ECT159-Inverters c Harmonics

download ECT159-Inverters c Harmonics

of 20

Transcript of ECT159-Inverters c Harmonics

  • 8/8/2019 ECT159-Inverters c Harmonics

    1/20

    E/CT 159 first issued september 1993

    Jean Nol Fiorina

    Joined Merlin Gerin in 1968 as alaboratory technician in the ACS(Alimentations et ConvertisseursStatiques) department where heparticipated in the performancesetting up procedures for staticconverters. In 1977 he obtained his

    ENSERG Engineering degreefollowing a 3 years evening courseand rejoined the ACS department.Starting as development engineer hewas soon afterwards entrusted withprojects. He became laterresponsible for design projects inEPS department (Electronic PowerSystem).He is in some ways the originator ofmedium and high power inverters.At present he is with the UPSDivision where, as responsible forInnovations he works on the

    preparation of new UPS designs oftomorrow.

    n 159inverters andharmonics

    (case studies ofnon-linear loads)

  • 8/8/2019 ECT159-Inverters c Harmonics

    2/20

    Cahier Technique Merlin Gerin n 159 / p.2

    glossary

    UPS Uninterrupted Static Power Supply - Static UPSIEC International Electrotechnical CommissionCIGREE Confrence Internationale des Grands Rseaux Electriques et Electroniques

    (International conference on hight voltage electric systems)PWM Pulse Width ModulationD global distortion rateHn individual ratio of harmonics of order n n phase angle shift of harmonic component at t = 0In effective current of harmonic component of order nUref reference voltage

    distortion factorVn effective voltage of harmonic component of order nZsn output impedance for harmonic of order n

  • 8/8/2019 ECT159-Inverters c Harmonics

    3/20

    Cahier Technique Merlin Gerin n 159 / p.3

    inverters and harmonics(case studies of non-linear loads)

    summary

    1. Introduction p. 42. Characteristics of non-sinusoidal Harmonic analysis of a periodic

    function p. 4Effective value of a non-sinusoidalalternating quantity p. 4Distortion rate p. 4Power factors and cos 1 p. 5Distortion factor p. 5Crest factor p. 5Relation between current distortionand voltage distortion p. 5

    3. Impedances of some conventional Impedance of a transformer p. 6Impedance of an alternator p. 7Output impedance of an inverter p. 7Impedance of line p. 11

    4. Micro and mini-computer loads Description p. 12Influence of source impedance p. 12Calculation of source powerfor supplying RCD type loads p. 13

    5. Conclusion p. 16Appendix 1: influence of line impedances on voltage distortions p. 16Appendix 2: input filters in computer/micro-processor equipment p. 18Appendix 3: bibliography p. 19

    alternating quantities

    sources

  • 8/8/2019 ECT159-Inverters c Harmonics

    4/20

    Cahier Technique Merlin Gerin n 159 / p.4

    1. introduction

    that modern inverters are excellentgenerators of sinusoidal voltage evenwhen they supply non-linear loads.This is considered quite normal asUPS are designed and very oftenutilised to supply computer/ microprocessor systems which drawnon-sinusoidal currents.

    view of frequency stability as well asvoltage stability , performancessuperior to those of the mains.The only doubtful characteristic is, inthe opinion of many engineers, itsability to deliver a sinusoidal voltageregardless of the shape of the currentdrawn by the load.The aim of this Cahier Technique isto clarify this point and to demonstrate

    Static UPS are virtually perfect electricgenerators.They are highly reliable and, bynature, ensure (within the performancelimits of the battery) the uninterruptedavailability of electric power.As regards electrical characteristics,the inverter (which constitutes the UPSgenerator) possesses from the point of

    2. characteristics of non-sinusoidal alternating quantities

    harmonic analysis of aperiodic functionAs a lternating non-sinusoidal currentsand voltages are the main topic of thisstudy, it will be worth while to reviewthe electric quantities in the presence ofharmonics.Fourier theorem states that any non-sinusoidal periodic function can berepresented by a series of termsconsisting:s of a sinusoidal term at fundamentalfrequency,s of sinusoidal terms whosefrequencies are whole multiples of thefundamental (harmonics),s and eventually of a continuouscomponent (DC component).The formula denoting the harmonicanalysis of a periodic function is asfollows:

    y (t) = Yo + Yn 2n = 1

    n =

    sin (nt - n)

    where:Yo: value of continuous componentgenerally equal to zero and consideredas such hereafter,Yn: effective value of harmonic oforder n, : pulsation of fundamental frequency,

    n: phase shift angle of harmoniccomponent at t = 0.

    effective value of a non-sinusoidal alternating

    quantityApplying the general formula

    Y rms = 1T y 2 (t) dt0

    T

    gives with harmonic representation:

    Y rms = Yn 2n = 1

    n =

    distortion ratesHarmonic rates(as defined in IEC dictionary)This parameter, also called harmonicdistortion or distortion factor representsthe ratio of the effective value ofharmonics (n 2) to that of thealternating quantity:

    THD % = DF % = 100Yn 2

    n = 2

    n =

    Yn 2n = 1

    n =

    Global rate of distortion(as defined by CIGREE)This parameter represents the ratio ofthe effective value of harmonics to thatof th e fundamental alone:

    D % = 100Yn

    2

    n = 2

    n =

    Y 1

    No te : when the distortion rate is low, asis most frequently the case for thevoltage, the two definitions lead inpractice to the same result.For example, if:

    Yn 2n = 2

    n =

    = 10 % de Y 1

    The IEC expression gives:

    THD = DF = 100 (0.1)2

    1 + (0.1) 2= 9.95 %

    Whereas the CIGREE expressiongives:

    D % = 100 0.11

    = 10 %

    Hereafter we shall retain for thedistortion rate, the expression Dwhich corresponds to a more analyticalview of the influence of harmonics on anon-deformed wave.

