EC FAN FDPOPERATING MANUAL
Regal Beloit Italy S.p.A.
Via Modena, 1824040 Ciserano (BG) ITALYPhone +39 035 873 111Fax +39 035 884 319www.regalbeloit.com
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
3/40
INDEXINDEX
1. DEFINITIONS AND WARNINGS ..............................................................................................................................................5
1.1 Object of this manual .........................................................................................................................................................5
1.2 Symbols used ......................................................................................................................................................................5
1.3Qualifiedpersonnel ............................................................................................................................................................5
1.4Useforintendedpurposeonly ...........................................................................................................................................5
1.5Safetyinstructions ..............................................................................................................................................................6
1.6Informativeletter ...............................................................................................................................................................7
1.7Safeoperatingarea.............................................................................................................................................................7
2. REGULATORY REFERENCES ....................................................................................................................................................8
2.1Mechanicalandelectricalsafety ........................................................................................................................................8
2.2Electro-MagneticCompatibility(EMC) ...............................................................................................................................8
3. DATA PLATE .............................................................................................................................................................................9
4. TRANSPORT AND STORAGE .................................................................................................................................................10
5. PACKING CONTENTS .............................................................................................................................................................10
6. UNPACKING ...........................................................................................................................................................................11
7. PRODUCT DESCRIPTION .......................................................................................................................................................11
8. TECHNICAL FEATURES ..........................................................................................................................................................12
8.1Dimensionaldrawings ......................................................................................................................................................13
8.2Motor-driverconnections ...............................................................................................................................................15
9. INSTALLATION .......................................................................................................................................................................15
9.1Commissioning .................................................................................................................................................................15
9.2Operation .........................................................................................................................................................................16
9.3Ambientoperatingcondition ...........................................................................................................................................16
9.4Faninstallation .................................................................................................................................................................16
9.5Electricalconnections .......................................................................................................................................................17
9.5.1Powersupply ............................................................................................................................................................18
9.5.2Controlboardconnection ........................................................................................................................................18
9.5.3Connectiondetails ...................................................................................................................................................19
9.5.3.1Analog ..........................................................................................................................................................19
9.5.3.2Modbuscommunication ..............................................................................................................................21
9.5.3.3Tachometric,alarmandfilteroutput ...........................................................................................................22
9.5.3.4InputImpedances ........................................................................................................................................22
10. OPERATING MODES AND SETTING OPTIONS .....................................................................................................................22
10.1Speedcontrol .................................................................................................................................................................23
10.1.1Analogspeedcontrol .............................................................................................................................................23
10.1.2Modbustemporaryspeedcontrol .........................................................................................................................23
10.1.3Modbusfixedspeedcontrol ..................................................................................................................................23
10.1.4Speedcontrolcurves:examples ............................................................................................................................24
10.2Asynchronousemulation ................................................................................................................................................24
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
4/40
10.2.1Analogasynchronousemulation ........................................................................................................................... 24
10.2.2Modbustemporaryasynchronousemulation ....................................................................................................... 24
10.2.3Modbusfixedasynchronousemulation ................................................................................................................. 24
10.2.4Asynchronousemulationcurves:examples ........................................................................................................... 25
10.3PIDclosedcontrolloop ..................................................................................................................................................25
10.3.1Modbustemporaryref.PIDclosedcontrolloop ....................................................................................................25
10.3.2Modbusfixedref.PIDclosedcontrolloop ............................................................................................................. 25
10.3.3Modbuspositive/negativefeedback ...................................................................................................................... 26
10.4Changingtheoperationmode .......................................................................................................................................26
11. OTHER FEATURES ..................................................................................................................................................................26
11.1Filteralarm .....................................................................................................................................................................26
11.2Softstart .........................................................................................................................................................................27
12. SOA LIMITATIONS .................................................................................................................................................................27
12.1Speedlimitation .............................................................................................................................................................27
12.2Powerlimitation .............................................................................................................................................................27
12.3Outputcurrentlimitation ............................................................................................................................................... 27
12.4Inputcurrentlimitation ..................................................................................................................................................27
13. OTHER VARIABLES ................................................................................................................................................................28
13.1 Busvoltage .....................................................................................................................................................................28
13.2 Motorvoltage .................................................................................................................................................................28
14. DERATING AND OVERHEATING PROTECTIONS ..................................................................................................................28
14.1 Driveroverheating:DERATING .......................................................................................................................................28
14.2 Motoroverheating:THERMALPROTECTOR ...................................................................................................................28
15. MASTER & SLAVE MODE ......................................................................................................................................................29
15.1 MasterandSlave0-5VPWMout(for1.05kW-1-phaseonly) ......................................................................................29
16. COMMUNICATION ................................................................................................................................................................29
16.1 Temporaryholdingregister ............................................................................................................................................31
16.2 Fixedholdingregister .....................................................................................................................................................31
16.3 Holdingregisterdescription ...........................................................................................................................................31
16.4 Inputregisterdescription ...............................................................................................................................................36
16.5 FaninfoandModbusregisters .......................................................................................................................................37
17. ALARM HANDLING ...............................................................................................................................................................38
17.1 Monitoring......................................................................................................................................................................38
17.2 Modbusregisters-Alarmdescription ............................................................................................................................38
17.3 BlinkingLED-Alarmdescription ....................................................................................................................................38
17.4 Digitalalarmoutput .......................................................................................................................................................39
17.5 Alarmreset .....................................................................................................................................................................39
18. AVAILABLE SOFTWARE .........................................................................................................................................................39
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
5/40
1. DEFINITIONS AND WARNINGS
1.2 Symbols used
1.3 Qualified personnel
ForthisInstructionManualandproductlabels,a"Qualifiedperson"issomeonewhoisfamiliarwiththeinstallation,mounting,start-upandoperationoftheequipmentandthehazardsinvolved.Heorshemusthavethefollowingqualifications:• Trainedandauthorizedtoenergize,de-energize,clear,groundandtagcircuitsandequipmentinaccordancewithestablished
safetyprocedures.• Trainedinthepropercareanduseofprotectiveequipmentinaccordancewithestablishedsafetyprocedures.• Trainedinrenderingfirstaid.
1.4 Use for intended purpose only
TheequipmentmaybeusedonlyfortheapplicationstatedinthemanualandonlyinconjunctionwithdevicesandcomponentsrecommendedandauthorizedbyNicotra Gebhardt.
As to the "WARNING" and "CAUTION"messages,thesafetymessageisasymbol(atrianglecontaininganexclamationmark)fol-lowedbythetextindicatingtherisklevel.Itspurposeistowarntheuserofthepotentialpersonaldamagethatmayresultfromanincorrectuseofthemachineorfromthenon-compliancewiththeuseandmaintenanceinstructions.Failuretocomplywiththesesafetymessagescouldcausedamageand/orthepartialortotaldestructionoftheproductorotherequipmentconnectedtoitorharmpeople.
As to the "NOTICE"message,thesafetymessagedoesnotindicatepreciselyarisk,itisonlyforinformation.
Pictogram Description
Indicatesapotentialrisksituationthatcanlead to death or serious damage, if it notprevented (ex. amputations, severe burns,loss of vision or hearing loss or visual orauditorysensorialimpairment).Indicatesapotentialrisksituationthatcouldcause less severe orminor damage, if notprevented(ex.cuts,scratches,irritation).
NOTICEmessage:itisusedfornon-physicalinjuries.
Dangertopersonsduetoelectricity.
The operationswhose execution requiresqualified or specialized staff to avoid anydangerareindicatedwiththissymbol.
WARNINGWARNING
CAUTIONCAUTION
1.1 Object of this manual
Theaimofthismanualisgivinginstrutionsconcerninginstallation,useandmaintenanceofFDPfans.
This manual refers to fans having a driver with a 5 firmware revision or higher.
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
6/40
This manual is an integral part of the EC Fan FDP and it must be carefully read before using it since it gives important indications with regards to its safe installation, use and maintenance. Keep it with care.
