ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye...

33
ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana- Champaign [email protected]

Transcript of ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye...

Page 1: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

ECE 476 Power System Analysis

Lecture 10: Per Unit, Transformers, Load, Generators

Prof. Tom Overbye

Dept. of Electrical and Computer Engineering

University of Illinois at Urbana-Champaign

[email protected]

Page 2: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Announcements

• Please read Chapter 3; start on Chapter 6• H5 is 3.4, 3.10, 3.14, 3.19, 3.23, 3.60, 2.38, 6.9

• It should be done before the first exam, but does not need to be turned in

• First exam is Tuesday Oct 6 during class• Closed book, closed notes, but you may bring one 8.5 by

11 inch note sheet and standard calculators.

2

Page 3: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Service Entrance Grounding

Image: www.osha.gov/dte/library/electrical/electrical_10.gif

We’ll talk moreaboutgroundinglater in the semesterwhen wecover faults

3

Page 4: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Three Phase Per Unit

1. Pick a 3f VA base for the entire system,

2. Pick a voltage base for each different voltage level, VB. Voltages are line to line.

3. Calculate the impedance base

Procedure is very similar to 1f except we use a 3f VA base, and use line to line voltage bases

3BS

2 2 2, , ,3 1 1

( 3 )

3B LL B LN B LN

BB B B

V V VZ

S S S

Exactly the same impedance bases as with single phase!

4

Page 5: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Three Phase Per Unit, cont'd

4. Calculate the current base, IB

5. Convert actual values to per unit

3 1 13 1B B

, , ,

3I I

3 3 3B B B

B LL B LN B LN

S S S

V V V

Exactly the same current bases as with single phase!

5

Page 6: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Three Phase Per Unit Example

Solve for the current, load voltage and load power in the previous circuit, assuming a 3f power base of300 MVA, and line to line voltage bases of 13.8 kV,138 kV and 27.6 kV (square root of 3 larger than the 1f example voltages). Also assume the generator is Y-connected so its line to line voltage is 13.8 kV.

Convert to per unitas before. Note thesystem is exactly thesame!

6

Page 7: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

3f Per Unit Example, cont'd

L

2*

1.0 00.22 30.8 p.u. (not amps)

3.91 2.327

V 1.0 0 0.22 30.8

p.u.

0.189 p.u.

1.0 0 0.22 30.8 30.8 p.u.

LL L L

G

Ij

VS V I

ZS

Again, analysis is exactly the same!

7

Page 8: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

3f Per Unit Example, cont'd

LActual

ActualL

ActualG

MiddleB

ActualMiddle

0.859 30.8 27.6 kV 23.8 30.8 kV

0.189 0 300 MVA 56.7 0 MVA

0.22 30.8 300 MVA 66.0 30.8 MVA

300 MVAI 125 (same cur0 Amps

3138 kV

I 0.22 30.

rent!)

8

V

S

S

Amps 275 30.8

Differences appear when we convert back to actual values

8

Page 9: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

3f Per Unit Example 2

•Assume a 3f load of 100+j50 MVA with VLL of 69 kV is connected to a source through the below network:

What is the supply current and complex power?

Answer: I=467 amps, S = 103.3 + j76.0 MVA

9

Page 10: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Per Unit Change of MVA Base

• Parameters for equipment are often given using power rating of equipment as the MVA base

• To analyze a system all per unit data must be on a common power base

2 2

Hence Z /

Z

base base

OriginalBase NewBasepu actual pu

OriginalBase NewBasepu puOriginalBase NewBase

BaseBase

NewBaseOriginalBase NewBaseBasepu puOriginalBase

Base

Z Z Z

V VZ

SS

SZ

S

10

Page 11: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Per Unit Change of Base Example

•A 54 MVA transformer has a leakage reactance of 3.69%. What is the reactance on a 100 MVA base?

1000.0369 0.0683 p.u.

54eX

11

Page 12: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Transformer Reactance

• Transformer reactance is often specified as a percentage, say 10%. This is a per unit value (divide by 100) on the power base of the transformer.

• Example: A 350 MVA, 230/20 kV transformer has leakage reactance of 10%. What is p.u. value on 100 MVA base? What is value in ohms (230 kV)?

2

1000.10 0.0286 p.u.

350

2300.0286 15.1

100

eX

12

Page 13: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Three Phase Transformers

• There are 4 different ways to connect 3f transformers

Y-Y D-D

Usually 3f transformers are constructed so all windings

share a common core13

Page 14: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

3f Transformer Interconnections

D-Y Y-D

14

Page 15: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Y-Y Connection

Magnetic coupling with An/an, Bn/bn & Cn/cn

1, ,An AB A

an ab a

V V Ia a

V V I a

15

Page 16: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Y-Y Connection: 3f Detailed Model

16

Page 17: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Y-Y Connection: Per Phase Model

Per phase analysis of Y-Y connections is exactly the same as analysis of a single phase transformer.

Y-Y connections are common in transmission systems.

Key advantages are the ability to ground each side and there is no phase shift is introduced.

