EBSCO Discovery Service (EDS) EDS используют 8000 организаций (май 2015)
EBH EDS - EURAPO · 2021. 4. 26. · EBH EDS EDS features EDS HIGH PRESSURE UNIT • 9 SIZES for...
Transcript of EBH EDS - EURAPO · 2021. 4. 26. · EBH EDS EDS features EDS HIGH PRESSURE UNIT • 9 SIZES for...
EBHEDS
INTEGRATED COMFORT SYSTEMS
EN DUCTED UNITS
EBH
ED
S
EBH high pressure ducted units and EDS Double Skin units, thanks to their high pressure fan
decks, permit to satisfy every request of heating and cooling applications in big environments,
where ducted air distribution is requested. They are suitable for horizontal installation.
These are units for COOLING and HEATING applications; they are fed with cold and hot water
and used according to their relevant performance features. EBH and EDS units are components
of cooling and/or heating systems; consequently, they are without any safety devices on the
water circuit. These units have been designed for temperatures up to 75 °C. .
EBH | EDS HIGH PRESSURE UNITS
EDSHIGH PRESSURE UNIT
EBHHIGH PRESSURE UNIT
DUCTED UNITS EBH | EDS
EBH features
EBHUNIT WITH AIR SUPPLY
PLENUM
• 6 SIZES for horizontal ducted installation, 2 and 4 pipe system.
• HIGH PRESSURE: they are designed for ducted installation with external static pressure up to
300 Pa.
• STRUCTURE is realized in galvanized metal sheet, insulated internally; in order to facilitate all
maintenance operations, the structure is divided in three separate and independent sections
(condensate tray, fan deck, air filter).
• HEAT EXCHANGERS can have 2, 3 or 4 rows, made by copper pipes and aluminium fin pack;
5-row coils are available for sizes 060 and 070. Up to size 050 all coils are provided with air vent
valves. For sizes 060 and 070, the air vent valve is supplied only with the valve kit (optional).
• REVERSIBLE WATER CONNECTIONS: these high-pressure units can be ordered with right
(standard) or left water connections; it is possible to reverse the water connections on site, if
necessary.
• FAN DECK is composed by a 3 speed motor and two centrifugal galvanized steel scrolls. All
motors are provided with a permanently connected capacitor and thermal protection of the
windings with automatic reset.
• CONDENSATE TRAY is realized in galvanized steel with water discharge pipes on both sides.
• AIR FILTER consists of a washable polyester acrylic fibre, pleated and protected by a metal
frame.
The filter section can be easily removed for cleaning and maintenance. Filtration class G3.
• ELECTRIC PANEL is composed by a terminal board with screw terminals contained in an ABS
plastic box (IP30). A supporting relay is supplied as standard starting from size 040.
• 4 BRACKETS are supplied along with the unit, to fix it to the ceiling.
EBH
ED
SEB
H E
DS
EDS features
EDSHIGH PRESSURE UNIT
• 9 SIZES for horizontal ducted installation, 2 pipe system.
• HIGH PRESSURE: they are designed for ducted installation with external static pressure up to
300 Pa.
• DOUBLE SKIN STRUCTURE is composed by insulated 25 mm thick panels, colour RAL9002,
and aluminium supporting frame.
• HEAT EXCHANGERS can have 2, 3 or 4 rows, made by copper pipes and aluminium fin pack;
5-row coils are available for sizes 060 and 070. Up to size 050 all coils are provided with air
vent valves.
• NOT REVERSIBLE WATER CONNECTIONS: EDS units can be ordered with right (standard) or
left water connections.
• FAN DECK is composed by a 3 speed motor and two centrifugal galvanized steel scrolls. All
motors are provided with a permanently connected capacitor and thermal protection of the
windings with automatic reset.
• CONDENSATE TRAY is realized in galvanized steel with water discharge pipe located on the
water connections’ side.
• AIR FILTER consists of a washable polyester acrylic fibre, pleated and protected by a metal
frame. The filter section can be easily removed for cleaning and maintenance. Filtration class
G3.
• ELECTRIC PANEL is composed by a terminal board with screw terminals contained in a high
protection box (IP44). A supporting relay is supplied as standard starting from size 040.
• 4 BRACKETS are supplied along with the unit, to fix it to the ceiling.