Before using the EC Fan FDP, read carefully the following general safety rules.
• Aftertakingoffthepackagingmakesurethatthefanisintact.Incaseofdoubtdonotuseitandcontactanauthorizedservicecentre.
• Checkthatthefanisnotdamagedinanyofitsparts.Thesafetyconceptofthefanisvalidonlyinperfectconditions.
RISK OF ELECTRICAL SHOCKS
• Anydamagedsocket,connectionterminalorcablemustbereplacedimmediatelybyqualifiedtechniciansorbyauthorizedservicecentre.
• Incaseofrepairorreplacementoftheconnectioncablesand/orofthedamageddevicesorthatdonotworkproperly,pleasecontacttheauthorizedservicecentre.
• Incorrectorimproperinstallationmaycausethesystemtomalfunctionand/orresultindamagetopeopleand/orproperty.• Alwaysdisconnectthepowersupplybeforeopeningthe fan.
Any installation and/or maintenance tasks are only to be carried out by skilled, specialist personnel.Existing electrical systems must comply with the rules in force in the country where the FDP fan is installed.Before doing any maintenance, make sure that the power supply and the batteries have been disconnected.Install an all-pole disconnecting device in the power supply system (in accordance with IEC 60335-1 or IEC 60204-1, as applicable).Conform to the wiring diagrams shown in the section “ELECTRICAL CONNECTIONS” of this manual.
Thefollowingwarnings,cautionsandnotesareprovidedforyoursafetyandhasameansofpreventingdamagetotheproductorcomponentsattheconnectedmachines.Specificwarnings,cautionsandnotesthatapplytoparticularactivitiesarelistedatthebeginningoftherelevantchaptersandarerepeatedorsupplementedatcriticalpointsthroughoutthesesections.Please read the information carefully, since it is provided for your personal safety and will also help prolonging the service life of your fan.
1.5 Safety instructions
WARNINGWARNING
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge on condition that they are supervised and instructed concerning use of the appliance in a safe way and understand the hazards involved.-> Children shall not play with the appliance-> Cleaning and user maintenance shall not be made by children without supervision
WARNINGWARNING
The use and maintenance manual of any domestic appliance or similar device incorporating a FDP fan shall include the following clauses.
WARNINGWARNING
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
7/40
ALL RIGHTS ARE RESERVED ACCORDING TO THE INTERNATIONAL COPYRIGHT CONVENTIONS,
Thereproductionofanypartofthismanual,inanyform,isforbiddenwithoutthepriorwrittenauthorizationofthemanufacturer.
Thecontentofthisguidecanbemodifiedwithoutpriornotice.Greatcarehasbeentakenincollectingandcheckingthedocumentationcontainedinthismanualtomakeitascompleteandcomprehensibleaspossible.
Nothingcontainedinthismanualcanbeconsideredasawarranty,eitherexpressedorimplied-including,notinarestrictiveway,thesuitabilitywarrantyforanyspecialpurpose.
Nothingcontainedinthismanualcanbeinterpretedasamodificationorconfirmationofthetermsofanypurchasecontract.
The Nicotra Gebhardt productshavenotbeenconceivedtoworkinareasatriskofexplosions.Incaseofdamageormal-function,theFDPfansmustnotbeuseduntiltheCustomerCareTechnicalServicehasrepairedit.
Theinstallerandthemaintenancemanmustknowthecontentofthismanual.Althoughthemainfeaturesoftheequipmentdescribedinthismanualarenotsubjecttochange,themanufacturerreservestherighttomodifythecomponents,detailsandaccessoriesitdeemsnecessarytoimprovetheproductortomeetmanufacturingorcommercialrequirementsatanytimeandwithoutbeingobligedtoupdatethismanualimmediately.
1.6 Informative letter
WARNINGWARNING
The original configuration of the fan must not be changed at all, except as prescribed in this manual.On receiving the fan, make sure the supply corresponds to what has been ordered.In case of non-compliance immediately inform the manufacturer.Also make sure the FDP fan has not been damaged during transport.
For information concerning the nearest supporting center, please get in touch with your retailer.
WARNINGWARNING
1.7 Safe operating area
Thedriversareprotectedagainstoverloadconditionsandasafeoperatingareaisdefinedbyalimitofspeed,outputpowerandmotorcurrent.FormoredetailsrefertotheANNEX"AnalogSignalConsiderations".
Customer Care Technical Service
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
8/40
2. REGULATORY REFERENCES
ThesefanswithECdrivesystemsaredesignedforincorporationinequipment,fulfillingtherequirementssetbytheMachinery Directive (MD - Dir. 2006/42/EU),andthosepartsoftheLow-Voltage Directive (Dir. 2014/35/EU)whichareapplicableinaccord-ancewiththeMD,whereitconcernselectricalsafety.ElectricalsafetyisgenerallyachievedbyapplicationoftheprovisionsoftheEN 60204-1 standard “Electrical equipment of ma-chines - General requirements”.Selectedrangesmaybedesignedtobesuitableforincorporation(ascomponents)withinproductswhichcomplywiththestand-ardsEN 60335-1 “Household and similar electrical appliances - Safety - General requirements” and 60335-2-40 “Household and similar electrical appliances - Safety - Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers”.Suchsafetyrequirementsarecoveredasfarasnecessaryforapartlycompletemachine,sub-assemblyorcomponent,asthesefansarespecificallyintendedforincorporationwithinothermachines.Theresponsibilityforthemechanicalandelectricalsafetyoftheinstalledfanisthusofthemanufacturerofthecompletemachineand,forthisreason,itisstrictlyforbiddentoputthefaninoperationbeforethemanufacturerofthemachinehasassessedanddeclaredthatthecompletemachinefulfilsalltheessentialsafetyrequirementssetforthbytheMD.Please,checktheDeclarationofIncorporationwhichaccompanieseachproduct,oraskyourNicotra Gebhardtsalesrepresentative,foradditionalinformation.
2.1 Mechanical and electrical safety
Single-phase drive systems: FDP 1 kW,
ThedriversoftheseproductsincorporateanActivePowerFactorControlmodule,toprovideharmonicsfilteringandcompliancewiththeEMCrequirementsapplicabletodomesticandequivalentenvironments(“firstenvironment”),orwiththeadvancedre-quirementsforharmonicdistortionwhichoftenapplytodatacenters.Morespecifically:theycomplywiththerequirementssetin
EN 61000-6-3 – Electromagnetic compatibility (EMC). Part 6-3:Genericstandards.Emissionstandardforresidential,commercialandlight-industrialenvironments.
EN 61000-6-4 – Electromagnetic compatibility (EMC). Part 6-4:Genericstandards-EmissionstandardforindustrialenvironmentswhichthisproductisincorporatedmustcomplywiththeEMCDirective2004/108/EC.
2.2 Electro-Magnetic Compatibility (EMC)
Specific electrical safety and EMC standards are applied according to the available models of conformity declaration (identified as 985732, 985740 and 985748):
EMC standards
61000-6-3 (household)
61000-6-4 (industrial)
Electrical safety
standards
60204 (machines) 985732 985748
60335 (domesticappliances)
985740 n/a
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
9/40
3. DATA PLATE
Themanufacturer’sidentificationplateislocatedonthefan.Severalsafetywarningsareappliedtothefan;suchwarningsmustbestrictlyfollowedbyeveryonedealingwiththisproduct.The company is not to be held responsible for damage to property or accidents to people which might occur if the above-men-tioned warnings are not observed. In such a case, the operator is the only person responsible.
Theidentificationplateislocatedonthefanscrollcase.
REF. DESCRIPTION1 MODEL DESIGNATION2 REGAL BELOIT ITALY CODE3 MODIFICATION LEVEL4 PRODUCTION LOT NO.
5 NO. PHASES & CURRENT TYPE
6 ELECTRICAL FREQUENCY7 VOLTAGE8 IP PROTECTION GRADE
9 MOTOR INSULATION CLASS
10 CAPACITORVALUE(WHENPRESENT)11 MAXIMUMCURRENTINPUT12 MOTOR RATED POWER
13 RATED RPM
To improve the Electromagnetic compatibility a ferrite should be put on the power supply cable (close to the driver). The compliancy to the standards is intended for a single fan. No tests have been made on multiple installations.
