ELE 351L lab 3
-
Upload
asad-ur-rehman -
Category
Documents
-
view
217 -
download
0
Transcript of ELE 351L lab 3
-
8/10/2019 ELE 351L lab 3
1/11
ELE 351L
Electrical Energy Conversion
Section 1
LAB INSTRUCTOR:Kashif Bangash
Lab report 3
Single Phase Transformer Modeling
Muhammad Shafiq Asad - 37907
Asad Ur Rehman Muhammad-41798
Sheehan Fernandes-49935
Sohail Nouraei -48489
Submitted on: 11/11/2014
-
8/10/2019 ELE 351L lab 3
2/11
Page 2of 11
Abstract
This lab is going to be about single phase transformer modeling. First of all, in this lab
we were required to learn how to appropriately model single phase transformers and
transformer banks. Secondly, we were going to carry out transformer open circuit and
short circuit tests. Lastly, we had to study the transformer regulation and efficiency with
varying loads. The important equations needed to understand before performing the
experiments were:
Open circuit test
short circuit test
a
SNpN
(t)sV
(t)pV
(t)si*sN(t)pi*pN
cX1j
cR1Y
E
ocVocI
YE
ocIocVocPcosp.f
ocVocIY
E
scIscVZ
SE
scIscVscPcosp.f
eq
jX
eq
R
scI
scVZSE
-
8/10/2019 ELE 351L lab 3
3/11
Page 3of 11
Table of Contents
Section Page Number
Abstract 2
Procedure 4
Conclusion 11
-
8/10/2019 ELE 351L lab 3
4/11
Page 4of 11
Procedure
Open Circuit Test
Figure 1
Table 1
Short Circuit Test
Figure 2
Quantity Value
V 400 V
I 0.05 A
P 0 W
Watt meter
A
Watt meter
-
8/10/2019 ELE 351L lab 3
5/11
Page 5of 11
Note:- All below values are of primary side not secondary side of transformer
Quantity Value Units
V 60 V
I 1.5 A
P 85 W
Table 2
Q1) With the information above from Table 1 & 2 compute the equivalent circuit of the
transformer of the form provided
|YE| = IOC/VOC= 0.05 / 400 = 0.000125
= cos-1
( POC / IOC VOC) = cos-1
( 0 / ( 400 x 0.05) = cos-1
( 0 )
-
8/10/2019 ELE 351L lab 3
6/11
Page 6of 11
= 90
YE = 0.00012590 = 0 + 0.000125j
GC= 0 and BM = 0.000125
RC = 1 / GC =
RC =
XM = 1/ BM
XM = 8000j
|ZSC| = VSC / ISC= 60/1.5 = 40
= cos-1
( PSC / ISC VSC) = cos-1
( 85 / ( 60 x 1.5) = 19.19
ZSC = 40 19.19 = 37.78 + 13.15j
Req= 37.78
Xeq= 13.15j
Question 3:
Open Circuit Test
-
8/10/2019 ELE 351L lab 3
7/11
Page 7of 11
Quantity Value
V 400 V
I 0.05 A
P 0 W
Short Circuit Test
Quantity Value Units
V 100 V
I 2.6 A
P 140 W
Q2) With the information above from steps 1 & 3 compute the equivalent circuit of the
transformer of the form provided.
|YE| = IOC/VOC= 0.05 / 400 = 0.000125
= cos-1
( POC / IOC VOC) = cos-1
( 0 / ( 400 x 0.05) = cos-1
( 0 )
= 90
YE = 0.00012590 = 0 + 0.000125j
-
8/10/2019 ELE 351L lab 3
8/11
Page 8of 11
GC= 0 and BM = 0.000125
RC = 1 / GC =
RC =
XM = 8000j
|ZSC| = VSC / ISC= 100/2.6 = 38.46
= cos-1
( PSC / ISC VSC) = cos-1
( 1400 / ( 100 x 2.6) = 57.42
ZSC = 38.46 57.42 = 20.71 + 32.41j
Req= 20.71
Xeq= 32.41j
1. Connect voltmeter to the secondary side of the same transformer used in step 1 and
adjust the input voltage at the primary side to 400 V(line to line voltage) then measure
the no load voltage(no load voltage mean connect voltmeter to the secondary side of
transformer when no load is connected to the secondary side of transformer)
Vnl = 400 V
Voltage regulation: Compares the output voltage of the transformer at no load with the output
voltage at full load
100%
fls,V
fls,V
nls,V
VR
100%
fls,V
fls,V/pV
VR
a
-
8/10/2019 ELE 351L lab 3
9/11
Page 9of 11
The transformer efficiency can be computed by:
= (PinCore lossCopper loss)/Pin
2.
Connect resistive load (R = 685.7 ) to the secondary side of the transformer in step 4
and two Watt meter one to the primary side and another one to the secondary side
(figure 3). Then record your measurements of Vfl, Pinand Poutin the following table. Also
compute the voltage regulation and the efficiency of the transformer.
Vfl Pin Pout VR
370 V 210 W 190 W 8.11 % 9.52 %
Table 5
3. Repeat step 5 but use inductive load(XL=j 685.7 ) at the secondary side
Vfl Pin Pout VR
395 V 70 W 40 W 1.27 % 42.9 %
Table 6
4. Repeat step 5 but use capacitive load(XL= -j 685.7 ) at the secondary side
Vfl Pin Pout VR
405 V 10 W -5 W 1.23 % 50 %
Table 7
-
8/10/2019 ELE 351L lab 3
10/11
Page 10of 11
5. Repeat step 5 but connect load of ( 685.7 + j 685.7 )
Vfl Pin Pout VR
380 V 120 W 110 W 5.26 % 8.33%
Table 8
-
8/10/2019 ELE 351L lab 3
11/11
Page 11of 11
Conclusion
The purpose of this experiment was to familiarize us with the concept of open circuit
and short circuit tests and how to carry them out. First, we measured the values of voltage,
current and power using open circuit and short circuit test. Then, we used the values obtained
from the tests to calculate the equivalent circuit of the given transformer.
The second part of this experiment was aimed to increase our understating of the
concept of voltage regulation and efficiency as well as the reactions different types of loads
have on the output power. Finally, we connected different types of loads to our system
(resistive, capacitive, inductive and mixed) and measured the change in the circuit's voltage
regulation and efficiency. We saw that the voltage regulation is at its highest when we use a
purely resistive load and the efficiency is at its highest when the load is purely capacitive.