Ecology with Economy! - jcma2.jp · Economic Advantages – 3 Advantages By switching the cable...

2
Recommended cables applicable to increasing the conductor size ECSO design is recommended to be applied to Low-voltage Cross-linked Polyethylene Insulated Cables (CVT) and Low-voltage eco-cables (EM-CET) used in factories and buildings which are operated with high loading or medium loading within the operating categorization. If applied to transmission and distribution cables with high loading, there is a big advantage, but it is necessary to pay attention because size up (optimization) may affect the strength of the steel tower and the utility pole, the diameter of the duct, etc. Low-voltage cables used in factories, buildings, etc. are laid in racks (shelves) and pits (grooves) and are recommended because they are relatively unlikely to have problems in application. Selection Table – ECSO (Environmental Current Rating) Table The following is the environmental current rating calculated as JCS 4521:2014 Table2. Environmental Current Rating Conductor Size CVT Environmental Current Rating(A) Conductor Size EM-CET Environmental Current Rating(A) High Loading Operation Mid. Loading Operation Low Loading Operation High Loading Operation Mid. Loading Operation Low Loading Operation 8 mm 2 8 9 12 8 mm 2 8 9 12 14 mm 2 13 15 20 14 mm 2 13 15 21 22 mm 2 20 23 31 22 mm 2 21 24 33 38 mm 2 32 37 49 38 mm 2 34 39 52 60 mm 2 55 64 85 60 mm 2 59 68 91 100 mm 2 82 95 127 100 mm 2 88 102 137 150 mm 2 107 124 165 150 mm 2 116 134 179 200 mm 2 151 174 232 200 mm 2 164 189 252 250 mm 2 182 210 280 250 mm 2 196 226 302 325 mm 2 285 329 439 325 mm 2 306 353 471 200 mm 2 dual 302 348 464 200 mm 2 dual 328 378 504 250 mm 2 dual 364 420 560 250 mm 2 dual 392 452 604 325 mm 2 dual 570 658 878 325 mm 2 dual 612 706 942 ・High loading: 100% in the daytime, 60% to 80% in the night ・Medium loading: 100% in the daytime, 50% in the night ・Low loading: 100% only in the daytime Standards to be referred (1) Japanese Standard: JCS 4521:2014 "Calculation of the Environmental Current Rating of the Electric Cables : 600V Cross-linked Polyethylene Insulated Cables" (2) JEAC 8001-2016 “The Interior Wiring Code” (3) lnternational Standard: IEC International Standard (planned) JCMA proprietary The Japanese Electric Wire & Cable Makers' Association We at JCMA are making every possible effort to ensure all the data and information provided on this brochure are accurate. However, we make no guarantee or warranty regarding the accuracy of them. We do not intend to state that the data and information are correct, without any errors, reliable, or most updated. We may change or update the information on this brochure without any notice. Any inquiries and comments are to be made to JCMA. The Japanese Electric Wire & Cable Makers' Association Konwa Bldg., 2nd Floor, 1-12-22, Tsukiji, Chuo-ku, Tokyo, JAPAN 104-0045 TEL 03-3542-6035 FAX 03-3542-6037 http://www.jcma2.jp/index.html JCMA proprietary © The Japanese Electric Wire & Cable Makers’ Association 2017 Considering the environmental and economical aspects (ECSO:Environmental and Economical Conductor Size Optimization) ECSO ECSO Cost reduction by increasing the conductor size ECSO Design Conventional Design Introducing New Design Technology Introduction also in The Interior Wiring Code

Transcript of Ecology with Economy! - jcma2.jp · Economic Advantages – 3 Advantages By switching the cable...

Page 1: Ecology with Economy! - jcma2.jp · Economic Advantages – 3 Advantages By switching the cable from the conventionally used size to ECSO designed size, we can get the Advantages

Recommended cables applicable to increasing the conductor size ECSO design is recommended to be applied to Low-voltage Cross-linked Polyethylene Insulated Cables (CVT) and Low-voltage eco-cables (EM-CET) used in factories and buildings which are operated with high loading or medium loading within the operating categorization. If applied to transmission and distribution cables with high loading, there is a big advantage, but it is necessary to pay attention because size up (optimization) may affect the strength of the steel tower and the utility pole, the diameter of the duct, etc. Low-voltage cables used in factories, buildings, etc. are laid in racks (shelves) and pits (grooves) and are recommended because they are relatively unlikely to have problems in application.

Selection Table – ECSO (Environmental Current Rating) Table The following is the environmental current rating calculated as JCS 4521:2014

Table2. Environmental Current Rating

Conductor Size CVT Environmental Current Rating(A) Conductor Size EM-CET Environmental Current Rating(A)High Loading Operation Mid. Loading Operation Low Loading Operation High Loading Operation Mid. Loading Operation Low Loading Operation

8 mm2 8 9 12 8 mm2 8 9 1214 mm2 13 15 20 14 mm2 13 15 2122 mm2 20 23 31 22 mm2 21 24 3338 mm2 32 37 49 38 mm2 34 39 5260 mm2 55 64 85 60 mm2 59 68 91

100 mm2 82 95 127 100 mm2 88 102 137150 mm2 107 124 165 150 mm2 116 134 179200 mm2 151 174 232 200 mm2 164 189 252250 mm2 182 210 280 250 mm2 196 226 302325 mm2 285 329 439 325 mm2 306 353 471200 mm2 dual 302 348 464 200 mm2 dual 328 378 504250 mm2 dual 364 420 560 250 mm2 dual 392 452 604325 mm2 dual 570 658 878 325 mm2 dual 612 706 942

・High loading: 100% in the daytime, 60% to 80% in the night ・Medium loading: 100% in the daytime, 50% in thenight ・Low loading: 100% only in the daytime

Standards to be referred(1) Japanese Standard: JCS 4521:2014 "Calculation of the Environmental Current

Rating of the Electric Cables : 600V Cross-linked Polyethylene Insulated Cables"(2) JEAC 8001-2016 “The Interior Wiring Code”(3) lnternational Standard: IEC International Standard (planned)

JCMA proprietary

The Japanese Electric Wire & Cable Makers' AssociationWe at JCMA are making every possible effort to ensure all the data and information provided on this brochure are accurate. However, we make no guarantee or warranty regarding the accuracy of them. We do not intend to state that the data and information are correct, without any errors, reliable, or most updated. We may change or update the information on this brochure without any notice. Any inquiries and comments are to be made to JCMA.

