EEV-KIT For Multiple refrigeration system. Preliminary information, all of contents are subject to...
-
Upload
beatrix-wheeler -
Category
Documents
-
view
214 -
download
0
Transcript of EEV-KIT For Multiple refrigeration system. Preliminary information, all of contents are subject to...
EEV-KITEEV-KITFor Multiple refrigeration systemFor Multiple refrigeration system
Preliminary information, all of contents are subject to final confirmation by MHI 2
Contents 1. System summary
2. Function of direct expansion type air handling unit ( DX AHU )3. Function of master EEV-Control Unit
4. Function of slave EEV-Control Unit
5. Function of outdoor unit
Preliminary information, all of contents are subject to final confirmation by MHI 3
1. System summary System summary #1
RC-E4
Re
turn
air
Exhaust airOutdoor air
Outdoorunit
Thi-A
SARA
Master EEV CONTROL UNIT manages total system
1. Basic operation can be done by remote controller (RC-E4) .
2. Central control including other KXE6 system can be done. (In such case, superlink adaptor is required.)
3. External input for switching operation mode is available. (Input signal to master EEV Control Unit)
Superlink adaptor
RC-E4
Thi-AF
FANMaster EEV Control Unit
Sensor (2pcs)
Return airtemp. sensorThi-A
Supply air temp. sensorThi-AF
Master EEV-KIT
Return air or Outdoor airDirect
expansion type air -
handling unit
Outdoorunit
Central control( SC-SL3N )
Slave EEV Control Unit
Sensor x 3EEV x 1 EEV-Set
Slave EEV-KIT #1
Heat exchanger temp.Sensor (Thi-R1,R2,R3)
StrainerStrainer
Slave EEV Control Unit
Sensor x 3EEV x 1 EEV-Set
Slave EEV-KIT #2
Heat exchanger temp.Sensor (Thi-R1,R2,R3)
StrainerStrainer
Slave EEV Control Unit
Sensor x 3EEV x 1 EEV-Set
Slave EEV-KIT #3
Heat exchanger temp.Sensor (Thi-R1,R2,R3)
StrainerStrainer
Preliminary information, all of contents are subject to final confirmation by MHI 4
1. System summary System summary #2
OA processing specifications
Selection of return/supply air temp. control is available (by master EEV CONTROL UNIT)
Air-conditioning (Air circulation) specifications
This control system is the return air (R/A) temp. control system which is same as that for standard packaged air conditioner.Thermostat ON/OFF control is done by detecting the temperature difference between the R/A temp. (or room temp. sensed by remote controller sensor) and the set R/A temp. (room temp.) by remote controller (R/C).
Outdoor air
Exhaust air
This control system is the supply air (S/A) temp.control system which has following 3 systems.B) Controlling No. of indoor units by detecting the temp. difference between the set S/A temp. by R/C and the S/A temp. C) Controlling the S/A temp. constant according to the set S/A temp. by R/C, and thermostat ON/OFF control is done by detecting R/A temp. D) Controlling the S/A temp. constant according to the set S/A temp. by master EEV control unit in advance, and thermostat ON/OFF control is done by detecting the R/A temp. (R/C sensor
temp.).
Outdoor
Outdoor
Indoor
Indoor
Return air
Cool/hot air
Cool/hot air
OutdoorUnit
OutdoorUnit
OutdoorUnit
Air handling
unit
Air handling
unit
Preliminary information, all of contents are subject to final confirmation by MHI 5
System control type
Set temp
Thermostat ON/OFF
System control A : Return air temp. control
R/Aby R/C
R/ASet temp ( by R/C ) =R/A sensor
System control B : Supply air temp. control
S/Aby R/C
S/ASet temp ( by R/C ) =S/A sensor
System control C : Supply air temp. control
S/Aby R/C
R/ASet temp+2deg =R/A sensor
System control D : Supply air temp. control
S/Aby PCB
R/ASet temp ( by R/C ) =R/A sensor
Supplemental explanation
Preliminary information, all of contents are subject to final confirmation by MHI 6
1. System summary System summary #3
R/C
External Control
Master control PCB and Slave control PCB are supplied as EEV Control Unit.That shall be installed in the control box for air handling unit at customer side.