HIGH PRESSURE UNIT EDS
EBH WITH VALVE
• quiet operation
• reliability
• excellent quality/price ratio
• high coefficient of performance
• sturdiness and solid construction
• accurate choice of each single component
• environmentally friendly sandwich panels (EDS model)
• high protection electric panel (IP44), available also on EBH models
• easy installation and maintenance operations
The big advantages of the EURAPO high pressure units are:
EBH
ED
S
• VALVE KIT 3 way 4-port regulating valves with ON/OFF or modulating actuators, provided with
copper connection kit and insulation shell (supplied loose).
• CONDENSATE PUMP with 6 m maximum head.
• CONDENSATE TRAY in stainless steel.
• SPECIAL FILTER made of washable polyester acrylic fibre, filtration class F5.
• ADDITIONAL COILS for hot water with 2 or 3 rows, for units to be installed in 4-pipe systems.
• DISTRICT COOLING COILS: Heat exchangers with a reduced number of circuits, suitable for
applications where the water thermal head is about 9 °C.
• ELECTRIC HEATER it is an additional section to be mounted on the air outlet, provided with all
necessary safety thermostats. The heating capacity is different from size to size, up to 9 kW.
• AIR DELIVERY/AIR INTAKE PLENUM with several frontal spigots.
• RAL 9001 PAINTING with oven dried epoxy powders. All RAL colours are available.
• REGULATING SYSTEMS: the whole range of EURAPO regulators is available: fan speed
selectors, electro-mechanical controllers, electronic controllers with microprocessor, digital
regulators with a centralized supervision system communicating via Bus based on standard
protocols. For more information, please either refer to the specific EURAPO technical literature
or visit the official web site www.eurapo.it.
Accessories for EBH units:
Additional coils Electric heater Valve kit
Condensate pump Air delivery/air intake plenum RAL 9001 painting
• VALVE KIT 3 way 4-port regulating valves with ON/OFF or modulating actuators, provided with
copper connection kit.
• CONDENSATE PUMP with 6 m maximum head.
• SPECIAL FILTER made of washable polyester acrylic fibre, filtration class F5.
• DISTRICT COOLING COILS: Heat exchangers with a reduced number of circuits, suitable for
applications where the water thermal head is about 9 °C.
• ELECTRIC HEATER it is an additional section to be mounted on the air outlet, provided with all
necessary safety thermostats. The heating capacity is different from size to size, up to 9 kW.
• AIR DELIVERY/AIR INTAKE PLENUM with several frontal spigots.
• REGULATING SYSTEMS: the whole range of EURAPO regulators is available: fan speed
selectors, electro-mechanical controllers, electronic controllers with microprocessor, digital
regulators with a centralized supervision system communicating via Bus based on standard
protocols. For more information, please either refer to the specific EURAPO technical literature
or visit the official web site www.eurapo.it.
Accessories for EDS units:
Electric heater Air delivery/air intake plenumValve kit Special filter
Analogue plus consoleDisplay console
EBH
ED
S
STANDARD TECHNICAL DATA AT DIFFERENT Pa OF EXTERNAL STATIC PRESSURE-ASYNCHRONOUS
Technical data EBH UNIT:
STANDARD TECHNICAL DATA 50 Pa EXTERNAL STATIC PRESSURE-ASYNCHRONOUS
Technical data EDS UNIT:
Models EBH EBH EBH EBH EBH EBH020 030 040 050 060 (4) 070 (4)
MAX External static pressure [Pa] 125 175 200 250 300 300
Total cooling capacity [kW] (1)
MAX 6,95 9,49 11,80 13,72 23,44 27,62
MED 5,90 8,23 10,40 12,60 20,94 25,56
MIN 4,30 7,11 8,91 11,36 16,37 23,55
Heating capacity [kW] (2)
MAX 7,08 11,40 14,30 17,40 27,46 34,03
MED 6,20 9,62 12,20 15,53 24,05 30,96
MIN 4,55 8,20 10,40 13,90 18,00 28,05
Air volume [m3/h]
