Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions...

14
Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130 Liberty Street Little Ferry, NJ 07643 Karl Environmental Group Project #: 18-0913 January 8, 2019 Prepared for: Mr. Lou Albanese Supervisor of Buildings & Grounds Little Ferry School District 130 Liberty St. Little Ferry, NJ 07643 Prepared by: Karl Environmental Group 20 Lauck Road Mohnton, PA 19540 Tel: (800) 527-5581 Fax: (610) 856-5040

Transcript of Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions...

Page 1: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Effective and Economical

Environmental Solutions

Lead-in-Drinking Water Screening Little Ferry School District

Trailer testing 130 Liberty Street

Little Ferry, NJ 07643

Karl Environmental Group Project #: 18-0913

January 8, 2019

Prepared for:

Mr. Lou Albanese

Supervisor of Buildings & Grounds Little Ferry School District

130 Liberty St. Little Ferry, NJ 07643

Prepared by:

Karl Environmental Group 20 Lauck Road

Mohnton, PA 19540 Tel: (800) 527-5581 Fax: (610) 856-5040

Page 2: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Karl Environmental Group Project 18-0913

VOICE: (610) 856-7700 20 LAUCK ROAD, MOHNTON, PA 19540 FAX: (610) 856-5040 http://www.karlenv.com

January 8, 2019 Mr. Lou Albanese Supervisor of Buildings & Grounds Little Ferry School District 130 Liberty St. Little Ferry, NJ 07643 Re: Lead-in-Drinking Water Screening Little Ferry School District Trailer Testing Karl Environmental Group Project #: 18-0913 Dear Mr. Albanese, Thank you for selecting Karl Environmental Group (“Karl”) for this project. This report details the methods and findings of the lead-in-drinking water screening performed in Trailers located at 130 Liberty Street, Little Ferry, New Jersey (the “Site”) on December 28, 2018. 1.0 PROJECT BACKGROUND Karl Environmental was contacted by Mr. Lou Albanese of the Little Ferry School District (the “Client”) to conduct a lead-in-drinking water screening to determine the lead content of water sampled from representative water collection points at the Site. The purpose of the screening is to determine if any collection points exhibit lead levels higher than the recommended Action Level (AL). Water collection points can include any water source, including:

• Potable water sources

• Non-potable water sources

20 Lauck Road Mohnton, PA 19540 Tel: (800) 527-5581

Fax: (610) 856-5040 Web: www.karlenv.com

Page 3: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Karl Environmental Group Project 18-0913

VOICE: (610) 856-7700 20 LAUCK ROAD, MOHNTON, PA 19540 FAX: (610) 856-5040

http://www.karlenv.com

2.0 LEAD IN DRINKING WATER Lead is a toxic substance that can be harmful to human health. As compared to adults, children are more susceptible to the detrimental health effects of lead, as their nervous systems are not yet fully developed. They can be exposed to lead in a variety of ways including through food, soil, deteriorating lead-based paint, and drinking water. Lead can leach into drinking water from plumbing materials such as pipes and solder, as well as brass plumbing fixtures. There are no federal guidelines that require the testing of drinking water in schools supplied by a municipal water utility, however, the United States Environmental Protection Agency (EPA) provides general guidance for screening of the potable water sources from which children may drink. 3.0 DRINKING WATER SAMPLING METHODOLOGY Karl Environmental collected drinking water samples which were selected to include both potable and non-potable water sources located at the Site. Karl Environmental collected twenty (20) water samples from Site on December 28, 2018. At each collection point, Karl Environmental filled a sample collection bottle from the selected water source after the water in each building had not been used for 6-8 hours, but no more than 18 hours, and prior to the building opening. This initial sample at each collection point represents the First Draw (FD) sample. The samples were sealed and couriered directly to Suburban Testing Labs (Suburban), a New Jersey certified laboratory (NJ Lab ID #PA081) located at 1037F MacArthur Road in Reading, Pennsylvania for analysis by EPA method 200.8. The SD samples were place on hold and were only analyzed in the case that analysis of the corresponding FD sample identified lead concentrations at or above the action level of fifteen (15) parts per billion (ppb) or greater.

Page 4: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Karl Environmental Group Project 18-0913

VOICE: (610) 856-7700 20 LAUCK ROAD, MOHNTON, PA 19540 FAX: (610) 856-5040

http://www.karlenv.com

4.0 DRINKING WATER ANALYSIS RESULTS The analytical lead in drinking water results for each FD sample collected are listed in Table 1, below:

Table 1: Analytical Lead Results for Drinking Water Samples Collected from Harrington Park Elementary School

Sample I.D. Location Type of

Collection Point

Lead Concentration

(mg/L)

Above Action Level?