Ex: Lay out example of one master control unit and six slave control units
Power cable
Sensor wiring
Superlink signal wiring
Remote controller wiring
External input signal wiring05 tapping screw
Duct for power cableDuct for sensor wire Signal wire
Preliminary information, all of contents are subject to final confirmation by MHI 7
2 or more refrigeration systemsare connected to 1 air handlingunit system which has 2 or more direct expansion heat exchanger coils.
2 . Function of DX AHU
Thi-R1Thi-R2Thi-R3
Thi-AFThi-AFAN
RCRC
EEV-Set
01 03
Slave EEV-Control ASSY
1303
0101
0501
0903
O/U Address
O/U AddressI/U Address
Master EEV-Control ASSY
(EEVKIT6-E-M)
Signal line
RC-E4
(EEVKIT6-E-C)
EEV-KIT : SlaveEEV-Control ASSY
EEV-Control UnitSensors ( 3pcs )
Thi-R1Thi-R2
Thi-R3
EEV-SET
Strainer
EEV
Strainer
EEV-Control UnitSensors ( 2pcs )
Thi-A Thi-AF
EEV-Control ASSY
EEV-KIT : Master
Preliminary information, all of contents are subject to final confirmation by MHI 8
The system composition of the DX AHU for multiple refrigeration system is as follows. (1) Master EEV Control ASSY (EEVKIT6-E-M) ①Master EEV Control Unit ②Air Sensor Assy. (Thi-A, Thi-AF) (2) Slave EEV Control ASSY (EEVKIT6-E-C) ①Slave EEV-Control Unit ②Heat exchanger Sensor Assy.
(Thi-R1, Thi-R2, Thi-R3) (3) EEV-Set (EEV-body, -coil, 2 x Strainers) (4) Outdoor unit for KXE6 system
2 . Function of DX AHU
Preliminary information, all of contents are subject to final confirmation by MHI 9
2 .3 Master EEV-Control Unit At least one set of master EEV-Control Unit is required forthe DX AHU for multiple refrigeration system. Its principal functions are as follows.• The window function to interconnect the building
management system and the unit through superlink signal system.
• The function to change operation mode of the unit.• The functions to control indoor fan operation, to receive
control signal and to send signal for displaying on the remote controller.
• The function to change temperature control.• The function to change multiple step control.
2 . Function of DX AHU
Preliminary information, all of contents are subject to final confirmation by MHI 10
2 .4 Slave EEV-Control Unit In response to multiple refrigeration system, some setting is required for slave EEV-Control Unit to communicate with master EEV-Control Unit. The principal settings are as
follows.
• Select the number of salve EEV-Control Units depending on the number of refrigeration systems and of heat exchangers to be controlled, and set model capacities and addresses.
• Slave EEV-Control Unit controls the refrigerant flow volume according to the operation mode and operation command from master EEV-Control Unit.
The refrigerant control value of slave EEV-Control Unit must be set in response to the temperature control value set by master EEV-Control Unit.
2 . Function of DX AHU
Preliminary information, all of contents are subject to final confirmation by MHI 11
2 .5 Outdoor unit
• The outdoor unit for KXE6 system is used for DX AHU.• For the multiple refrigeration system of direct expansion
type air handling unit, some settings are required.
2 . Function of DX AHU
Preliminary information, all of contents are subject to final confirmation by MHI 12
3 . Function of master EEV-Control Unit
CnNCnT2
SW5: See item 3.2J1: See item 3.9
SW1-SW4: See item 3.1 、 2 、3
SW7: See item 3.7
SW6:See item 3.4 、 5 、6
Preliminary information, all of contents are subject to final confirmation by MHI 13
3 .1 SW1-SW4
3 . Function of master EEV-Control Unit
Contents Remarks
SW1 Rotary switch (Blue)Changing the temperature interval formultiple step control in cooling mode
See item 4.3.2for details
SW2 Rotary switch (Blue)Switching the control by return air
temperature or supply air temperatureSee item 4.3.3
for details
SW3 Rotary switch (Green)Changing the temperature interval formultiple step control in heating mode
See item 4.3.2for details
SW4 Rotary switch (Green)Switching the control by return air
temperature or supply air temperatureSee item 4.3.3
for details
Switch
(Note) ・ SW1-SW4 are not for address setting of master EEV-Control Unit. ・ The address of master EEV-Control Unit is fixed [00] in advance so that it is no necessary to be set.