  • 8/8/2019 ECT159-Inverters c Harmonics

    5/20

    Cahier Technique Merlin Gerin n 159 / p.5

    crest factorAs defined by IEC, it is the ratio of crestvalue to the effective value of a periodic

    quantity.

    relation between currentdistortion and voltagedistortionFor a given voltage source, it is alwayspossible to define an outputimpedance, even if the latter isfrequency dependent. To the extentwhere this impedance is independent ofthe current value (linear case) it ispossible to calculate for each currentharmonic a corresponding voltageharmonic and thus to deduce theindividual harmonic rate (percentage).The effective value of voltage harmonicof order n equals:Un = Zsn . InwhereZsn: output impedance for harmonic nandIn: effective current of harmonic n.The individual rate of harmonics oforder n for this voltage is equivalent to:

    Hn = UnU 1

    whereU1 = effective value of fundamentalvoltage.The global distortion rate of voltage isthus obtained by means ofexpression:

    D % = 100Un 2

    n = 2

    n -

    U 1

    and also:

    D % = 100 Hn2

    n = 2n -

    The input impedance for variousharmonic frequencies plays thereforean important role in bringing about theonset of voltage distortion. The higherthis input impedance, the greater will bethe voltage distortion rate for a givennon-sinusoidal current.

    Individual harmonic rateThis parameter represents the ratio ofthe effective value of a harmonic oforder n to that of the alternatingquantity (according to IEC dictionary) orto that of the fundamental alone(according to CIGREE),s according to definition in IECdictionary:

    Hn % = 100 Yn

    Yn 2n = 1

    n =

    s and according to CIGREE defi nition:

    Hn % = 100 YnY1

    This latter definition will be retained insubsequent reasoning.

    power factors and cos 1According to IEC, the power factor isthe ratio of the effective power P to theapparent power S:

    = PS

    This power factor should not beconfused with the phase shift anglefactor (cos 1) which represents thecosine of angle formed by the phaseelements of fundamental componentsof voltage and current:

    1 = cos 1 = P 1S 1

    where:P 1 = effective power of fundamentalcomponentS 1 = apparent power of fundamentalcomponent.

    distortion factor According to standard specification

    IEC 146-1-1, this factor enables todefine the relation between powerfactor and cos 1:

    = cos 1

    Where voltages and currents areperfectly sinusoidal the distortion factorequals 1 and cos 1 is equal to thepower factor.

  • 8/8/2019 ECT159-Inverters c Harmonics

    6/20

    Cahier Technique Merlin Gerin n 159 / p.6

    of Ucc R is of the order of 1 % toseveral % (this latter value becomingcorrespondingly smaller as the powerrating of transformer increases).In practice, as regards harmonics,since only the inductance impedance isfrequency dependent, it is theinductance alone which determines thebehaviour/performance of thetransformer.s in three phase transformers, it isnecessary to take into account thedifferent possible connection types ofprimary and secondary windings, asthese exert an influence on the sourceimpedance for some harmonics (inparticular, third harmonic andmultiples of 3).In fact, in the case of a transformerwhich supplies to each of its secondarywindings distorted and balancedcurrents comprising harmonics of order3 and multiples of 3, say 3 k, andconsidering that these currents arebalanced, it is thus possible to write foreach of these phases:

    I1 3 k = I sin 3 k t

    I2 3 k = I sin 3 k ( t - 23

    )

    I3 3 k = I sin 3 k ( t - 43

    )

    or

    I1 3 k = I sin 3 k t

    I2 3 k = I sin (3 k t - k 2 )

    I3 3 k = I sin (3 k t - k 4 )

    These equations show that thethree currents are in phase. It is thisphenomenon which leads one toobserve in the neutral conductor ofsome wiring installations (neon tubesfor example) the presence of muchhigher currents than originallyanticipated.

    3. impedances of some conventional sources

    Very often the impedance Zs (at 50 Hz)of a generator is given as percentage ofnominal impedance of load Zc:

    Zs % = 100 ZsZc

    For the nominal current, the voltagedrop across this impedance represents,therefore, as percentage in relation tothe nominal voltage, the value of thissource impedance:

    Zs . InUn

    % = 100 Zs . InUn

    where Zc . In = Un

    Zs . InUn

    % = 100 Zs . InZc . In

    = 100 ZsZc

    impedance of atransformerFigure 1 represents an equivalent circuitdiagram of a single phase transformerseen from secondary winding.The transformer impedance consists ofan inductance L in series with aresistance R. An equivalent value of therelative impedance is given by thetransformer short-circuit voltage Ucc.Indeed, by definition, the short-circuitvoltage is the voltage that must beapplied across a winding in order toinduce a nominal current in the otherwinding also under short-circuit,

    Ucc % = 100 UccUn

    Ucc % = 100Zs . In

    Un = 100ZsZc = Zs %

    This short-circuit voltage is made up oftwo terms: Ucc R et Uccx (see fig. 2).s in distribution transformers or generalpurpose transformers with ratingssuperior to 1 kVA, the value of Uccxranges from 4 - 6 %, whereas the value

    The behaviour of a transformer towardsthese harmonics is therefore dependenton the homopolar impedance Zh of thetransformer (refer to CahierTechnique n 18 Analyse desrseaux triphass en rgime perturb l'aide des composantes symtriques).Two types of secondary windings aresuitable for not amplifying or reducingharmonic distortions:s star connected secondary withdistributed neutral

    fig. 1: equivalent circuit diagram of a single phase transformer seen from secondary winding.

    fig. 2: Kapp triangle of a transformer (values referred to secondary).

    e

    L R

    A B

    Ucc Uccx = L I2n

    Ucc = R I2n I2cc = I2nR

  • 8/8/2019 ECT159-Inverters c Harmonics

    7/20

    Cahier Technique Merlin Gerin n 159 / p.7

    When primary windings are delta orstar connected with the neutral pointconnected to the source neutral(see fig. 3), the harmonic impedancesof order 3 and multiples are neitherencouraged nor discouraged(Zh = Zd).The transformer behaves as threesingle phase transformers.s ZIGZAG connected secondaryThese connections ensure minimumdistortion in secondary - in fact, in thiscase, the harmonic currents of order3 k do not circulate in the transformerprimary, and the impedance Zs is nolonger dependent on secondarywindings. The inductance is thus very

    low: Uccx 1 %, and the resistance isreduced roughly by half whencompared with the resistance of deltastar connected transformer of samerating.Figure 4 and the following calculationexplain why currents of pulsatingfrequency 3 k are not found in thetransformer primary (homopolarcurrent equal to zero).

