

Nominal setting of S2,S3 switch

Control signal: 0~10VDC; Feedback signal: 0~10VDC; ( factory setting)DA mode; When lose control signal (voltage type), means input a minimum control signal, the actuator shaft retracts.

Control signal: 4~20mA; Feedback signal: 4~20mA; DA mode; When lose control signal (current type), means input a minimum control signal, the actuator shaft retracts.

2 3 41

2 3 41

ON

OFF

S2

S3

ON

OFF 2 3 41

S2

2 3 41

S3

2 3 41

2 3 41

ON

OFF

S2

S3

ON

OFF 2 3 41

S2

2 3 41

S3

1.Dip switch sample when used with electric control valve.

2.When used with Pressure independent control valve,the fifth dial code is OFF,other dip switch are the same with electric control valve.

By aperture potentiometer, max. aperture can be setted from 100% to 30%.Flexibility adjust the relationship between the relative flow and opening of valve body,the factory default value is 100%.

Proportional actuatorOpening adjustment potentiometer

maximum opening

30

40

50

60 70

80

90

100

Mounting Orientation

Dimensions

Medium is chilled/hot water Medium is steam

Installation downwards is forbidden random direction is OK

44

Page 15: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

Electric Parameter

Function Parameter

Electric Motor

Operating VoltageTR1800-X24.../ TR3000-X24.../TR5000-X24..TR1800-X220.../ TR3000-X220.../TR5000-X220

Frequency

Power consumptionTR1800/3000/5000-D...TR1800/3000/5000-D...F1K/F10K/F2...TR1800/3000/5000-X...

Impedance (only for proportional type)voltage input impedancecurrent input impedance

Load requirements(only for proportional type)voltage output load requirementcurrent output load requirementUp and down dead band

Sensitivity

Control Signal typeTR1800-X.../TR3000-X.../TR5000-X...TR1800-D.../TR3000-D.../TR5000-D...

Synchronous motor with permanent magnetic

24VAC± 15%220VAC± 15%

50Hz or 60Hz available

13VA13VA15VA

>100K<0.167K

>1K<0.5K≤2%

≤1% ≤1.5%

proportional3-position

15

Technology Data

Installation Sheet

Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com

1.Prepare for assembling the actuator, take down the fixed litting stly,and then disentangle the clip.

2.Keep the actuators’s axis and valve’s stem concentric. Make these two connecting faces keep coinciding and Observe by observation hole.Put the actuator on the convex platform of valve body.Then lock the two screws on the clip.

3.Full the fixed litting to the grooved and lock by two screws.

4.The status after assembled.

Observation hole

Page 16: Electric Actuator - Tiger Control · Electric Actuator Suitable for valve ... // 2 ... will repeat automatic self-stroking when power on each time. 2.If you don't need automatic ...

EnvironmentCondition

Material

Control SignalTR1800-X.../TR3000-X.../TR5000-X...TR1800-D.../TR3000-D.../TR5000-D...

Feedback SignalTR1800-X.../TR3000-X.../TR5000-X... TR1800-D.../TR3000-D.../TR5000-D..TR1800/3000/5000-D...-SF0K.12TR1800/3000/5000-D..-SF10K.12TR1800/3000/5000-D..-SF2.12

IP degree

Permissible medium temperature

Running Enviroment tempreture: Enviroment humidity:

Transportation Enviroment tempreture: Enviroment humidity:

Storage Enviroment tempreture: Enviroment humidity:

CoverBracketGear

Product DimensionsWeight

Lifetime

certificate

0(2)~10VDC, 0(4)~20mA24VAC/220VAC

0(2)~10VDC, 0(4)~20mAno0-1K resistance feedback0-10K resistance feedbackSPDT feedback

IP54

-25~+150℃(water)/2~+180℃(steam)2~+220℃(high tempreature steam valve) /2~+450℃(super-high tempreature steam valve)Notes: 1. When medium temperature is below 0℃ (R12, R22, R134a, R202, glycol), the stem of the valve should be protected by electric heating cover(THOT-1/THOT-2) to avoid frosting and icing.

-10~+60℃ ≤95% RH

-30~+65℃≤95% RH

-15~+50℃≤95% RH

aluminum die castingaluminum die casting(surface anti-rust process)metal gear

refer to the dimension figure 5.2Kg

100 thousand times

CE, RoHS, REACH

16Tiger Controls Equipment Co., Ltd

Http:// www.tiger-control.com