Preliminary information, all of contents are subject to final confirmation by MHI 14
3 .2 Multiple step control
Step control SW5-1 SW5-2None ★OFF ★OFF4-step ON OFF6-step OFF ON8-step ON ON
3 . Function of master EEV-Control Unit
Set by SW1 Temp. interval Set by SW3 Temp. interval
★0 Invalid ★0 Invalid1 0.2 1 0.22 0.5 2 0.53 1.0 3 1.04 1.5 4 1.55 2.0 5 2.0
Other Nos. Invalid Other Nos. Invalid
Cooling Heating
Set temp. + 1.0 + 2.0 + 3.0 + 4.0
All ON
1st step 2nd step
3rd step 4th step (All OFF)
32sets24sets
16sets
8sets
Multiple step control is the control to change the number of indoor unit to be operated step by step in response to the difference between set temperature and return air temperature.
SW5-1 and SW5-2 : Setting steps to be controlled SW1 and SW3 : Change temp. interval to step up or down
[Ex. 4-step control by 1.0degC temp. interval in heating]
(With 32 slave EEV-Control Unit)*Retaining at least for 1 minute on each step. (See item 4.3.12) for changing the retaining time interval)
★Factory default
Preliminary information, all of contents are subject to final confirmation by MHI 15
3 .3 Switching return/supply air temp. control
• System control A : Return air temp. control The system will carry out thermostat ON/OFF control by detecting the temp. difference between the return air (room) temp. set with remote controller and the actual return air temp. (or the sensed temp. by R/C sensor).• System control B : Supply air temp. control The system will carry out multiple step control by detecting the temp. difference between the supply air temp. set with remote controller and the actual supply air temp. • System control C : Supply air temp. control The system will carry out control to keep the supply air temp. constant by the supply air temp. set with remote controller and carry out thermostat ON/OFF control by detecting the temp. difference between the set temp. and the actual return air temp. (or the sensed temp. by R/C sensor)• System control D : Supply air temp. control The system will carry out control to keep the supply air temp. constant by the supply air temp. set on the control PCB in advance and carry out thermostat ON/OFF control by detecting the temp. difference between the set temp. and the actual return air temp. (or the sensed temp. by R/C sensor).
3 . Function of master EEV-Control Unit
System control SW2 SW4 RemarksSystem control A ★OFF ★OFF Return air temp. controlSystem control B ON OFF Supply air temp. controlSystem control C OFF ON Supply air temp. controlSystem control D ON ON Supply air temp. control
By using SW2 and SW4, following 4 types of system control can be selected.
★Factory default
OFF: Set 0 ON : Set other No.
Preliminary information, all of contents are subject to final confirmation by MHI 16
3 .4 SW6
3 . Function of master EEV-Control Unit
Switch Function ON/OFF Setting Remarks
SW6-1 ★OFF
SW6-2 ★OFF
★OFF Valid
ON Invalid
SW6-4 Rserved ★OFF Invalid Keep OFF
See item 4.3.6for details
SW6-3 Hot startSee item 4.3.5
for details
As persetting
Automatic operation valid/invalidand switching operation pattern
★Factory default3 .5 Hot start Set hot start valid/Invalid by SW6-3.
What is hot start In order to prevent cold air from blowing out at the starting period of operation in heating, the fan operation is kept under the stand- by condition. However, since there is some opinion that this function is not required for the direct expansion type air handling unit, it makes possible to cancel this function with this switch.
