Elect Protection

download Elect Protection

of 53

Transcript of Elect Protection

  • 7/31/2019 Elect Protection

    1/53

    ELECTRICAL PROTECTION(PMI Workshop)

    ENGINEERING

    Knowledge Management System

    ELECTRICAL ENGG.

  • 7/31/2019 Elect Protection

    2/53

    WORKSHOP ON ELECTRICAL PROTECTION

    @ PMI

    TODAYS TOPIC

    (1) PROTECTION OF AUX POWER SUPPLY SYSTEM

    (2) PROTECTION OF GENERATOR

  • 7/31/2019 Elect Protection

    3/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    AUXILIARY POWER SUPPLY SYSTEMIt is the Electric power supply systemrequired to run the auxiliary equipment ofa power plant smoothly, reliably andeconomically. In case of interruption itshould be possible to restore in fastestpossible time.

    The auxiliary power system is bestdescribed by the Key SLD.

    KSLD.pdf/SLD.pdf

  • 7/31/2019 Elect Protection

    4/53

  • 7/31/2019 Elect Protection

    5/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    ELEMENTS OF Aux Power Sup System ARE Transformers

    Motors

    Switchgears

    Connectors like Bus-duct/Cables DC System

    All these above elements are to be protectedagainst faults and abnormal operating

    conditions. Therefore the other element is Protection system

  • 7/31/2019 Elect Protection

    6/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    TRANSFORMER PROTECTION

    Transformer faults are of 5 categories

    Winding & terminal faults(70% of all faults)

    Core faults Tank faults

    Abnormal operating conditions

    Un-cleared external faults

  • 7/31/2019 Elect Protection

    7/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    SEVERAL CASES OF FAULTS

    Earth fault with star connected transformerhaving NGR (Neutral Grounding Trans/Resitr.)

    In this case Fault Current depends on(i) NGR value

    (ii) Distance of fault from the neutral

    Primary side relay can not detect if the fault is at< 30% distance away from neutral.

    It would be necessary to provide a 64R LV

  • 7/31/2019 Elect Protection

    8/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    100%

    100%Distance From Neutral

    Earth

    FaultCurrentPrimary Current

    Secondary Fault Current

    10%

    30%

  • 7/31/2019 Elect Protection

    9/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Earth fault with star connected transformerhaving Neutral solidly grounded

    In this case Fault Current depends on

    (i) Transformer Impedence only; NGR value is zero

    (ii) Distance of fault from the neutral

    This is the case for LT Transformers where thesystem is solidly earthed. Heavy earth fault currentflows in the secondary and primary current is alsosubstantial.

  • 7/31/2019 Elect Protection

    10/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    20

    100%Distance From Neutral

    PerUnit

    EarthFaultCurrent Primary Current

    Secondary Current

    10

    15

    5

  • 7/31/2019 Elect Protection

    11/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Phase to Phase fault

    This case shall be like the previous slide. There isno additional resistance to restrict phase to phasefault so heavy fault current flows in the secondaryand primary.

  • 7/31/2019 Elect Protection

    12/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Inter-turn fault

    This is not very likely phenomenon , unless thetransformer is subjected to several Short-Circuit

    stress.For transformers connected to O/H line directly,very steep-front high voltage may cause inter-turninsulation failure & inter-turn fault.

    Shorted turns shall have very high current butprimary relay may not see the fault as very high turn

    ratio shall be applicable for the shorted turns.

  • 7/31/2019 Elect Protection

    13/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    100

    25%

    Percent Of Winding turns Shorted

    Per Unit

    FaultCurrent

    Primary input Current

    Fault Current in shorted turns

    60

    80

    40

    20

    0 5 10 15 20

    10

    8

    6

    4

    2

    Per Unit

    PrimaryCurrent

  • 7/31/2019 Elect Protection

    14/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Core fault

    Any conducting bridge across laminated structure ordefective core insulation may allow eddy current toflow across. This will generate local heating anddegeneration of transformer oil and further gasgeneration.

    Electrical relays shall not be able to detect thisother than the gas operated relays.