The Japanese Electric Wire & Cable Makers' AssociationKonwa Bldg., 2nd Floor, 1-12-22, Tsukiji, Chuo-ku, Tokyo, JAPAN 104-0045

TEL 03-3542-6035 FAX 03-3542-6037http://www.jcma2.jp/index.html

JCMA proprietary

© The Japanese Electric Wire & Cable Makers’ Association 2017

Considering the environmental and economical aspects

(ECSO:Environmental and Economical Conductor Size Optimization)

E C S OE C S O

Cost reduction by increasing the conductor size

ECSO Design

Conventional Design

Introducing New Design Technology

Introduction alsoin The InteriorWiring Code

15002203 JCMA 最適導体パンフ英文.indd 1-2 2017/08/02 14:22:01

Page 2: Ecology with Economy! - jcma2.jp · Economic Advantages – 3 Advantages By switching the cable from the conventionally used size to ECSO designed size, we can get the Advantages

Economic Advantages – 3 Advantages By switching the cable from the conventionally used size to ECSO designed size, we can get the Advantages as follows (Fig.1).❶ CO2 Emission reduction ❷ Peak-demand control ❸Energy SavingThese 3 advantages can bring in/direct financial advantages to us. Table. 1 shows one example of financial advantages calculated, together with the years needed to be break-even for the investment.

Eco-friendly conductor size selection (effect trial calculation) software which can be easily calculated by anyone is released below.

http://www.jcma2.jp/ecso.html

Outline By increasing the conductor size of the power cab le , you can reduce the t ransmiss ion / distribution losses, which leads to reduction of CO2 emissions and energy saving. We at JCMA have establ ished the design technologies of optimum conductor size (ECSO*1) to pub l i sh " JCS 4521 : Ca l cu la t ion o f t he Environmental Current Rating for the Electric Cables", which put the ECSO design methods together. This standard is also introduced in the "JEAC 8001-2016 The Interior Wiring Code ". Since the environmental issues need to be addressed in a global base, we are making the term, ECSO as an Internationally Common Key Word, to ensure the intelligence to be shared globally, and to have it as a global standard.

※1 Environmental and Economical Conductor Size Optimization

Design Technology for Optimum Conductor Size (ECSO)

From ‘Minimum Initial Cost’ to ‘Minimum Life Cycle Cost’*2

 Preference has always been given to the lowest initial cost, i.e., the smallest possible conductor, as long as safety measures (current rating and preventing the voltage drop) are secured. Design technology for optimum conductor size (ECSO) is to define the most appropriate size to make the life cycle cost lowest, which means the larger cables. This technology considers both economical and environmental aspects, to make it possible to design the optimum conductor size.

※2 Life Cycle Cost = Initial Cost + Running (operational) Cost

E c o l o g y w i t h E c o n o m y !

JCMA proprietary JCMA proprietary

3 Energy Saving – reducethe distribution loss by 2%The cables selected by ECSO design can transmit the power with a leeway, so the loss (or heat generation) can be less.

Cut peak demand lower by 2%

During the peak demand time zone, the load at the plants can be lowered – this can be used favorably on negotiation of the power tariff for the following year.

2

Small LargeConductor Size

Smal

lLa

rge

Cost

Pow

er C

onsu

mpt

ion

ECSO Design: Select the size to make the LCC minimum

Conventional Design : Select the size to make the initial cost minimum, which leads to the higher life cycle cost.

Life Cycle Cost

Initial Cost

Running Cost

Demand Terminal

Conductor size twice as largeConductor

size twice as large

Table 1 - Calculation results of Economic Advantages - High Loading Condition

Max. Load

Current

〔A〕

Increasingthe Conductor Size Existing → ECSO

3 Advantages※3 ROIvs

Invst.※4

(year)

Energy Saving

(kWh/year)

CO2Reduction

(CO2-t/year)

Peak Demand Control (kW)

30 8 mm2 → 38 mm2 24,200 10.9 5.0 3.0

40 14 mm2 → 60 mm2 23,700 10.7 4.9 4.3

50 14 mm2 → 60 mm2 37,000 16.7 7.7 2.8

75 38 mm2 → 100 mm2 24,600 11.1 5.1 5.6

100 38 mm2 → 150 mm2 52,600 23.7 11.0 4.5

125 60 mm2 → 200 mm2 48,600 21.9 10.1 5.7

150 100 mm2 → 200 mm2 29,800 13.4 6.2 6.2※3 Calculated amount per 1,000m length of cable※4  Three ef fects are proportional to the length of the cable, but

the number of years to recover the increased investment is determined regardless of length.

0 6 12 18 24

Fig. 1 - Power Consumption - Transition by Hour

❶&❸Reduce by 2%

❷ Reduce by 2%After increasingthe conductor size

3 Advantages

CO2Emissionreduction by 2%

By reducing the wasted distribution loss, we can help reduce CO2 emission.

1

Conventional Design Distribution

loss 4%

ECSO Design Distribution

loss 2%

Power Generation

Power Plant

Each Loading Terminal

Each Loading Terminal

Before increasingthe conductor size