Preliminary information, all of contents are subject to final confirmation by MHI 17
3 .6 Automatic operation control #1
3 . Function of master EEV-Control Unit
Automatic operation control pattern SW6-1 SW6-2Automatic operation control is invalid ★OFF ★OFF
Automatic operation control A ON OFFAutomatic operation control B OFF ONAutomatic operation control C ON ON
Heating
Cooling
▲
Set temp. (Ts)
-2 + 1- 1 +2
Fan
Heating
Cooling
▲
Set temp. (Ts)
- 1.5 +0.5
- 0.5 +1.5
Fan
Heating
Cooling
▲
Set temp. (Ts)
- 1 +0.5
- 0.5 + 1
Fan
Automatic operation control is carried out with switching operation mode (cooling, fan, heating) automatically by detecting the temp. difference between the set temp. and the actual return air temp.
By using SW6, following 3 patterns of automatic operation control can be selected. ★Factory default.
Automatic operation control A
Automatic operation control B
Automatic operation control C
Preliminary information, all of contents are subject to final confirmation by MHI 18
3 .7 SW7 Switch Function ON/OFF Setting Remarks
★OFF InvalidON Valid
★OFFON
★OFFON
OFF 3-speed
★ON 1-speed
SW7-3As per setting
See following tablefor details
SW7-1
Fan speed controlSW7-4
Check indoor fan operation
Supply air temp. settingat system control D
SW7-2
3 . Function of master EEV-Control Unit
Switch Factory default Setting 1 Setting 2 Setting 3
SW7-2 ★OFF ON OFF ON
SW7-3 ★OFF OFF ON ON
Set temp. in cooling 16℃ 1 ℃4 18℃ 12℃Set temp. in heating 25℃ 23℃ 27℃ 29℃
3 .8 Supply air temp. setting at system control D
★Factory default.
SW7-1 is used for the operation check of indoor fan, before connecting refrigeration piping.
Indoor fan can operate by switching SW7-1 ON.
(This function is useful for prior check of indoor fan before shipment)
Preliminary information, all of contents are subject to final confirmation by MHI 19
3 .9 Jumper
3 . Function of master EEV-Control Unit
Jumper Function Short/Open Setting
★Short Fan operation is not available
Open Fan operation is availableJ1
Availabilty of fan operation,during oil return operation
In case that the air handling unit is operated as OA processing unit, the function of J1 is for comply with the requirement to keep operation of indoor fan during oil return operation in spite of defrosting in heating.The conditions to keep operation of indoor fan during defrosting in heating is following 3.If the one of following conditions are satisfied, J1 can be cut (open). If not, don’t cut (open) J1.
・ If the dampers are installed at the indoor heat exchangers in each refrigeration system and the damper for the system in defrosting can be shut off.・ If the outdoor units are heat recovery units (KXRE6 models), and the defrost can be done between the indoor heat exchangers and PFD box in each refrigeration system.・ If the height difference between the outdoor unit and indoor heat exchanger is within 20m. (Note) Max. height difference is 20m. However if the height difference exceeds 10m, 300cc of refrigerant oil shall be charged additionally on site.
★Factory default.
<Conditions>
Preliminary information, all of contents are subject to final confirmation by MHI 20
3 .10 External input Function
Terminal BlockTB2
Remarks
CnN1
CnN2
CnN3 For emergency stop 8, 9
CnI 2PFor overcurrent anomaly
of fan motor15, 16
Connector
6PFor switching operation mode
(Cooling, Fan, Heating)See following table
for details4, 5, 6, 7
3 . Function of master EEV-Control Unit
No signal Cooling Heating Fan
CnN1 0 1 0 1
CnN2 0 0 1 1
SwitchOperation mode
0 : Open (OFF), 1: Short (ON).
It is available to change operation mode by external input signal
Be sure to input with no voltage contact.