  • 7/31/2019 Elect Protection

    15/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Tank fault

    This fault results in

    loss of cooling oil

    over heating of core & winding

    deterioration of insulation

    Electrical relays shall not be able to detect this

    unless it develops into an electrical fault.

  • 7/31/2019 Elect Protection

    16/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    EXTERNAL FAULTSOver load

    Transformer is designed based on temperature risecriteria. Any over load is viewed in terms of theheating caused by the over load.

    Over load can be allowed considering the initialthermal status of the transformer. IEC 60354 givesthe guide for transformer overloading.

    The time constant of forced cooled transformers is

    less as compared to that of the natural cooled ones.

  • 7/31/2019 Elect Protection

    17/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    EXTERNAL FAULTSSystem Fault

    Current fed by a transformer is responsible forheating of its winding. Heat generated isproportional to Sq of the current.

    For a transformer having 4% impedance may feedup to 25 times its rated current. Which means 625times heat will be generated as compared to its fullload operation.

    Normally transformers are specified to stand thefault for 2 secs. Over current relays are provided to

    clear the fault before it reaches the limit.

  • 7/31/2019 Elect Protection

    18/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    EXTERNAL FAULTSOver voltage

    There could be two types of over voltage

    Transient O/V

    Power frequency O/VPower frequency over voltage causes stress

    in insulation, increase in the value of Fluxassociated with excessive increase ofmagnetizing current.

  • 7/31/2019 Elect Protection

    19/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    EXTERNAL FAULTSReduced system frequency

    Like power frequency over voltage, itincrease the value of Flux associated withexcessive increase of magnetizing current.

    Reduction in frequency associated withincrease in voltage would be very harmful tothe transformer.

    For bigger transformer V/f protection isprovided.

  • 7/31/2019 Elect Protection

    20/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    OVER HEATING OF TRANSFORMERRating of a transformer is based on a specificvalue of allowable temperature.

    At low temperature over loading may beallowed as per IEC60354 guidelines.

    Sustained over load ,if it takes thetemperature of the winding 10 deg C abovepermissible temperature, the life of insulationwill be eaten away by about a half of original.

    WTI/OTI is used for alarm as well as tripping

    of the HV side breaker. LV side is isolated byinter-tripping of LV breaker.

  • 7/31/2019 Elect Protection

    21/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    SUMMARY OF FAULTS AND PROTECTION(i) Primary winding Ph-Ph 87,50

    (ii) Primary winding Ph-E 87,50

    (iii) Secondary winding Ph-Ph 87

    (iv) Secondary winding Ph-E 87,64R(v) Inter-turn 87,63

    (vi) Tank Fault 87,63

    (vii) Core Fault 87,63

  • 7/31/2019 Elect Protection

    22/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    SUMMARY OF FAULTS AND PROTECTION

    (i) Primary winding Ph-Ph 87,50(ii) Primary winding Ph-E 87,50

    (iii)Seccondary winding Ph-Ph 87

    (iv) Seccondary winding Ph-E 87,64R

    (v) Inter-turn 87,63

    (vi) Tank Fault 87,63(vii) Core Fault 87,63

    (viii) Over Fluxing 99

    (ix) Over Loading/ Design margin,WTI(Alarm/Trip)Heating OTI (Alarm), Cooler Alarm

    (x) Gas generation 63(xi) Fire Protection Trip and Alarm

  • 7/31/2019 Elect Protection

    23/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    PROTECTIONS FOR Stn TRANSFORMER

    (i) 87 Internal Ph-Ph / Ph-Earth(ii) 51 Ph-Ph / Ph-Earth (Covers up to 11kv

    System also. So def time for co-ordination)

    (iii) 64R HV HV Winding Ph-Earth

    (iv) 64R LV LV Winding Ph-Earth

    (v) 51N LV Winding Ph-Earth (upto 1kV)

    (vi) 63

    (vii) WTI Alarm/Trip

    (viii) OTI Alarm/Trip

    (ix) Cooler/OLTC Alarm(x) Fire Protection Alarm/Trip

  • 7/31/2019 Elect Protection

    24/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    PROTECTIONS FOR UNIT TRANSFORMER