    For a turn ratio

    N 2N 1

    ,

    the current circulating for instance in

    the primary winding 1 equals:

    N 2N 1

    (i 1 - i 3)

    with

    i 1 = I 1 3 k = I sin 3 k t

    i 3 = I 3 3 k = I sin 3 k ( t - 43

    )

    = I sin (3 k t - 4 )

    this gives

    N 2N 1 (i 1 - i 3) = 0

    The ZIGZAG connected secondarywinding acts therefore as an attenuatorto harmonics of order 3 k. This type oftransformer is often used as an outputtransformer for classic inverters of highrating.

    As a general rule, the other types ofconnection are to be avoided, inparticular those that do not allow theneutral to be distributed in thesecondary; in fact for these Zh = .

    impedance of an alternatorAn alternator can also be representedby a voltage source in series with aninductance and a resistance.However, this inductance assumes verydifferent values according to the speedof current variations to which it isrelated.During such current variation, theequivalent reactance passes

    progressively from a value called sub-transient to its synchronous value via atransient value. These different valuesreflect the variation of the alternatormagnetic flux.As regards current harmonics, only thesub-transient reactance is to beconsidered in any phenomenon lastingless than 10 ms.This reactance, referred to aslongitudinal sub-transient reactanceis denoted as X''d.For an alternator of current production,this reactance amounts to 15 - 20 %.In traditional machines but of designoptimised in this respect, a value of12 % can be achieved.Finally, in special machines, someconstructors claim values decreasing to6 %.In conclusion, it is worth recalling that,except in very particular cases, thealternator output impedance isconsiderably greater than that of atransformer; consequently, the sameapplies to the voltage distortion rate inthe presence of distorted currents.

    output impedance of aninverterThe impedance of an inverter isessentially dependent on the outputimpedance of its filter and on the typeof regulation adopted.

    Principe of an inverterAn inverter comprises first of all aconverter referred to as mutator i.e.switching device which converts the DCvoltage supplied by a rectifier or a DCbattery into AC voltage.

    fig. 4: transformer with ZIGZAG connected secondary and attenuation of harmonics of order 3 k.

    fig. 3: winding connections of three-phase transformers which have a homopolar impedance Zh equal to a direct impedance Zd.

    primary

    A

    B

    C

    a

    b

    cn

    secondary

    a

    b

    cn

    A

    B

    CN

    IIN

    N(I - I )

    1

    2

    N 1

    N 1

    N 1

    N2

    N2

    N2

    N2

    N2

    N2

    1 3 3 1

    I 2

    I 3

  • 8/8/2019 ECT159-Inverters c Harmonics

    8/20

    Cahier Technique Merlin Gerin n 159 / p.8

    In a single phase unit, there aretwo ways of achieving this conversion:s half-bridge converter (see fig. 5a),s full-bridge converter (see fig. 5b).The square wave voltage appearingbetween A and B is then filtered so asto obtain in the output of the unit asinusoidal voltage wave with a lowdistortion rate.In practice, the switching device(mutator) produces several positiveand negative pulses (see fig. 6) whichmakes it possible to reduce the size ofthe filter and to have a faster actingvoltage regulator.

    By modulating the relative time

    intervals corresponding to conductionand non-conduction periods, it ispossible to spread the voltage duringthe period in such a way as to makethe conduction time of the switchingdevice practically proportional to theinstantaneous value of thefundamental.

    This principle is called PWM (PulseWidth Modulation) - (MLI in french).The filter inserted behind the switchingdevice (mutator) is generally of the Land C type (see fig. 7).

    The inverter is therefore a voltagesource with the filter impedance inseries.Voltage V is the voltage measured atno load, and the impedance consistingof L and C elements in parallel is theimpedance measured when terminalsA and B are short-circuited (obtainedby applying Thevenin theorem;see fig. 8).

    Classic invertersWhen the commutation frequency islow, regulation can:s cope with variations of current drawnby user equipment,s compensate for voltage variation ofDC battery (or rectifier),s have, however, difficulties in dealingpermanently with variations of currentdue to harmonics generated during halfcycle.In these inverters, the outputimpedance is equal to the impedanceof their filter. They can, therefore, bedescribed as classic inverters since

    fig. 8: equivalent circuit diagram of an inverter seen from its output.

    fig. 6: output voltage of switching unit (mutator) with 5 pulses per half period.

    fig. 5a: principle of switching unit (mutator)half-bridge converter.

    fig. 5b: principle of mutator full-bridge converter.

    V

    closedopen

    openclosed

    T/2 T

    t

    + E

    V

    T/2 T

    t

    + E

    V

    t

    + E

    - E

    0

    + E

    II

    B A II

    1

    2

    3

    4

    B

    I3I3I4 I4

    AB

    A

    openI1closedI2

    closedI1openI2

    T/2 T

    t

    + E

    t+ E/2

    - E/2

    loadB A

    + E

    + E/2

    0

    VA

    VAB

    openI2

    closedI1closedI2

    openI1

    I1

    I2

    V

    t

    fundamental

    AB

    L

    CV

    fig. 7: output filter of an inverter.

    A

    B

    mutator Cuser(receiver)

    L

  • 8/8/2019 ECT159-Inverters c Harmonics

    9/20

    Cahier Technique Merlin Gerin n 159 / p.9

    In general, it is then useful to show thewhole output circuit part(switching unit + filter) in the form of aseries impedance Z 1 together with aparallel impedance Z 2 (see fig. 11).By applying Thevenin theorem, it ispossible to transform the circuitdiagram into that shown in figure n 12.Vm = voltage measured at no loadthus:

    V'm = Vm . Z 2Z 1 +Z 2

    operationally they function in the sameway as the early design units (due tothe limited capacity of semi-conductorsto operate at high frequencies).The output impedance of theseinverters is therefore frequencydependent and can be represented bythe diagram used in figure 9.s thus at low frequencies theimpedance of the filter is nearly equalto L.s at high frequencies the filter

    impedance differs little from 1C .

    s at resonant frequency

    Fo =1

    2

    LC

    the impedance of the filter assumes ahigh value that can attain, in terms ofmagnitude, the value of the nominalload impedance of the equipment(Zs = 100 % Zc).In practice, frequency Fo is thereforechosen so as not to correspond to thepossible frequency of currentharmonic, i.e. 210 Hz (harmoniccurrents of order 4 are non-existent orare of very small amplitude).This being the case, various ingenious

    ways have been devised byconstructors in an effort to reduce theoutput impedance.For example:s additional filters,s special connection circuits for thetransformer inserted behind thethree-phase switching device(mutator).At first sight, classic inverters have abehaviour towards harmonic currentscomparable to that of well designedalternators and therefore lesssatisfactory than that of transformers.

