Economizers for Data Centers Peter Rumsey, P.E.

Transcript of Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water...

Page 1: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Economizers for Data CentersPeter Rumsey, P.E.

Page 2: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Energy Consumption in Typical Data Center

Servers and Data

Equipment55%

HVAC (Fans, Compressors,

etc.)30%

Lighting3%

Other12%

Page 3: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Some Definitions

Air Side EconomizersThe use of outside air directly supplied to the space for cooling purposes

Water Side EconomizersThe use of cooling tower water to provide chilled water to a chilled water cooling systemIsolated from chilled water loop with heat exchangerAlso known as “free cooling”

Page 4: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Air Side Economizers

Page 5: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

San Jose, CAWYE Psychrometric Chart

RH = 20%

RH =

60%

RH

= 80

%

h = 30 Btu/lb ⎯⎯→

h = 40 Btu/lb ⎯⎯→

h = 50 Btu/lb ⎯⎯→

0.0000

0.0020

0.0040

0.0060

0.0080

0.0100

0.0120

0.0140

0.0160

0.0180

0.0200

0.0220

0.0240

0.0260

0.0280

0.0300

30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

Dry Bulb Temperature (F)

Hum

idity

Rat

io (l

bs H

2O p

er lb

s dr

y ai

r)Air-Side EconomizeToa<55 100% Econ – 3140 hrs/yrToa>55 and Toa<70 partial Econ. – 4096 hrs

Page 6: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

LBNLData Center Benchmarking Case Study

Page 7: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

HVAC Power Consumption

29%31%

25%

50%

36%

31% 32%

54%

22%

46%

35%

1 2 3 4.1 4.5 5 6.2 7 8.1 8.2 9

Facility No. - Data Center No.

All values are shown as a fraction of the respective data center total power consumption.

Worst Case "HVAC Efficiency"

Best Case "HVAC Efficiency"

California Energy Commission and NYSERDA Data Center Benchmarking

Page 8: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

CRAC Units Versus

Air Handlers

Page 9: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

How did they do it?

Data Center 8.1• Air cooled CRAC units• No economizing• Constant Speed Fans• Humidification control• All CRAC units on

Data Center 8.2••

••

Central chilled water plantCentral air handling units with VFDs and ECONOMIZERSMinimal humidity controlData Monitoring – Gateways, EMCS

Page 10: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

City of Oakland Data Center

Page 11: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control
Page 12: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control
Page 13: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

House Air System Air Side Economizer

and Chilled Water System

VFD

Cold Aisle

Cold Aisle

Hot Aisle

Hot Aisle

Hot Aisle

DX Package Unit For use on nights and weekends

Economizer Capable

BD

Page 14: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Results

Doubled Cooling CapacityAllowed for the removal of several portable coolers

Annual Energy Savings$20,000 per year

Humidification on low humidity days with electric humidifier

Page 15: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Analyses for other facilities – New Construction

Data Center Size

Annual Energy Saved (kWh)

Annual Energy

Cost Saved

Savings by Design

Incentive

Estimated Cost to

Implement

Estimated Simple

Payback (years)

30,600 SF 498,000 $69,800 $10,500 $21,000 0.2

9,600 SF 200,000 $28,000 $7,500* $15,000 0.3

Page 16: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

THE HUMIDITY ISSUE

San Jose, CAWYE Psychrometric Chart

RH = 20%

RH =

60%

RH

= 80

%

h = 30 Btu/lb ⎯⎯→

h = 40 Btu/lb ⎯⎯→

h = 50 Btu/lb ⎯⎯→

0.0000

0.0020

0.0040

0.0060

0.0080

0.0100

0.0120

0.0140

0.0160

0.0180

0.0200

0.0220

0.0240

0.0260

0.0280

0.0300

30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

Dry Bulb Temperature (F)

Hum

idity

Rat

io (l

bs H

2O p

er lb

s dr

y ai

r)

Dewpoint < 38 Deg F and Tdb <70 deg FHumidify 1200 Hours Per Year

Page 17: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Comparison of Economizer versus Compressor Cooling

Cooling Costs – Air Cooled CRACs or Chillers (1.2 kW/ton)100% recirculation - $3.26/cfm/yrEconomizer in San Jose - $1.65/cfm/yr49% savings

Cooling Costs – Water Cooled Chiller (system 0.8 kW/ton)100% recirculation - $2.17/cfm/yrEconomizer in San Jose - $1.22/cfm/yr43% savings

Includes additional costs of humidification with electric humidifier up to 30% RH at 70 deg F - $0.36/cfm/yr

Page 18: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Water Side Economizers

Page 19: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Free Cooling

Page 20: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Water Side Economizer In Series with Chilled Water

M

M

M

CHW Return 65 Deg F

CHW 60 Deg F

CHW Supply 50 Deg F

Chiller #2

Chiller #1

CHW Supply 50 Deg F

CWS

CWS

CWR

CWR

Page 21: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

San Jose, CAWYE Psychrometric Chart

RH = 20%

RH =

60%

RH

= 80

%

h = 30 Btu/lb ⎯⎯→

h = 40 Btu/lb ⎯⎯→

h = 50 Btu/lb ⎯⎯→

0.0000

0.0020

0.0040

0.0060

0.0080

0.0100

0.0120

0.0140

0.0160

0.0180

0.0200

0.0220

0.0240

0.0260

0.0280

0.0300

30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

Dry Bulb Temperature (F)

Hum

idity

Rat

io (l

bs H

2O p

er lb

s dr

y ai

r)

Free Cooling / WaterSide EconomizeIf Chilled Water Supply Temperature is 50 deg F…Twb<40 100% Econ – 570 hrs/yrTwb>40 and Twb<55 partial Econ. – 4610 hrs/yr

Twb=40 deg F

Twb=55 deg F

Page 22: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control

Another way to look at it….

0.1 to 0.2 kW/tonWater Side Economizer0 - ? kW/tonAir Side Economizer0.5 – 0.8 kW/tonWater Cooled Chiller - System1.2-1.4 kW/tonAir Cooled Chiller - System1.2-1.4 kW/tonAir Cooled CRAC Efficiency

Page 23: Economizers for Data Centers - cfroundtable.org Center 8.2 • • • • Central chilled water plant Central air handling units with VFDs and ECONOMIZERS Minimal humidity control