EATON Transformer Module
Transcript of EATON Transformer Module
w w w . e a t o n . c o m
Standard Features
l When used with standard system, EATON Transformer Module provides isolated and Step-down 120/208/240 V AC outputs.
l Multiple Output receptacles: 120/208/240 V AC.
EATON Transformer ModuleQuick Start
86-86000-03 B03 - Page 3
STEP 1 EATON Transformer Module Unpacking and Parts Check
Warranty and Product Registration
EATON TransformerQuick Start Manual
Tower Stand Extenders
EATON Transformer Module Box Contents
Stabilizer Bracket(4 screws included)
41
Transformer Rail Kit
Transformer Cable
610 mm / 24 inch
EX RT 5/7/11 Systems
Quick Start
www.eaton.com
STEP 2 EATON Transformer Module Tower Configuration (with EX RT only)
Tower Configuration of Standard System with Transformer Module
Transformer Module
E X 11 R T
E X B 11 R T
Power Module
Battery Module(up to 6)
Power Module
Battery Module
Transformer Module
5
1
1
2
2
4
4
4
4
33
86-86000-03 B03 - Page 4
STEP 3 Rack Configuration
See EX RT 5/7/11 or 9140 UPS Systems Installation and User Manual for details.
E X
1 1
R T
OF
FO
N
E X
1 1
R T
OF
FO
N
E X 1 1 R T
OFF
ON
E X 1 1 R T
OFF
ON
1
2
3
FINISHED PANEL (rack orientation)
1
2
3
A. Prepare the power module front panel logo and LCD display for rack orientation. Apply to all modules (Power Module shown).
Stack-up sequence in Rack configuration
EX RT UPS 9140 UPS
2. POWER MODULE (upper, EX RT 5/7/11)
1. EATON Transformer Module (Top)
OFF
ON
EX 11 RT
EX RT Transformer
EX RT Transformer
EX RT Transformer
EX RT Transformer
EX RT Transformer
EX RT Transformer
3. BATTERY MODULE (lower, EX RT EXB 5/7/11)
4. BATTERY MODULE (bottom, EX RT EXB 5/7/11)
2. 9140 UPS
1. EATON Transformer Module (Top)
3. EBM
4. EBM
(Shown with power module and 2 battery modules)
B. EATON Transformer Rack Installation
3
4
4
4
4 2
21
4
4
51
6 6
6
1. Attach both front mounting ear brackets to module with supplied screws. (For this step, it is possible to adjust the position of both front mounting brackets.)2. Attach rear support brackets to module. These brackets prevent the module from sliding out of the rack.3. Attach rails together and secure with wing nuts, and finger tighten. (both sides).4. Attach both rails to rear and front of rack with supplied flathead screws (as shown).5. Use caution when sliding unit into rack. Temporarily secure unit to rack with thumb screws on front mounting
brackets.6. Secure rear support brackets to rails.
6
86-86000-03 B03 - Page 5
STEP 4 Setup and installation
Main Output Circuit Breaker
Load 2: 4 NEMA 5-15/20R, 120 Vac
Load 3 Circuit Breaker
Load 2 Circuit Breaker
Load 1: 1 NEMA L6-30R, 208 Vac
Load 1 Circuit Breaker
Transformer ProtectBreaker
Load 4: 4 NEMA 5-15/20R, 120 Vac
Load 4 Circuit Breaker
Transformer I/O Box
AC Input
AC Output
Load 3: 1 NEMA L6-30R, 208 Vac
AC INPUT
UPSTREAMCIRCUIT BREAKER(NOT SUPPLIED)
Transformer Module
Bypass AC
Normal AC
Simplified Connection Diagram
To Load
Rear Panel of the optional Transformer Module
Electrical Characteristics Nominal power 11 kVANominal current 63 AInput voltage 208-240 VacOutput Voltage 120/208/240 VacFrequency 50/60 Hz ±10 %)Isolation (EN 61558-1-2-4) 3.75 kV / 5 M ohmsOperating temperature From 0° to +40 °CMax. operating rel. humidity 95 %Derating/altitude Pn-10 % > 1000 m
86-86000-03 B03 - Page 6
STEP 5 Systems Connections with EX RT UPS
EATON Transformer Module, Power Module, and Battery Module Connections
System Connections with Transformer Module
AC Normal INPUT
Transformer OUTPUT TO LOAD
Battery Module EX RT EXB 5/7/11
Power ModuleEX RT 5/7/11
EATON TransformerModule
Transformer Main OutputCircuit Breaker
Follow connection diagram for appropriate input/output voltages.
Connection Diagram (bottom of Transformer I/O Box)
L3 L2 L1 Lb Ld N Lc La
208 Vac
240 Vac
AC Input
120 Vac
208 Vac
AC Output
120 Vac
240 Vac
Transformer Module Terminal block capacity: maximum 4 AWG solid or stranded wire on transformer module.
1. Check that the battery circuit breaker is OFF (“0”) position.
2. Connect the battery power cable to the connectors of the power and battery modules,
3. Connect the battery detection cable between connectors of the power and battery modules.
4. Turn on battery module circuit breaker, power module, I/O Box, circuit breaker, and Transformer Module Main Output Circuit Breaker.
5. Push ON button on the Power Module for more than 3 seconds.
Battery ModuleCircuit Breaker
Battery Power Cable
Power ModuleConnector
Battery DetectionCable
1
2
3
Power Module Circuit Breaker
4
4
WARNING To avoid overloading 120 VAC output windings, distribute loads evenly between Load 2 and Load 4 (on rear of Transformer Module) and between 120 VAC output terminals (Lb-N, La-N.)
AC Input from Power Module
(208 VAC shown)
AC Output to Load(120 VAC shown)
L3 L2 L1 Lb Ld N Lc La
Transformer Module I/O Box
See EX RT 5/7/11 Systems Installation and User Manual for initial start-up procedures.
86-86000-03 B03 - Page 7
STEP 6 Systems Connections with 9140 UPS
EATON Transformer Module, 9140 UPS, EBM connections
System Connections with 9140 UPS
Transformer OUTPUT TO LOAD
Transformer Main OutputCircuit Breaker
EATON Transformer Module
Follow connection diagram for appropriate input/output voltages.
Connection Diagram(right of Transformer I/O Box)
L3 L2 L1 Lb Ld N Lc La
208 Vac
240 Vac
AC Input
120 Vac
208 Vac
AC Output
120 Vac
240 Vac
Transformer Module Terminal block capacity: maximum 4 AWG solid or stranded wire on transformer module.
1. Check that battery breaker is on OFF position.
2. Connect the battery cable between EBM and UPS,
3. Connect power cables to the UPS and transformer module.
4. Turn on battery module circuit breaker, UPS output circuit breakers, transformer module main Output Circuit Breaker.
5. Start UPS.
1
3
(4) 20 A/250 VOutput Circuit Breakers
(3) C19Output Receptacles
(2) C13Output Receptacles
Ground Bonding Screw
Output TerminalBlock Cover
Input TerminalBlock Cover
EBM BatteryConnector
3
4
3
2
See 9140 UPS Installation and User Manual for initial start-up procedures.