The EMC tests are conducted without 485 communication wire, analog signals or Bluetooth devices.
WARNINGWARNING
REF. DESCRIPTION14 THERMALPROTECTOR(Y/N)15 OPERATING TEMPERATURE RANGE16 UNITEXCEEDS30KG(Y/N)17 UNITEXCEEDS85dB(A)SOUNDPOWER(Y/N)
18 OPERATING MANUAL
19 OVERALLEFFICIENCY(η)20 EFFICIENCYCATEGORY(STATICORTOTAL)
21 MEASUREMENT CATEGORY USED TO DETER-MINETHEENERGYEFFICIENCY(A-D)
22 EFFICIENCY GRADE AT OPTIMUM ENERGY EFFI-CIENCY POINT
23 ErPCOMPLIANCE24 CUSTOMERCODE(WHENAPPLICABLE)25 PRODUCTION DATE
The compliancy to the standards are intended for a single fan.No tests have been made on multiple installations.
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
10/40
4. TRANSPORT & STORAGE
Correct transport, storage, erection and mounting, as well as careful operation and maintenance are essential for proper and safe operation of the equipment.Protect the fan against physical shocks and vibration during transport and storage. Also, be sure to protect it against water (rainfall) and excessive temperatures.
WARNINGWARNING
If the fan must be subject to long-term storage, the storage time without application of any power supply shall not exceed two years since fan production or since operating the fan for at least half-an-hour continuously. The storage site shall have a temperature between -20°C and +70 °C, a Relative Humidity lower than 75%, and not be subject to condensation or exposed to dust.
CAUTIONCAUTION
5. PACKING CONTENTS
6xxxxxfdp xXx xxxx xxxXXX12345
ThefanisdeliveredinacardboardboxinsidewhichtherearetheinstallationinstructionsandtheoptionsrequiredbytheCustomerattimeoforder.AlltheseoptionswillbemounteddirectlybytheManufacturer.
Apartfromthe"options",theCustomercanorder"accessories"afterwards.Inthiscase,theCustomerwillhavetoinstallthembyhim/herself.
Thefollowingdataareprintedonthepackingitself:
REF. DESCRIPTION1 ART. CODE2 MODEL DESCRIPTION3 BATCH CODE
1
2
3
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
11/40
6. UNPACKING
Check the fan. Before installing the FDP fan, check to ensure that all of the items listed are present and that there are no visible signs of damage.
1. Removethefanfromthebox.2. Removeallthecomponentsfromthepackaging.
WARNINGWARNING
Dispose of all packing components in compliance with the laws in force in the country of use.
RECYCLE
7. PRODUCT DESCRIPTION
Fan-Decksarecompactfans,designedtoprovidehighvolumeflowrate,withsmallpressure levels,bycombiningsidebysidetwodouble-inletforwardcurvedcentrifugalfans,driveninexpensivelybyasinglecommonelectricalmotor.Theside-by-sidefansarefitted,togetherwiththemotorstand,onamountingplatewhichnormallyactsalsoasapressurebulkheadintheventilationmachine.Single-impeller,aswellastripleofquadrupleversionmayalsobebuilt,forspecialrequirements.
Mounting-plate designBesidesastandardrange,custom-specificFDfansarenormallyco-designedwithourcustomer,toprovidethebestintegrationofthefaninthestructureofseries-producedmachines.Mountingplatesarefrequentlyused,inverticalflowfancoilunits,alsoascondensationdrainagecollectors,includingadrain-pipeconnector.
TheFansofseriesFDPcombinehighenergyefficiencyandlownoiselevel.Thankstothe“EC”(electroniccommutation)motors,theirelectronics integratespeedcontrolandprotectingsystem.Thisreducesthenumberofdifferentcomponentsrequiredtoprovidethesefunctions,comparedtofanswithtraditionalmotors.
ThemainfeatureofEC-motorisoperatingwithoutsliplosses,whichallowconsumingsignificantlylesspowerthanconventionalACmotors.
Thisoccursatallspeedlevels,especiallywithpartialloadoperation.TheECcompletedrivesystem(i.e.thecombinationofthepermanent-magnetmotorwithitselectronicdriver)hasamuchhigherenergyefficiency,incomparisonwithadrivesystembasedonaconventionalACmotor.
Energy saving system• HighefficiencyEC-motor• Compactmotordesign• Highintensityneodymiummagnets• Noobstructionofintakeduetobuild-oncontrolunit-lessaerodynamiclosses
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
12/40
REF. DESCRIPTION
1 Scroll2 Inletport3 Outletport4 Rotor(forward-curvedblades)
5 ECmotor
6 Driver7 IDplate
General Features
• Sensorlesscontrol• Simpleinstallationduetoplugandplay• Designedfordoubleinletfans
Interface
• Analogue interface forspeedcontrol
• FullMODBUS interface com-pliancy
High efficiency of direct driven centrifugal fan
• Integratedsolution• Topratingefficiency• Plugandplayoperation• Noneedtoconfigurelong listsofinverterparameters• Lowsoundlevel• Highreliability
8. TECHNICAL FEATURES
Size Motor code Driver code Driver phases
Abs. curr. (A)
Abs. pow. (W)
Min. temp. (°C)
Max. temp. (°C)
IP class protection
180/240 Z 1413G6 1431C1 1 Ph 2.81 A 641 W -20°C +40°C IP 32
200/190 N 1413G6 1431C1 1 Ph 2.65 A 621 W -20°C +40°C IP 32
200/190 N 1413H3 1431C1 1 Ph 4.63 A 1085 W -20°C +40°C IP 32
200/240 N 1413H4 1431C1 1 Ph 4.62 A 1069 W -20°C +40°C IP 44
200/240 N 1413H3 1431C1 1 Ph 4.62 A 1069 W -20°C +40°C IP 32
9/7 A 1413H3 1431C1 1 Ph 4.61 A 1071 W -20°C +40°C IP 32
9/9 A 1413H3 1431C1 1 Ph 4.56 A 1063 W -20°C +40°C IP 32
OtherdatarelatedtothetechnicalfeaturesarereportedontheIDplateshowninchapter3.
1
6
7
2
3 3
4
5
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
13/40
8.1 Dimensional drawings
6N4406 - FDP 180/240 Z 1413G6
6N4407 - FDP 200/190 N 1413G6
6N4408 - FDP 200/190 N 1413H3
The plate dimensions and the anchor points can be different.
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
14/40
6N4404 - FDP 200/240 N 1413H4
6N4405 - FDP 200/240 N 1413H3
6N4409 - FDP 9/7A 1413H3
6N4410 - FDP 9/9A 1413H3
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
15/40
8.2 Motor - driver connections
InthestandardarrangementoftheFDPfan,themotoristurningclockwisewhenseenfromthecable-entryside,andtheelectricalconnectionsofthemotorcabletothedriverboardaremadeasshowninthefollowingfigure.Theactualpositionofthemotorconnectionsontheprintedcircuitboardmaydiffer,betweendifferentdrivermodels.
These connections are carried out by Nicotra Gebhardt and cannot be modified by the end user.
WARNINGWARNING
9. INSTALLATION
The fan installation must be carried out only by competent and qualified staff.
9.1 Commissioning
Work on the device/system by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material.Only suitably qualified personnel trained in the setup, installation, commissioning and operation of the product should carry out work on the device/system.The FDP fan must be grounded through the PE connector on the driver.The following terminals can carry dangerous voltages even if the driver is inoperative:• the power supply terminals L, N or R, S, T• the motor terminals U, V, W
WARNINGWARNING
In the final installation, the device shall be directly connected to the supply terminals and shall have a contact separation in all poles, providing full disconnection under overvoltage category III conditions.