LF-Blank-01 Blank N/A <0.001 No

LF-Blank-02 Blank N/A <0.001 No

KS-01 Kitchen Sink 1 KS 0.007 No

KS-02 Kitchen Sink 2 KS <0.001 No

KS-03 Kitchen Sink 3 KS <0.001 No

WR-01 Nurses Room 1 KS 0.005 No

WFR-01 Trailer 9 WF Right 1 WF <0.001 No

WFR-02 Trailer 9 WF Right 2 WF <0.001 No

WFR-03 Trailer 9 WF Right 3 WF <0.001 No

WFR-04 Trailer 9 WF Right 4 WF <0.001 No

WFL-01 Trailer 9 WF Left 1 WF <0.001 No

WFL-02 Trailer 9 WF Left 2 WF <0.001 No

WFL-03 Trailer 9 WF Left 3 WF <0.001 No

WFL-04 Trailer 9 WF Left 4 WF <0.001 No

11WFR-01 Trailer 11 WF Right 1 WF <0.001 No

11WFR-02 Trailer 11 WF Right 2 WF <0.001 No

11WFL-01 Trailer 11 WF Left 1 WF <0.001 No

11WFL-02 Trailer 11 WF Left 2 WF <0.001 No

11WFL-03 Trailer 11 WF Left 3 WF <0.001 No

11WFL-04 Trailer 11 WF Left 4 WF <0.001 No

WF = Water Fountain

KS = Kitchen Sink

*Trailer 11 Water Fountain Right 3 & water fountain 4 were shut off due to leak

Page 5: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Karl Environmental Group Project 18-0913

VOICE: (610) 856-7700 20 LAUCK ROAD, MOHNTON, PA 19540 FAX: (610) 856-5040

http://www.karlenv.com

5.0 CONCLUSIONS & RECOMMENDATIONS Karl Environmental collected twenty (20) water samples from collection points at the Site. None of the FD samples revealed lead levels at or above the recommended AL of 15 ppb at the Site. Based on the findings of the lead in drinking water screening the following recommendations are offered at this time:

• A non-potable water sign should be placed at all water sources not tested.

• Continue to monitor lead in drinking water levels as part of a regular sampling and maintenance plan. Additional parameters may also be considered for analysis, such as: Antimony, Asbestos, Cadmium, Copper, Mercury, Nickel, Silver, Zinc, and biologicals.

• Where in use, regularly clean aerators to prevent the build-up of debris behind the screen which may contribute to elevated lead levels.

• Use only cold water for food and beverage preparation. Hot water is more likely to contribute to the corrosion of plumbing materials and therefore contain a greater level of contaminants from the plumbing system.

• In the event that water drinking source(s) are remediated, the source(s) should be resampled before being placed back into service.

• Replace any known or discovered lead piping with with lead-free piping.

• Check piping for ground wiring for electricity. Such wiring may cause premature corrosion of the affected piping and lead to contamination of the water contained within.

6.0 LIMITATIONS The main purpose of the sampling event outlined within this report was to screen potable water sources for potential lead contamination. No other heavy metals or additional contaminants were analyzed. Lead concentrations can change as water continues to move through the water system. Each sample was a grab sample and represents lead concentrations only at the specific time collected. Interpretation of these results is only valid if facility is served by a municipal water supplier or water utility.

Page 6: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Karl Environmental Group Project 18-0913

VOICE: (610) 856-7700 20 LAUCK ROAD, MOHNTON, PA 19540 FAX: (610) 856-5040

http://www.karlenv.com

7.0 CLOSING Thank you for using Karl to assist you with this project. Please do not hesitate to call if you have any questions relating to this report or for any other environmental health and safety concerns.

Respectfully submitted, Karl Environmental Group

Jake Edwards Industrial Hygienist [email protected] 610-856-7700 (Office) 610-856-5040 (Fax) Attachments: A – Laboratory Analytical Report

Page 7: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Karl Environmental Group Project 18-0913

VOICE: (610) 856-7700 20 LAUCK ROAD, MOHNTON, PA 19540 FAX: (610) 856-5040

http://www.karlenv.com

Attachment A

Laboratory Analytical Results

Page 8: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Project:

Aja Slater

Results Report Order ID: 8124584

Attn: Regulatory ID:

Little FerryKarl Environmental Group

20 Lauck Road

Mohnton, PA 19540

Sample Number: 8124584-01

Collector: client

Site: LF Blank 01

Collect Date: 12/28/2018 1:17 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 15:57 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-02

Collector: client

Site: LF Blank 02

Collect Date: 12/28/2018 1:17 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 16:03 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-03

Collector: client

Site: KS 01

Collect Date: 12/28/2018 8:33 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead 0.007 mg/L EPA 200.8 01/06/19 16:05 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-04

Collector: client

Site: KS 02

Collect Date: 12/28/2018 8:33 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 16:07 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-05

Collector: client

Site: KS 03

Collect Date: 12/28/2018 8:33 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 16:09 RJS01/05/19 RPV0.001 1

Report Generated On: 01/07/2019 12:06 pm 8124584

STL_Results Revision #1.6 Effective: 07/09/2014

Page 1 of 7

Page 9: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Sample Number: 8124584-06

Collector: client

Site: WR 01

Collect Date: 12/28/2018 8:38 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead 0.005 mg/L EPA 200.8 01/06/19 16:14 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-07

Collector: client

Site: WF R01

Collect Date: 12/28/2018 8:00 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 16:16 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-08

Collector: client

Site: WF R02

Collect Date: 12/28/2018 8:00 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 16:18 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-09

Collector: client

Site: 11 WF L01

Collect Date: 12/28/2018 10:05 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 16:20 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-10

Collector: client

Site: 11 WF L02

Collect Date: 12/28/2018 10:05 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:29 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-11

Collector: client

Site: 11 WF L03

Collect Date: 12/28/2018 10:06 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:35 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-12

Collector: client

Site: 11 WF L04

Collect Date: 12/28/2018 10:06 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:38 RJS01/05/19 RPV0.001 1

Report Generated On: 01/07/2019 12:06 pm 8124584

STL_Results Revision #1.6 Effective: 07/09/2014

Page 2 of 7

Page 10: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Sample Number: 8124584-13

Collector: client

Site: WF R03

Collect Date: 12/28/2018 8:01 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:40 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-14

Collector: client

Site: WF R04

Collect Date: 12/28/2018 8:02 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:42 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-15

Collector: client

Site: WF L01

Collect Date: 12/28/2018 7:58 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:44 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-16

Collector: client

Site: WF L02

Collect Date: 12/28/2018 7:58 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:46 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-17

Collector: client

Site: WF L03

Collect Date: 12/28/2018 7:59 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:48 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-18

Collector: client

Site: WF L04

Collect Date: 12/28/2018 7:59 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:50 RJS01/05/19 RPV0.001 1

Sample Number: 8124584-19

Collector: client

Site: 11 WF R01

Collect Date: 12/28/2018 10:01 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:52 RJS01/05/19 RPV0.001 1

Report Generated On: 01/07/2019 12:06 pm 8124584

STL_Results Revision #1.6 Effective: 07/09/2014

Page 3 of 7

Page 11: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Sample Number: 8124584-20

Collector: client

Site: 11 WF R02

Collect Date: 12/28/2018 10:01 am

Sample ID:

Sample Type: Grab

ByAnalysis DateByPrep DateDFR.L.MethodUnitsResult Department / Test / Parameter

Metals

Lead < 0.001 mg/L EPA 200.8 01/06/19 17:58 RJS01/05/19 RPV0.001 1

Sample Receipt Conditions:

All samples met the sample receipt requirements for the relevant analyses.

All results meet the requirements of STL's TNI (NELAC) Accredited Quality System unless otherwise noted. If your results contain any data qualifiers or

comments, you should evaluate useability relative to your needs.

If collectors initials include "STL", samples have been collected in accordance with STL SOP SL0015.

All results reported on an As Received (Wet Weight) basis unless otherwise noted.

This laboratory report may not be reproduced, except in full, without the written approval of STL.

Results are considered Preliminary unless report is signed by authorized representative of STL.

The test pH, Lab is performed in the Laboratory as soon as possible. These results are not appropriate for compliance with NPDES, SDWA, or other

regulatory programs that require analysis within 15 minutes of sample collection and should be considered for informational purposes only.

Reviewed and Released By:

Alana Kopicz

Project Manager II

Report Generated On: 01/07/2019 12:06 pm 8124584

STL_Results Revision #1.6 Effective: 07/09/2014

Page 4 of 7

Page 12: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Page 5 of 7

Page 13: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130

Page 6 of 7

Page 14: Effective and Economical Environmental Solutions...Effective and Economical Environmental Solutions Lead-in-Drinking Water Screening Little Ferry School District Trailer testing 130