MAX 1145 1910 2680 3250 4414 5548
MED 920 1520 2130 2870 3750 4936
MIN 620 1205 1655 2470 2649 4374
Sound pressure level [dB(A)] (3)
MAX 53 54 58 61 65 70
MED 47 50 52 57 62 68
MIN 37 46 46 54 54 65
Absorbed current [A]
MAX 0,72 1,76 2,03 2,85 7,50 8,19
MED 0,52 1,45 1,64 2,39 4,29 7,61
MIN 0,32 1,30 1,28 2,06 2,61 6,85
Power input [W]
MAX 171 352 451 588 1060 1801
MED 119 305 361 512 790 1631
MIN 72 267 274 440 543 1446
N° rows (standard) 4 4 4 4 4 4
Power supply [V-ph-Hz] 230-1-50/60
Models EDS EDS EDS EDS EDS EDS EDS EDS EDS004 006 008 020 030 040 050 060 070
MAX External static pressure [Pa] 50 50 50 125 175 200 250 300 300
Total cooling capacity [kW] (1)
MAX 2,54 3,10 4,13 7,33 9,77 12,85 13,64 24,06 27,13
MED 1,87 2,40 3,54 5,51 7,73 10,25 12,14 21,52 25,08
MIN 1,10 1,61 2,69 3,28 6,63 8,25 10,83 16,80 23,09
Heating capacity [kW] (2)
MAX 2,65 3,61 4,77 7,89 12,09 15,21 17,14 25,09 31,95
MED 1,97 2,77 4,07 5,75 9,21 11,79 14,96 22,09 29,16
MIN 1,07 1,70 3,16 3,37 7,75 9,30 13,13 16,74 26,50
Air volume [m3/h]
MAX 400 596 848 1383 2230 3026 3472 4414 5548
MED 283 432 693 932 1577 2162 2894 3750 4936
MIN 143 245 506 494 1273 1598 2438 2649 4374
Sound pressure level [dB(A)] (3)
MAX 42 44 46 53 56 56 60 65 70
MED 40 41 44 46 50 51 57 62 68
MIN 38 39 41 42 48 47 54 54 65
Absorbed current [A]
MAX 0,26 0,35 0,46 0,84 2,28 2,37 3,98 7,50 8,19
MED 0,21 0,28 0,37 0,53 1,20 1,69 2,81 4,29 7,61
MIN 0,15 0,19 0,29 0,31 1,00 1,29 2,21 2,61 6,85
Power input [W]
MAX 59 80 102 187 352 511 666 1060 1801
MED 46 62 84 121 235 365 557 790 1631
MIN 33 44 65 69 191 267 456 543 1446
N° rows (standard) 4 4 4 4 4 4 4 4 4
Power supply [V-ph-Hz] 230-1-50/60
(1) Air temperature: 27 °C d.b., 47% rel. humidity - Water temperature: 7/12 °C
(2) Air temperature: 20 °C, 50% rel. humidity - Water inlet temperature:
45/50 °C.(3) Pressure level in open field at 1 m distance.
(4) Performances are out of scope Eurovent FCP.In order to select the EBH or EDS ducted fancoil with District Cooling coils, please use the EURAPO software for selection.
C
A
F
134
B
134
D
31,5
E
21
91,5H
200
350
G
78,2
I
Model A B C D E F G H I Connections Spigots
020÷030 990 902 408 927 366 634 963 307 404 G 1/2” F 3
040÷050 1240 902 408 1177 366 634 1213 300 404 G 1/2” F 4
060÷070 1635 1160 518 1572 476 892 1608 311 514 G 1” M 5
Dimensions [mm] EBH UNIT
Model A B C D E F G H I Connections
004 882 742 924 390 799 250 855 306 798 G 3/4” M
006÷008 1007 867 1049 390 924 250 855 306 798 G 3/4” M
020÷030 1132 992 1174 440 1049 300 855 357 798 G 3/4” M
040÷050 1382 1242 1424 440 1299 300 855 357 798 G 3/4” M
060÷070 1777 1637 1819 550 1694 410 1030 467 978 G 1” M
Dimensions [mm] EDS UNIT
OPTIONAL PLENUM
EST
W80%
70%
60%
50%
40%
30%
20%
10%
0%
W80%
70%
60%
50%
40%
30%
20%
10%
0%
EST (Energy Saving Technology) is applied to the EURAPO fan coil units and cassette units. It permits to
obtain extremely low electrical absorption and a continuous modulation of the air flow, constantly related to
the concrete need of energy in the room.
EST technology is composed by a brushless motor combined to a dedicated electronic device (inverter),
managed by specific regulators developed by EURAPO.
In comparison to the traditional units equipped with asynchronous three-speed-motors, the fan coil and
cassette units with brushless motors can obtain a considerable energy saving, by reducing the power
consumption up to 70%.
Thanks to the step-less modulation of the fan speeds it is possible to accurately regulate the air volume in a very
precise way, in strict relation to the real need of air conditioning in the room. Oscillations in the temperature
and relative humidity are reduced at lowest level: a guarantee for the highest comfort in the room.