    (i) 87 Internal Ph-Ph / Ph-Earth(ii) 51 Ph-Ph / Ph-Earth (Covers up to 11kv

    System also. So def time for co-ordination)

    (iii) 64G1/64G2 HV Winding Ph-Earth

    (iv) 64R LV LV Winding Ph-Earth

    (v) 51N LV Winding Ph-Earth (upto 1kV)

    (vi) 63

    (vii) WTI Alarm/Trip

    (viii) OTI Alarm/Trip

    (ix) Cooler/OLTC Alarm(x) Fire Protection Alarm/Trip

  • 7/31/2019 Elect Protection

    25/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    PROTECTIONS FOR LT TRANSFORMER

    (i) 87 (>5MVA) Internal Ph-Ph / Ph-Earth--OR--

    50 (

  • 7/31/2019 Elect Protection

    26/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    MOTORS PROTECTIONS

    Causes for Motor failure

    External

    Unbalanced Supply

    Under Voltage

    Single Phasing

    Reverse Phase Sequence

  • 7/31/2019 Elect Protection

    27/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    MOTORS PROTECTIONS

    Causes for Motor failure

    Internal

    Bearing Failure

    Winding Fault

    Over Load

  • 7/31/2019 Elect Protection

    28/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    POSSIBLE FAULTS & ITS PROTECTION

    Thermal (Over Load) protection

    Majority of winding failure are caused byover loading on either unbalanced supplyvoltage or by single phasing.

    Excessive heating leads to windinginsulation failure and further electricalFaults.

    Sustained over load of a few percentagemay result in premature aging of the motor

    insulation.

  • 7/31/2019 Elect Protection

    29/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Start/Stall Protection

    Motor draws around 6 times current duringstarting. But it is not a constant value. Thequantum of current reduces as it reaches itsrated speed.

    So to distinguish starting from stalling, it is

    required to measure the time also alongwith the inrush of current.

    Some times it is found that starting time ismore than safe stalling time. Then itbecomes difficult to provide the stalling

    protection.

  • 7/31/2019 Elect Protection

    30/53

  • 7/31/2019 Elect Protection

    31/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Stalling Protection when tSTARTING < tSTALLINGIt is very simple to have this protection byfollowing current and time settings:

    tSTARTING < tSETTING < tSTALLING

    and

    IFULL-LOAD< ISETTING < I STARTING

  • 7/31/2019 Elect Protection

    32/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Stalling Protection when tSTARTING > tSTALLINGOver and above time & current sensing a speedswitch signal is also required to sense that themotor has taken-off. Here as motor speeds up,current reduces and cooling increases and motor

    remains safe even after tSTARTING exceeds tSTALLINGThe following current and time settings:

    tSTARTING< tSETTING< tSTALLING and IFULL-LOAD< ISETTING < I STARTINGwhen ANDED with the speed switch contactgives desired stalling protection. The speed switchsetting is normally kept at 20%.

  • 7/31/2019 Elect Protection

    33/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    SHOULD A MOTOR STALL WHILE RUNNING

    The motor current will increase from rated valueto its starting current value. Presently thissituation is protected by 51I,alarmed by 50Aand RTD tripping through control system.

    However with numerical relays it is possible tocapture the conditions of Motor has startedand current is nominal which signifies motorrunning. Now if current again reaches itsstarting time value , stalling situation can be

    detected.

  • 7/31/2019 Elect Protection

    34/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    However, this protection shall operate in theevent of restarting of motors after a voltage dip( EHV Fault nearby or Auto C/O).

    The difference could be only the duration ofhigh current flow which will be less ascompared to the situation at the time of starting.

  • 7/31/2019 Elect Protection

    35/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Short circuit Protection

    Motor short circuit protection is provided formotor terminal flash-over or major windingfaults.

    Motor instantaneous over current protection(50) is provided for this. However 50 settingis kept at 800% of rated current to take careof motor starting.

  • 7/31/2019 Elect Protection

    36/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Earth Fault Protection

    Any fault due to any cause, in statorwinding will result into an earth fault.

    For LT motors, where system is solidly

    earthed, earth fault relay in the residualcircuit with 20% setting serves the purpose.

    HT motors where system is earthed throughNGR, sensitive earth fault relay with CBCTis provided.