17

Page 18: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

D-D Connection

Magnetic coupling with AB/ab, BC/bb & CA/ca

1 1, ,AB AB A

ab ab a

V I Ia

V I a I a

18

Page 19: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

D-D Connection: 3f Detailed Model

To use the per phase equivalent we need to usethe delta-wye load transformation

19

Page 20: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

D-D Connection: Per Phase Model

Per phase analysis similar to Y-Y except impedances are decreased by a factor of 3.

Key disadvantage is D-D connections can not be grounded; not commonly used.

20

Page 21: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

D-Y Connection

Magnetic coupling with AB/an, BC/bn & CA/cn

21

Page 22: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

D-Y Connection V/I Relationships

, 3 30

3030Hence 3 and 3

For current we get

1

13 30 30

31

303

AB ABan ab an

an

AnABab an

ABa AB

ab

A AB AB A

a A

V Va V V V

V a

VVV V

a a

II a I

I a

I I I I

a I

22

Page 23: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

D-Y Connection: Per Phase Model

Note: Connection introduces a 30 degree phase shift!

Common for transmission/distribution step-down sincethere is a neutral on the low voltage side.

Even if a = 1 there is a sqrt(3) step-up ratio

23

Page 24: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Y-D Connection: Per Phase Model

Exact opposite of the D-Y connection, now with a phase shift of -30 degrees.

24

Page 25: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Load Tap Changing Transformers

• LTC transformers have tap ratios that can be varied to regulate bus voltages

• The typical range of variation is 10% from the nominal values, usually in 33 discrete steps (0.0625% per step).

• Because tap changing is a mechanical process, LTC transformers usually have a 30 second deadband to avoid repeated changes.

• Unbalanced tap positions can cause "circulating vars"

25

Page 26: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

LTCs and Circulating Vars

slack

1 1.00 pu

2 3

40.2 MW

40.0 MW

1.7 Mvar

-0.0 Mvar

1.000 tap 1.056 tap

24.1 MW 12.8 Mvar

24.0 MW-12.0 Mvar

A

MVA

1.05 pu 0.98 pu

24 MW

12 Mvar

64 MW

14 Mvar

40 MW 0 Mvar

0.0 Mvar

80%A

MVA

26

Page 27: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Phase Shifting Transformers

• Phase shifting transformers are used to control the phase angle across the transformer– Also called phase angle regulators (PARs) or quadrature

booster transformers

• Since power flow through the transformer depends upon phase angle, this allows the transformer to regulate the power flow through the transformer

• Phase shifters can be used toprevent inadvertent "loop flow" and to prevent line overloads.

27Image Source: en.wikipedia.org/wiki/Quadrature_booster#/media/File:Qb-3ph.svg

Page 28: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Phase Shifter Example 3.13

slack

Phase Shifting Transformer

345.00 kV 341.87 kV

0.0 deg 216.3 MW 216.3 MW

283.9 MW 283.9 MW

1.05000 tap

39.0 Mvar 6.2 Mvar

93.8 Mvar 125.0 Mvar

500 MW

164 Mvar 500 MW 100 Mvar

28

Page 29: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Autotransformers

• Autotransformers are transformers in which the primary and secondary windings are coupled magnetically and electrically.

• This results in lower cost, and smaller size and weight.

• The key disadvantage is loss of electrical isolation between the voltage levels. Hence auto-transformers are not used when a is large. For example in stepping down 7160/240 V we do not ever want 7160 on the low side!

29

Page 30: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Load Models

• Ultimate goal is to supply loads with electricity at constant frequency and voltage

• Electrical characteristics of individual loads matter, but usually they can only be estimated– actual loads are constantly changing, consisting of a large

number of individual devices– only limited network observability of load characteristics

• Aggregate models are typically used for analysis• Two common models

– constant power: Si = Pi + jQi

– constant impedance: Si = |V|2 / Zi

30

Page 31: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Generator Models

• Engineering models depend upon application• Generators are usually synchronous machines• For generators we will use two different models:

– a steady-state model, treating the generator as a constant power source operating at a fixed voltage; this model will be used for power flow and economic analysis

– a short term model treating the generator as a constant voltage source behind a possibly time-varying reactance

31

Page 32: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Power Flow Analysis

• We now have the necessary models to start to develop the power system analysis tools

• The most common power system analysis tool is the power flow (also known sometimes as the load flow)– power flow determines how the power flows in a network– also used to determine all bus voltages and all currents– because of constant power models, power flow is a

nonlinear analysis technique– power flow is a steady-state analysis tool

32

Page 33: ECE 476 Power System Analysis Lecture 10: Per Unit, Transformers, Load, Generators Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Linear versus Nonlinear Systems

A function H is linear if

H(a1m1 + a2m2) = a1H(m1) + a2H(m2)

That is

1) the output is proportional to the input

2) the principle of superposition holds

Linear Example: y = H(x) = c x

y = c(x1+x2) = cx1 + c x2

Nonlinear Example: y = H(x) = c x2

y = c(x1+x2)2 ≠ (cx1)2 + (c x2)2

33