WARNINGWARNING
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
16/40
9.2 Operation
Ensure correct grounding connections. The ground cable must be enough to carry the maximum supply fault current which nor-mally will be limited by the fuses or MCB. Suitably rated fuses or MCB should be fitted in the main supply to the driver, according to any local legislation or codes.
WARNINGWARNING
The driver operates at high voltages.Certain parameter settings may cause the driver to restart automatically after an input power failure.
CAUTIONCAUTION
9.3 Ambient operating conditions
The installation place must be in accordance with the IP protection degree of the fan. In this respect, refer to the ID plate de-scribed in chapter 3.
Humidity Range: 90% non-condensingAltitude: if the fan is to be installed at an altitude > 1000m, derating is required.Shocks: do not drop the fan or expose it to sudden shock.Vibration: do not install the fan in an area where it is likely to be exposed to constant vibrations.
CAUTIONCAUTION
9.4 Fan installation
Placethefanaccordingtoyourneeds,afterhavingcheckeditsdimensionsandthepositionofthefixingholes.
The driver must NOT be removed from the related FDP fan type and size.The driver cannot be used separate from the related fan.
WARNINGWARNING
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
17/40
9.5 Electrical connections
REF. DESCRIPTION
1 Powersupply2 Controlboardconnection3 Communication4 BlinkingLED
5 Relayconnection
2 13
4
FDP 1.05kW 1-Phase
Before carrying out any intervention on the electrical system, disconnect the power supply by means of main switch.
Make sure that a differential switch (circuit breaker) has been installed upstream the line and that it functions properly.
Work on the driver/fan by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material.Only suitably qualified personnel trained in the set-up, installation, commissioning and operation of the product should carry out work on the driver/fan. This driver must be grounded.The power supply terminals L, N (1-Phase) and the motor terminals U, V, W can carry dangerous voltages even if the driver is inoperative.
WARNINGWARNING
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
18/40
9.5.1 Power supply
Theendusermustconnectthepowersupplycableandthecommandsignaltothecontrolboard,whilethemotorconnectionisalreadydonebyNicotra Gebhardt.
FDP 1.05kW 1-PhaseSinglePhase220/240V±10%@50/60HzTheperformance in the range [200V-264V]@50Hz/60Hz isalwaysthesameduetothePFCmoduleinsidethedriver.
Min. and max. wire section:Spring-loadedpush-inclamp,suitablefor• 0.2mm²-24AWGupto2.5mm²-12AWG(stranded)or
4mm²(solid)wireUseabladedscrewdriver,0.6x3.5mmmax,tounlock.
As concerns the cable minimum section, check the requirements issued by the country of installation.
Min. and max. section:• 0.13 - 1.31 mm2(26-16AWG)solidorstrandedcable.
9.5.2 Control board connection
FDP 1.05kW 1-Phase
1 GND2 IN3 +10V4 GND
5 B6 A
7 OUT TACHOOUT
ANALOGUESIGNAL IN
MODBUSRS485
7 ← 1
Do not reverse the input signal or connect the +10V to signal ground. The driver could be damaged.Do not apply signals with voltage outside the indicated limits, the driver could be damaged.
WARNINGWARNING
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
19/40
9.5.3 Connection details
Inthisparagraphareexplainedthefeatureandthepossibleconnectionofthecontrolboard.Thecontrolboardterminalsareopto-insulated.
The available features can be different depending on the fan model.
9.5.3.1 Analog
ThisisthedriverdefaultmodeandthesignalmustbeconnectedintotheANALOGINPUTandthereferencetoGND.TheanaloginputcanacceptalsoaPWMsignalwithf>1kHz.
WARNINGWARNINGDo not use devices having the signal GND connected to the NEUTRAL cable of the power supply. The driver may be damaged or not functioning properly.
Theavailable+10Vpowersupplyofthedriverisintendedtobeusedwithapotentiometerofminimum2KOhm,withamaxabsorbedcurrentof5mA.Anydifferentdevicesconnectedtoitcouldbring to an undesired functioning of thedriverorofconnecteddevice.Nicotra Gebhardt canprovideadedicatedpotentiometer:REGPOTcodeK43138.
Without using the STOP switch Using the STOP switch
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
20/40
Iftwoormorefansareinstalledinthesamecompartmentandoperatedinparallel,thefansmuststartandstopatthesametime.
An auto-restarting alarm occurs when a fan is forced to run forward (or backward) rotation with a speed higher than 150 rpm.
Ifanext.4-20mAdeviceisused,itisnecessarytoadd0.1%precisionresistancesbetweentheANALOGINPUT and GND.Thevalueoftheresistancecanrangefrom:125Ω->Vsignalrangesfrom0.5Vto2.5Vto500Ω->Vsignalrangesfrom2Vto10V
TAC
HO
/ AL
ARM
/ FI
LTER
GN
D
MO
DBU
S -B
MO
DBU
S -A
GN
D
TRAN
SUC
ER IN
PUT
ANAL
OG
INPU
T
ENAB
LE
+10V
+24V
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
21/40
9.5.3.2 Modbus Communication
AModbusRTUprotocolisavailableonallthefanmodels.ThelinemustbeconnectedtoMODBUS-A,MODBUS-BandGNDpins.TherearetwopossibleModbusconnections:1)DuringthefanfunctioningthroughanyRS-485serialconnection2)WiththedriverpoweredoffthroughanUARTserialconnection
ToconnectOFFLINEthedrivertoaPCwhenthefanispoweredoff,aUSBtoUARTconvertercanbeused:K431A6for1-phasedrivers.AMOLEXconnector"1"isusedtoconnectthecabletothedriver.
ToconnectthedrivertoaPCduringthefanfunctioning,aUSBto485convertercanbeused:K431F8.
1
Specifications and drivers can be downloaded from Nicotra Gebhardt website: https://www.nicotra-gebhardt.com
1-phase
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
22/40
9.5.3.3 Tachometric, Alarm and Filter Output
Theanalogueoutputchannelisconfigured,bydefault,toprovideatachometricoutputsignal.
Thetachometricoutputisa0to5VPWMwaveformat1KHz(forFDP1.05kW-1-Phonly).
whenthespeedisequalorhigherthanthespeedminanditis0%whenthespeedislower.ThedevicereadingtheoutputmustbeconnectedtoTACHO\ALARM\FILTERpinandGND.Themaxcurrentsuppliedoftheoutputis0.2mA.
Remember that the SpeedReal is 0 whenever the required speed is lower than Speedmin unless the fan is in the dragging phase.
Thesameanalogueoutputchannelcanbereconfigured,bychangingthevalueinHoldingRegister46(seeparagraph16.3atpage34),asaDigitalAlarmOutput(refertochapter17andparagraph17.4),orinoneofthealternativealarmmodesdescribedinpa-ragraphs11.1and11.2.
Input Impedances Feature available on
ANALOG INPUT 20kΩ FDP1.05kW1-Phase
9.5.3.4 Input Impedances
10. OPERATING MODES AND SETTING OPTIONS
Dependingonthefanmodel,thereare4possibleOperating Modes andforeachmode3possibleSetting Options.
TheoperatingmodesandthesettingoptionscanbechosenbymodifyingtheINPUTTYPEHolding Register 34.
Speed Control
OPERATING MODES
PID Closed Control
Loop
Asynchro-nous Emulation
Constant Airflow
Sensorless*SETTING OPTIONS
Modbus Control(Temporary setting)
Fixed Modbus(Permanent setting)
Analog Signal Control
*Thissettingisnotcurrentlyavailable.Ifnecessary,contactRegalBeloitItalyS.p.A.
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
23/40
10.1 Speed control
(INPUT TYPE = 1 Default factory setting)Throughthissettingthefanspeedisproportionaltotheanalogvoltageinput.ThefanspeedislimitedbytheSafeOperatingArea,therefore,dependingonthefanworkingpoint,thefancouldbenomoreabletoincreasethespeedcoherentlytothesetvoltagevalue.Toavoidthelossofsignaldynamic,aspeedlimitrescalingisnecessarybymodifyingthevalueoftheMaxSpeedHolding Register 2.ItisalsopossibletorescaletheminSpeedbymodifyingtheHolding Register 1.TheanalogsignalcanbereadfromtheInput Register 14.