    Inverters with PWM and appropriateregulationWhen the switching frequency of theswitching unit (mutator) is high (atleast several kHz) and the regulationsystem allows rapid interventionthrough the modification to pulsewidths during the same period, it isnaturally possible to maintain theinverter output voltage within itsdistortion limits even when dealing withhighly distorted currents.

    The block diagram of such inverter,shown in figure 10 is as follows:The output voltage Vs is constantlycompared with a reference voltageUref which is sinusoidal and has a verylow distortion rate (< 1 %).The voltage difference is thenprocessed by a correction circuit oftransfer function C (p) whose aim it isto ensure the performances and thestability of control circuit systems.The resulting voltage issued from thiscorrection circuit is then amplified bythe switching unit (mutator) itself andits ancillary control circuit with anamplification gain A.The voltage Vm supplied by the

    switching unit is shaped by the filterconsisting of L and C elements beforebecoming the output voltage Vs.In practice, one should take intoaccount:s the impedance of the transformer, ifpresent in the circuit, in order to obtainthe total value of inductance (often theinductance is integrated within thetransformer. That is why it does notappear in circuit diagrams),s the output impedance of theswitching unit which according todesigns, is not necessarily negligible.

    fig. 12: transformed equivalent circuit diagram of switching unit seen from output.

    fig. 11: equivalent circuit diagram of a switching unit seen from output.

    fig. 10: block diagram of a PWM inverter.

    Fo F

    L

    C 1

    Zs

    ZcC

    Vm L Vs I

    -

    UrefC (p) A

    +

    V'm Vs

    Zs

    Vm Z Vs

    Z 1

    2

    fig. 9: variation of output impedance in a classic inverter with frequency.

  • 8/8/2019 ECT159-Inverters c Harmonics

    10/20

    Cahier Technique Merlin Gerin n 159 / p.10

    Everything happens as if the outputimpedance of the inverter were dividedby 1 + (p) . H (p).To throw further light on thisimpedance, it is convenient to carry outadditional calculations.In the band-pass of regulation, theproduct (p) . H (p) being 1,calculations are as follows:1 + (p) . H (p) ( p) . H (p)

    Z's Zs (p) . H (p)

    since

    Zs = Z 1 . Z 2Z 1 + Z 2

    and

    H (p) =Z

    2Z 1 + Z 2

    thus

    Z's Z 1 . Z 2Z 1 + Z 2

    . 1 (p)

    . Z 1 + Z 2Z 2

    thus

    Z's Z 1 (p)

    This means that in the band-pass ofregulation, the output impedance ofinverter is equal to the seriesimpedance of the filter for the wholeoutput circuit divided by theamplification gain of the action chain.Beyond the band-pass of regulation,the output impedance becomes againthe impedance of filter which by thenbecomes the impedance of a capacitoroffering a low impedance at highfrequencies. Hence the shape of thecurve of output impedance in functionof frequency (see fig. 14).

    fig. 13: transformed block diagram of a PWM inverter.

    fig. 14: comparison of output impedances between classic inverter and PWM inverter in function of frequency.

    With PWM inverters, the output impe-dance remains very low up to highfrequencies and the output voltage dis-tortion due to circulating currents, evenhighly distorted currents, is negligible.Limitation of currentThe semi-conductors utilized inswitching units can deliver a maximumcurrent, above which their performancecan no longer be guaranteed. It istherefore advisable to limit the currentto this maximum value in order toensure reliability of performance.As soon as the current drawn by theload exceeds the maximum value setfor the inverter, the latter becomes agenerator of constant current until the

    current value required by the loaddrops below the fixed threshold limit.Under these conditions, the outputvoltage does not follow the shape of thereference voltage and remains distortedas long as the load current exceeds thethreshold limit.This voltage distortion is all the moresignificant, the longer the durationstage above the threshold limit.

    Zc

    V Zs Vs IVref H (p)(p)

    1

    Zs

    classic inverter

    PWM inverter F

    Zs = measured in output by short-circuiting V'm, thus:

    Zs = Z 1 . Z 2

    Z 1 + Z 2

    Ratio Z 2Z 1 + Z 2

    is the transfer function

    of the filter, say H (p):

    thus H (p) = Z 2Z 1 + Z 2

    To simplify still further, it is convenientto replace the product C (p) x A by (p) which represents the transferfunction of action chain.The block diagram becomes thatshown in figure 13, where Zs = output

    impedance in the absence of regulationas is the case in classic inverters.When a current is drawn by the load, avoltage drop appears at the terminals ofthe output impedance Zs, such that:V1 - Vs = ZsIDeveloping still further:V1 = . ( p) . H (p) = Vref - VsV1 = (Vref - Vs) . (p) . H (p)V1 = Vs + ZsIVs + ZsI = (Vref - Vs) . (p) . H (p)

    thus:Vs 1 + (p) . H (p) =V ref (p) . H (p) - ZsI

    thus:

    Vs = V ref. (p) . H (p)

    1 + (p) . H (p)

    - ZsI1 + (p) . H (p)

    The first term represents the resultobtained for a conventional controlsystem with no disturbance present.