Preliminary information, all of contents are subject to final confirmation by MHI 21
3 .11 External output Contents of output information
TerminalBlock TB2 Remarks
CnM3 5POoperation command toindoor fan motor (Hi/Lo)
1, 2, 3
CnT2 5PCooling / Defrost
Oil return / Low temp.10, 11, 12,
13, 14See following table
for details
Connector
3 . Function of master EEV-Control Unit
Pin No. ofconnector
Function
CnT2-1 Common
CnT2-2 Output during cooling operation
CnT2-3Output during defrosting operation for one or morerefrigeration systems
CnT2-4Output when any one of refrigeration systems startsoil return operation
CnT2-5 Output when the reurtn air temp. becomes below 0℃
The voltage of the relay (locally provided) for output signal should be DC12V.
Max. load of relay should be LY2F (Omron).
Preliminary information, all of contents are subject to final confirmation by MHI 22
3 .12 Backup operation
3 . Function of master EEV-Control Unit
When some trouble happens on one of refrigeration system in multiple refrigeration system, switching to backup operation is available.
No Function Display on R/C
★STANDARD ★Normal operation
TYPE 1 Backup operation
Actual meaning
17PRESSURECONTROL
Remote Controller function
When a trouble happens on one of refrigeration system in multiple refrigerant systems, the system stops once.
However if the setting mentioned in the following table is done by remote controller, the multiple refrigeration systems except damaged one can be operated as emergency operation with displaying “Backup” on the remote controller.
★ factory default
Preliminary information, all of contents are subject to final confirmation by MHI 23
3 .13 Change the retaining time interval to shift the controlling step at multiple step control
3 . Function of master EEV-Control Unit
No Function Display on R/C
★STANDARD ★ 1 minute
HIGH SPEED 1 3 minute
HIGH SPEED 2 5 minutes
Actual meaning
02 FAN SPEED SET
Remote Controller function
★ factory default
The retaining time interval to change the number of indoor units to be controlled at multiple step control is set at one minute interval before shipment.
However this retaining time interval can be changed as following table by using remote controller function setting for indoor unit function No. 02.
Preliminary information, all of contents are subject to final confirmation by MHI 24
4 . Function of slave EEV-Control Unit
SW7: See item 4.5
SW1-SW4 and SW6 can be set according to the required specifications
SW1-SW4 : For address setting. See item 4.1
SW6: For model capacity selection. See item 4.4
SW5: See item 4.3
Preliminary information, all of contents are subject to final confirmation by MHI 25
4 . Function of slave EEV-Control Unit
4 .1 SW1-SW4 (Address setting)Contents
SW1 Rotary switch (Blue) Indoor unit address (10's)
SW2 Rotary switch (Blue) Indoor unit address (1's)
SW3 Rotary switch (Green) Outdoor unit address (10's)
SW4 Rotary switch (Green) Outdoor unit address (1's)
Switch
Set the address of slave EEV-Control Unit as follows.
01
01
SW3 SW4
SW1 SW2
Outdoor unit address
Indoor unit address:
For single use: 01, 02, 03 ・・・・・・・・ (in series)For combination use: 01, 03, 05 ・・・・・ (odd number)
(Note) Arbitrary No. is selectable in same manner as KXE6
Shall be set according to the following rule from lower order No. in series.