  • 7/31/2019 Elect Protection

    37/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Under Voltage Protection

    Motor may stall under severe under voltagecausing serious damage to it.

    Time delayed under voltage trip is providedhaving system voltage falling below 80% fora duration of 1000 mS.

  • 7/31/2019 Elect Protection

    38/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    RTD Temperature Detection

    This gives actual direct measurement ofmotor temperature. Severe over load/development of hot spot is detected byRTD.

    RTDs are provided in all HT motors whichare embedded during manufacturing.

    RTDs are fed into the control system whichfurther sends trip signal/ generates alarm.

  • 7/31/2019 Elect Protection

    39/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Protection against excessive no. of Starts

    Starting should be blocked if the permittednumber of starts are exceeded.

    It is possible to build a thermal replica of the

    motor in a numerical relay which will allownumber of starts considering actual thermalstatus of the motor.

  • 7/31/2019 Elect Protection

    40/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Summary Of Motor Protection

    HT Motors87 For >2000MW Ph-Ph & Ph-Erth(Intnl)

    50x3 For tSTALLINGU/V For under voltage protection

  • 7/31/2019 Elect Protection

    41/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Summary Of Motor Protection

    LT Motors (Breaker Controlled)50x3 For Ph-Ph & Ph-Erth51x2 For Over Load (IDMT)

    50Ax1 For Alarm

    50N1 For Earth FaultU/V For under voltage protection

  • 7/31/2019 Elect Protection

    42/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    Summary Of Motor Protection

    LT Motors (Contactor Controlled)

    Fuse For Ph-Ph & Ph-Erth

    49 For Over Load (IDMT)U/V Contactors drop @ V

  • 7/31/2019 Elect Protection

    43/53

  • 7/31/2019 Elect Protection

    44/53

    WORKSHOP ON ELECTRICAL PROTECTION @ PMI

    OUR NEXT TOPIC

    GENERATOR PROTECTION

  • 7/31/2019 Elect Protection

    45/53

    GEN. PROTN. PHILOSOPHY

    The numerical relays constituting the protectionfor each Main Generator Circuit, is configuredinto two independent Numerical ProtectionSystemseach fed from a separate DC supply,

    At least one numerical protection system shall bealways available to detect and operate for anytype of fault in the Generator Circuit, undercondition of failure of the other numericalprotection system AND/OR on failure of theassociated DC supply systems of other numericalprotection system.

  • 7/31/2019 Elect Protection

    46/53

    AC/DC SEGREGATION

  • 7/31/2019 Elect Protection

    47/53

    CLASSIFICATION OF GENERATORPROTECTIONS

    INTERNAL FAULTi) PHASE TO PHASE FAULTS PROTECTION

    ALL DIFFERENTIAL PROTECTIONS

    II) PHASE TO EARTH PROTECTION FOR STATOR WINDING64G1, 64G2, 64R, 64IT

    EXTERNAL FAULT

    21G, 51NGT, 46G,

    ABNORMAL OPERATING CONDITIONS

    98, 50GDM, LFPR/RP, 59, 99

  • 7/31/2019 Elect Protection

    48/53

    PROTECTION FUNCTION CLASSOF TRIP

    Remark on grouping ofprotection

    Generator Differential Protection, 3 pole (87 G) havingoperating time of 25 milli sec. or lower at five timesthe current rating.

    A

    Overall Differential Protection (87GT). A

    87 G and 87 GT shall be on twodifferent channels of protection.

    Generator Transformer Differential protection(87 T)

    A 87 T shall be in a differentchannel than 87 GT

    Over hang differential protection(87 HV) A 87 HV shall be in a differe ntchannel than 87T

    Stator Earth Fault Protection covering 100% of winding(64G1), operating on low frequency signal injectionprinciple suitable for continuous monitoring of statorinsulation even during machine shut down.

    A

    Stator Standby Earth Fault Protection covering 95% ofwinding (trip) (64 G2) with adjustable time delay.

    A

    64 G1 and 64 G2 shall be ontwo different channels ofprotection.

    Inter-turn Fault Protection (95G1), throughcomparison of zero sequence voltage on generatorphase and neutral side.