    Here, the disturbance is introduced bymeans of current I circulating in theinternal impedance Zs.In the absence of regulation, the termdenoting the disturbance would haveassumed a value of ZsI.With regulation, this disturbance islimited to:

    ZsI1 + (p) . H (p)

  • 8/8/2019 ECT159-Inverters c Harmonics

    11/20

    Cahier Technique Merlin Gerin n 159 / p.11

    Influence of line impedance onvoltage distortionSince the line impedance is additionalto the source impedance, it has theeffect of increasing the distortion rate ofthe voltage in installations drawingdistorted currents.Figure 16 shows an example where anuser installation U 2 draws a highlydistorted current. When this occurs, thedistortion rate measured at its inputterminals is D 2; however, because ofthe impedance divider consisting of Zsand ZL 2, a distortion rate D is measuredat the output terminals of the source Dbeing smaller than D 2.Consequently, to minimise the influence

    of receiver installations which generateharmonic currents in other receivers,it is recommended to supply the receiverinstallations through a special line.Readers interested in further details canrefer to appendix 1.

    Such cases are met essentially whensingle-phase loads consisting of acapacitor in front of a rectifier giving ahigh crest factor. The latter is usually ofthe order of 3 (crest value 3 times theeffective value of current) whereas for apure sine wave it is only 2 .The performance of the PWM inverterfor this type of load is examined inchapter 4.

    impedance of lineThere is always a length of cable ofgreater or lesser importance betweenthe voltage source and each userinstallation.

    Value of line impedanceThe line impedance consists essentiallyof an inductance L in series with aresistance R (see fig. 15). The value ofthe inductance is hardly dependent onthe section of conductors and is usuallyassumed to be 0.1 /km (at 50 Hz)which is roughly equivalent to0.3 H/m.The value of the resistance isdependent on the section of the cableand is taken as r = 20 /km for 1 mm 2section.For example, a cable of 16 mm 2 section

    exhibits a resistance of 1.25 /km anda reactance of only 0.1 /km.As a first approximation, it will bepossible to represent a cable by itsresistance only in the case of small andmedium size power rating installationswhere the use of small sectionconductors is quite common.Note : for harmonic frequencies, it mightbe necessary to take into account theskin effect.In this respect, one must remember thatin a copper conductor, the equivalentconduction thickness, referred to asskin thickness, is given by the formula:

    a (mm) = 66F (HZ)

    Thus, at 50 Hz the skin thickness is9.3 mm, whereas at 1 kHz it is reducedto 2.1mm.The skin effect must therefore be takeninto account for large sectionconductors which generally carryharmonic currents of high order.

    fig. 17: output impedance of different sources in function of frequency.

    fig. 16: supply to polluter receiver (U 2 ) by means of special line.

    fig. 15: equivalent circuit diagram of line.

    In conclusionFigure 17 below shows the variationof output impedances of varioussources of same p ower rating withfrequency.

    eZs

    source

    DZL

    ZL D

    U

    U

    1

    2 22

    1

    L R

    0

    50

    100

    150

    50 250 500 750

    ratio of output impedanceto nominal load impedance

    classicinverter

    PWM inverter

    F (Hz)

    Zs

    Zc%

    alternator X"d = 12 %

    transformer Uccx = 4 %

  • 8/8/2019 ECT159-Inverters c Harmonics

    12/20

    Cahier Technique Merlin Gerin n 159 / p.12

    It is clearly apparent that the PWMinverter exhibits by far the lowestoutput impedance. To better clarify thispoint, figure 18 shows three sources,each with the same impedance at150 Hz.It is thus obvious that the impedance ofa classic transformer as well as theimpedance of the supply line, mustboth be taken into account whendistorted currents are to be supplied toa load.The PWM Inverter is by far the bestgenerator on the market as regards itsability to minimise the voltage harmonicdistortion. It is 5 to 6 times better thana transformer of the same rating.

    Figure 20 shows the voltages andcurrents obtained with a relatively lowsource impedance consisting of aninductance and a resistance such thattheir short-circuit voltages referred tothe load power are respectivelyUccx = 2 % and Ucc R = 2 %.It must be pointed out the distortionrate of the voltage v in the rectifierinput is already important as it reaches7.5 % even despite a low sourceimpedance.The current i starts flowing as soon asthe voltage e becomes higher than Ubut its rate of rise is limited by thesource inductance.This inductance extends the time ofcurrent circulation when voltage e

    becomes again smaller than v.It is therefore essentially the value ofthe source inductance whichdetermines the shape of current i.It is apparent that the current is highlydistorted compared with a perfect sinewave and, in addition, slightly out ofphase with respect to the sourcevoltage. In this example, the powerfactor is equal to 0.72.

    descriptionThese single-phase loads, as manyother types of electronic equipment, aresupplied by means of switched-modepower supplies.Thus, a load of RCD type (Resistances,Capacitors, Diodes) has been retainedin Standard Specification NF C 42-810to characterise inverters of rating below3 kVA.A load of RCD type consists of a Graetzfull-bridge converter and preceded by acapacitor. The latter acts as an energystorage reservoir in order to supplycurrent to the load between twosuccessive peaks of the rectifiedvoltage.The supply source is represented by avoltage e and an output impedanceZs.In the examples cited in this chapter,the time constant of discharge of thecapacitor through the resistance is fixedat 125 ms (see fig. 19).Current i starts flowing when voltage eexceeds the DC voltage U andcirculates for a relatively short time torecharge the capacitor to its nominalvoltage.

    influence of sourceimpedanceIn the previous example it is shown thatthe load cannot be considered as a

    generator of harmonic current, but onthe contrary, that the current is highlydependent on the source impedance.Figure 21 shows the variation of currenti and voltage v in the rectifier inputwhen the source impedance changesfrom Uccx = 0.25 % to Uccx = 8 %

    4. micro and mini-computer loads

    fig. 19: basic circuit diagram of micro and mini-computer type load.

    e

    Zs i

    v C R U

    electric cable transformer PWM inverter

    =

    S = 12 kVAS = 60 kVA

    S = 6 mm 2

    I = 30 m

    fig. 18: sources exhibiting same impedance at 150 Hz.