For more details refer to the ANNEX -> Analog Signal Considerations.
TheMAXandminspeeddefaultvaluesareinfunctionofthefansizes.
10.1.1 Analog speed control
(INPUT TYPE = 0)ThroughthissettingthefanrunsatthespeeddefinedbymodifyingtheHolding Register 66. Thesettingismaintainedmeanwhilethefanispoweredonanditislostwhenthefanispoweredoff.
10.1.2 Modbus temporary speed control
(INPUT TYPE = 2)ThroughthissettingthefanrunsatthespeeddefinedbymodifyingtheHolding Register 21. Thesettingispermanentandfanstartsatthedefinedspeedeachtimeitispoweredon.
10.1.3 Modbus fixed speed control
Therelationshipbetweencontrolvoltageandfanspeedisdescribedinparagraph10.1.4and,withmoredetail,inchapter1oftheTechnicalAnnextothismanual.
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
24/40
Thefollowingfiguresshowasetofperformancecurvesatdifferentspeedsettingslimitedbythefanmaxworkinglimitcurve(seeparagraph1.6).
10.1.4 Speed control curves: example
10.2 Asynchronous emulation
(INPUT TYPE = 7)Throughthissettingtheslipisproportionaltotheanalogvoltage.
10.2.1 Analog asynchronous emulation
Throughthismodethereisthepossibilitytoemulatethebehaviorofanasynchronousinductionmotorwithaslipandapowerlimitationdependentontheloadandspeed(thereforetherecouldbesomedifferencesfromeachsize).Thecontrolisexpressedinpercentageinsteadofadefinedmeasureunit.Theloweristheslipthehigheristheperformanceandviceversa.
(INPUT TYPE = 8)ThroughthissettingthefanemulatesanACIMmotorandtheslipisdefinedbymodifyingtheHolding Register 66. Thesettingismaintainedmeanwhilethefanispoweredonanditislostwhenthefanispoweredoff.
10.2.2 Modbus temporary asynchronous emulation
(INPUT TYPE = 9)ThroughthissettingthefanemulatesanACIMmotorandtheslipisdefinedbymodifyingtheHolding Register 30. Thesettingispermanentandfanstartsatthedefinedconstantslipeachtimeitispoweredon.
10.2.3 Modbus fixed asynchronous emulation
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
25/40
Thefollowingfiguresshow5curveswiththefollowingslippercentage:100%,80%,60%,40%and20%.
10.2.4 Asynchronous emulation curves: example
The slip has not a physical meaning and must be intended as a 100% full performance and 0% fan stop.
10.3.1 Modbus temporary ref. PID closed control loop
(INPUT TYPE = 11)InthismodethePIDreferenceisdefinedbymodifyingtheHolding Register 66. Thevalueofthereferenceisexpressedinstepsof0.1Volt(thereforetheregisterrangesfrom0to100)ThePIDerroriscalculatedinthefollowingway:
Error=(ModbusREG_66 - ANALOGInput)
10.3.2 Modbus fixed ref. PID closed control loop
(INPUT TYPE = 11)InthismodethePIDreferenceisdefinedbymodifyingtheHolding Register 50. Thevalueofthereferenceisexpressedinstepsof0.1Volt(thereforetheregisterrangesfrom0to100)ThePIDerroriscalculatedinthefollowingway:
Error=(ModbusREG_50 - ANALOGInput)
10.3 PID closed control loop
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
26/40
10.3.3 Modbus positive/negative feedback
Dependingontheapplicationitcouldbenecessarytoinvertthefeedbackbehavior.ThroughtheHolding Register 31itispossibletomultiplyby-1thePIDerror.
Whentheregisterissetto0->Error=(Reference - Measure);Whentheregisterissetto1->Error=(Measure - Reference).
10.4 Changing the operation mode
Hereareshowntheactionspassingfromoneoperationmodetoanotherone.
ACTION ACTIONS A ACTIONS B
TemporarySetting->FixedSetting
Thefanmustfollowthetargetcorrespondingtothevaluestoredtherelatedregister.
Fanisputinstopmodeandafterthedataaresavedthefanfollowsthetargetcorrespondingtothevaluestoredintotherelatedregister.
FixedSetting->TemporarySetting Thefanmuststopwaitingforanewregister66value. Thefanmuststopwaitingforanewregister66value.
TemporarySetting->AnalogSignal
Thefanmustfollowthetargetcorrespondingtotheanalogvalueattheinputs.
Fanisputinstopmodeandafterthedataaresavedthefanfollowsthetargetcorrespondingtotheanalogvalue.
AnalogSignal->TemporarySetting Thefanmuststopwaitingforanewregister66value. Thefanmuststopwaitingforanewregister66value.
FixedSetting->AnalogSignal
Thefanmustfollowthetargetcorrespondingtotheanalogvalueattheinputs.
Fanisputinstopmodeandafterthedataaresavedthefanfollowsthetargetcorrespondingtotheanalogvalue.
AnalogSignal->FixedSetting
Thefanmustfollowthetargetcorrespondingtothevaluestoredtherelatedregister.
Fanisputinstopmodeandafterthedataaresavedthefanfollowsthetargetcorrespondingtothevaluestoredintotherelatedregister.
11. OTHER FEATURES
ThisfeatureisusefulwhenthespeedofthefanisnotdirectlysetbytheuserasfanssetinConstantAirflowAsynchronousEmu-lationorPIDmode.Thealarmisactivewhenaspeedthresholdisovertaken(5Vor10Vdependingonthefanmodel).
11.1 Filter alarm
Toactivatethisfeature,theHolding Register 46mustbesetatvalue2andtherequiredSpeedThresholdvaluemustbesetintothe Holding Register 55.Thedigitaloutputofthedriverchangesitsstatus.
Increasing the fan speedThe probe voltage
decreases
The probe voltage decreases
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
27/40
Inthefollowingparagraphthestartingphaseofafanisshown.• ThefirstphasewhenthefanreceivesacommandtostartrunningistheALIGNMENT.Duringthisphasethedriveralignstherotor.• Thesecondphaseisthedraggingphase,wherethefangraduallyincreasesitsspeedtotheminimuminopenloop.Inthisphase
thecurrentandspeedvaluespresentintheInputRegistercan’tbetakeninconsideration.• Thelastphaseistheclosedloopwherethesensorlesscontrolisactiveandfromtheminimumspeedtothetargetspeedthe
fanaccelerateswithdifferentrampsbasingonthefansizeandthewheelinertia.Theaccelerationanddecelerationvaluesaredifferentandtoavoidovervoltagealarmorlossofsynchronismalarm,thedecelerationisalwayslower.
11.2 Soft start
During the ALIGNMENT and DRAGGING phases a Loss of Synchronism alarm could occur if there is a condition of wrong rotor starting position or wrong position estimation during the open loop phase. This is not a blocking alarm; therefore the fan stops and auto-restarts after few seconds.
12. SOA LIMITATIONS
Thespeedlimitscanbeadjustedforthesignalrescaling,butalsotolimitthenoiseinthefinalapplication.The Input Register 2indicatestheSpeedReference(minimumspeedduringalignmentanddraggingandtheSetSpeedinClosedControlLoop).The Input Register 3indicatestheMeasuredSpeed.
12.1 Speed limitation
Thedriverissetbyfactorydefaulttothemaxachievableelectricalinputpowertothedriverdependingonthemodel.DuringthefunctioningitispossibletomonitorthepowerabsorptionbyreadingtheInput Register 31.Ifforsomeapplicationitisnecessarytokeeptheabsorptionofthefanbelowadefinedpowervalue,itispossibletoreducethemaxpoweroutbymodifyingtheHolding Register 36.