refrigerantsystem (*)
Indoor addressrefrigerantsystem (*)
Indoor address
No.1 (01) 01, 02, 03, 04 No.5 (05) 17, 18, 19, 20
No.2 (02) 05, 06, 07, 08 No.6 (06) 21, 22, 23, 24
No.3 (03) 09, 10, 11, 12 No.7 (07) 25, 26, 27, 28
No.4 (04) 13, 14, 15, 16 No.8 (08) 29, 30, 31, 32
Following example shows the rule to set I/U address for multiple step control. (O/U address is for single use case)
* In ( ) shows O/U address for single use
Preliminary information, all of contents are subject to final confirmation by MHI 26
4 . Function of slave EEV-Control Unit
4 .2 Address setting #1<Example 1>
0101
0205
0309
0413
1st step 2nd step 3rd step 4th stepSlave EEV-Control x 4 4-step control 4 Refrigeration system
SW5-1
SW5-2 ON
OFF
Master PCB
All Slave PCB SW5-1
SW5-2
ON OFF
Slave EEV-Control x 8 4-step control 4 Refrigeration system 01
010309
0102
0310
1st step 2nd step 3rd step 4th step
0205
0413
0206
0414
SW5-1
SW5-2 ON
OFF
Master PCB
<Example 2>
Preliminary information, all of contents are subject to final confirmation by MHI 27
4 . Function of slave EEV-Control Unit 4 .2 Address setting #1
Thi-R1Thi-R2Thi-R3
Thi-AFThi-A FAN
RCRC
04
03
02
01
1304O/U Address
I/U Address
0903
0101
0502
O/U Address
EEV-SET
Master EEV-Control
Slave EEV-Control
RC-E4
Signal line
Slave EEV-Control x 4 4-step control 4 Refrigeration system
00
SW5
SW5-1
SW5-2 ON
OFF
Master PCB
All Slave PCB SW5-1
SW5-2
ON OFF
Don’t forget to switch SW5-1 of
slave EEV-Control Unit ON
<Example 1>
Preliminary information, all of contents are subject to final confirmation by MHI 28
4 . Function of slave EEV-Control Unit
4 .3 SW5Switch
★OFF for single refrigeration system
ON for multiple refrigeration system
★OFF Invalid
ON Valid
Contents
SW5-2Indoor address setting
(100's)
Switching PCB settingfor single/multiple
refrigeration systemSW5-1
★Factory default(Note)
Be sure to set SW5-1 ON, when using this EEV-Control Unit (EEVKIT5-E-C) as the slave EEV-Control Unit for multiple refrigeration system.
If forgetting to set SW5-1 ON, the air handling unit for the multiple refrigerant system can not be operated.
Don’t forget to set all of slave EEV-Control Units SW5-1 ON !
Preliminary information, all of contents are subject to final confirmation by MHI 29
4 . Function of slave EEV-Control Unit
P22 P28 P56 P71 P140 P224 P280
SW6-1 OFF ON OFF OFF OFF OFF ON
SW6-2 OFF OFF ON OFF OFF ON ON
SW6-3 OFF OFF ON OFF ON ON ON
SW6-4 OFF OFF OFF ON ON ON ON
Model capacitySwitch
4 .4 SW6 (Model capacity selection)Set the model capacity according to the heat exchanger capacity.
Preliminary information, all of contents are subject to final confirmation by MHI 30
4 . Function of slave EEV-Control Unit
4 .5 SW7
Switch Function ON/OFF Setting Remarks
★OFF Normal
ON Test run
★OFF Normal
ON +15degC setting
★OFF Return air temp. control
ON Supply air temp. control
★OFF
ON
same function forKXE6 indoor unit
SW7-1
Switching the control methodof refrigerant flow volume
ReservedSW7-4
SW7-3
Test run for drain motor
+15degC setting at supply airtemp. control in heating
See item 5.3.6for details
Keep OFF
SW7-2
See item 5.3.7for details
Note:
1. shows factory default.★
2. SW7-4 should be kept OFF.
Preliminary information, all of contents are subject to final confirmation by MHI 31
4 . Function of slave EEV-Control Unit
4 .7 Switching the control method of refrigerant flow volume
• Switching the control method of refrigerant flow volume with SW7-3.
• When SW7-3 is O FF , it will become return air temp. control and EEV is controlled to keep the super heat constant.
• When SW7-3 is O N , it will become supply air temp. control and EEV is controlled to keep the supply air temperature constant.
Be sure to set this function in accordance with the setting of master EEV-Control Unit!
Be sure to set all of slave EEV-Control Unit the same!
Preliminary information, all of contents are subject to final confirmation by MHI 32
• The outdoor unit to be able to connect to the master and slave EEV-Control Unit for DX AHU is KXE6 and KXRE6 series.
• For Applying the outdoor unit of these series to the air handling unit for multiple refrigeration system, the following setting shall be done on the outdoor unit.
• Setting shall be done by using the 7- segment display function of outdoor unit.
5 . Function of outdoor unit