    ~

  • 8/8/2019 ECT159-Inverters c Harmonics

    13/20

    Cahier Technique Merlin Gerin n 159 / p.13

    Uccx crest power current spectrum global distortionfactor factor rate of voltage

    % H3 H5 H7 H9 H11 H13

    0.25 2.7 0.64 87 64 38 15 1 7 2.80.5 2.63 0.65 85 60 33 11 4 7 3.51 2.51 0.68 81 52 24 6 7 6 5.42 2.35 0.72 76 42 14 7 6 3 7.54 2.19 0.75 69 29 8 8 4 4 11.26 2.1 0.77 63 21 8 6 3 3 14.28 2 0.78 59 17 8 5 3 2 16.8

    whilst the resistive part has beenarbitrarily fixed at Ucc R = 2 % .Table in figure 22 brings to light, forthese different impedances, thevariation of the different characteristicparameters relating to current andvoltage; when the source impedanceincreases, the power factor improveswhereas the distortion rate (see page 4)of the voltage in the input of userinstallation increases.It is the value of the distortion ratewhich determines the choice of thesource. A distortion rate of 5 % is oftenthe limiting value admissible for receiverinstalla-tions that can be either pollutersor polluted.Curves in figure 23 page 14 show thevariation or the global distortion rate ofvoltage in the input of the rectifier infunction of two parameters:s when the short-circuit voltage of thesource varies from 0 to 8 %,s for 3 values of resistive short-circuitvoltage (Ucc R = 0, Ucc R = 2 % andUcc R = 4 %).They also show that, in practice, it is theinductive short-circuit voltage thatdetermines the voltage distortion rateexcept when this short-circuit voltage islower than 1 %.

    calculation of source powerfor supplying RCD typeloadsKnowing the active power absorbed bythe rectifier (Pr), it is essential tochoose correctly the power source (Ps)that must supply it.

    fig. 22: variation of principle characteristic parameters of current and voltage for a computer type load supplied from a source of impedance Ucc R constant and equal to 2 % for values of Uccx varying from 0.25 % to 8 %.

    Hn % = 100 I NI 1

    = PS

    v

    u

    i

    e

    t

    fig. 20: currents and voltages of a computer type load of 1 kW with source such that: Uccx = 2 % and Ucc R = 2 %.

    fig. 21: variation of current and voltage at the computer type load input when the short-circuit voltage Uccx changes from 0.25 % to 8 % while the short-circuit voltage Ucc R remains constant and equal to 2 %.

    I crestI rms

    0,25 %0,5 %

    1 %2 %4 %8 %

    Uccx

    t

  • 8/8/2019 ECT159-Inverters c Harmonics

    14/20

    Cahier Technique Merlin Gerin n 159 / p.14

    order of 1 % (in accordance withfigure 23),s for a distortion rate of 10 %, ashort-circuit voltage of the order of 3 %must be retained.For a transformers if Uccx = 4 %s for D = 5 % a power ratio of:

    PsPr

    = 4 %1 %

    = 4 is sufficient,

    s for D = 10 % the power ratio wouldbe:

    PsPr

    = 4 %3 %

    = 1.33

    but in this case, a value at least equal

    to 1.43 would be required by the powerfactor.s if Uccx = 6 %s for D = 5 % a power ratio of:

    PsPr

    = 6 %1 %

    = 6 is necessary ,

    s for D = 10 %, a power ratio of 2 isrequired.

    Note : for a transformer, it is oftennecessary to take a much higher powerratio considering that distortions canalready be present in the network.A distortion rate of 3 % due solely tothe working of the rectifiers, leads oneto retain a inductive short-circuitvoltage of 0.45 % (in accordance withfigure 23) which amounts to multiplyingby 2.2 the power ratings oftransformers to obtain a distortion rateof 5 %.

    For an alternatorAs distortion rates of 5 % and 10 %lead to inductive short-circuit voltagesof 1 % and 3 % respectively, powerratios of alternator to rectifier aretherefore equal to respectively:

    Uccx1 %

    and Uccx3 %

    .

    If Uccx = 18 %, it will be necessary:s for D = 5 %to have a power ratio of:

    PsPr

    = 18 .

    s for D = 10 %to have a power ratio of:

    PsPr

    = 18 %3 %

    = 6.

    For an inverters classic inverterAs it was explained in our discussionon source impedances, this type ofinverter of single phase mode exhibitsan impedance comparable to that of analternator of good design (with Uccx ofthe order of 12 %).As generally the output distortion of aninverter must be limited at 5 %, then itis desirable to retain a power ratio ofthe order of 12.Inverters of the classic type areavailable today mostly in three phaseversion. In these, always assuming adistortion rate of 5 %, the power ratio is7 when operated with a transformerwhose secondary is connected inZIGZAG.s PWM inverter with appropriateregulation(reminder: its impedance is at leastfive times lower than that of atransformer for which the power ratingmust be multiplied by 4).

    In our development hereafter, theimpedance of the supply line isneglected (or integrated into Ucc ofsource).A first indication is provided by thepower factor:

    = PS

    This power factor is dependent on thetotal short-circuit voltage upstream ofrectifier but can be given a meanvalue of the order of 0.7.Having established this first criterion,the power of the source musttherefore be at least equal to theactive power absorbed by the rectifiermultiplied by

    10.7

    or 1.43.

    The second criterion is related to adistortion rate that would beacceptable:s if a distortion rate of 5 % isenvisaged, it is possible to retain aninductive short- circuit voltage of the

    fig. 23: variation of voltage distortion rate at input of microprocessor type load with respect to Uccx and several values Ucc R of the source.

    0 1 2 3 4 5 6 7 8

    5

    10

    15

    Uccx %

    U = 0

    U = 2 %U = 4 %

    voltage distortion

    rate as %CCRCCR

    CCR

  • 8/8/2019 ECT159-Inverters c Harmonics

    15/20

    Cahier Technique Merlin Gerin n 159 / p.15

    As long as the current drawn by theload exhibits a crest value lower thanthe limiting threshold value for theequipment, the distortion rate remainsvery low and inferior to 5 %. As soon asthe threshold limit is reached, thevoltage supplied by the inverterbecomes distorted (sine wave becomesaffected by crest flattening) and thevoltage distortion rate increases.Experience shows that, in order toavoid a voltage distortion exceeding5 %, it is necessary to set the thresholdlimit for current at 1.5 times the crestvalue of the nominal effective current ofthe inverter,

    thus I limit = 1.5 2 I rms.