12.2 Power limitation
Thedriversaresetbyfactorydefaulttothemaxpeakcurrentoutthatchangesdependingonthemotorwindingscharacteristics.DuringthefunctioningitispossibletoreadthepeakmotorcurrenttothemotorbyreadingtheInput Register 12. ItispossibletoreducethemotorcurrentbymodifyingtheHolding Register 7.Itissuggestedtokeepthemotorcurrentabove3500mA.
12.3 Output current limitation
ThisfeatureisnotavailableforFDPs.
12.4 Input current limitation
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
28/40
13. OTHER VARIABLES
Thereareothervariablesthatcanbemonitoredforasafeuseofthefan.
13.1 Bus voltage
TheBUSvoltageistheDCvoltageonthebuscapacitors.Thedriveriscontinuouslymonitoringthisvoltageandwillstopthemotorintheeventofunder-voltageorover-voltage.ThevaluecanbemonitoredthroughtheInput Register 9.
13.2 Motor voltage
Themotorvoltageisthepeakvalueofthephasevoltagemodule.Toknowthermslinetolinevalue,itmustbemultipliedby√3/2.ThevaluecanbemonitoredthroughtheInput Register 13.
14. DERATING AND OVERHEATING PROTECTIONS
Whenthetemperatureofthedrivercomponentsovertakesadefinedtemperaturethreshold,theperformanceisautomaticallyreducedtodecreasetheheating.ItispossibletocheckinrealtimethetemperaturebyreadingtheInput Register 15. Ifitisnotpossibletoreachasteadythermalequilibrium,thedrivershutsdown.Theprotectionactslimitingthecurrenttothemotor.Inthisconditionthedrivergoesinalarm(seechapter17).Oncethetemperatureonthedriverdecreasesunder75°C,thealarmisautomaticallyreset.
14.1 Driver overheating: DERATING
ThemotorisprotectedthroughoneormoreThermalProtectors.Ifthemotortemperatureistoohigh,thethermalprotectoropensonephaseandthedriverrecognizestheerrorandstopsthefan(seechapter17).
14.2 Motor overheating: THERMAL PROTECTOR
The Motor Winding temperature and the driver derating are dependent on the fan size and on the fan working point. Therefore, it is possible that the fan could work at 50°C without a performance limitation.
The Driver and motor areas are rated for operating in a temperature range between -20°C and +40°C. The derating is tested and guaranteed from +40°C to +50°C. Higher temperatures could damage the motor winding or the performance could be significantly reduced.
WARNINGWARNING
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
29/40
15. MASTER & SLAVE MODE
Thissingle-phasedriverhasatachometricoutputrangingfrom0to5VandaspecialconfigurationmustbesetontheslavefanforaMaster&Slaveconnection.ItispossibletodrivetwofansinamasterandslaveconfigurationbysettingtheMASTERinanypreferredmodeandtheSLAVEinMaster&Slavemodeonly.TheSLAVEoperatingmodemustbechanged(INPUT TYPE = 3).The MASTER must have the Holding Register 46setat0=TACHO.
15.1 Master and Slave 0-5V PWM out (for 1.05 kW 1-phase only)
AMaster&SlaveconnectionisnecessarywhenthefanshavetooperateinparallelandinanyConstant-Airflowmode,orundercontroloftheinternalPIDregulator.Havingtwoormorefansself-controllingindependently,whileoperatinginparallel,canmakethesystemunstable.AMaster&Slaveconnectionisneitherneedednorrecommendedwhenthefansinparallelarerunniginanyspeed-controlmode,evenifundercontrolofacommonexternalPIDregulator.
TAC
HO
/ AL
ARM
/ FI
LTER
TAC
HO
/ AL
ARM
/ FI
LTER
GN
D
GN
D
MO
DBU
S -B
MO
DBU
S -B
MO
DBU
S -A
MO
DBU
S -A
GN
D
GN
D
TRAN
SUC
ER IN
PUT
TRAN
SUC
ER IN
PUT
ANAL
OG
INPU
T
ANAL
OG
INPU
T
ENAB
LE
ENAB
LE
+10V
+10V
+24V
+24V
GND GNDIN IN+10 +10GND GNDB BA AOUT OUT
MASTER SLAVE
MASTER SLAVE
16 COMMUNICATION
Protocol interface:MODBUSRTU(RS485orBluetooth)
Baud rateThebaudratecanbesetthroughtheHolding Register 47 andthepossiblespeedsare:RS-485 CABLE:9.6kbpsand19.2kbps(higherspeedsarenotallowedduetotheboardOpto-Insulators)UART OFFLINE CABLE:9.6kbps,19.2kbps,38.4kbpsand57.6kbps.
Parity and Stop bitsTheparityandthestopbitscanbechosenbymodifyingtheHolding Register 48andthepossiblechoicesare:
0 No parity, 2 Stop Bits (default)
1 Odd parity, 1 Stop Bit
2 Even parity, 1 Stop Bit
The value of the Holding Registers is NOT coerced if trying to set a not allowed value.
Whentryingtoenteravalueinanyholdingregister,thevalueisnotoverwrittenifthenewvalueisoutsidetheloadboundaries.
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
30/40
Supported Function:
03 Read Holding Registers
04 Read Input Registers
06 Write Single Holding Register
Modbus Communication TimeoutWiththisfeatureitispossibletostopthefanwhenthecommunicationislost,afteraperiodoftimesetintheHolding Register 56.Theregistercanbesetto:
Broadcast AddressTheBroadcastaddressis0.
1-Phase
1.05kW
Baud rate 9600
Parity and Stop Bits 0
Modbus Address 1
Whenthetimeoutoccurs,thedrivergoesinalarmconditionandthecommunicationmustberestoredandthealarmmustbecleared.ThealarmisindicatedintheInputregister17withthevalueof255(0xFF).
Modbus AddressTheslavedeviceaddresscanbechangedfromvalue1to247bymodifyingtheHolding Register 45.Thedefaultaddressfromfactoryconfigurationis1.
RS-485 Default Communication Parameters
0 No Communication Timeout
1 to 32767 Time expressed in seconds, therefore it is possible to set from 1sec to 9h 6m 8 sec
UART (OFFLINE) Default Communication Parameters
1-Phase
1.05kW
Baud rate 9600
Parity and Stop Bits 0
Modbus Address 1
Changing the Baud rate has an immediate effect, while the other communication parameters require the complete fan power off and consequently power on (wait until the complete discharge of the capacitors and the led turning off, otherwise the changes are not written into the EEPROM).
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
31/40
16.1 Temporary holding register
The Holding Register 66isaspecialregisterusedineachoperatingmodeforsettingthespeed,theairflow,theslipandthePIDreference.Itisnotaphysicalregisteranditcanbewritten,butitisnotpossibletoreaditsvalue.Thesettingremainsactiveuntilthefanispoweredon.
If the fan is powered off but there is a residual charge, the microcontroller of the driver is still functioning. Therefore, if it is powered on in this situation the value set through the register 66 is still active.
16.2 Fixed holding register
ThedriversHoldingRegisterspermanentlystoredintotheEEPROMare64,butonly26registersaremodifiablebytheenduser(seethetableinthefollowingpage).ThemostimportantHolding Register 34 is the Input TyperelatedtotheselectionoftheOperatingMode.
0 Reset
1 Min Speed
2 Max Speed
7 Max Current
21 Fixed Speed Setting
30 Asynchronous Slip Setting
31 PID positive/negative
32 Avoid Range Start
33 Avoid Range End
34 Input Type
36 Max Power Out
39 Constant Airflow Setting
42 Min Airflow
43 Max Airflow
45 Modbus Address
46 Tacho\Alarm\Filter
47 Modbus Baud rate
48 Modbus Parity and Stop Bits
50 External PID Setting
51 PID Kp
52 PID Ki
53 PID Kd
54 PID Time
55 Speed Threshold
56 Communication Timeout
16.3 Holding register description
The Holding Register must be set with the fan stopped. Changing the parameters while the fun is running may cause unexpected behavior.