    A

    Duplicated Loss of field protection (40G1/2 ). A 40G1 and 40G2 shall be on twodifferent channels of protection.

    Back up Impedance Protection, 3 pole (21G) alongwith suitable timer for Co -ordination with lineprotections

    A

    Backup Earth Fault Protection on GeneratorTransformer HV neutral (51NGT)

    A

    21 G and 51 NGT be indifferent channels

    Negative Sequence Current Protection, alarm and I 22t

    element for trip (46G) matching with the machinecharacteristics.

    A

    Duplicated Low -Forward Power / reverse powerInterlock for steam turbine generator (37 /32G1 &37/32 G2), each having two stages,

    a) short time delayed interlocked with turbinetrip

    b) long time delayed independent ofturbine trip.

    B

    A

    37/32 G1 and 37/32 G2 shall bein two different channels ofprotection

    Two Stage Rotor Earth Fault Protection (alarm & trip)

    operating on principle of continuously monitoring rotorinsulation value even during machine shut downperiod (64F).

    A

    CHANNEL WISE GROUPING AND TRIPPING LOGIC

  • 7/31/2019 Elect Protection

    49/53

    Definite Time Delayed Over -Voltage Protection(59G) for alarm and trip.

    A

    Generator Under Frequency Protection with alarmand stage tripping (81G) with df/dt elements.

    C

    Over Fluxing Protection (99) for Generator /Generator Transformer having inverse time

    characteristics suitable for Generator /GeneratorTransformer over fluxing capability.

    A

    Over Flux function (99) shallbe in a different channel thanO/V and U/F functions

    Accidental Back Energisation protection foraccidental closu re/flashover of EHV breaker orEHV disconnecting switch (50GDM)

    1. Based on Under voltage and Over currentMeasurement

    2. Over current relay enabled/disabled byHV CB aux contact and drop out/pick uptimers.

    A

    A

    50 GDM based on th e twoprinciple shall be on twodifferent channels.

    Instantaneous and time delayed Over Currentprotection to be used on HV side of excitationtransformer.

    A

    Generator Pole slipping protection A

    Generator under voltage relay for interlocks

    Unit Transformer Differential Protection, 3 pole(87UT)

    A

    Unit Transformer LV back-up earth fault protection( 51NUT).

    A

    Unit Transformer LV REF (64 UT LV) A

    Unit transformer back -up over current protection(51UT).

    A

    87 UT & 51 NUT can be in onechannel and 64 UT LV & 51UTshall be in another channel.

    Gen Transformer OTI/WTI trip Turbine Trip After turbine trip through classB other breakers are tripped.GT WTI/OTI IN DIFFCHANNELS

    Gen Transformer Buchholtz, PRD /othermechanical Protections

    A GT BUCH & PRD IN DIFFCHANNELS

    Unit Transformer OTI/WTI trip UT LV CB Trip& signal forchange over ofunit board.

    UT WTI & OTI IN DIFFCHANNELS

    Unit Transformer Buchholtz, PRD /othermechanical Protections

    A UT BUCH & PRD IN DIFFCHANNELS

    CLASS A : TO TRIP HVCB,TURBINE,FIELD, UT LV CBCLASS B : TO TRIP HVCB,FIELD,UT LV CB : CLASS C : TO TRIP HV CB

    CHANNEL WISE GROUPING AND TRIP LOGIC

  • 7/31/2019 Elect Protection

    50/53

    TypicGeneprotesche

  • 7/31/2019 Elect Protection

    51/53

    GRP NETWORKING The numerical relays constituting the protectionsystem for all the Generator Circuits shall be wired

    to a central operator work station, located in CentralControl Room .

    From the operators work station, it shall be possible to extract all the alarms,

    events and fault data captured by numerical relays change / upload relay Settings for various numerical relays.

    Sharing of the data with switchyard SAS throughSubstation Level LAN shall also be possible.

    The communication protocol IEC 61850 is preferred

    for Generator Circuit LAN.

  • 7/31/2019 Elect Protection

    52/53

    THANKS

    FORPATIENT HEARING

    !

  • 7/31/2019 Elect Protection

    53/53