    The corresponding crest factor ofcurrent is then equal to1.5 2 that is 2.12.Figure 24 shows the variation(evolution) of voltage and current in a5.2 kVA inverter with a threshold limitset at:

    5,000220

    . 1.5 . 2 = 48 A .

    A voltage distortion rate of 5 % isreached here for an apparent power of5.2 kVA, that is slightly greater than5 kVA which is its design parameter forrating.The power factor of the RCD load is, inthis case very close to 0.8 (0.79) andconsequently the inverter does notneed to be over-dimensioned in orderto supply this type of load (except whenthe distance between inverter andloads is relatively significant, this beinghowever, true for all sources).In the example shown in figure 24, a5 kVA inverter is capable of supplying a4 kW rectifier with a distortion rate

    inferior to 5 %.

    Thus P inverter = P R0.8

    = 1.25 P R

    It is worth noting that the fact of limitingthe current improves the power factor.In the preceding paragraph dealing withtransformer, it was noticed that, with apower factor of rectifier amounting to0.7, it was necessary, even in theabsence of constraints on the distortionrate, to choose a transformer whosepower rating was at least equal to1.43 P R.

    The PWM inverter appears therefore tobe the ideal source of voltage forsupplying not only loads of RCD typebut also all receiver equipment whichare generators of harmonic currents(non-linear loads).In the preceding section, we havediscussed the case of inverters and

    single phase loads; the samereasoning can indeed be applied tothree phase equipment providing theequipment is fitted with independentregulation in each phase (this isgenerally the case with this type ofequipment).

    fig. 24: variation of output voltage of 5 kVA inverter with threshold limit set at 48 A.

    Urms : 220 V

    Irms : 20 A

    power factor : 0.69

    crest factor : 2.4

    distortion rate : 3 %

    apparent power : 4.4 kVA

    active power : 3 kW

    48A

    48A

    48A

    Urms : 220 V

    Irms : 11 A

    power factor : 0.61

    crest factor : 3.6

    distortion rate : 2.7 %

    apparent power : 2.4 kVAactive power : 1.5 kW

    Urms : 220 V

    Irms : 24 A

    power factor : 0.79

    crest factor : 2

    distortion rate : 5 %

    apparent power : 5.2 kVA

    active power : 4.17 kW

    Urms : 220 VIrms : 29 A

    power factor : 0.82

    crest factor : 1.64

    distortion rate : 10 %

    apparent power : 6.3 kVA

    active power : 5.2 kW

  • 8/8/2019 ECT159-Inverters c Harmonics

    16/20

    Cahier Technique Merlin Gerin n 159 / p.16

    s first assuming that Z 2 = 0 (load veryclose to transformer).Curves in figure 23 will giveD = 4.6 % = D 2.s it is necessary now to calculate D etD2 with a line 100 m/10 mm 2(i.e. 100 m long and a section 10 mm 2):s thus short-circuit impedances of theline referred to P R:

    U'2ccx = l .P R

    Un 2 . 100

    U'2cc R = R . P RUn 2

    . 10

    thus with:

    l = 0.1 . 1001,000

    = 10 m

    r = 20 . 1001,000

    . 110

    = 0.2

    s characteristics of transformer:50 kVA (with Uccx = 4 % etUcc R = 2 %).It is necessary to calculate theimpedances of the inductive short-circuit and resistive short-circuit of thetransformer but referred to the activepower of micro-computers, thus:

    U'1ccx = U1ccx . P RPs

    U'1cc R = U1cc R . P RPs

    thus

    U'1ccx = 4 % . 1050

    = 0.8 %

    U'1cc R = 2 % . 1050

    = 0.4 %

    5. conclusion

    them to supply a low distortion voltageto receivers that are generators ofharmonic currents (non-linear loads).

    market for supplying electronic andmicro-processor loads. The high speedresponse of their regulation systemsendows them with a very lowharmonic impedance; thus enables

    Static inverters equipped with PWM arenearly perfect sources of voltage.Besides their qualities as regardsvoltage stability and frequency stability,they are the best generators on the

    appendix 1: influence of line impedances on voltage distortions

    The end of paragraph 3 stresses thefact that it is desirable to supplyreceivers that are generators ofharmonic currents by means of speciallines.This is true for loads of RCD type, butalso for all receivers utilising powerelectronics such as rectifiers, batterychargers, speed controllers etc.The use of a special line provides

    isolation of harmonics throughimpedance (see fig. 25).

    For a clean receiverThe distortion rate D 1 is practicallyidentical to D, and this is all the moretrue as the impedance of line Z 1 issmall compared with that ofreceiver Zp.For a non-linear receiverD2 will be all the more lower as thesum Z 2 + Zs will remain low, in otherwords as the non-linear receiver willhave a low power rating in relation to

    its supply.The following example shows moreclearly the influence of Z 2 on D and D 2.Lets consider a set of micro-computerabsorbing 10 kW at 230 V that is beingsupplied by a cable conductor 100 mlong connected to a transformer.s characteristics of cable:s section: 10 mm 2,s L = 0.1 /km at 50 Hz,s r = 20 /km for a 1 mm 2 section.

    fig. 25: power supply through a specific line a receiver generator of harmonic currents.

    e

    Zs

    D

    D

    Zp

    Ls Rs

    U1ccx U1

    Z

    Z

    I r

    Dcleanreceiver

    non-linearreceiver

    1

    2

    1

    2

    CCR

  • 8/8/2019 ECT159-Inverters c Harmonics

    17/20

    Cahier Technique Merlin Gerin n 159 / p.17

    fig. 26a: voltage distortion rates due to Uccx for various values of Ucc R .