CAUTIONCAUTION
Do not set the values outside the indicated limits, the driver could stop working without any alarm indication, it could be reset or work in an undefined condition.
WARNINGWARNING
If the below reported "Allowed values" are written between square brackets, they must be read as "maximum" and "minimum".
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
32/40
Holding Register 0: RESET [Adim] Thisregistercanbeusedtoresetthefanbywritingthevalue1onit.Thisregisterautomaticallyretuntovalue0afterbeingreset.Thedriverwillresetanyerrorconditionanditwilltrytorestart.
Allowed values =0and1 Default value =0
Holding Register 1: Min Speed [RPM] Thisregisterisusedtosettheminimumspeedofthefan.
Allowed values =[DefaultValue,MaxSpeed] Default value =tablebelow
200/1901413H3
200/240 1413H3
9/71413H3
9/91413H3
200/1901413G6
180/2401413G6
200/240 1413H4
1.05kW 1-Phase 400 400 400 400 400 400 400
Holding Register 2: Max Speed [RPM] Thisregistercanbeusedtosetthemaxspeedofthefan.
Allowed values =[MinSpeed,DefaultValue] Default value =tablebelow
Holding Register 7: Max Current [mA] Thisregistercanbeusedtoreducethemaxmotorcurrent.
Allowed values =[1,Defaultvalue] Default value =tablebelow
Although the value of the Max Current can be set at any value being lower than the original default one, it is not recommended using a value that is 0.3 times below the default one.
200/1901413H3
200/240 1413H3
9/71413H3
9/91413H3
200/1901413G6
180/2401413G6
200/240 1413H4
1.05kW 1-Phase 1550 1550 1550 1550 1550 1550 1550
Holding Register 16: Speed Threshold Low [RPM] Thisregistercanbeusedtosetthespeedthresholdlow.Theregisterisactivewhentheregister 46 is set to the value 3.
Allowed values =[0,SpeedThresholdHigh] Default value =0
Holding Register 21: Fixed Speed setting [RPM] ThisregistercanbeusedtosetthespeedinFixed Speed Control Mode. TheregisterisactivewhentheInputTypeHolding Register 34 is set to the value 2.
Allowed values =[MinSpeed,MaxSpeed] Default value =0
200/1901413H3
200/240 1413H3
9/71413H3
9/91413H3
200/1901413G6
180/2401413G6
200/240 1413H4
1.05kW 1-Phase 3850 3850 3850 3850 2450 2450 3850
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
33/40
Holding Register 30: Asynchronous Slip. [%] ThisregistercanbeusedtosettheslipofanemulatedACIMmotor.TheregisterisactivewhentheInputTypeHoldingRegisterissettothevalue9.
Allowed values =[0,100] Default value =0
Holding Register 31: PID Positive/Negative [Adim] ThisregistercanbeusedtoinvertthefeedbackbehaviorofthePID.
Allowed values =0and1 Default value =0
Holding Register 32: Avoid Range Start [RPM] ThisregistercombinedwiththeAvoidRangeEndcanbeusedtoskipsomeresonancefrequenciesofthefan.
Allowed values =[0,AvoidRangeEnd] Default value =20000
Holding Register 33: Avoid Range End [RPM] ThisregistercombinedwiththeAvoidRangeStartcanbeusedtoskipsomeresonancefrequenciesofthefan.
Allowed values =[AvoidRangeStart,20000] Default value =20000
Holding Register 34: Input Type [Adim]Thisregisterdefinesallthepossibleoperatingmodes:
Allowed values =[0,12] Default value =1
0 ModbusSpeedControl Thespeedissetbymodifyingtheregister661 AnalogSpeedControl Thespeedissetthroughtheanalogsignal2 ModbusFixedSpeedControl Thespeedissetbymodifyingtheregister213 Master&Slave Thefanisconfiguredasslaveandfollowsthemaster4 AnalogConstantAirflow* Theconstantairflowissetthroughtheanalogsignal5 ModbusTemporaryConstantAirflow* Theconstantairflowissetbymodifyingtheregister666 ModbusFixedConstantAirflow* Theconstantairflowissetbymodifyingthereg.397 AnalogAsynchronousEmulation Theemulationissetthroughtheanalogsignal8 ModbusTemporaryAsynchronousEmulation Theemulationissetbymodifyingtheregister669 ModbusFixedAsynchronousEmulation Theemulationissetbymodifyingtheregister3010 AnalogRef.PIDClosedControlLoop **11 ModbusTemporaryRef.PIDClosedControlLoop ThePIDref.issetbymodifyingtheregister6612 ModbusFixedRef.PIDClosedControlLoop ThePIDref.issetbymodifyingtheregister50
*Thesesettingsarenotcurrentlyavailable.Ifnecessary,contactRegalBeloitItalyS.p.A.**Thissettingisnotavailableinthisdriver.
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
34/40
Holding Register 36: Maximum Power [W] Thisregistercanbesettoreducethepowerouttothemotor.
Allowed values =[10,DefaultValue] Default value =tablebelow
Value
1.05kW 1-Phase 1050
Holding Register 39: Constant Airflow [m3/h]*Thisregistercanbeusedtosettheconstantairflowvalue.TheregisterisactivewhentheInputTypeHoldingRegisterissettothevalue6.*Thissettingisnotcurrentlyavailable.Ifnecessary,contactRegalBeloitItalyS.p.A.
Allowed values =[MinAirflow,MaxAirflow] Default value =0
Holding Register 45: Modbus Address [Adim]ThisregistercanbeusedtochangetheModbusaddressofadriver.
Allowed values =[1,247] Default value =1
Holding Register 46: Tachometric / Alarm / Threshold [Adim] Thisregistercanbeusedtosetthedigitaloutputfunction.
Allowed values =tablebelow Default value =0
Thepossiblesettingsare:
0 Tachometric ThedigitaloutputindicatesthemeasuredspeedthroughaPWMsignal
1 Alarm Thedigitaloutputindicateswhenanalarmoccurs
2 Threshold ThedigitaloutputindicateswhenthespeedsetintheHoldingRegister55isovertaken
3 Out of Functioning Range Thedigitaloutputindicateswhenthefanisworkinginadefinedrangeofspeeds
Holding Register 47: Modbus Speed [10−1 kbps] ThisregistercanbeusedtosettheModbusspeed.
Allowed values =tablebelow Default value =96
96 correspondingto9.6kbps
192 correspondingto19.2kbps
384 correspondingto38.4kbps(notavailableusingtheopto-insulatedterminalblock)
576 correspondingto57.6kbps(notavailableusingtheopto-insulatedterminalblock)
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
35/40
Holding Register 48: Modbus Stop Bits [Adim] (Default = 0) Thisregistercanbeusedtosettheparityandthestopbits.
Allowed values =tablebelow Default value =0
0 2StopBits/NoParity
1 1StopBit/EvenParity
2 1StopBit/OddParity
Holding Register 50: External Set [10−1 V] ThisregistercanbeusedtosetthereferenceofthePIDcontrol.
Allowed values =[0,100] Default value =0
TheregisterisactivewhentheInputTypeHoldingRegisterissettothevalue12.
Holding Register 51: Kp [Adim] ThisregistercanbeusedtosettheProportionalGainofthePIDcontrol.
Allowed values =[0,32767] Default value =0
Holding Register 52: Ki [Adim] ThisregistercanbeusedtosettheIntegralGainofthePIDcontrol.
Allowed values =[0,32767] Default value =0
Holding Register 53: Kd [Adim] ThisregistercanbeusedtosettheDerivativeGainofthePIDcontrol.
Allowed values =[0,32767] Default value =0
Holding Register 54: Period [ms] ThisregistercanbeusedtosetthetimeconstantofthePIDcontrol.
Allowed values =[0,32767] Default value =0
Holding Register 55: Speed Threshold (or Speed Threshold HIGH) [RPM] Thisregistercanbeusedtosetthespeedthreshold,whenthemeasuredspeedintheInputRegister3overtakesthethresholdvalue.