The possibility to reach very low air volumes makes the units extremely quiet at the lowest motor revolutions.EST technology is designed in particular for offices, hospitals, nursing homes and hotels.
It is available for the EURAPO range of fan coil units, cassette units and ducted units.
6
Energy saving with EST fancoil
5 speed 4 speed 3 speed 2 speed 1
m3/h m3/h
speed 6
Asynchronous fan coil absorption (W)
EST fan coil absorption EST (W)
speed 5
speed 4
speed 3
speed 2
speed 1
STANDARD TECHNICAL DATA AT DIFFERENT Pa OF EXTERNAL STATIC PRESSURE-EST
Technical data HIGH PRESSURE UNIT ESTEBH
STANDARD TECHNICAL DATA 50 Pa EXTERNAL STATIC PRESSURE-EST
Technical data HIGH PRESSURE UNIT ESTEDS(1) Air temperature: 27 °C d.b.,
47% rel. humidity - Water temperature: 7/12 °C (2) Air temperature: 20 °C, 50% rel. humidity
Water inlet temperature: 45/40 °C (3) Pressure level in open field at 1 m distance.In order to select the EBH or EDS ducted fancoil with District Cooling coils, please
use the EURAPO software for selection.
Models ESTEBH ESTEBH ESTEBH ESTEBH ESTEBH020 030 040 050 060 (4)
MAX External static pressure [Pa] 125 175 200 250 300
Total cooling capacity [kW] (1)
MAX 6,75 9,94 13,64 14,40 23,16
MED 5,62 8,13 11,22 13,25 17,84
MIN 4,23 7,11 8,43 11,90 11,16
Heating capacity [kW] (2)
MAX 7,07 11,52 16,24 18,07 27,08
MED 5,65 9,07 12,87 16,25 19,99
MIN 4,11 7,81 9,35 14,37 11,70
Air volume [m3/h]
MAX 1040 1948 2848 3217 4337
MED 796 1471 2160 2834 2999
MIN 549 1241 1484 2442 1609
Sound pressure level [dB(A)] (3)
MAX 54 57 60 64 68
MED 47 50 55 61 62
MIN 38 46 46 58 59
Absorbed current [A]
MAX 1,08 1,12 1,85 2,17 3,93
MED 0,58 0,68 0,97 1,59 2,12
MIN 0,29 0,53 0,53 1,12 0,56
Power input [W]
MAX 161 261 405 478 771
MED 75 132 196 341 351
MIN 36 91 82 234 96
N° rows (standard) 4 4 4 4 4
Power supply [V-ph-Hz] 230-1-50/60
Models ESTEDS ESTEDS ESTEDS ESTEDS ESTEDS ESTEDS ESTEDS004 008 020 030 040 050 060
MAX External static pressure MAX [Pa] 50 50 125 175 200 250 300
Total cooling capacity [kW] (1)
9 V 4,32 4,36 8,33 8,96 12,65 14,37 23,77
7 V 3,58 3,64 7,04 7,77 11,30 13,01 20,93
6 V 2,37 2,44 5,07 7,11 10,77 11,71 18,39
Air volume [m3/h]
9 V 798 914 1659 1961 2956 3787 4337
7 V 619 718 1301 1589 2500 3223 3599
6 V 367 443 836 1402 2333 2739 2999
Sound pressure level [dB(A)] (3)
9 V 50 49 57 57 61 63 68
7 V 46 45 54 54 58 60 66
6 V 43 42 48 52 56 57 62
Absorbed current [A]
9 V 0,55 0,65 1,90 1,48 1,79 3,05 3,93
7 V 0,40 0,44 1,23 0,96 1,28 2,24 2,93
6 V 0,24 0,26 0,61 0,97 1,03 1,65 2,12
Power input [W]
9 V 61 69 231 233 372 616 771
7 V 42 48 146 159 257 430 541
6 V 24 27 71 130 221 294 351
N° rows (standard) 4 4 4 4 4 4 4
Power supply [V-ph-Hz] 230-1-50/60
ESTEDS unit is available for cooling operation only.
Eurapo SrlVia A. Malignani, 1233170 Pordenone - ItalyT +39 0434 572552F +39 0434 [email protected]
www.eurovent-certification.comwww.certiflash.com
District COOLING
by EURAPO6D
C030
2 - E
N04
.21
As programs and technologies are always improving,
description, data and drawings must be intended as merely
indicative and can be modified without any notice.
ISO 9001certified companyCert. no. 731005773