    U'2ccx = 10 . 10 -3 . 104

    (230) 2. 100

    = 0.19 %

    U'2cc R = 0.2 . 104

    (230) 2. 100 = 3.8 %

    s total short-circuit impedances:

    U'ccx = 0.8 % + 0.19 % = 0.99 %

    U'cc R = 0.4 % + 3.8 % = 4.2 %

    thus

    U'ccx = U'1ccx + U'2ccx

    U'cc R = U'1cc R + U'2cc R

    s the voltage distortion rates D L and

    DR related to impedances ofinductive short-circuits and resistiveshort-circuits.These values are obtained from curvesin figure 26a and figure 26b and arerespectivelyDL = 3.9 %,

    DR = 3.9 %.

    s distortion rate at input of personalcomputers:

    D 2 = (3.9 ) 2 + (3.9 %) 2 = 5.52 %.

    s voltage distortion rates D L and D R atthe source:

    D L = D' L . U'1ccxU'ccx

    D R = D' R . U'1cc RU'1cc R

    thus:

    D L = 3.9 % . 0.80.99

    = 3.15 %

    D R = 3.9 % . 0.44.2

    = 0.37 %.

    s voltage distortion rate D at the source

    D = D L2 + D R2

    D = (3.15 %) 2 + (0.37 %) 2 = 3.17 %.

    s in this example, the supply linecauses D and D 2 to change as follows

    D from 4.6 % to 3.17 %,

    and D 2 from 4.6 % to 5.52 %.fig. 26b: distortion rates due to Ucc R for various values of Uccx.

    0 1 2 3 4

    5

    10

    Uccx %

    distortion ratedue to Uccx

    U = 0CCR

    U = 2 %CCR

    U = 4 %CCR

    0 1 2 3 4

    1

    2

    3

    %

    Uccx = 0

    Uccx = 1 %

    Uccx = 2 %

    Uccx = 3 %

    Uccx = 4 %

    distortion ratedue to UCCR

    UCCR

    %)2

  • 8/8/2019 ECT159-Inverters c Harmonics

    18/20

    Cahier Technique Merlin Gerin n 159 / p.18

    fig. 28: basic circuit diagram of an antiparasitic interference filter.

    fig. 27: basic circuit diagram switched mode power supply to RCD load.

    appendix 2: input filters in computer/micro-processor equipment

    Their purpose is to stop thepropagation of disturbances caused byswitched mode power supplies towardsother equipment installations that couldbe adversely affected.Conversely, they help attenuate somedisturbances present in the networkwhich are likely to alter the functioningof electronic and data informationequipment.The question is to know if these filtersattenuate harmonic currents generatedby RCD loads.Interference rejection in networkSwitched mode power supplies operateat high frequencies in an effort toreduce the size and weight oftransformers.In figure 27, the load resistance R is thebasic circuit shown in figure 19 isreplaced by a transformer and its load.In this circuit, the line current remainsidentical because of the presence ofcapacitor C.To achieve silent operation, the

    switching frequency is always high andin any case in excess of 20 kHz.The commutation times of a transistor(change from non-conducting toconducting state and vice versa) arevery brief and do not, in some cases,exceed a few tens of nano seconds.These high frequency commutations(switching) do generate HF interferencethat is propagated by conduction andradiation. This gives rise to thepresence of parasitic interference alongthe line upstream of the switchingdevice, that is in the mains (on this

    subject, it is recommended to refer toCahier Technique n 149Electromagnetic Compatibility).In order to limit the circulation of theseHF currents, constructors of datainformation processing equipmentinsert filters upstream of the switchedmode power supply unit; a typicalcircuit of such filters is shown infigure 28.These filters reduce disturbances:s of common mode which affect in thesame way both conductors with respectto earth,

    s of differential mode which are presentbetween the two conductors.Inductance L offers a high impedanceto currents of common mode butpractically none to those of differentialmode as its windings are wound inopposition.Disturbances of common mode areconducted to earth by capacitors C 1and blocked by inductance L.Disturbances of differential mode are

    attenuated by capacitors C A and C Rwhich, at high frequency, offer a lowimpedance between the conductors.

    Protection of switched mode powersupplyThe filter inserted between the ACmains and the RCD supply ensures asecond function: it protects the RCDsupply from impulse type over-voltagesand from HF interference of differentialand common mode which are presentin the mains.

    Leakages to earthThe presence of capacitors C 1 causesa leakage current at 50 Hz to flow toearth.Design standards generally specifyvalues of leakage current not to beexceeded (a few milliamperes forequipment connected to a mains point).For example, standard specificationIEC 950 relating to data processingequipment recommends that theseleakage currents should be kept below3.5 mA for equipment connected to amains point.

    In fact, currents of the order of 1 to2 mA have been measured by UTE.If a line supplies several electronic anddata processing equipment, the sum ofthe leakage currents can trip the highlysensitive differential residual currentdevice (30 mA) inserted in the line.

    Filtering of harmonicsThe filters inserted between the mainsand the RCD supply operate efficientlyin the frequency band-pass ranging

    from 10 kHz to 100 MHz.Unfortunately, they are of no useagainst harmonic currents injected intothe mains network.This is due to the fact that harmoniccurrents produced by RCD supplies areof relatively low frequency: 1 kHzcorresponds in fact to a harmonic oforder 20 in relation to a fundamental at50 Hz!

    C

    + 12 V

    0 V

    mainssupply

    RCD supplyCC

    C

    C

    L

    Imc Imd

    Imc Imd

    R A

    1

    1 , ,@ @P P, ,@ @P P, ,@ @P P, ,@ @P P, ,@ @P P, ,@ @P P

  • 8/8/2019 ECT159-Inverters c Harmonics

    19/20

    Cahier Technique Merlin Gerin n 159 / p.19

    appendix 3: bibliography

    Normess IEC 146-1-1Semi-conductor converters. Generalrequirements and line commutatedconvectors - part 1-1: specificationsbasic requirements.s IEC 950Safety of information technologyequipment including electrical businessequipment.(NF C 77-210, modification 1incorporated).s NF C 42-810Alimentations sans interruption, depuissance nominale infrieure 3 kVA.

    Cahiers Techniques Merlin Gerins Analyse des rseaux triphass enrgime perturb l'aide descomposantes symtriquesCahier Technique n 18- by B. De METZ-NOBLAT.s EMC: electromagnetic compatibilityCahier Technique n 149- by F. VAILLANT.

  • 8/8/2019 ECT159-Inverters c Harmonics

    20/20

    l ll h