Allowed values =[0,MaxSpeed] Default value =0
Allowed values (Functioning Indication mode) =[SpeedThresholdLow,MaxSpeed]
SpeedThreshold=0meansthatitis DEACTIVATED
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
36/40
Allowed values =[0,9hour8min8sec] Default value =0
AttheendoftheperiodsetintotheregisterthefanstopsandthereisanAlarmindication.Torestartaresetcommandmustbesent.CommunicationTimeout=0meansthatitisDEACTIVATED
16.4 Input register description
TheModbusInputRegistersareintotal33,butonly14areusefulfortheenduser.
2 SpeedReference [rpm] 15 ModuleTemperature [10-1°C]
3 MeasuredSpeed [rpm] 17 Alarm2 [Adim]
9 BusVoltage [10-1V] 28 EnableInput [10/216V]
10 Alarm1 [Adim] 29 AnalogInput [10/216V]
12 MotorCurrent [mA] 30 TransducerInput [10/216V]
13 MotorVoltage [10-1V] 31 MeasuredPower [W]
14 AnalogInput [10-1V] 32 InputCurrent [mA]
Input Register 2: Speed Reference [rpm] Thisregisterindicatesthespeedreferenceduringthefunctioning.Duringthestartingphase,itisequaltotheMinSpeedandthengraduallyincreasestothetargetspeeddependingontheselectedmode.
Input Register 3: Measured Speed [rpm] Thisregisterindicatesthespeedduringthefunctioning.
Input Register 9: Bus Voltage [10−1 V] ThisregisterindicatestherectifiedvoltageafterthePFCstage.
Input Register 10: Alarm 1 [Adim] ThisregistermustbecombinedwiththeAlarm2register(seethetableinparagraph17.2)
Input Register 12: Motor Current [mA] Thisregisterindicatesthepeakvalueofthelinecurrentmodule.Toknowthermsvalue,itmustbedividedby√2.
Input Register 13: Motor Voltage [10−1 V]Thisregisterindicatesthepeakvalueofthephasevoltagemodule.Toknowthermslinetolinevalue,ithastobemultipliedby√3/2.
Input Register 14: Analog Voltage [10−1 V]Thisregisterindicatestheanalogvoltagevaluepresentattheinput.
Input Register 15: Module Temperature [10−1 °C]Thisregisterindicatesthetemperatureofthepowermoduleofthedriver.Whenthevalueexceedsthetemperaturethreshold,thedriverentersinaderatingprocesswheretheperformancesareautomaticallydecreaseduntilathermalequilibriumbelowthetemperaturethresholdisreached.Ifthisequilibriumisnotreached,thefanstopsandanalarmconditionisactivated.Assoonastheheatingdecreasesandthepowermoduletemperatureisbelowthetemperaturethreshold,thealarmisautomaticallyreset.ThisthresholdvaluecanbereadinHolding Register 29.
Holding Register 56: Communication Timeout [s]Thisregistercanbeusedtosetatimeoutperiodforthecommunication.
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
37/40
Input Register 17: Alarm 2 [Adim] ThisregistermustbecombinedwiththeAlarm1register.
Input Register 28: Enable Input [Adim] ThisinputindicatestheENABLEstate.Thevaluemustbemultipliedby10V/216tohavethecorrespondingvoltagevalue.
Input Register 29: Analog Input [Adim] ThisinputindicatestheReferenceValue.Thevaluemustbemultipliedby10V/216tohavethecorrespondingvoltagevalue.
Input Register 30: Transducer Input [Adim] ThisinputindicatestheTransducerValue.Thevaluemustbemultipliedby10V/216tohavethecorrespondingvoltagevalue.
Input Register 31: Measured Power [W] Thisregisterindicatestheabsorbedpower.
Input Register 32: Input Current [mA] Thisinputindicatestheinputabsorbedcurrent.
16.5 Fan info and Modbus registers
The Holding Register 44 indicates the fan model.
The Input Register 0indicatesthedriverfirmwareversionandtheInput Register 1indicatesthedrivermodel.
1-Phase
1.05kW
Firmware Version 6
Frequency Converter
Model41505
Frequency Converter
Code1431C1
200/1901413H3
200/240 1413H3
200/2401413H4
9/71413H3
9/91413H3
200/1901413G6
180/2401413G6
1.05kW 1-Phase 1 2 2 3 4 5 6
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
38/40
ThesystemstatuscanbedisplayedthroughtheLEDonthedriverplate(seepar.9.6).InthefollowingfigureontherighttheblinkingLEDisshown.
17.3 Blinking LED - Alarm description
17. ALARM HANDLING
Whenamalfunctioningoccurs,thedriverhastwopossiblebehaviorsdependingonthecauseofthealarm:
BLOCKING Thecauseofthealarmisverydangerous->Thedriverstopsimmediately.Torestartthefan,oncetheproblemhasbeencorrected,itisnecessarytoresetthefanorpowerthedriverofffor5minutes.
AUTO-RESTARTING Thecauseofthealarmiscontingenttoawrongsettingorwrongworkingcondition.Thealarmindica-tionsareactivated,butaftersomesecondsthefantriestorestartautomatically.
Thealarmscanbemonitoredthroughthreedifferentways:• ModbusRegisters• BlinkingLED• DigitalOutput
17.1 Monitoring
Inthefollowingtable,thealarmsandthevaluesstoredintherelatedModbus Input Register 10 and Input Register 17 areindicated.
17.2 Modbus registers - Alarm description
Alarm 1 Alarm 2 Description Actions Type0 0 Default operation – No Errors No Actions ALARM 1
1 0 Memory error Blocking condition ALARM 2
2 0 Short Circuit Blocking condition ALARM 3
3 0 Loss of synchronism Auto-restarting condition ALARM 4
4 1 Input Voltage outside range (only with motor stopped) Auto-restarting condition ALARM 4
4 32 BUS overvoltage (instantaneous measurement) Auto-restarting condition ALARM 4
4 33 BUS undervoltage (instantaneous measurement) Auto-restarting condition ALARM 4
4 34 Input relay not closed Auto-restarting condition ALARM 4
4 49 Missing phase – U cable disconnected Blocking condition ALARM 4
4 50 Missing phase – V cable disconnected Blocking condition ALARM 4
4 51 Missing phase – W cable disconnected Blocking condition ALARM 4
4 52 High starting current Auto-restarting condition ALARM 4
4 113 Overtemperature Auto-restarting condition ALARM 4
4 255 Loss of communication Blocking condition ALARM 4
The Driver is NOT protected against a very high-power supply voltage. A very low power supply voltage during the motor running could damage Driver.
WARNINGWARNING
1 sec.
Rev. 0 - 11/12/2020
OPERATING MANUALOPERATING MANUALENEN
39/40
ThedriveroutputcanbeconfiguredasAlarmoutputbymodifyingtheHolding Register 46tovalue1.Duringthenormalfunctioning,thevalueis0Vand,whenanalarmoccurs,theoutputvalueis5V(or10Vdependingonthefanmodel).
17.4 Digital Alarm Output
Thealarmsareautomaticallyresetfollowingtheactionofthetablebelow:
17.5 Alarm Reset
Operating Mode Input Type Action
Analog 1,4,7,10 Signalsetto0V
Fixed 2,6,9,12 Registers21,39,30and50setto0
AsconcernstheTemporaryModbusmode,itisnecessarytoresetthefanbysettingtheHolding Register 0tovalue=1insteadofsettingto0theRegister 66.
Temporary 0,5,8,11 Register0setto1
The Holding Register 0 is a general reset and works also in the Analog mode and Fixed mode.
18. AVAILABLE SOFTWARE
AfreewaresoftwareisavailableonNicotra Gebhardtsite(http://www.nicotra-gebhardt.com)formonitoringthefan.Pleaserefertotherelatedmanualformoredetails
The software can be used for configuring the fan and monitoring the performance. The performance is estimated through an algorithm and, therefore, subjected to variable tolerance depending on the working point, airflow stability and the constant algorithm resolution itself.